Hunter Fan 44277 User Manual

1
G
Y
C
44272, 44277 Programmable ermostat
Installation Sheet
Preparation
Gathering Tools and Warnings
This thermostat is compatible with most conventional oil, gas, electric, hot water systems, single stage, and multi-stage heat pumps. This thermostat will not control line voltage systems.
You will need the following tools to complete your installation:
• Phillips Screwdriver (#2)
• Two 1.5V (AA) size alkaline batteries
Take note of these warnings and cautions before proceeding:
• Read all installation instructions before beginning installation! If you still need assistance after reading this manual, call our
Technical Support at 1-888-830-1326.
• Do not disconnect the wires from your old thermostat until all wires have been properly labeled. You must label all wires properly because wire color may not indicate the function of the wire.
• All wiring must be done in accordance with local code and ordinances.
• Always turn power off to your furnace/compressor before the installation process. Failure to do so could result in damage to your thermostat and/or your heating and cooling system. Do not restore power until your installation is complete.
• This thermostat is designed for use with 24V AC/millivolt systems with a maximum of 1 amp. Higher amp or line voltage systems will cause damage to your system and increase the risk of fire.
Old ermostat Removal
1
Conventional
RH
RC, R
Y, Y1
G, F
W, W1
W2
Y2
C
A
W2
After writing down the wire colors
RH
and letters, use the terminal stickers to label the wires. Figures 3a and 3b
RC
will help you depending on system type; Conventional or Heat Pump. Not all terminals will be used, this will
Y
be determined by your system type.
G
To ensure wires do not fall back into
W
the wall hole, you may tape them to the wall, or wrap them around a pencil.
Y2
Figure 4. may assist you if your old thermostat is a heat pump from one
C
of the listed Manufacturers and your wire labels do not match. It is located
A
on the back of this sheet. These tips will also help you in wiring:
Figure 3a.
• Only 1 reversing valve is needed
Heat Pump
R, V
Y, Y1, M
G, F
L, F, X
O, R
B
W2, E, X,
Aux
Y2
C, X, X1, B
R
Y
G
L
O
B
E
Y2
C
to run a heat pump. If both “O” and “B” are present, “B” may be a common wire.
• Often, 2-wire heat only systems do not have terminal labels. Connect 1 wire to the Rh terminal and the other to W.
• If you have a 3-wire hot water system, the damper valve control wire will be labeled and attached to the “A” terminal.
• If you need further assistance with wiring, or determining your system type, you can contact our Technical Support Department. See the “Technical Support” section for information.
Figure 3b.
Installation
Mounting the Wallplate
1. Remove the mounting plate by pulling it straight off the back of the Thermostat. Figure 5.
2
4. Check the charts on the back of this sheet and identify your system type. They are divided by Conventional and Heat Pump installations.
5. Raise all of the levers on the terminals you will be using. Heat Pump Installation labels are located on the left of the terminal blocks on the mounting plate and Conventional labels are on the right. If your installation does not call for the jumper, remove it now. It is located underneath the wire holes, between the RH and RC terminals on the conventional side. Figure 9.
6. If one of the terminals you need has a tab in front of it, use your nger to break the tab away. Figure 9.
Note: Only break tabs you know you will be using. Double
check your wiring conguration and make sure you are familiar with the terminals you will be using.
Levers
RH
Jumper
W
Insert Wires
W G Y RC RH
Tabs
Figure 9.
7. Insert the bare end of each wire all the way into the appropriate hole in the terminal block that matches the wire label then lower the lever. This will lock each of the wires in place. Tuck excess wire back into wall after they have been locked in the mounting plate.
Note: Do not insert the wires into the holes in the top of the
mounting block. The wires should be inserted into the front close to the hole in the mounting plate. See Figure 8.
8. Before mounting the thermostat onto the mounting plate, turn it over and nd the 2 switches located on the circuit board next to the battery compartment.
1. Turn off power to your compressor and furnace.
2. Remove the cover to your existing thermostat. Some thermostats may have screws or other locking devices that must rst be removed. Once the wallplate is exposed, locate the wire terminals and try to identify the wire designations. If the wire terminals are not visible, they may be connected to the back of the wallplate. Look for any additional screws, tabs, or locking devices to remove the wallplate. See Figure 1. If you are still unable to nd the terminals for the wires, it may be necessary to contact the manufacturer of the original thermostat.
W
G
Y
RC
Wallplate
Wallplate
ermostat Cover
W
G
Y
RC
ermostat Cover
Figure 1.
Labeling Your Wires
Use the table in Figure 2. to write down your wire colors and the letter designations on the old thermostat. This will allow you to keep a record of your old thermostat’s wiring conguration should you need to refer to it at a later time. This will also help our Technical Support Department determine your system type and proper wiring, should you need to contact them. Wire color does not indicate the function of the wire, this is being used only to help determine which wire has what letter designation.
Wire Color Wire letter
Figure 5.
2. Pull the wires through the back of the mounting plate, ensuring none of the wire labels are removed. Figure 6.
C
Y
W
RH
G
Figure 6.
3. Using a Phillips Screwdriver, Partially install 1 screw into the top hole of the thermostat. Ensure the thermostat is level using the bubble level on the mounting plate Figure 7., then install the other screw. Tighten both screws until secure. Figure 8.
bubble level
Figure 7.
9. Set the system switch to “Conv” if you have a conventional HVAC system or “HP” if you have a heat pump system. Set the furnace type to “Elc” if you have an electric convention system or a heat pump. “Gas/Oil” will be used if you have gas or oil based conventional system. Figure 10.
Note: Conventional systems use the compressor for air
conditioning and a separate furnace for heat. Heat pump systems use the compressor for both heating and cooling.
Gas
Oil
Elc
Conv HP
H.P.
Cnv.
Elec Gas
Figure 10.
10. Lay the ribbon across the battery compartment and install 2 (AA) Batteries into the back of the thermostat over it, Figure
10., and snap the thermostat on to the mounting plate. Refer to “Setup” on page 10 of your owner’s manual to continue setup, scheduling, and daily use.
RH
W
Y
C
G
Figure 11.
Technical Support
If you have any additional questions or problems with your Hunter thermostat, please call:
USA: 1-888-830-1326
Figure 2.
©2010 Hunter Fan Company 44032-01 R20100414
Figure 8.
Hours of operation are from 7:00 am to 7:00 pm Monday - Friday and 8:00 am to 5:00 pm on Saturday, Central Time. You may also contact us over the Internet at www.hunterfan.com.
Canada: 1-866-268-1936
Figure 4.
Hunter Carrier Coleman Comfortmaker Bryant, Payne Rheem Ruud
R R R R R R R R R V-VR
Y Y or Y1 Y Y Y Y Y Y Y M
E W2 W2 W1 W2 W2 W W W1 Y
E E Jumper to W2 E E X2 Jumper to W2 E E
O O O O O O O R
B B B
G G G G G G G G G F
L L or F L L or X L L X L
C C X C, X, X1 C, X, X1 X B B C X
Trane,
Weathertron
York Lennox (1) Lennox (2)
HEAT PUMP
Single Stage Heat Pump
Jumper
R
Y
G
R
Y
G
Heat 24V Supply
Compressor Contact
Fan Relay
Wall
4 Wire Heat / Cool
Jumper
RH
RC
Y
G
W
RH
W
CONVENTIONAL
5 Wire Heat / Cool
Heat Power
Y
G
Cool Contactor
Fan Relay
Heat Contactor
Wall
RH
RC
Y
G
W
RH
RC
Y
G
W
Heat Power
Cool Power
Cool Contactor
Fan Relay
Heat Contactor
Wall
L
O
Cool Relay / Valve
O
B
ermostat Mounting Plate
W2
ermostat Mounting Plate
Y2
C
A
W2
Y2
C
A
Aux/E
ermostat Mounting Plate
Y2
C
Single Stage Heat Pump W/Aux Heat
Jumper
R
Compressor Contact
Y
G
L
O
E
C
may not be present.
Heat 24V Supply
Fan Relay
Wall
System Monitor*
Cool Relay / Valve
Auxiliary Heat
Common*
Jumper
RH
RC
W
3 Wire Cool Only
RC
Y
G
Y
G
Jumper
Cool Power
Cool Contactor
Fan Relay
Wall
3 Wire Heat Only
RH
RC
Y
G
W
RH
G
W
Heat Power
Fan Relay
Heat Contactor
R
Y
G
L
Wall
O
B
Aux/E
ermostat Mounting Plate
ermostat Mounting Plate
W2
ermostat Mounting Plate
Y2
C
A
W2
Y2
C
A
Y2
C
* The common wire “C” and system monitor wire “L” may or
Single Stage Heat Pump W/Heat Reversing
Jumper
R
Compressor Contact
Y
G
L
B
E
C
may not be present.
Heat 24V Supply
Fan Relay
Wall
System Monitor*
Heat Relay / Valve
Auxiliary Heat
Common*
Jumper
RH
RC
W
2 Wire Heat Only
RH
Y
G
W
Heat Power
Heat Contactor
Wall
3 Wire Hot Water with Damper Valve
Jumper
RH
RC
Y
G
W
RH
W
Heat Power
Heat Contactor
R
Y
G
L
Wall
O
B
Aux/E
ermostat Mounting Plate
ermostat Mounting Plate
W2
ermostat Mounting Plate
Y2
C
A
W2
Y2
C
A
A
Damper Valve
Y2
C
* The common wire “C” and system monitor wire “L” may or
Multi-Stage Heat Pump
4 Wire with Common
Jumper
RH
RC
Y
G
W
RH
Y
G
W
Heat Power
Cool Power
Cool Contactor
Fan Relay
Heat Contactor
Wall
Conventional Multi-Stage
Jumper
RH
RC
Y
G
W
RC
Y
G
W
Heat Power
Cool Contactor
Fan Relay
Heat Contactor
R
Y
G
L
Wall
O
B
Aux/E
ermostat Mounting Plate
ermostat Mounting Plate
W2
ermostat Mounting Plate
Y2
C
C
Common
A
W2
Y2
C
A
W2
Y2
Second Stage Heat Second Stage Cool
Y2
C
* The common wire “C” and system monitor wire “L” may or
Jumper
R
Compressor Contact
Y
G
L
Cool Relay / Valve
O
E
Second-Stage Cool
Y2
C
may not be present.
Heat 24V Supply
Fan Relay
Wall
System Monitor*
Auxiliary Heat
Common*
Loading...