Explanation of Symbols .............................................................. 33
CERTIFICATE OF CONFORMITY TO EUROPEAN DIRECTIVES ..34
3
XCORE COMPONENTS
LCD Display
1
2
3Station Number
4Program Designator
5Day of the Week
6Interval Watering
7Odd/Even Watering
8Flashing Sprinkler
9
10
11
12
13
14
Run Times
Start Times
System O
Umbrella
Seasonal Adjustment
Rain Drop
Crossed Rain Drop
Calendar
Allows user to set each valve station run time from 1 minute to 4 hours
Allows 1 to 4 start times to be set in each program
Indicates currently selected station number
Identies program (A, B, or C) in use
Identies day of the week
Identies month when programming current date
Identies if Odd or Even watering has been selected
Indicates that watering is taking place
Allows user to discontinue all programs and watering. Also allows the user to set the programmable
“rain o,” which stops watering for a period from 1 to 7 days.
Indicates that the rain sensor is active
Allows the user to make run time changes according to the seasons without reprogramming the controller.
Bars on the le allow quick visual reference to the seasonal adjustment percentage. When using Solar Sync
ET Sensor, will display seasonal adjust updated daily by sensor.
Indicates watering will occur on the selected day
Indicates the watering will NOT occur on the selected day
Indicates interval watering schedule has been programmed. Icon also appears when programming the
current day
4
XCORE COMPONENTS
Wiring Compartment
15Lithium Battery
16Internal Junction BoxJunction box in outdoor models for making AC power connections
17Terminal StripUse to attach transformer, sensor, and valve wires from their source to the controller
18Reset ButtonUse to reset the controller (located on right side of controller)
19REMAllows for connection of Hunter SmartPort
20Sensor Bypass Switch
Control Buttons
ButtonIncreases the selected item ashing in the display
ButtonDecreases the selected item ashing in the display
Button
Button
Button
The replaceable lithium battery (included) allows the controller to be programmed in the absence
of AC power. In addition, the battery will provide power for backup timekeeping in the event of a
power outage.
®
and Hunter Remote Controls
Ignores “Clik” weather sensor input when in Bypass position
Returns selected ashing display to previous item
Advances the selected ashing display to the next item
Selects program A, B, or C for dierent watering zone requirements
55
XCORE COMPONENTS
Indoor Model
Note: Plug may
look dierent from
illustration
Outdoor Model
(Internal Transformer
Included)
Terminal
block for -E
(International
6
models only)
6
XCORE COMPONENTS
Dial Settings
RunNormal dial position for all controller automatic and manual operation
Current Time/Day
Start Times
Run Times
Water Days
Seasonal Adjustment
Manual-One Station
1
System O
SOLAR SYNC Settings
External Transformer (Indoor Model Only)
Allows current day and clock time to be set
Allows 1 to 4 start times to be set in each program
Allows user to set each valve station run time from 1 minute to 4 hours
Allows the user to select interval days to water
Allows user to make run time changes according to the seasons without reprogramming the controller.
Bars on the le allow quick visual reference to the seasonal adjustment percentage.
Allows user to activate a one-time watering of a single valve
Allows user to discontinue all programs and watering. Also allows the user to set the programmable
“rain o,” which stops watering for a period from 1 to 7 days
Allows user to program settings when using Solar Sync ET Sensor
A plug in transformer is provided to supply AC power to the controller
7
MOUNTING THE CONTROLLER TO WALL
Note: The indoor version of the X-Core is not water-
proof or weather-resistant, and must be installed indoors
or in a protected area.
1. Secure one screw into the wall. Install screw anchors if attaching
to drywall or masonry wall.
2. Slide the keyhole on top of the controller over the screw.
3. Secure the controller in place by installing screws in the holes
below the terminal strip.
NOTE:Do not plug transformer into power source until
controller is mounted and all valve wiring has
been connected.
NOTE: For XC - x01 - A: If the supply cord is damaged, it
must be replaced by the manufacturer or service agent,
or a similarly qualied person in order to
avoid hazard.
NOTE: The door on outdoor units must remain closed
for maximum water resistance.
B
A
C
8
CONNECTING VALVES AND TRANSFORMER
Installation of the X-Core should only be done by trained personnel.
1. Route valve wires between the control valve location and controller.
2. At valves, attach a common wire to either solenoid wire on all
valves. This is most commonly a white colored wire. Attach a
separate control wire to the remaining wire of each valve. All
wire connections should be done using waterproof connectors.
3. Route the valve wires through the conduit. Attach the conduit
through the bottom right side of the controller.
4. Secure the white valve common wire to the C (Common) screw
on the terminal strip. Attach each of the individual valve control
wires to the appropriate station terminals and tighten their
screws.
5. Indoor Models: route the transformer cable through the hole on
the le side of the controller and connect the wires to the two
screws marked 24 VAC.
Outdoor Models: transformer wires are already connected to the
AC terminals so all that is required is to connect primary power
to the junction box (see below).
NOTE: X-Core outdoor models are water and
weather-resistant throughout document. Connecting
the outdoor X-Core to primary AC power should only be
done by a licensed electrician following all local codes.
Improper installation could result in shock or re hazard.
Valve 4
Valve 3
BAT
Valve 2
Valve 1
Connect the two transformer
wires to the two AC Terminals
High Voltage Wiring (Outdoor Model only)
Valve
Wires
Valve Common Wire
1. Route AC power cable and conduit through the ½" (13 mm)
conduit opening on the le side bottom of the cabinet.
2. Connect one wire to each of the two wires inside the junction
box. The ground wire should be connected to the green wire.
Wire nuts are provided to make these connections.
Note: For –E models only: Connect the wires to the AC
terminal block inside the junction box. AC supply wires must
be 14 AWG (1.85 mm) or larger with appropriate circuit breaker
for the wire size. A switch or circuit-breaker shall be included
in the building installation (in close proximity to the controller,
within easy reach of the operator) and marked as the disconnecting device for the equipment.
3. Replace the junction box cover.
9
ACTIVATING THE BATTERY
Battery Compartment
Lithium Battery
Aer installing your X-Core, make sure to remove the battery
contact insulator to allow the X-Core to keep time in the event of
a power outage.
CAUTION:
RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN
INCORRECT TYPE. DISPOSE OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS.
REPLACING THE BATTERY
A high-energy lithium battery is included with your X-Core
controller. The battery allows the user to remotely program the
controller without connecting AC power. It is also used to keep
the current time and day during power outage conditions.
To replace the battery:
1. Remove the screw from the battery holder.
2. Slide the battery holder down to access the battery.
3. Remove and replace the new battery into the battery holder
and reinstall the battery holder.
NOTE: This positive(+) side of the battery should face
the inside of the battery holder.
Battery
(--)
Battery type: CR2032 3V
(+)
Holder
24VA C
SEN C P 1 2 3 4 5 6 7 8
BAT
10
CONNECTING A MASTER VALVE
NOTE: Complete this section only if you have a
master valve installed in your irrigation system. A
master valve is a “normally closed” valve installed at the
supply point of the main line that opens only when the
controller initiates a watering program.
1.
At the Master Valve, attach the common wire to either solenoid
wire of the valve. Attach a separate control wire to the remaining
solenoid wire.
2. The common wire should be attached to the C terminal inside the
controller. The other wire coming from the master valve should
be attached to the P terminal inside the controller. Tighten each
terminal screw.
Valve 4
24VA C
SENCP12345678
BAT
Master
Valve Wire
Master Valve
Valve 3
Valve 2
Valve 1
Valve Wires
Valve Common Wire
11
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.