Hunter Stoves HERALD 14 CE Installation And Operating Instructions Manual

H E R A L D 1 4
H E R A L D 1 4
H E R A L D 1 4H E R A L D 1 4
C E
C E
C EC E
M U L T I F U E L
M U L T I F U E L
M U L T I F U E LM U L T I F U E L
C L E A N B U R N
C L E A N B U R N
C L E A N B U R N C L E A N B U R N
S T O V E
S T O V E
S T O V ES T O V E
Installation and Operating Instructions
A Hetas certified engineer must carry out the installation of this appliance; alternatively, your local Building Control Officer can approve the completed installation, should a non-certified engineer undertake the installation. It is an offence, under UK law, not to comply with this advice. Please hand these instructions to the stove user when the installation is complete. Leave the system ready for operation and instruct the user in the correct use of the appliance and operation of controls.
Herald 14 CE
Technical Specification
Stove Mass 163 kg
Wood
Total Efficiency 78.6%
Nominal Heat Output 11.5 KW
Mean CO Emission (at 13% O2) 0.57 % Mean Flue Gas Temperature 339 °C
Flue Gas Mass Flow 6.4 g/s
Ancit
Total Efficiency 79.4 %
Nominal Heat Output 9.0 KW
Mean CO Emission (at 13% O2) 0.18 % Mean Flue Gas Temperature 275 °C
Flue Gas Mass Flow 7.2 g/s
This appliance is not suitable for use in a shared flue
This appliance is suitable for continuous burning
Assembly Instructions
PLEASE READ THESE INSTRUCTIONS CAREFULLY
It is important that your stove is correctly installed, as Hunter Stoves Limited cannot
accept responsibility for any fault arising through incorrect use or installation.
Flue Collar
Place the Flue Gasket on the top, or rear outlet as required. Place the Flue Collar on top of the Gasket. Secure to the four locating tabs, inside the flue outlet, using the M6 nuts & bolts supplied. Fit the 2 - M8 carriage bolts, washers & nuts into the Damper Holes, located on each side of the Flue Collar.
Blanking Plate
Fit the Flue Gasket and Blanking Plate on the remaining free outlet and secure it, using 2 - M6 countersunk screws & nuts.
Fire Bricks
and slide to the right.
When the left side of
The Fire Bricks, in this appliance, are factory fitted. The following set of photos show the removal sequence that you will need to employ when servicing your Hunter stove.
Baffle Brick
Lift the Baffle Brick
the Brick clears the Baffle Support, lower the Brick into the Fire Box and remove.
Side Bricks
Remove all of the Riddling bars. Lift the side brick out of the groove in the side plate.
Rear Brick
Pull the top edge of the Rear Brick towards you,
lift and remove.
To assemble these Fire Bricks, simply reverse the above procedure.
Installation Instructions
These instructions cover the basic principles to ensure satisfactory installation of the stove, although detail may need slight modification to suit particular local site conditions. In all cases the installation must comply with current Building Regulations, Local Authority Byelaws, European and national standards and other specifications or regulations as they affect the installation of the stove. It should be noted that the Building Regulations requirements may be met by adopting the relevant recommendations given in British Standards BS 8303, BS 6461 and BS 7566 as an alternative means to achieve an equivalent level of performance to that obtained following the guidance given in Approved Document J.
Health And Safety Precautions
Handling
Adequate facilities must be available for loading, unloading and site handling.
Fire Cement
Some types of fire cement are caustic and should not be allowed to come into contact with the skin. In case of contact, wash immediately with plenty of water.
Asbestos
This stove contains no asbestos. If there is a possibility of disturbing any asbestos in the course of installation then please seek specialist guidance and use appropriate protective equipment.
Metal Parts
When installing or servicing this stove, care should be taken to avoid the possibility of personal injury.
Important Warning
This stove must There must not be an extractor fan fitted in the same room as the stove as this can cause the stove to emit fumes into the room.
be installed into a chimney that serves any other heating appliance.
not
Installation
Chimney
The chimney height and the position of the chimney terminal should conform to Building Regulations.
Check that the chimney is in good condition, dry, free from cracks and obstructions. The diameter of the flue should not be less than 150mm and not more than 230mm. If any of these requirements are not met, the chimney should be lined by a suitable method.
The chimney must be swept before connection to the stove. Where the chimney is believed to have previously served an open fire installation, it is possible that the higher flue gas temperature from the stove may loosen deposits that were previously firmly adhered, with the consequent risk of flue blockage. It is therefore recommended that the chimney be swept a second time within a month of regular use after installation.
If you have any doubts about the suitability of your chimney, consult your local dealer/stockist.
If there is no existing chimney then either a prefabricated block chimney in accordance with Building Regulations Approved Document J, or a twin-walled insulated stainless steel flue to BS 4543 can be used. These chimneys must be fitted in accordance with the manufacturer’s instructions and Building Regulations.
Flue Draught
A flue draught of minimum 1.2mm to a maximum 2.5mm water gauge is required for satisfactory appliance performance. The flue draught should be checked under fire at high output. If it exceeds the recommended maximum, a draught stabiliser must be fitted so that the rate of burning can be controlled and to prevent over firing. If the reading is less than the recommended minimum than the performance of the appliance will be compromised.
Connection to the Chimney
An existing fireplace opening can be bricked up or sealed with a register plate. A short length of flue pipe of a minimum 152mm internal diameter may then be used to connect the stove to the chimney. This flue pipe should be of 316 grade stainless steel or vitreous enamelled, nominal thickness 1.2mm. Ensure that the pipe end is no closer than 76mm to the side or rear chimney walls.
Ideally, the old fireplace should be filled in so that there is a smooth streamlined entry into the flue way. The length of any horizontal run of flue pipe must not exceed 152mm. It is essential that all connections between the stove and chimney-flue are sealed and made airtight. Both the chimney and flue pipe must be accessible for cleaning and if ANY parts of the chimney cannot be reached through the stove (with baffle brick removed), a soot door must be fitted in a suitable position to enable this to be done.
Air Supply
The room or space containing this appliance needs a permanent, unobstructed air opening of at least 4950 mm2. If a draught stabiliser is fitted, the air opening should be at least 9150 mm2. Due consideration should be given to air requirements for any other appliances in the same room or space.
Loading...
+ 11 hidden pages