Hunter Fan 43665 User Manual

Model 43665 Programmable Thermostat
44005-01 05/09/2007
1
Table of Contents
INTRODUCTION
INSTALLATION
PROGRAMMING
2
Weekday/Weekend Programming 22 7-Day Programming 25 Everyday Programming 27 Program Options 29
(continued)
Table of Contents (continued)
PROGRAMMING (continued)
OPERATIONS
3
Programmable Fan 29
OPERATIONS (continued)
TROUBLESHOOTING
WIRING DIAGRAMS
4
Read This Before Installing Thermostat
IMPORTANT
Read the entire installation section of this Owner’s
1
Manual thoroughly before you begin to install or oper-
ate your Hunter Thermostat.
Remove the Mylar label from the LCD display window.
INSTALLATION
All installation is normally performed at your
2
thermostat.
ARMCHAIR PROGRAMMING
You can program your thermostat before installation by
3
inserting the batteries and following the instructions starting on page 16. This can be done while you relax in your favorite chair and is a very good way to familiarize yourself with all the functions of your Hunter Thermostat.
SYSTEM COMPATIBILITY
Your Thermostat is designed to operate with most
4
gas, oil, electric, or 2-wire hot water heating and air conditioning systems. It will also operate single-stage heat pumps that do not have auxiliary or emergency heat. These have 24 volt or millivolt control systems and represent most central heating, air conditioning, or space heating units in the United States. This thermostat will not control 120/240 Volt systems or millivolt systems.
COMPRESSOR PROTECTION
The thermostat provides a 3.5 minute delay after shut-
5
ting o the heating or cooling system before it can be restarted. This feature will prevent damage to your com­pressor caused by rapid cycling.
5
TEMPERATURE RANGE
Your thermostat can be programmed between 45°F
6
and 95°F (7°C and 35°C). However, it will display room temperatures from 15°F to 99°F (-9°C and 37°C). “HI” will be displayed if the temperature is higher than 99°F (37°C), and “LO” will be displayed if the temperature is lower than 15°F (-9°C).
AUTO RECOVERY
Your thermostat is set from the factory to gradually
7
recover the room temperature from an energy saving program to your comfort program. Therefore, the ther­mostat may turn your system on several minutes prior to your programmed time. This operation is normal, but can be turned o. Refer to the Options Menu information on pages 16.
OPERATION
NOTE: The INDIGLO® Night-Light will not function when
8
the battery power is low.
BATTERY WARNING
Two fresh AA alkaline batteries should provide well
9
over one year of service. However, when the batteries become drained, the Low Battery Indicator will ash on the display. when this message occurs, install new alkaline bat-
teries. You have appoximately one minute to change the batteies and keep the thermostat’s clock and program set­tings. Once the batteries have become too low to ensure proper operation, your system will be turned o, and the display will be cleared except for the ashing Low Battery Indicator on the LCD display.
CAUTION: When only the battery Icon ashes on the display, the display, the thermostat is shut down and your
system will no longer operate. In this condition, there is no
6
REMOTE SENSORS (does not apply to thermostat model
44660)
Your thermostat can support 3 remote sensors that
1
will measure the temperature from three dierent locations - two indoor and one outdoor. To congure your thermostat to work with the remote sensors, follow the instructions for Sensor Channel selection on page 14 of this manual. To congure the remote sensors, consult the Remote Sensor Instruction Manual.
NOTE (does not apply to thermostat model 44660) This device complies with Part 15 of the FCC Rules. Operation
is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must ac­cept any interference received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reason­able protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accor­dance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment o and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit dierent from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
7
INSTALLATION
What You Need
This thermostat includes two #8 slotted screws and two wall anchors for mounting. To install your thermostat, you should have the following tools and materials.
Remove Old Thermostat
CAUTION: Do not remove any wiring from existing thermo­stat before reading the instructions carefully. WIRES MUST BE LABELED PRIOR TO REMOVAL.
IMPORTANT! Turn o the power to the furnace at the
main power panel or at the furnace.
Remove existing thermostat cover. See Figure 1. Some ther-
mostats will have screws or other locking devices that must rst be removed. Once wall mounting plate is exposed, look for wires.
If wires are not visible, they may be connected to the back of the wallplate. Again, look for screws, tabs, etc. Some models have doors that open to expose wires and mounting screws. (See Figure 1).
Slotted Screwdriver(s) ■ Electric drill and 3/16" bit
Phillips Screwdriver ■
Hammer
TYPICAL HOME THERMOSTATS
Wall Mounting Plate Thermostat Cover
Wall Mounting Plate Thermostat Cover
Two 1.5 V (AA) size alkaline batteries
Figure 1
8
9
Wire Labeling
Each wire coming from the wall to the existing thermo-
stat is connected to a terminal point on that thermostat. Each of these terminal points is usually marked with a code letter as shown in Table A on the next page.
IMPORTANT! BEFORE DISCONNECTING ANY WIRES, AP-
PLY THE SELF-ADHESIVE LABELS PROVIDED TO THE WIRE AS SHOWN IN TABLE A and B ON PAGES 12-13. (For ex­ample, attach the label marked W to the wire that goes to the W or H terminal on your existing thermostat.)
IGNORE THE COLOR OF THE WIRES since these do not always comply with the standard.
After labeling wires, disconnect them from the existing
thermostat terminals.
Remove existing wallplate. To make sure wires do not
fall back into wall opening, you may want to tape them to the wall.
If hole in wall is larger than necessary for wires, seal this
hole so that no hot or cold air can enter the back of the thermostat from the wall. This air could cause a false thermostat reading.
(continued)
INSTALLATION
G
W/B
Y1
Y/O
RC
RC1
RH
Y1
Mount Wallplate and Thermostat
Remove the wallplate from your thermostat by pressing
the release tab on the bottom of the thermostat. (See Figure 2.)
Position wallplate on wall and pull existing wires
through large opening. Then level for appearance. Mark holes for plastic anchors provided if your existing holes do not line up with those on the Hunter wallplate.
Figure 2
Drill holes with 3/16" bit and gently tap anchors into
the opening. Insert mounting screws provided into wall anchor and tighten. (See Figure 3.) holes until ush with wall.
Reposition wallplate to wall, pulling wires through large
opening. Insert provided mounting screws into wall an­chors and tighten.
Figure 3
10
11
Connect Wires and Mount Thermostat to Wallplate
Straighten bare end of each wire and cut or strip it to
1/4” maximum. Insert each labeled wire into its maching terminal.
Hold the wires in each terminal and tighten the terminal
screws securely, otherwise a loose wire could cause op­erational problems with your system or thermostat.
Push excess wire back into hole to prevent interference with
mounting of the thermostat.
Make sure the System Switch is set to OFF.
Insert two AA size alkaline batteries, observing the polarity
marked on the unit.
On the back of the thermostat, nd Switch SW1 at the lower
right-hand corner.
1) If your system is a gas furnace, then position the switch to HG.
2) If your system is an electric furnace, then position the switch to HG.
3) If your system is a single stage heat pump, then position the switch to SSHP.
Insert the upper tabs on the thermostat body into the
slot at the top of the wallplate. Press bottom of the ther­mostat body to snap it into the wallplate. (NOTE: Do not force the thermostat onto the wallplate, as the terminal pins may be damaged. If it does not snap properly, the thermostat may not work.)
Switch on the main power at the panel or furnace.
PROGRAMMING
Option Menu
Your thermostat has many settings that can be adjusted to t your system and preferences.
option
ret/clear
Language Selection
option
Battery Status
■ to see how much power remains in the
option
thermostat’s battery.
Press to enter the Option Menu and to change to the next option selection.
Press at any time to return to normal mode.
or to select English, Spanish, or French.
1
2
12
Fahrenheit or Celsius (F°/C°) selection
option
12 Hour or 24 Hour Clock selection
option
SPAN selection
option
or to change the SPAN setting to 1, 2, or 3. The
Auto Season Changeover Deadband
option
or to set the deadband between Heating and
3
or to change the thermostat display between Fahrenheit and Celsius.
4
or to change the time format display between 12 hour (AM / PM) and 24 hour (Military).
5
factory setting is 2. Setting 1 will cause shorter cycle times. Set­ting 3 will cause longer cycle times.
6
Cooling when the System Selection is set to Auto. See page 39 for more information on the Auto Season Changeover feature.
13
PROGRAMMING
Auto Recovery selection
option
or to enable “YES” or disable “NO” the Auto
■ To change between Heat or Cool recovery modes.
NOTE: Auto Recovery is one of the ENERGY STAR® features of this thermostat. Refer to the Auto Recovery section on pages 45-46 for more information.
Remote Sensor Channel (does not apply to thermostat model 44660)
■ to reach the Sensor Channel Set screen.
option
■ to select sensor for RF channel setting ( for Indoor 1, for
sensor
7
Recovery Mode. The factory setting is “YES.”
8
Indoor 2, or for Outdoor)
1
2
14
PROGRAMMING
15
or to set RF communication channel (1-15) for
■ If you do not have, or are not using the a second or outdoor re-
NOTE: The thermostat will not control your HVAC sysytem from the remote sensor set up as Outdoor . However, it is crucial that you DO NOT place remote sensor or outdoors.
LCD Contrast adjustment
option
or to change the LCD contrast between 0 and
the selected remote sensor.
mote sensor, set the channel to - -.
1
2
9
9. Lower numbers lighten the display. Higher numbers darken the display. The factory setting is 5.
Loading...
+ 34 hidden pages