CE Notice ................................................................................... 15
ENG
2
SEASONAL ADJUSTMENT
WATER DAYS
ALL
MANUAL-ALL STATIONS
START TIMES
SYSTEM OFF
CURRENT TIME/DAY
1
MANUAL-ONE STATION
RUN TIMES
ACTIVE
SENSOR BYPASS
RUN
SEASONAL ADJUSTMENT
WATER DAYS
ALL
MANUAL-ALL STATIONS
START TIMES
SYSTEM OFF
CURRENT TIME/DAY
1
MANUAL-ONE STATION
RUN TIMES
ACTIVE
SENSOR BYPASS
RUN
ENG
XC COMPONENTS
2 3
4 6
1
AM PM
%24HR
MO TU WE TH FR SA SU ODD
EVEN
2,4...30
1,3...29
9 11
8
7
A
C
PRG
A
C
PRG
13
Note: Plug may
look different from
Illustration.
1
10 5 12
14
D
24VAC
RST
18
Indoor Model
SEN C P 1 2 3 4 5 6 7 8
BAT
B
15
17
SENSOR BYPASS
ACTIVE
SEN C P 1 2 3 4 5 6 7 8
24VAC
BAT
RST
15
18
16
Terminal block
for -E (International
models only)
B
19
17
Outdoor Model
(Internal Transformer Included)
ENG
A – LCD Display
1. Run Times – Allows user to set each valve station run time
from 1 minute to 4 hours.
2. Start Times – Allows 1 to 4 start times to be set in each
program.
3. Station Number – Indicates currently selected station number.
4. Program Designator – Identifies program (A, B, or C) in use.
5. Day of the Week – Identifies day of the week
6. Interval Watering – Identifies month when programming current date.
7. Odd/Even Watering – Identifies if Odd or Even watering has been
selected.
8. Flashing Sprinkler – Indicates that watering is taking place.
9. System Off – Allows user to discontinue all programs and
watering. Also allows the user to set the programmable "rain off"
which stops watering for a period from 1 to 7 days.
10. Umbrella – Indicates that the rain sensor is active.
11. Seasonal Adjustment – Allows the user to make run time
changes according to the seasons without reprogramming the
controller. Bars on the left allow quick visual reference to the
seasonal adjustment percentage.
12. Rain Drop – Indicates watering will occur on the selected day.
13. Crossed Rain Drop – Indicates the watering will NOT occur on
the selected day.
14. Calendar – Indicates interval watering schedule has been
programmed. Icon also appears when programming the current day.
B – Wiring Compartment
15. Lithium Battery – The replaceable lithium battery (included) allows
the controller to be programmed in the absence of AC power. In
addition, the battery will provide power for backup timekeeping in
the event of a power outage.
16. Internal Junction Box – Junction box in outdoor models for
making AC power connections.
17. Terminal Strip – Use to attach transformer, sensor, and valve wires from
their source to the controller.
18. Reset Button – Use to reset the controller.
C – Control Buttons
Button – Increases the selected item flashing in the display.
Button – Decreases the selected item flashing in the display.
Button – Returns selected flashing display to previous item.
Button – Advances the selected flashing display to the next item.
Button – Selects program A, B or C for different watering zone
requirements.
19. Sensor Bypass Switch.
Dial Settings
Run – Normal dial position for all controller automatic and manual
operation.
Current Time/Day – Allows current day and clock time to be set.
Start Times – Allows 1 to 4 start times to be set in each program.
Run Times – Allows user to set each valve station run time from 1
minute to 4 hours.
Water Days – Allows the user to select interval days to water.
Seasonal Adjustment – Allows user to make run time changes ac-
cording to the seasons without reprogramming the controller. Bars
on the left allow quick visual reference to the seasonal adjustment
percentage.
Manual-One Station – Allows user to activate a one-time watering
1
of a single valve.
ALL
Manual-All Stations – Allows user to activate a one-time watering
of all valve stations or a few selected stations.
System Off – Allows user to discontinue all programs and water-
ing. Also allows the user to set the programmable rain off which
stops watering for a period from 1 to 7 days.
D – External Transformer (Indoor Model only)
A plug in transformer is provided to supply AC power to the controller.
2
SEN C P 1 2 3 4 5 6 7 8
RST
24VAC
BAT
Valve Common Wire
Connect the Two
Transformer Wires to
the Two AC Terminals
Valve 1
Valve 2
Valve 3
Valve 4
Valve
Wires
ENG
MOUNTING THE CONTROLLER TO WALL
NOTE: The indoor XC is not waterproof or weather resistant, and must be installed indoors or in a protected area.
1. Secure one screw into the wall. Install screw anchors if attaching
to drywall or masonry wall.
2. Slide the keyhole on top of the controller over the screw.
3. Secure the controller in place by installing screws in the holes
below the terminal strip.
Do not plug transformer into power source until control ler is mounted and all valve wiring has been connected.
CONNECTING VALVES AND TRANSFORMER
Installation of the XC should only be done by trained personnel.
1. Route valve wires between the control valve location and controller.
2. At valves, attach a common wire to either solenoid wire on all
valves. This is most commonly a white colored wire. Attach a
separate control wire to the remaining wire of each valve. All wire
connections should be done using waterproof connectors.
3. Route the valve wires through the conduit. Attach the conduit
through the bottom right side of the controller.
4. Secure the white valve common wire to the C (Common) screw on
the terminal strip. Attach each of the individual valve control wires
to the appropriate station terminals and tighten their screws.
5. Indoor Models: route the transformer cable through the hole on
the left side of the controller and connect the wires to the two
screws marked 24VAC.
Outdoor Models: transformer wires are already connected to the
AC terminals so all that is required is to connect primary power to
the junction box (see below).
E – High Voltage Wiring (Outdoor Model only)
NOTE: XC outdoor models are water and weather resis tant. Connecting the outdoor XC to primary AC power
should only be done by a licensed electrician following
all local codes. Improper installation could result in
shock or fire hazard.
1. Route AC power cable and conduit through the ½" (13mm) conduit
opening on the left side bottom of the cabinet.
2. Connect one wire to each of the two wires inside the junction box.
The ground wire should be connected to the green wire. Wire nuts
are provided to make these connections. Note: For –E models only: Connect the wires to the AC terminal block inside the junction box. AC supply wires must be 14 AWG (1.85 mm) or larger
with appropriate circuit breaker for the wire size. A switch or circuit-breaker shall be included in the building installation (in close
proximity to the controller, within easy reach of the operator) and
marked as the disconnecting device for the equipment.
3. Replace the junction box cover.
ACTIVATING THE BATTERY
After installing your XC make sure to remove the batter y contact insulator to allow the XC to keep time in
the event of a power outage.
3
ENG
REPLACING THE BATTERY
A high-energy lithium battery is included with your
XC controller. The batter y allows the user to remotely
program the controller without connecting AC power.
It is also used to keep the current time and day during
power outage conditions. To replace the battery:
1. Remove the screw from the battery holder.
2. Slide the battery holder down to
access the battery.
24VAC
RST
3. Remove and replace the new battery
into the batter y holder and reinstall the
battery holder.
BAT
NOTE: This positive(+) side of the battery should face
the inside of the battery holder.
Battery type: CR2032 3V
CONNECTING A MASTER VALVE
NOTE: Complete this section only if you have a master
valve installed in your irrigation system. A master valve
is a "normally closed" valve installed at the supply point
of the main line that opens only when the controller
initiates a watering program.
1. At the Master Valve,
attach the common wire
to either solenoid wire
of the valve. Attach a
separate control wire to
the remaining solenoid
wire.
24VAC
BAT
RST
Master Valve Wire
Master Valve
SEN C P 1 2 3 4 5 6 7 8
Valve Common Wire
Lithium Battery
Battery
(--)
Battery Compartment
SEN C P 1 2 3 4 5 6 7 8
Valve 4
Valve 3
Valve 2
Valve
Wires
Valve 1
2. The common wire should be attached to the C terminal inside the
controller. The other wire coming from the master valve should be
(+)
Holder
attached to the P terminal inside the controller. Tighten each terminal screw.
CONNECTING A PUMP START RELAY
NOTE: Complete this section only if you have a pump
start relay installed. A pump start relay is a device that
uses a signal from the controller to actuate a separate
electrical circuit to energize a pump to provide water to
your system.
The controller should be mounted at least a 15 ft (4.5 m) away from
both the pump start relay and pump to minimize any potential electrical interference.
1. Route a pair of wires from the pump relay into the controller.
2. Connect a common wire to the C (Common) terminal inside the
controller and connect the remaining wire from the pump start
relay to the P terminal.
Relay holding current draw must not exceed .30 amps. Do not connect
the controller directly to the pump or damage to the controller will result.
PSR Series
Pump Start Relay
4.5 Met ers Minimum (15')
To Pump
XC
RUN
SENSOR BYPASS
SYSTEM OFF
CURRENT TIME/DAY
MANUAL-ALL STATIONS
MANUAL-ONE STATION
ACTIVE
ALL
START TIMES
1
RUN TIMES
SEASONAL ADJUSTMENT
WATER DAYS
4
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.