VSX Series Specifications.................................................................................................................. 47
The VSX controller may be used as a
standalone controller for up to 60 stations, or
103 stations in a decoder system. It may also
be part of a central system, connected to a
central computer via radio or hardwire communications. You can upgrade a standalone
VSX controller to a networked controller at
any time, by adding communications kits and
connecting it to a central computer.
Two Controllers in One: The VSX actually
has two different “brains” for storing and
running two different kinds of irrigation
programs. The keypad on the controller can
create and run Field Controller Programs in
one brain. An optional central control system, with a computer and communications,
can create and transmit System Programs to
the other brain.
Page 4
Field Controller Programs
VSX OPERATING MANUAL
Field Controller Programs (FCPs) are the
Programs numbered 1 through 64, which you
can write from the keypad or the central computer. You can change them in the field at any
time. They will run at the start times you
specify and do exactly what you tell each one
to do. They can also be remote-controlled from
the VSX Express central computer software, if
a central is installed.
Most of this manual is concerned with configuring and operating FCPs through the keypad.
System Programs
System Programs are calculated by the Surveyor or Vista control software, and downloaded from the central computer to each field
controller. They are often based on automatic
calculation from local weather conditions (ET,
or evapo-transpiration), and they are almost
always Flow Optimized. You can view the
System Programs in each Field Controller, but
you may not edit them there. You can also
delete the System Program information from a
Field Controller, but you must replace it with
FCPs or the controller will not irrigate.
Generally, FCPs are used as the primary
irrigation programs during grow-in (when there
may not be a central computer), and are used
later on for special purposes, after the central
computer has taken over the primary daily
irrigation. They can be used to germinate seed
in repair areas, or for other special cases where
the superintendent desires absolute control
over each irrigation event.
Computerized System Programs are designed
to operate the largest systems, more or less
automatically. The superintendent can modify
their general parameters at any time, but they
handle the details of irrigation events internally. Computerized System Programs do not
need to be micro-managed (station by station);
they only need to be adjusted in groups of
similar stations (All Greens, Hole 14 Tee, etc.).
Detailed instructions on System Programs are
provided in the software manual for the central
software.
Why two different kinds of Programs?
Different superintendents manage their irrigation in different ways, and irrigation systems go
through many different phases in their annual
cycle. The VSX Field Controller is equipped to
handle every phase of irrigation, including
grow-in, seasonal changes, overseeding, winterization, and special applications like fertilization, frost control, and dew wipe.
5
Page 5
®
VSX Option & Settings Displays
Options
(Press Options
button from
time/date display)
Pause W atering
List FC Settings
Edit FC Settings
Block Programming
Create
Edit
Remove
Remove Program
Remove Preset
Edit Decoders (decoder
controllers only)
V iew SYS Events
Rem SYS Events
Radio Xmit Test
(Radio controllers only)
Edit FC Settings
(From Options,
Edit FC Settings)
Address
Time
Date
Main % Scale
Schedule Length
Schedule Day
Day Change
FCP Inhibit?
Response
MR Runtime
MR Pump
PINs
Program Options
(Options when a
Program or Preset
name is selected)
Edit Program Name
Set Program % Scale
Cycles
Cycle Delay
Skip Days
Pump
Schedule Options
(Options when
Schedule is
selected)
Daily (up to 31-day
schedule)
Day of Week
(SMTWTFS)
1.Stops all irrigation; enables and disables Rain Shutdown.
2.Sets run times and order for stations and Blocks.
3.Accesses multiple options and controller settings.
Different sets of options appear, depending on mode
controller is in (with other keys).
4.Saves field inputs and edits.
5.Selects between fixed choices in the display, and selects
Rain Shutdown yes/no when Off is pressed.
6.Alphanumeric buttons for data entry.
7.Clears display error messages; erases Program Name in
Edit mode.
6
8.Determines type of schedule and actual water days On/Off
for the selected Program
9.Navigate backward/forward through displays, Programs,
and Option choices.
10. Defines Start Time for automatic Programs; launches
Preset programs immediately..
11. Starts one or more stations immediately.
12. Cycles through available Preset names, allows access for
creation or editing, or immediate start with Start button.
13. Cycles through available Program names, allows access
for creation or editing, or immediate start with Start button.
14. Escapes current function and exits to next highest level.
Page 6
Programming & Operations
VSX OPERATING MANUAL
Note: The VSX keypad display has a built-in
timer, and will automatically exit any programming mode after 3 minutes if left untouched. If you are using the password
protection feature, you will be required to log
back in, once this has happened. Any data not
saved will be lost if the controller auto-exits.
Emergency Functions (OFF and Pause):
OFF: If you need to stop all irrigation at a
controller immediately, press the OFF button
to the right of the display. You may see a brief
message, STOPPING ALL IRRIGATION,
followed by:
Rain Shutdown: Rain Shutdown turns off all
automatic functions, permanently, until a
human operator manually removes the controller from the Rain Shutdown mode (from
the VSX keypad or a central computer). If
you want to enter the Rain Shutdown mode,
press ENTER. The display will show:
If you do NOT want to enter Rain Shutdown,
press the OFF button again (upper right of
the keypad) or any other button except
ENTER. This will simply shut down all
current irrigation until the next scheduled
Start Time. Note that if another automatic
Program was scheduled to start one minute
later, the controller will begin irrigating
again in one minute.
To turn off Rain Shutdown (and restore the
controller to automatic operations): When the
display shows RAIN SHUTDOWN!, press
OFF. The display will show:
Press ENTER, and the controller will return to
the automatic mode.
Pause: The VSX controller features dynamic
pause, which will suspend all irrigation at the
controller temporarily. This will apply to
manual, semi-automatic, automatic, and Preset
Programs. The irrigation will remain paused
until resumed by a human operator or until 30
minutes have elapsed. The controller will
resume irrigating where it left off.
You will have to remember to place the
controller back into automatic operation
when irrigation is required again.
Note that Pause will cause the end of the
“water window” to be ignored – the end time
of the paused Program will be pushed back for
the duration of the Pause.
7
Page 7
®
To Pause a controller: Press OPTIONS. The
display will show:
Press ENTER to select this Option. The display
will show:
“YES” will be capitalized. To Pause the controller,
press ENTER. The display will then show:
To Resume watering, press ENTER while the
display says Resume Watering? The display
will then show:
the controller into Pause, it will automatically
resume after 30 minutes.
(The “no” selections will be in lower case.
Press the TOGGLE button to switch between
YES and NO. If you do not want to pause/
resume the irrigation, TOGGLE to NO and
press ENTER, or simply press EXIT.)
Controller Setup
When you start up a brand new VSX controller,
or if you have erased the controller memory
and are reprogramming from scratch, you must
set up some basic operating information first.
Press the OPTIONS button. The display will
show “Pause Watering?”
Press the OPTIONS button again. The display
will show “List FC Settings?”
Press ENTER. The display will automatically
sequence the current information for the field
controller in the following format:
Press ENTER with YES capitalized, and the
controller will resume irrigating where it left
off when you paused it. No irrigation will be
missed. After 3 minutes, the Resume W atering?
display will disappear, but the display will
continue to flash PAUSE with the amount of
time left to automatic resume. Press OPTIONS
to return to the Resume Watering? display.
Note that if the controller was paused for 20
minutes, the currently active and any subsequent
stations will be moved back in time 20 minutes.
If the Program would normally have ended at
5:30 AM, it would now end at 5:50 AM.
If you forget to Resume irrigation after placing
Version number: The version of field controller software installed in the VSX.
Time: On start up, this may be incorrect, but it
will show the time of day that VSX thinks it is.
Date: On start up, this may be incorrect, but it
will show the day of week and year that VSX
thinks it is.
Size: This will show how many stations the
VSX can operate, and in conventional systems
it will either be 20, 30, 40, 50, or 60. You may
expand the VSX controller hardware in increments of 10 stations at any time, up to a maximum of 60 stations. In decoder systems, the
Size will always be 103.
AC: Shows the frequency of the incoming AC
power . This is a very important setting, since
the VSX uses the AC power frequency to count
time. North American systems are generally set
to 60 Hz (Hertz). Many international systems
are set to 50 Hz. If you are not sure which
8
Page 8
VSX OPERATING MANUAL
VSX Field Controller Options:
setting to use, consult a local licensed electrician for the correct value. Refer to the installation
instructions if you need to change this setting.
Address: The unique identification number for
a particular VSX controller in a central system.
If your controller is a standalone, you may
leave this set to “0” unless you plan to use it
with Maintenance Radio.
Main Scale: Indicates that the controller will
operate each station for 100% of its scheduled
Run Time.
Cur Sch Len: A VSX may be programmed on
a multiple day schedule (from 1 to 31 days).
This shows the actual schedule length of the
controller.
Cur Sch Day: This shows which day (of the
schedule in the previous setting) that the controller thinks it is – in this case, day 1 of a
1-day schedule.
Day Change: The time at which the schedule
day changes. The default is midnight, but you
may change the time of day-change to any hour
of the day.
Inhibit is OFF: This setting is only meaningful
in central systems, and shows the status of the
Field Controller Programs (FCPs). If they have
been inhibited, they will not run.
Response: This setting is only meaningful in
central systems, and shows how much communicating the VSX controller will perform with
the central computer.
MR Run Time: This is the default time-out for
stations started with Maintenance Radio without a run time specified. If you forget to turn
the station off, VSX will turn it of f for you in
30 minutes.
MR Pump: This specifies whether the Pump
output turns on whenever a station is started by
a Maintenance Radio command.
Current ET Day: This is only used in central
systems which calculate “look ahead” schedules based on evapo-transpiration rates, and
download them to the controller. This display
will indicate which day of the ET schedule you
are on.
When the controller has finished sequencing
through the FC Settings, it will show the current
day and time. There may be a “POWEROUTAGE” message flashing in the display.
Press the CLEAR button to clear this message.
If you continue to press the OPTIONS button,
you will cycle through all of the available
controller options:
Pause Watering? Stops irrigation temporarily;
restarts where it left off.
List FC Settings? Automatically displays vital
Field Controller settings.
Edit FC Settings? Allows you to change vital
Field Controller settings.
Block Prgraming? Allows you to group
multiple stations into a single “block” for
programming purposes. See Blocks on page 23.
Remove Program? Allows you to delete a
single program, including all station run times.
Remove Preset? Allows you to delete a single
Preset, including all station run times.
Edit Decoders? Allows setup and/or changes
to decoder/station assignments.
View SYS Events? Allows you to view the
downloaded System Program events.
Del SYS Events? Allows you to delete the
downloaded System Program events.
Radio Xmit Test? (Radio controllers only)
Generates a 5-second test tone for diagnostics.
Edit FC Settings: Of all the Field Controller
options, this is the most vital to set up on a
new installation. Many of the powerful
features of VSX will not work, or will not
9
Page 9
®
work as intended, until these settings are
made.
Press OPTIONS 3 times and the display will
show “Edit FC Settings?” In this menu, you
are able to change many of the settings displayed in the “List FC Settings” menu above.
Press ENTER, and the display will show “Set
Address?”
You may now press ENTER, to set or change
the Address, or press OPTIONS again, to view
further settings. You can also use the BACK
and NEXT buttons to move backward and
forward through the settings. Whenever the
display shows a setting you want to change,
press ENTER to edit it.
Set Address: Your VSX Field Controller
cannot communicate with Maintenance Radio
or a central system until it has an Address. Each
controller must have a unique 3-digit number,
so that the central interface and/or Maintenance
Radio can direct communications to the correct
controller. In central systems you will also need
to make sure that a list of correct Field Controller addresses is configured in the central software.
If your VSX controller is a standalone, and you
are not using Maintenance Radio, the Address
is not necessary.
bered. However, each controller must have a
unique address. If more than one controller has
the same numeric address, the system will
become confused and errors will occur.
Once the address is set, you may use the
OPTIONS, BACK, or NEXT buttons to view
more options, or you may press EXIT to leave
the Edit Settings mode.
The other changeable settings are:
Set Time?: To set the time, press ENTER. The
display will show:
Type the correct time (1:15, for example, in
hour, then minute format), and press ENTER.
The display will show:
The current am/pm selection will be capitalized. The other selection will be in lower case.
Press the TOGGLE button to switch between
AM and PM. When it is correct, press ENTER.
The display will show:
When the display shows “Set Address?”, press
ENTER. The display will show:
Type the address you want with the number
buttons on the keypad and press ENTER. The
display will show “SAVED! Address = 2”.
The address is now saved. You can use any 3digit number, and controllers in a central
system do not need to be sequentially num-
10
Press ENTER to set the time. The display will
briefly show SAVED! and the time you have
set. After a moment, the display will revert to:
Page 10
VSX OPERATING MANUAL
You may now press the OPTIONS, BACK, or
NEXT buttons to view more options, or you may
press EXIT to leave the Edit Settings mode.
Set Date: To set the Date, press ENTER at this
display. The display will then show:
Note: VSX dates are always shown in North
American format (month/day/year).
T ype the number for the correct month (1-12), in
this case “3” for March, and press ENTER (you
can also use the BACK/NEXT buttons to move
around in the Date). The display will then show:
You may now press the OPTIONS, BACK, or
NEXT buttons to view more options, or you may
press EXIT to leave the Edit Settings mode.
Set Main % Scale: “% Scale” allows you to
reduce or increase all of the Run Times in the
controller by the selected percentage (from 1 to
250%, in 1% increments). This enables you to
quickly adjust the amount of irrigation for
weather or other conditions without changing
the basic programs. At 50%, each Run Time
will only run half as long, and at 150%, each
Run Time will run one-and-half times as long.
Note: In the Program Options, you can also
scale individual Programs separately. The
effects of % scaling are cumulative. See Set
Program % Scale on page 30.
To set the Main % Scale from the Edit FC
Settings mode, press ENTER at this display.
The display will then show:
Type the number for today’s date (“8” in this
example), and press ENTER. The display will
show:
Type the correct year, and press ENTER. The
display will show:
Press ENTER to set the date. The display will
briefly show SAVED! and the date you have
set. After a moment, the display will revert to:
Type the percentage you want with the number
buttons on the keypad, and press ENTER. The
display will briefly show “SAVED!” and the
new % Scale amount. After a moment, the
display will revert to:
You may now press the OPTIONS, BACK, or
NEXT buttons to view more options, or you may
press EXIT to leave the Edit Settings mode.
Note that, whenever the controller is scaled up
or down (to any value other than 100%), a “+”
or “-” sign will appear as a reminder in the
upper left corner of the status display (before
the Day and Time information).
11
Page 11
®
Once the Main % Scale has been changed, the
scaled run times for all stations will be displayed when the Stations button is pressed in
any Program. To return to the original (or base)
run times, repeat the procedure above and
change the Main % Scale to 100%.
Set Schedule Length: The Schedule Length is
the number of days in a complete VSX watering
period, and allows the controller to track programs which do not water every day. If you
only water a certain plant type every other day,
for example, you could enter a 2-day Schedule,
and schedule that program to water on just one
of the days. The Schedule Length is tracked for
the entire controller. To set the watering Schedule for individual programs, go to the individual
Program and press SCHEDULE (see Schedule
on page 16).
If you are not sure what schedule you need,
start out with a 7-day schedule (so that it
matches the number of days in a calendar
week). You can always change it later.
If you always water everything every day , you
can also just set a 1-Day schedule.
To set the Schedule Length: Press ENTER at
the “Set Sched Len?” display. The display will
then show:
You may now press the OPTIONS, BACK, or
NEXT buttons to view more options, or you may
press EXIT to leave the Edit Settings mode.
Set Schedule Day: The Schedule Day shows
which day of the Schedule the controller thinks
it is. For example, if you had set a 7-day schedule for a Schedule Length (above), you could
tell the controller that today is Day 1 of the 7Day Schedule, meaning Sunday. If today
happens to be Wednesday, you could tell it that
today is Day 4 (of the 7-day schedule).
Another example would be if most of your
irrigation occurred every day, but a few programs only run every other day (regardless of
the day of the week). You could set up a 2-day
Schedule Length, and then tell the controller
which of the two days today is (1 or 2). In the
Program Schedule (see Schedule on page 17)
you can specify which days the individual
Programs will water .
To set the Schedule Day (for today): Press
ENTER at the “Set Sched Day?” display. The
display will then show:
The default Schedule Length is 14 days: the
maximum is 31 days. Type the number of the
new Schedule Length with the number buttons
on the keypad, and press ENTER. The display
will briefly show “SAVED!” and the new
Schedule Length selection. After a moment, the
display will revert to:
12
Type the number of the new Schedule Day with
the number buttons on the keypad, and press
ENTER. The display will briefly show
“SAVED!” and the new Schedule Day selection. After a moment, the display will revert to:
Page 12
You may now press the OPTIONS, BACK, or
NEXT buttons to view more options, or you may
press EXIT to leave the Edit Settings mode.
VSX OPERATING MANUAL
Set Day Change: The programmable Time of
Day Change option allows you to tell the
controller at what time one day changes into
another, when using the Daily Schedule option.
The default is, of course, midnight (12am).
However, this occurs right during the middle of
many irrigation cycles. If you water a certain
Program every other day, and the irrigation
spans across midnight with multiple cycles, you
may lose the portion of the irrigation which
technically falls on a non-irrigation day.
To prevent this and similar confusion, you may
specify a different hour for your irrigation days
to change. Usually this is done after all irrigation is completed. If your night’s irrigation is
completed by 7 in the morning, you might wish
to set the Day Change to 8:00am. Then, all of
your irrigation will fall within a single irrigation
day.
Note: Time of Day Change only applies to
Daily schedules. Day of Week schedules always
change at midnight.
You may only set the Day Change to an exact
hour (no minutes).
To set the Day Change: Press ENTER at the
“Set Day Change?” display. The display will
then show:
The current selection will be capitalized. Other
selections will be in lower case. Press the
TOGGLE button to switch between AM and
PM. When it is correct, press ENTER. The
display will show:
Press ENTER to set the Day Change. The
display will briefly show SAVED! and the time
of Day Change hour you have set. After a
moment, the display will revert to:
You may now press the OPTIONS, BACK, or
NEXT buttons to view more options, or you may
press EXIT to leave the Edit Settings mode.
Set FCP Inhibit?: FCPs (Field Controller
Programs) are the Programs numbered from 1
through 64 in the Field Controller. The controllers may also irrigate with a master system
program from the central computer, which is
independent of the FCPs, and both types of
programs may run at the same time.
FCP Inhibit will prevent all of the numbered
FCPs from running, so that the only irrigation
will be that sent out by the central computer’s
master system program.
Type the number for the Day Change hour (8,
in this example) with the number buttons on
the keypad, and press ENTER. The display
will show:
Remember that FCP Inhibit ON means the
FCPs will NOT run. FCP Inhibit set to OFF
means the FCPs will run normally.
13
Page 13
®
T o set FCP Inhibit: Press ENTER at the “Set FCP
Inhibit?” display . The display will then show:
The current selection will be capitalized (default is OFF). The “on” selection will be in
lower case. Press the TOGGLE button to switch
between OFF and ON. When it is correct, press
ENTER. The display will flash “SAVED!” and
your selection. After a moment, the display will
revert to:
The current selection will be capitalized
(default is PARTIAL). The “full” selection will
be in lower case. Press the TOGGLE button to
switch between PARTIAL and FULL. When it
is correct, press ENTER. The display will flash
“SAVED!” and your selection. After a moment,
the display will revert to:
You may now press the OPTIONS, BACK or
NEXTbuttons to view more options, or you may
press EXIT to leave the Edit Settings mode.
Set Response?: This will set the level of Field
Controller response to the central computer (if
it is present and communicating). In the Partial
Response setting, the field controller will report
any alarm conditions (such as Fuse Open,
Overload, Power Outage, etc.) if they occur .
In the Full Response setting, the Field Controller will report all events as they occur, including every station start and station stop, as well
as alarms. Full Response will also continuously
update the Station Status Display on the central
computer.
If full reports are not desired, or cause too
much communications “chatter”, you can set
this to Partial.
You may now press the OPTIONS, BACK, or
NEXT buttons to view more options, or you may
press EXIT to leave the Edit Settings mode.
Set MR Runtime?: MR = Maintenance
Radio. This determines the time-out timer
setting for stations started by Maintenance
Radio without specified Run Times.
If you simply start a station with Maintenance
Radio without a specific run time (see Sending
a Maintenance Radio command on page 41)
and forget to turn it off, this setting will automatically shut it off after the time shown, to
prevent flooding and damage. The default
value is 30 minutes. You may select a longer or
shorter setting, from 1 minute to 18 hours, for
this safety feature.
To set MR Runtime: Press ENTER at the
“Set MR Runtime?” display. The display will
then show:
To set Response: Press ENTER at the “Set
Response?” display . The display will then show:
14
Type the number for the default Maintenance
Radio timer (example: 20 minutes) with the
Page 14
VSX OPERATING MANUAL
number buttons on the keypad, and press
ENTER. The display will show:
Press ENTER to set the MR Runtime. The
display will briefly show SAVED! and the MR
Runtime you have set. After a moment, the
display will revert to:
You may now press the OPTIONS, BACK, or
NEXT buttons to view more options, or you may
press EXIT to leave the Edit Settings mode.
Set MR Pump?: MR = Maintenance Radio.
This determines whether the Pump output in
the Field Controller will be activated whenever
Maintenance Radio starts stations. If you are
using the Pump output to activate a Pump Start
Relay or a Master Valve, you can choose to
have that output come on whenever a Maintenance Radio command starts a station.
You may now press the OPTIONS, BACK, or
NEXT buttons to view more options, or you may
press EXIT to leave the Edit Settings mode.
Set PINS: The VSX controller has 2 levels of
optional password protection:
The Supervisor level can perform all programming functions.
The Operator level can perform basic functions
(START and STOP commands) which do not
affect the automatic programs and their options.
Each level of access can be protected by a
4-digit Personal Identification Number (PIN).
To set PINs: Press ENTER at the “Set PINs?”
display. The display will then show:
T ype any 4 digits (there must be exactly four,
from 0001 to 9999) which you will be able to
remember, and press ENTER. The display will
show:
To set MR Pump: Press ENTER at the “Set MRPump?” display. The display will then show:
The current selection will be capitalized (default is YES). The “no” selection will be in
lower case. Press the TOGGLE button to
switch between YES and NO. When it is
correct, press ENTER. The display will flash
“SAVED!” and your selection. After a moment,
the display will revert to:
T ype exactly the same PIN number again and
press ENTER. The display will show “SAVED!”.
If you fail to enter the same number the second
time, the display will show ERROR! You will
then need to reenter the PIN and enter the
confirmation a second time.
Once the PIN has been entered correctly, the
display will show:
15
Page 15
®
Writing a Field
Repeat the sequence above to enter an Operator’s
PIN number. You are not required to enter a
second level of password protection. If you do not
want an Operator level, simply press ENTER at
this display without entering anything.
If the second (verification) entry of either
Supervisor or Operator level PINs results in an
error, no PIN has been created.
You may change the passwords at any time, but
you must first log on to the controller with the
existing Supervisor-level PIN. If you forget
your PIN, you can clear the password settings.
Contact your distributor or Hunter Field Services for help to clear the password settings.
When you press the EXIT button at any time on
the keypad, it will exit the function you are in and
return to the next-highest level in the controller .
After you exit all the way back to the normal
time/date display , and press EXIT again, the
display will show “LOGGED OFF”. This means
that a valid PIN must be entered to log back on
before any programming or operations take place
(if PINs are enabled). If you do not log off when
finished, the controller will log off automatically
after 3 minutes of no activity .
When the PIN settings are complete, press
ENTER. The display will flash “SAVED!” and
your selection. After a moment, the display will
revert to:
You may now press the OPTIONS, BACK, or
NEXT buttons to view more options, or you may
press EXIT to leave the Edit Settings mode.
Controller Pr ogram
Press the PROGRAM SELECT button. The
display will show:
This indicates that you are in Program # 1,
with 0 out of 64 total Programs in use. The
numbers may vary if there are already programs in the controller’s memory. There may
already be a program name in place of the
dashes. You can edit any Program at any time.
For now, we will work on Program 1 as the
controller came “out of the box”.
Naming a Program:
Press the OPTIONS button. The display will
show “Edit Prg Name”?
Press ENTER. The bottom line of the display
will show “Alpha entry mode”, and the cursor
will be flashing on the first space.
Use the buttons on the keypad to type in a
name for the Program. You may mix letters and
numbers to create accurate names for each
Program (up to 10 total characters long).
Typing Instructions:
Each number button also has a series of letters
of the alphabet assigned to it. While the display
says “Alpha entry mode” the buttons will type
letters only. Press the button rapidly to display
the letter you want. If you release the button
for more than about 1 second, the letter will be
selected and the cursor will advance to the next
position.
16
To type the word “TEE”, for example, press
the “T” button (#8) once, and wait for a second. You may hear a faint beep, and the cursor
will advance to the next space.
Page 16
Press the #3 button twice, rapidly, to display the
second letter (e). Wait for a second, and the
cursor will advance to the next position. Repeat
this procedure to type another “e”. The display
should now read “TEE”.
If you make a mistake, you can use the BACK
and NEXT buttons to position the cursor on any
existing space, and type a new character .
To create a dash instead of a character, press the
NEXT button to skip over a space and resume
typing.
VSX OPERATING MANUAL
To delete a character and leave the space blank,
press the “1” (one) or “0” (zero) buttons once
when in the Alpha entry mode. They do not
have letter assignments and will create a blank
space.
You can also create special symbols with the
“1” (one) or “0” (zero) buttons when in the
Alpha entry mode only. With the first button
press, they create a blank space. If you continue
to press them they will cycle through the
following symbols:
T o erase an entire Program Name, press CLEAR.
To type numbers, press the TOGGLE button.
The bottom line of the display will show “Numentry mode”. Now the buttons will type the
number on the button, instead of the letters. To
delete a number and leave a space, TOGGLE
back to Alpha entry more and use the “1” or
“0”, then TOGGLE back to Num entry mode to
continue typing numbers.
When the name in the display is correct, press
ENTER. The display will show “SAVED!” for
a moment, then return to:
(where ## is the number of the program,
and xxxxxxxxxx is the new Program name
you have entered).
Press the EXIT button to leave the Edit Prg
Name programming. The display will return to
the Program Select level, and will show the
new name of the Program.
Assigning a Schedule to a Field
Controller Program:
The Schedule for a Program determines the
days on which the Program will run. There are
two types of Schedules: Daily or Day of Week.
Daily: Uses the controller calendar to
determine the watering schedule (see Set
Schedule Length on page 12). TOGGLE
each day Yes or No.
Day of Week: Uses the days of the week
(Monday, Tuesday, etc.) to determine the
17
Page 17
®
watering schedule. TOGGLE each day from
Capital (water) to lower case (no water).
Press the PROGRAM SELECT button repeatedly until the name or number of the Program
you want appears in the display. Once you have
pressed PROGRAM SELECT, you can also use
the BACK and NEXT buttons to go backward
or forward through the available Programs.
When the Program you want appears in the
display, press the SCHEDULE button. If the
Program has no Schedule assigned yet, the
display will show:
You may press SCHEDULE again to see the
Day of Week option (you can also use
TOGGLE, or BACK and NEXT, to move
between the options).
Note: If the Program already has a Schedule
assigned, the SCHEDULE button will immediately show the existing Schedule. If you want to
change to the other type of Schedule, press the
OPTIONS button, and TOGGLE between the
selections as described above.
When the display shows the option you want to
use, press ENTER.
If you select Daily, the display will show
something like:
(the cursor will be flashing under the
“Y” corresponding to the current day).
Prg## will show the Program number selected.
Today= # will display what today’s number is,
in the controller calendar, as in Day 2 of a
14-Day Schedule.
Day 1-7 shows the number of days in the
controller calendar (as set in the Edit FC
Settings selections). If the calendar is longer
than 7 days, the remaining days will be shown
on other pages when you finish setting up the
first seven days.
The “Y”s show Yes for each of the days (default
setting is all days to Yes, regardless of how
many days are in the controller calendar). A
“Y” means the Program will run on that day; an
“n” means it will not.
T o set the days for Yes or no, press the TOGGLE
button. TOGGLE will change the setting for the
day from “Y” to “n”. When the day is set correctly,
use the NEXT key to advance to the next day, and
press TOGGLE again to set up the day. Continue
through all the days of the calendar . If there are
more than 7 days, when you press NEXT after
the 7th day is set, the display will show the next
“page” of days.
Do not press ENTER until all the days are set
correctly. If you accidentally press ENTER
before you are finished, the display will show
“Enter to Save”. Press EXIT instead, then
press the SCHEDULE button again to re-enter
the scheduling mode.
After you have set up the entire Daily Schedule
for the Program, press ENTER. The display will
show “Enter to Sav e”. Press ENTER again. The
display will briefly show “SA VED!”, and then
will return to the Program Name.
18
Page 18
VSX OPERATING MANUAL
Example:
A controller has a 14-day schedule. You want to
set up a Program to irrigate Monday and Thursday of the first week, and Tuesday and Friday
of the second week. Monday is the first day
(“Day 1”) of the Schedule.
Use the NEXT button and the TOGGLE to create:
After the 7th day, press NEXT again, and the
display will advance to Days 8 through 14.
Continue to press NEXT and use TOGGLE to
configure the second week:
Press the TOGGLE button to change the
capital “T” (or any other letter) to a lower-case
“t”. Press TOGGLE again, and the day will
change back to a capital “T”. Press the NEXT
(or BACK) button to move to a different day.
Create capital letters for each day you want to
water, and lower-case letters for each day you
want to skip.
When the whole week is configured correctly,
press ENTER. The display will briefly show
“SAVED!”, and then will return to the Schedule
days you have created.
Example: You want the Program to water all
weekdays, but not weekends. In DOW mode,
use the TOGGLE and NEXT buttons to create:
After you have set up the entire Daily Schedule
for the Program, press ENTER. The display
will show “Enter to Save”. Press ENTER
again. The display will briefly show “SAVED!”,
and then will return to the Program Name.
If you select Day of Week, the display will
show something like:
The Program number for the selected Program
will be displayed. DOW = will show which day of
the week today is. The S•M•T•W•T•F•S display
represents each day of the week. The cursor will
be under the day of the week that the controller
thinks it is (in the example above, Tuesday).
Capital letter days are watered. Lower-case
lettered days are non-water days.
This shows that Sunday and Saturday will not
be water days, but that the rest of the days will
irrigate.
Press EXIT to leave the Schedule editing
mode. The display will show:
You must press the ENTER button with YES
capitalized to save the new Program Schedule.
If you want to discard it, press the TOGGLE
button to capitalize NO and press ENTER, and
the Schedule will not be saved.
T o change a Schedule which has already been set:
Press the PROGRAM SELECT button until the
Program you want to change appears in the
display.
19
Page 19
®
Press the SCHEDULE button. The display will
show the type of Schedule currently set up for
the Program.
Press the OPTIONS button. The display will show:
(Type of Schedule)
You may then press SCHEDULE, or use the
BACK and NEXT buttons, to cycle through the
choices available. When the display shows the
type of Schedule you want, press ENTER.
Complete the steps for the Schedule types
shown above to finish the new schedule.
Assigning a Start Time to a Field
Controller Program:
The Start Time for a Program determines the
time of day at which the Program will run.
Press the PROGRAM SELECT button repeatedly until the name or number of the Program
you want appears in the display. Once you have
pressed PROGRAM SELECT, you can also use
the BACK and NEXT buttons to go backward
or forward through the available Programs.
display, press the START button. The display
will show:
You can actually perform two different functions from here.
If you press START again, the program will
begin running immediately (so, be careful!).
This is the Semi-automatic Start feature.
If you press ENTER, the display will show:
The “Prg01” will indicate the Program number
you selected. “XXXXXXXXXX” will be the
name of the Program, if applicable. “Start =”
will show the actual Start Time of day, or OFF
if no Start Time has been programmed yet.
To enter or change a Start Time, simply begin
typing with the number buttons on the keypad.
The number will appear in the display in place
of the word OFF or the previous Start Time.
When the Program you want appears in the
20
It is not necessary to enter leading zeroes. For
example, to create a Start T ime of 9:30 PM,
type 9 3 0 and press ENTER.
The display will then add AM|pm to the time.
Press the TOGGLE button to change between
AM and PM. When the time is correct, press
ENTER. The display will show “Enter toSave”. Press ENTER again, and the display
will show SAVED! and the time you have set
for the Start Time.
The controller will automatically start the
Program at the time shown.
Page 20
Programming Stations: Run Times,
Events, and Blocks.
A station is a single electrical output from the
field controller . In conventional systems, each
station is a specific screw terminal on the output
board. In decoder systems, each station is a
uniquely-numbered decoder output. The VSX
controller may have up to 60 stations, plus
separate Pump output (conventional), or 103
stations plus a Pump output in a decoder
system.
A run time is the length of time for which the
station will be activated, or in other words, how
long the sprinklers it controls will run. Each
station run time is separately programmed. Run
times may be programmed in 1-minute increments, from 1 minute to 18 hours, 12 minutes,
in hh:mm format.
A station may appear in more than one Program, and it may appear in the same Program
more than once. Stations may run in any order,
and are not required to run sequentially.
The Event refers to the order in which the
station will run. You can run any station in any
order, by setting its Event number. Events
always occur in sequence, from #1 to the last
event. You can assign any station # to any Event #.
Each Program may have up to 30 Events.
VSX OPERATING MANUAL
When the Program you want appears in the
display, press the STATIONS button. The
display will show:
(or actual numbers)
or 9:30pm or 9:30pm – 10:45pm
This first display shows the total time for the
Program selected, and the start and end times
for the Program. If it is a new Program, or the
Start Time has been cleared, the second line
will show “No Start Time”. If there is already
a Start T ime, it will be shown. If Station Run
Times already exist, the Start and the end time
for the Program will be shown.
Press the STATIONS button again. The display
will show (example):
To program individual stations:
Press the PROGRAM SELECT button repeatedly until the name or number of the Program
you want appears in the display. Once you have
pressed PROGRAM SELECT, you can also use
the BACK and NEXT buttons to go backward
or forward through the available Programs.
...or, if the station has never been programmed
before, as at initial installation, it will show:
This will show the station information for the
first “Event” in the Program. The Program
21
Page 21
®
selected is shown in the upper left. The Event
number is in the upper right. The station or
block is in the lower left. The actual Run Time
for the station is in the lower right.
To program a new Station Run Time, verify that
the cursor is under the Station number. (At the
station number position, you can also press the
TOGGLE button to change from a Station to a
Block. If you select a Block, the number will
refer to a Block number, not an individual
station. See Blocks on page 23 for more
information.)
Type the number of the station or Block you
want. Press ENTER.
The cursor will advance to the Run Time field.
T ype the Run T ime you want for that station or
Block (up to 18 hours and 12 minutes), and press
ENTER. The display will show “OK!” briefly , and
return to the Run Time you have entered.
You must now press the STATIONS button to
advance to the next event, and program another
station (or Block).
You can continue in this manner until all the
stations you want in the selected Program are
programmed. Remember that you can enter any
stations, in any order.
Event #1 will begin at the assigned Start T ime
for the Program (9:30pm) and run for 10
minutes. Event #2 will follow immediately
after it (Station #5 for 8 minutes), then Event
#3, and so forth. The total Run Time for the
Program is 100 minutes, so the end time shown
will be 11:10pm.
You may find it easiest to simply run the stations
in numerical order (where Event #1 = Station #1,
Event #2 = Station #2, etc.), but VSX has the
flexibility to run stations in any order .
When you have finished entering the Run T imes
for all the stations you want in the Program, press
the EXIT button. The display will show:
Example:
22
The “YES” will be capitalized. To continue
saving the changes, press ENTER. The display
will flash “SAVED!” and your selection. After
a moment, the display will revert to the Program Name.
If you just want to exit and NOT save the
changes, press TOGGLE to change “no” to
“NO” and press ENTER The changes will be
discarded, and the Run T imes will be left the
way they were.
Page 22
Blocks: A Block is a group of more than one
station (up to 8 per block) which will activate
all at once, which are given a single run time,
and which may be included in a sequence just
like a single station. A Block counts as a single
Event regardless of how many stations are
assigned to it. It is technically possible to create
a Block of only 1 station, but this defeats the
purpose of this feature.
When multiple stations are activated in a Block,
they are actually staggered at 1-second intervals
to prevent the simultaneous electrical inrush
draw of all the solenoids.
VSX OPERATING MANUAL
Blocks can also irrigate more efficiently than
single stations, because the “cloud” of spray
from multiple sprinklers running simultaneously cools hot surfaces, and reduces the
evaporation of individual sprinkler
applications.
Blocks may be used to help you in several
ways. They allow you to program and adjust
large numbers of sprinklers with fewer keystrokes, since many sprinklers of similar types
will have identical run times.
If you group similar sprinklers with similar
flow capacities into Blocks, you can have a
fairly constant level of flow, even for a large
number of sequencing Events.
Blocks may also be included in Preset
programs, and can be used to “syringe”
greens and other areas more efficiently and
quickly, while the course is in play. One or
two Blocks can wet an entire green in a
single run time or two.
Creating Blocks:
Blocks are created, edited, or deleted at the
Field Controller Option level. Each Field
Controller may have up to 64 Blocks, which
are always the same, regardless of which
Programs they are included in.
With no programs selected, from the basic
time date display on the controller, press the
OPTIONS button approximately 4 times
until the display shows:
By permitting Blocks to sequence (simultaneous
groups of 4 sprinklers down a fairway ,
for example), large areas can be irrigated with
fewer Programs and less complicated sequences.
Press ENTER. The display will show:
23
Page 23
®
To create a Block, press ENTER. The display
will show:
T ype the station number for the first station in the
block, and press ENTER. The display will show:
T ype the next station number and press ENTER,
and so on, up to 8 stations. When the block is
complete, press ENTER again. The display will
show SAVED! and will return to the Create ABlock? message. You may then create another
Block, or press EXIT to leave the Block mode.
Note that run times and Events are not assigned
to Blocks here. This only creates the Blocks, by
assigning stations to them. The actual run times
are assigned to the Blocks in the individual
Programs, under the Stations button functions.
Press OPTIONS again. The display will show:
Press OPTIONS again. The display will show:
To edit an existing Block, press the OPTIONS
button until Edit a Block? is shown, and press
ENTER. The display will show:
(this list will always show all of the
currently existing Blocks)
In this example, the controller already has
more than 5 Blocks created, and the arrow
symbol is prompting you to press the NEXT
button to view more Block numbers.
Editing and Removing Blocks:
Once Blocks are created, they may be edited, or
removed altogether . With no Programs selected,
from the basic time date display on the controller, press the OPTIONS button approximately 4
times until the display shows:
Press ENTER. The display will show:
24
Type the number of the Block you want to edit
(for example, “3”) and press ENTER. The
display will then show the station numbers
included in that block, and will also show “---”
for any unoccupied spaces in the Block. You
may now add more stations, or remove existing
stations from the Block.
To remove a station from an existing Block,
press the NEXT button to advance to the
station, and press CLEAR or “0” (zero).
Press ENTER.
To add a new station to an existing Block,
press the NEXT button to advance to the next
blank spot (---), type in the number of the new
station, and press ENTER. It is not necessary
to enter leading zeroes. For example, to add
Page 24
VSX OPERATING MANUAL
station 7 to a Block, simply type “7” at a blank
spot and press ENTER. You may then advance
to the next blank spot and enter, change, or
remove more stations in the Block.
You may also replace one station in an existing
Block with another. Press NEXT to advance to
the station you want to replace, simply type the
new station number right over it, and press
ENTER. This will remove the original station,
and add the new station in its place.
When the Block editing is complete, press
ENTER again. The display will ask:
If you want to save the Block edits, press
ENTER (with the YES capitalized). The
display will show:
The display will then revert to the Edit a Block?
option level.
The display will show REMOVED and the
block will be permanently deleted.
Station Options (changing Events):
As noted above, stations or Blocks can run in
any order. You do this by editing Events. There
are several options available to edit Events.
Remember: The Event refers to the order in
which the station will run. You can run any
station in any order, by setting its Event number . Events always occur in sequence, from #1
to the last event. You can assign any station # to
any Event #.
Events are part of a specific Program, so the
first step is to press PROGRAM SELECT on
the keypad until the Program you want to edit
appears in the display.
Then press the STATIONS button once. The
display will show the current total run time of
the Program. The easiest way to access most of
the functions for a specific event is to continue
pressing the STATIONS button until the display shows the Event you want to edit. When
the specific Event is shown in the display , press
the OPTIONS button.
To remove an existing Block, press the ENTER
button when Remove a Block? is shown. The
display will show:
In this example, the controller already has more
than 5 Blocks created, and the arrow symbol is
prompting you to press the NEXT button to
view more Block numbers.
Type the number of the Block you want to
remove (for example, “2”) and press ENTER.
The OPTIONS button will cycle through the
Station-level options, which are as follows:
25
Page 25
®
Delete an Event: To delete the data in an
existing Event, press ENTER when the displays
shows Delete an Event? The display will then
ask, Delete data in Event #x? (where x = the
number of the Event you were on). Press
ENTER. The display will show OK! and the
Event will be deleted.
To cluster Events, press STATIONS to get to
the station where you want to begin a Cluster
(often station 1), and press OPTIONS until the
display shows Cluster Events? Press ENTER.
The display will show:
(where x = the number of the Event
you were on).
Note that you don’t really delete Events, but the
data in the Events. In effect, the whole sequence
of stations or Blocks will move backward one
Event, to fill the slot that was just deleted.
Example: If the existing Events were as follows,
Event #1234
Station #5678
...and you then delete the data in Event #2, the
new Event list would look like:
Event #123
Station #578
Since there are only 3 remaining stations, the
last Event is now #3.
Cluster Events?: “Cluster” is a mass-programming function for large groups of similar stations.
When you first program a controller, you may
want to set up all the same types of sprinklers with
the same run time, see what happens, and adjust
individual stations from there. “Cluster” lets you
assign a single run time to large numbers of
sequentially numbered stations, with a minimum
number of keystrokes.
Type the number of the Event you want, or just
press ENTER to accept the choice offered. The
display will show:
Since 30 is the maximum number of Events in
a Program, the controller will always offer to
cluster up to Event #30. You may type any
existing Event number higher than the starting
Event to cluster to, and press ENTER. The
display will then show:
You may start at any station number. Simply
type the number of the station at which you
want to begin, and press ENTER. The display
will then show:
To do this, the Cluster command will assign a
consecutive sequence of station numbers to a
consecutive sequence of Event numbers, with a
single run time for all.
26
Page 26
VSX OPERATING MANUAL
Type the run time you want all the clustered
stations to use. The display will then show:
Press ENTER to cluster the stations and run
times you entered. The display will briefly
show “OK!” and then return to the ClusterEvent? Option. Press EXIT if you are done
programming stations, and the display will
return to the Stations display.
The controller will then assign the run time to
every station in the cluster, beginning with the
lowest numbered station and ending at the last
one in the cluster.
When you have finished entering the Run
Times for all the stations you want in the
Program, press the EXIT button. The display
will show:
The display will then revert to the Program
Name display.
Example:
The controller will create 12 Events, from 001
to 012. Stations 5 through 16 will run in sequence, for 10 minutes apiece.
If you want to save the new Run T imes, press
ENTER (with the YES capitalized). The display will show:
27
Page 27
®
Move an Event: You can also move the data
from one event to another location in a Program, if you want a specific station to keep its
run time, but activate in a different order.
In the example above, you might want to move
station #6 (Event #2) to activate after station
#14 (Event #10).
T o move an Event, press STA TIONS until the
Event you want to move appears in the display .
Press OPTIONS until “Move an Ev ent?” appears
in the display . Press ENTER. The display will show:
Press ENTER (you may also type in a different
Event number). The display will show:
Type the Event # you want to move the data to
(#10, in this example), and press ENTER. The
display will briefly show OK, and revert to the
Move Event? display .
The Event data has been moved. Note that the
other Events move forward to fill the slot
formerly occupied by station #6. No data was
lost. Only the order in which the stations will
activate has changed.
Note: If you try to move an Event # that does not
exist, or try to move an Event to an impossible #,
the display will briefly show ERROR! and return
28
Page 28
you to the option. If you only have 12 Events, you
can only move an Event within the 12 numbers.
You cannot have an “empty” Event in the middle
of a sequence. T rying to move to Event #13
would cause the ERROR! message.
Insert an Event: You can insert a new Event in
between existing Events. In the example above,
you might want to insert station #4, with a run
time of 7 minutes, in between stations #8 and
#9 (Events 3 and 4).
Press the STATIONS button to advance to the
Event where you want to insert an Event (Event
#4, in the example). Press the OPTIONS button
until the display shows Insert an Event? Press
ENTER. The display will show:
VSX OPERATING MANUAL
Press ENTER. The display will briefly show OK!
and will then revert to the Insert Event? option.
You have now created a blank Event at Event #4.
The stations and Event that were at #4 are now at
Event #5, and the rest of the sequence has been
pushed back, to make room for the new Event.
You may now press ST ATIONS until you arrive at
the blank Event, and fill it in (in this example,
Station #4 with a run time of 7 minutes).
The new Event data has been inserted. Note
that the later Events move back to make room
for the new Event. You have only inserted a
new Event into the Program sequence.
29
Page 29
®
Program Advanced Options
The previous sections covered the basic concepts of writing a Program from the VSX
controller keypad: Program, Schedule, Start
Time, and Station run times, as well as Blocks
and Events.
The Program Options provide additional power
and flexibility at the individual Program level.
They are:
Edit Program Name
Set Program % Scale
Cycles
Cycle Delay
Skip Days
Pump
Edit Program Name is covered in detail in the
section, “Naming a Program”, on page 16.
Set Program % Scale: This is one of the most
convenient and frequently used options in the
controller. In the Field Controller Settings
section, we described the “Main % Scale” (see
Set Main % Scale on page 11), which affects
the entire Field Controller.
“Program % Scale” allows you to reduce or
increase all of the Run Times in a single Program by the selected percentage (from 1 to
250%, in 1% increments). This enables you to
quickly adjust the amount of irrigation for
weather or other conditions without changing
the basic program. At 50%, each Run Time will
only run half as long, and at 150%, each Run
Time will run one-and-half times as long.
When this Option is selected at the Program
level, it permits you to tailor certain plant areas
for local conditions. If you only want to adjust
the greens irrigation, for example, without
affecting the fairway irrigation, you would %
Scale just those Programs with greens sprinklers in them.
Important: The effects of % Scale at the Main
(controller) and Program levels are cumulative.
The controller looks first at the Program Scale,
and then at the Main scale, to calculate the
scaled run time.
In other words, if the original (or base) run
time of a station is 10 minutes, and the Program % Scale is set to 150%, the scaled run
time would be 15 minutes. If the controller
Main Scale is then set to 50%, the net total run
time for the station would be 8 minutes. Fractions resulting from these calculations are
always rounded to the nearest minute.
Base Run Time ........................10 min.
Multiplied by ...........................x
Program Scale..........................
150%
Result .......................................15 min.
Multiplied by ...........................x
Main Scale ...............................50%
Result (rounded up to 8) ..........7.5 min.
To set Program % Scale: Press PROGRAM
SELECT until the name of the Program you
want to adjust appears. Press OPTIONS twice,
until Set Prg Scale? appears. Press ENTER.
The display will show:
Type the percentage scale you want with the
number buttons on the keypad, and press
ENTER. The display will briefly show
“SAVED!” and the new % Scale amount. After
a moment, the display will revert to:
30
Page 30
You may now press the OPTIONS, BACK, or
NEXT buttons to view more options, or you
may press EXIT to leave the Program Options
mode.
Note that, whenever a Program is scaled up or
down (to any value other than 100%) and saved,
a “+” or “-” sign appears as a reminder in the
upper left corner of the display before the
Program name, when pressing PROGRAM
SELECT to view Programs.
The “+” or “-” signs will also appear next to
the Total when STATIONS is first pressed in a
scaled Program. If you continue to press STATIONS to view individual Station run times, the
“+” or “-” sign will appear next to the Event
number, and the actual scaled run times are
shown in the run time area of the display. This
is a reminder that you are viewing a scaled run
time, and not the base run time.
Cycles: The Cycles option specifies the number
of times a Program will run. The default value
is 1, so that once you have created a Program, it
will run the entire sequence of stations once per
scheduled day.
You may specify up to 15 cycles per Program,
however. This is useful when your plants
require more water than the ground is capable
of absorbing in a single application (such as
very dense or compacted soil, or sloped areas),
or when you wish to keep an area wet with
many short applications (germinating seed,
grow-in, etc.). You can also specify a Delay
between each cycle at the next option setting.
VSX OPERATING MANUAL
Type the number of cycles you want with the
number buttons on the keypad, and press
ENTER. The display will briefly show
“SAVED!” and the new number of cycles. After
a moment, the display will revert to SetCycles? You may now press the OPTIONS,
BACK, or NEXT buttons to view more options, or you may press EXIT to leave the
Program Options mode.
Note that the next time you press the STATIONS
button while in this Program, the Total run time
will be updated to reflect the number of cycles of
the Program.
Cycle Delay: This is the amount of time the
Program will wait between multiple cycles,
before starting again. There is only 1 cycle
delay factor per Program, which will occur
between all cycles. If there is only 1 cycle,
Cycle Delay will not have any effect at all.
To set the Cycle Delay: Press PROGRAM
SELECT until the name of the Program you
want to adjust appears. Press OPTIONS until
Set Cycle Delay? appears. Press ENTER.
The display will show:
(or, Delay = ##:## if a delay has
already been programmed).
To set the number of Cycles: Press PROGRAM
SELECT until the name of the Program you
want to adjust appears. Press OPTIONS until
Set Cycles? appears. Press ENTER. The
display will show:
Type the length of the cycle delay you want in
hours:minutes format with the number buttons on
the keypad. (You can also clear out an existing
delay by typing “0” or pressing CLEAR). Press
ENTER. The display will show:
31
Page 31
®
Press ENTER to save the new delay. The
display will briefly show SAVED! and the
length of the cycle delay you have entered.
After a moment, the display will revert to SetCycle Delay? You may now press the
OPTIONS, BACK, or NEXT buttons to view
more options, or you may press EXIT to leave
the Program Options mode.
Note that the next time you press the STATIONS button while in this Program, the Total
run time will be updated to reflect the number
of cycles and the cycle delays of the Program.
time you want to temporarily halt a Program
without having to remember to turn it back on.
Skip Days count consecutive days, and do not
take into account the scheduled days “on” for
the particular Program. Skip Days will suspend
the Program for the specified number of calendar days. If the resume day was a “no water”
day for the Program’s normal schedule, it will
still be a “no water” day when the Skip Days
times-out.
Note that if you set Skip Days for a Program
while it is already running (after its automatic
Start Time), the Program will finish irrigating
normally, and the next day will count as the
first Skip Day.
Example:
Single Cycle
Program 1: GREENS
Cycles: 1
Total Run Time: 1 hour
Multiple Cycles
Program 1: GREENS
Cycles: 2
Total Run Time: 2 hours
Cycles with Delay
Program 1: GREENS
Cycles: 2
Cycle Delay: 2 Hours
Total Run Time: 4 Hours
Skip Days: Skip Days suspend a Program for a
specified number of days, after which the
Program will resume operating normally . You
can use Skip Days when a weather front is
approaching and you know you won’t need to
irrigate for 2 or 3 days, or when you have repair
work going on and you do not want any irrigation until the repairs are completed, or any other
To set Skip Days for a Program: Press PROGRAM SELECT until the name of the Program you want to suspend appears. Press
OPTIONS until Set Skip Days? appears.
Press ENTER. The display will show:
Type the number of days you want the Program
to Skip, and press ENTER. The display will
briefly show SAVED! and the number of Skip
Days you have entered. After a moment, the
display will revert to Set Skip Days? You may
now press the OPTIONS, BACK, or NEXT
buttons to view more options, or you may press
EXIT to leave the Program Options mode.
Note that if you return tomorrow (after the next
Time of Day change) and view the Skip Days
for the Program, the Skip Days will be updated
to show the remaining number of days to be
skipped. For example, if you enter 3 Skip Days
today , tomorrow the display will show “2”, and
the day after it will show “1”. The display will
count down the days until the Program resumes
32
Page 32
automatic operation. Also note that the maximum number of Skip Days is 999 days, or
approximately 3 years.
VSX OPERATING MANUAL
Pump: Every VSX controller has a separate
Pump output (red and white striped wire from
the power supply board in conventional systems, station number “0” in decoder systems).
The Pump option designates whether the
specified Program will automatically activate
this output.
The Pump output may activate a pump start
relay (such as Hunter Industries PSR series
relays) connected to a pump, or it may be used
to control a master valve. The Pump output
must never be connected directly into a highvoltage switch (see installation instructions for
further information).
In systems where the pump is activated by the
individual controllers, this option is used to
provide pump pressure to the Programs that
require it, and to operate without it for any
Programs that may not require it. For example,
if your controller operates both rotors and spray
heads connected to city water, you may have a
booster pump to provide additional pressure for
the rotors. In this case you could have the Pump
option set to “Yes” for the Programs containing
the rotors, but “No” for the Programs containing
the spray heads (if they would be over-pressurized with the booster pump).
The current selection will be capitalized
(default is YES). The “no” selection will be in
lower case. Press the TOGGLE button to
switch between YES and NO. When it is
correct, press ENTER. The display will flash
“SAVED!” and your selection. After a moment,
the display will revert to Use Pump? Y ou may
now press the OPTIONS, BACK, or NEXT
buttons to view more options, or you may press
EXIT to leave the Program Options mode.
Keep in mind that if any controller in the
system activates the pump, it is activated
regardless of whether any other controllers are
running Programs with Pump “No” selected.
To set the Pump: Press PROGRAM SELECT
until the name of the Program you want to set
the Pump for appears. Press OPTIONS until
Use Pump? appears. Press ENTER. The
display will show:
33
Page 33
®
Manual Starts
You can quickly start one or more stations in the
controller with the Manual button. Since more
than one station can be started with this command, this is often called a Manual Program.
The Manual Program is temporary and is not
retained in memory after the Program has
finished running.
You must specify a time for each station to run.
If you enter multiple stations, you may choose
whether to run them sequentially, or simultaneously.
You can create a Manual Program for up to 20
stations, although the controller only has the
electrical capacity to operate 8 to 12 typical
solenoids simultaneously. Decoder controllers
may operate up to 20 decoders simultaneously.
Manual does not interrupt Automatic or Semiautomatic FCPs or other Programs which may be
running. Any solenoids or decoders activated by
other Programs must be taken into account when
determining how many stations to turn on.
Type the number of the station you want to
start, and press ENTER. The cursor will then
move to the minutes section of the run time
section (00:00) of the display. T ype the amount
of time you want the station to run for, and
press ENTER. The display will briefly show
“OK!”, and then:
You may now enter more stations to start
manually, if you wish. If you only want to start
one station, simply press ENTER again, instead of entering another station. If you are
starting multiple stations, continue entering the
stations and run times until the Manual Program is complete, and then press ENTER
again. The display will show:
To start a Manual Program: Press the
MANUAL button on the keypad. The display
will show:
This selection determines whether the Pump
output (or decoder station #0, in decoder
systems) from the controller will also be
activated along with the Manual stations. Press
the TOGGLE button to change YES to NO if
you do not want the Pump active during the
Manual Program. When the Pump setting is
correct, press ENTER.
If you have only entered one station, the
display will briefly show “OK!” and the station
will begin running for the specified time.
If you have entered more than one station, the
display will show:
34
Page 34
“SEQ” means the stations will run sequentially,
in the order in which they were entered. If you
press the TOGGLE button to capitalize “SIM”,
all of the stations will begin simultaneously.
Use TOGGLE to capitalize the mode you want,
and press ENTER.
Note: Simultaneous starts are actually staggered
at one-second intervals to prevent simultaneous
inrush currents.
When stations begin running sequentially, the
display will show:
VSX OPERATING MANUAL
Semi-automatic Program
Operation
Any automatic Program can be easily started at
any time from the keypad. This is called “semiautomatic operation” and is useful for irrigating any area that is normally handled by an
automatic Program, right now. You can use this
to irrigate a fertilized area, or for frost or dew
control, or for any other purpose.
(where “xxx” is the number of the station
currently running, and “0:nn” is the amount
of time left to go on that station).
If you requested the stations to run simultaneously , the display will show:
(where “xxx” is the number of one of the
stations currently running, and “0:nn” is the
amount of time left to go on the station).
In the Simultaneous mode, the display will
sequence through all the stations currently running
and show the remaining time on each station.
To semi-automatically start a Program: Press
PROGRAM SELECT until the Program you
want to start appears in the display. Press the
START button. The display will show:
Press START again. The Program will begin
running. It will irrigate the entire Program,
including all Cycles and Delays.
If you semi-automatically run an automatic
Program during the day, it will still run later at
its assigned automatic Start Time.
35
Page 35
Presets
®
Presets are like automatic Field Controller
Programs, except that they have no Schedule or
Start Time. Instead, Presets are activated from
the keypad (or Maintenance Radio) whenever
you want to run them. They can be used to
syringe greens, clear dew or frost from an area,
water in chemical or organic applications, or
any other common task.
Presets work with either individual stations or
Blocks. Both can exist in the same Preset.
The difference between a Preset and a semiautomatic start is that a Preset can be written,
named, and stored to provide custom irrigation
for a specific purpose. The automatic Programs
may be overkill for syringing greens, for example. A Preset can be created to trigger two
Blocks of sprinklers, each for half a green, each
with a run time of 3 minutes. This would allow a
rapid cooling of the green while it is clear of
people, without risking over-watering. The Preset
can be named for what it is (“SYRNG GRN4”,
for example) and recalled and started anytime
you want to syringe that green.
will show “Alpha entry mode”, and the cursor
will be flashing on the first space.
Use the buttons on the keypad to type in a
name for the Preset. You may mix letters and
numbers to create accurate names for each
Preset (up to 10 total characters long). See
Typing Instructions on page 16 for detailed
instructions.
When the name in the display is correct, press
ENTER. The display will show “SAVED!” for
a moment, then return to:
(where ## is the number of the program,
and xxxxxxxxxx is the new Preset name
you have entered).
Press the EXIT button to leave the Edit Prg
Name programming.
Most of the Program Options are also available
for Presets. Presets may have multiple Cycles,
Delays, and may be % Scaled.
To Create a Preset: Press the PRESET button.
The display will show:
Press the OPTIONS button. The display will
show “Edit Prg Name”?
Press ENTER. The bottom line of the display
36
You do not create Schedules and Start T imes
for Presets. Instead, with the new Preset name
in the display, press STATIONS.
Refer to Programming Individual Stations
on page 21 for detailed instructions on entering
stations or Blocks and their run times. When
complete, press EXIT. The display will show:
If you want to save the new Run Times, press
ENTER (with the YES capitalized). The
display will show:
Page 36
VSX OPERATING MANUAL
Field Controller
The display will then revert to the Preset Name
display.
Advanced Options
Unlike Program Options, which only apply to the
selected Program, the Field Controller options
apply to the entire Field Controller, or provide
access to special functions. Several of them have
been covered in detail in other sections.
Field Controller level options are accessed by
pressing the Options button on the keypad
when no Program is selected in the display.
The remaining Field Controller options are
covered in detail here.
Remove a Program: This is used to completely remove, or delete, a specific Program
and all its information from the controller’s
memory. Use it to wipe out Programs which are
no longer needed, or which no longer serve
their purpose.
To start a Preset: With only the Day and Time
in the display, press the PRESET button until
the Preset you want to trigger appears in the
display. Press START. The display will show:
Press START again, and the Preset will begin
running.
You may start Presets while other Programs are
running, or while Manual station programs are
running. They will not interfere with one
another, unless you electrically overload the
controller . Be careful not to overload the hydraulic capacity of the piping when operating
multiple types of Programs and Presets.
To remove a Program: Press the OPTIONS
button until the display shows:
Press ENTER. The display will show:
Press PROGRAM SELECT until the name or
number of the Program you want to remove
appears in the display, and press ENTER. The
display will show:
37
Page 37
®
The display defaults to NO, because this is your
last chance to keep this Program. Make sure the
correct Program (the one you want to remove)
is shown in the display .
If you are certain you want to remove it, press
TOGGLE to capitalize YES, and press ENTER.
The display will briefly show REMOVED and
the Program and all its information will no
longer exist.
Remove Preset: This is nearly identical to
removing a Program, except that it removes a
Preset. Press the OPTIONS button until the
display shows:
Press ENTER. The display will show:
Press the PRESET button until the name or
number of the Preset you want to remove
appears in the display, and press ENTER. The
display will show:
Edit Decoders: This option only appears in
VSX Field Decoder Controllers. Decoder
controllers are always configured for 103
stations, plus a Pump output. Each station has a
corresponding decoder installed in the field,
connected to a two-wire path.
The Edit Decoder function allows you to
change the assignments of decoder identification numbers to station numbers in the field.
This can be used whenever a decoder is replaced, added, or exchanged with another
decoder, after initial setup.
Note: The Edit Decoder function may also be
used for initial setup of all the decoders in a
controller, but full system setup is much faster
and easier with the GVIK1 software available
from Hunter. GVIK1 has additional diagnostic
features for decoder systems.
Before editing a decoder, you must know the
Serial Number of the new decoder. This is a
unique 8-digit number, printed on a metallic
tag on the side of the decoder itself (such as the
GVIKDEC single-station decoder).
The GVIKDEC4 4-station decoders actually
have four individual Serial Numbers. The first
seven digits are fixed, and the 8th digit is
always 1, 2, 3, or 4, corresponding to the
individual color-coded outputs of the decoder
to the solenoids. These are also listed on the
metallic tag.
The display defaults to NO, because this is your
last chance to keep this Preset. Make sure the
correct Preset (the one you want to remove) is
shown in the display .
If you are certain you want to remove it, press
TOGGLE to capitalize YES, and press ENTER.
The display will briefly show REMOVED and the
Preset and all its information will no longer exist.
38
The Serial Number of an individual decoder
cannot be changed in the decoder itself. The
Edit Decoder function only assigns the predetermined Serial Numbers of the decoders to the
Station Numbers of the Field Controller.
The Power Factor (Pwr) has a default value of
2, with a possible range of 1-5. This determines
the amount of power consumed by a particular
decoder in the field. “2” is almost always the
Page 38
correct setting to use. The range of settings is
to handle unusual situations, including very
long wire runs or increased wire resistance due
to the age of the wire. Increased Power Factors
may detract from the total power available to
the field, and should be used only after consulting with Hunter Field Services.
VSX OPERATING MANUAL
If you press ENTER, the changes will be saved.
You may also TOGGLE to “NO” and press
ENTER if you want to discard the changes.
To Edit a Decoder: Press Options repeatedly
until the displays shows “Edit Decoders?”,
and press ENTER. The display will show:
The first station to be shown is always the
Pump output, which counts as a station in
decoder systems (technically, the Pump is
station #0). Subsequent stations are shown by
their station number, from 1 to 103.
Since the cursor is already under the Serial
Number, you can type in a new decoder Serial
Number for the Pump, if that is the decoder you
want to edit. You must type all 8 digits, and
press ENTER.
To advance to another station #, you can simply
press the STATIONS button until the number of
the station you want to edit appears. You may
also use the NEXT button to move the cursor to
the station field (“Pump”), then type the number of the station you want to edit, and press
ENTER. The display will immediately show
the decoder information for the new station you
have entered.
Continue editing any other decoders (press
Stations again or type the station number as
described above), and when you are finished,
press EXIT. The display will show:
Note: Decoder edits are automatically stored in
memory, and must be “dumped” every 4 edits.
If you edit more than 4 consecutive decoder
stations in a session, the display will periodically show the “Save Changes? YES|no” as
you advance with the STATIONS button. If
you want to save the changes you’ve already
made and continue editing, just press ENTER.
The display will briefly show SAVED! and
then the next Station.
Also, if you type the station numbers directly
into the station number field and press ENTER, you will also receive the “SaveChanges? YES|no” message if you entered a
station more than 4 digits higher than the last
one you edited. Just press ENTER. The display
will briefly show SAVED! and will then show
the Station you typed.
View SYS Events: This option allows you to
view (but not change) the events in the computer-generated central System Program that
have been downloaded to the Field Controller .
These are the events created by either a Vista
or Surveyor central system.
T o view the downloaded events, press OPTIONS
repeatedly until View SYS Events? appears in
the display , and press ENTER. The display will
show the first SYS event. The display will show
the event number, its start time, and the ET Day
on the first line, and the station number and its
run time on the lower line.
39
Page 39
®
You may then press NEXT (or BACK) to step
through the system events stored in the system
portion of the controller memory . If you see SYS
events you would like to edit, you must return to
the central computer to edit them.
Radio Xmit Test (Radio controllers only): The
Radio Transmit (Xmit) Test option only appears
in VSX controllers equipped with radio communications modules, and is used to test the radio
and communications board. If you are not certain
whether the radio communications are functioning properly , this test will generate a constant tone
for 5 seconds, which can be heard on a Maintenance Radio switched to the same frequency .
Remove SYS Events: This will delete the Vista/
Surveyor central events which have been downloaded to the Field Controller. This should only be
used if you need to remove the computer central
system program events from the controller .
If these events are deleted, the controller will
not irrigate, unless:
You have Field Controller Programs activated
in the controller.
You irrigate manually or through Maintenance
Radio commands.
You restore the information from the Vista or
Surveyor central computer (this can only be
done from the computer, with working communications).
To remove the SYS events: Press OPTIONS
until the Rem SYS Events? option appears,
and press ENTER. The display will show:
To run a radio test: Press OPTIONS until
Radio Xmit Test appears in the display, and
press ENTER. The display will show:
...for approximately 5 seconds. Then the
TRANSMITTING! message will disappear,
indicating that the test is concluded. You may
press ENTER to run the test again, if you wish.
You should hear a clear, solid tone on your
Maintenance Radio if the test is successful.
Maintenance Radio
Operations
The display defaults to NO, because this is
your last chance to keep the SYS Events.
If you are certain you want to remove the SYS
events, press TOGGLE to capitalize YES, and
press ENTER. The display will briefly show
REMOVED and all centrally-generated irrigation events will no longer exist.
40
Maintenance Radio is the term for the ability to
operate many VSX Controller functions from a
handheld walkie-talkie equipped with
TouchTone buttons (Hunter Golf Part # TRNR).
This convenient remote control option is a
time-saving favorite with superintendents and
other VSX users, and permits remote starting
and stopping of Programs, Presets, Blocks, and
individual stations, anywhere within the range
of the walkie-talkie.
Maintenance Radio operations require one of two
communications options in the VSX controller:
Page 40
VSX OPERATING MANUAL
Radio Communications. Whether built-in or
through the addition of the GFCKTR communications kit, radio-equipped VSX controllers
include StraightTalk™ to respond directly to
your TRNR walkie-talkie. No central computer
or other communications are required in this
case. The GFCKTR kit can be added to
standalone VSX controllers to add Maintenance
Radio ability at any time.
Hardwire Communications. Hardwired VSX
controllers communicate with a central computer over direct burial copper cables. To use
Maintenance Radio with hardwired controllers,
the central interface must be Maintenance
Radio-capable. In older systems, the GMR
option provided this capability. Newer systems
(May, 2001 and later) will usually have this
feature built-in to the T riSend™ central interface. If you are uncertain whether this option
was installed in your hardwired system, check
with your Hunter Golf distributor. If it was not,
you can always add a simple kit to the central
interface to enjoy Maintenance Radio’ s powerful remote control capabilities.
Note: ALL Maintenance Radio systems in the
United States must be licensed by the Federal
Communications Commission (FCC) under
Part 90 rules and regulations (application forms
included with each radio device). Canadian
radio systems must comply with licensing
requirements of Industry Canada Spectrum
Management. Most other nations have restrictions and licensing governing the use of professional radio equipment. Licensing radio equipment and selecting frequencies is the sole
responsibility of the user, and is NOT the
responsibility of Hunter Industries. Do not
operate an unlicensed system!
Maintenance Radio commands: Most of the
manual irrigation functions that can be started
from the VSX keypad can also be started from
Maintenance Radio. The command codes
follow a simple structure, consisting of (controller) address, function, stations or programs
affected, and timing.
One good, two bad: Maintenance Radio
commands are always two-way communications. The VSX Controller will confirm every
good command with a single beep tone, indicating that it will perform as instructed.
If the controller hears a command but cannot
understand it, or the command is “bad” (improperly formatted or impossible to execute),
you will hear two beep tones. If you do not
hear any confirmation tones at all back from
the controller, it is probable that the controller
did not hear you at all, or is switched off.
“Cheat sheet” stickers of command formats are
available in wallet card format. Most superintendents are able to memorize the common
commands very quickly, and use them daily.
The TRNR radio also features some convenient shortcuts to issuing commands. In addition to the standard 12-button number, #, and *
keys, there are four letter keys (A, B, C, and D)
which provide shortcuts to common functions
(see the Maintenance Radio Command Table
on page 43).
TRNR also has a “store and send” feature. By
pressing the “*” button one extra time at the
beginning of each command, the command is
stored and displayed on the radio’s LCD
display, instead of being sent out one keystroke
at a time. You may then review the command in
the display to make sure it is correct. When
you are ready to transmit, press the push-totalk switch once, briefly, and the entire command will be sent out in a single string.
You may also hold down the push-to-talk
switch and press the command buttons one at a
time. Remember to release the switch immedi-
41
Page 41
®
ately upon finishing the command, so that you
can hear the acknowledgement tone back from
the controller.
Sending a Maintenance Radio Command:
Both the controller and the radio must be
powered on, and switched to the correct frequency. As an example, we will turn on station
#1 at controller number #1.
Method #1 (store and send): Press **, 1 (the
controller address number), #, 1 (the station
number), ##. Now touch the push-to-talk
switch on the side of the radio. You should hear
the command being sent to the field (rapid
series of tones), then a confirmation tone back
from the controller. Station #1 at controller #1
should turn on, in a few seconds (allow for
valve opening time).
Method #2 (live): Hold down the push-to-talk
switch on the side of the radio, and press
*1#1##, without pausing. Release the push-totalk switch as soon as you are finished, and you
should hear a confirmation tone back from the
controller. Station #1 at controller #1 should
turn on, in a few seconds.
A station turned on with either of the above
methods will continue to run until you stop it
with another command, or until it reaches the
time-out limit set in the MR Runtime option
under Edit FC Settings (see Set MR Runtime
on page 14).
Generally, the last character determines
whether you are turning something on or off:
# = ON, and * = OFF. The “*” is also used
to begin new commands. The “#” character is
also used to separate different numbers
within a command.
If you want to turn on a station for a specific
amount of time, enter the time after the
station number and #, but before the last #. If
you don’t want to specify a time, you must
press ## at the end of the command to skip
the time setting.
For example, to turn on station 2 at controller 1
for 5 minutes, the command would be:
*1#2#5#.
*1#2
StartsControllerseparatorStation
commandaddressnumber
#5 #
separatorRun"ON"
timecommand
The station will turn on in a few seconds, and
run for five minutes. You do not need to issue
any further commands to this station. You may
shut it down sooner, however, by issuing the
“OFF” command.
To turn the same station off, repeat the above
steps, but end with “*” instead of “#”. The
command would be: *1#1*. This tells controller 1, station 1, to stop. If you want to use
store and send, remember to add an extra “*”
at the beginning.
42
Page 42
VSX OPERATING MANUAL
Maintenance Radio Functions and Commands:
FunctionCommand*Result
Start a Station*aaa#nnn#[tttt]#Starts station (#nnn) for a specified time (tttt) in
hours:minutes format, up to 18 hours, or the global MR
Time (set in Edit FC Settings) if no time is entered.
Stop a Station*aaa#nnn*Stops a specific station (#nnn)
“Syringe timing”: applies*aaa#300#tttt# ORSyringe Timing of active stations for “tttt” in hours:minutes
a run time to multiple*aaa#A#tttt#format, up to 18 hours.
stations already active
Procedure: First turn on multiple stations, one at a time, using
the “Start a Station” function.
Then enter the Syringe Timing command as shown to set the
run time for all stations currently running (or Active).
SHORTCUT KEY= A (Active stations)
Start one of the FCPs*aaa#310#ff#Semi-Auto start FC Program “ff”. This will start the designated
immediatelyautomatic Program immediately. The Program will still run at its
normally scheduled automatic Start time.
Start a Preset*aaa#311#pp# ORSemi-Auto start Preset “pp”. This will start a pre-programmed
*aaa#C#pp#Preset immediately.
SHORTCUT KEY= C (Cool-down)
Start a Block*aaa#312#bb#[tttt]#Start block #b for [tttt] HH:MM or global MR Time. This is exactly
the same as starting a Station, except that it starts a Block.
Stop all irrigation at a*aaa#320* ORStops all irrigation for the designated FC. This will include
Field Controller*aaa#D*Manual, Semi-Auto, Automatic, and Preset irrigation(permanent)everything stops.
SHORTCUT KEY= D (Delete activity)
Pause all irrigation at a*aaa#321* ORPause all irrigation f or FC. This will include Manual, Semi-Auto,
Field Controller (temporary-*aaa#B*Automatic, and Preset irrigation. Unlik e the Stop command, y ou
resumes where left off)can restart everything where it left off. It will restart automatically
after 30 minutes if no other commands are issued.
SHORTCUT = B (Break)
Cancel Pause for FC.*aaa#321# ORRestarts FC after a Pause The command is the same as for
*aaa#B#Pause, except that it ends in a “#” (= ON).
SHORTCUT = B (Break)
Communications Check*aaa#330#Returns a short beep if controller hears command
Radio Transmit test*aaa#331#Initiates Radio Transmit Test (5 second beep)
Check for Network Link*aaa#332#Returns 1 beep if FC has link to central, 2 if not
Check for Auto Operation*aaa#333#1 beep= FC is in Auto Op Mode, 2 beeps= FC is in Rain
Shutdown
*See next
page.
43
Page 43
®
*The letters in the commands table correspond
to the Legend Table below:
Legend for MR Command
aaaFC Address (1-999)
nnnStation Number (1-103)
ffFC Program Number (1-64)
ppPreset Number (1-64)
bbBlock Number ( 1-64)
ttttRun Time (1 to 18:12 HH:MM)
Display Messages (Status,
Errors and other Conditions)
Status Displays: Normally, the VSX display
will show the current day and time. It may also
show a “+” or “-” sign before the Day if the
controller has been % Scaled to a value other
than 100% (see Set Main % Scale on page
11). Whenever VSX is running a station for
any reason, the display will also indicate what
is running, why, and how much time is left on
the station:
If there is too much information to display in a
single screen, VSX will flash a series of
screens, each with more information about
station activity. The screens will continue to
cycle through all activity with updated information until all stations cease running.
If you would like to review all currently running stations more quickly, you can speed up
the review of the display by pressing Enter,
Back, Next, or any of the number buttons. This
will advance the station numbers of all currently active stations with every button push.
This does not affect irrigation, only the display.
If the controller is running a Block, the Block
number will not be listed in the status display,
but the individual stations within the Block
will be listed sequentially.
If a station is running and there is no activity
listed in the status display, it may have been
turned on manually at the valve, or there could
be a malfunction in the valve, or a possible
malfunction in the VSX outputs. If the VSX
has intentionally operated a valve it will always
appear in the status display. If you are not sure
why a sprinkler is running at any time, check
the controller display first.
1.Type of Activity
A=Automatic
S=Semi-automatic
Sim=Simultaneous Manual
Seq=Sequential Manual
P=Preset
SYS=System Program Event
SME=System Manual Event
2.Program or Preset Number
3.Current Station Number
4.Time remaining (in hours:minutes:secs) on current station
44
Other Messages: In addition to the status
display, VSX will sometimes display other
messages.
OVERLOAD! ### (where ### is a station
number): The VSX Field Controller is
equipped with automatic Overload protection
to prevent damage to the transformer . This
message indicates that a station or stations
caused the internal current monitoring electronics to trip, and turn off all stations that
were running.
When VSX detects an overload condition it
stops all stations currently running, and then
Page 44
VSX OPERATING MANUAL
attempts to restart whatever should be running,
every 30 seconds. It will continue this until the
overload condition is no longer detected. The
last station to have caused an overload is
displayed (###) in the message.
Pressing the ‘CLEAR’ key will clear this
message. If the overload occurs while you are
present at the controller, you can press CLEAR
to force the controller to immediately try to
restart, without waiting for the 30-second timer.
Generally , overloads are caused by too many
stations activated at once, or faulty solenoids or
wiring in field devices (valves and VIH sprinklers). Clearing the display does not solve the
problem. You should inspect the field solenoids
and wiring if this is a recurring problem.
FUSE OPEN!: This indicates that the fuse on
the power supply board (PSB) has blown. This
message remains on until the fuse is replaced.
The fuse is an AGC3, 3 amp, fast-blow only.
COLD START!: This indicates that the user
program memory has been corrupted, and was
automatically reset to default conditions. The
controller irrigation memory is completely
wiped out when this message appears, and must
either be restored from a central computer or
reprogrammed by hand. Pressing the ‘CLEAR’
key will clear this message.
Note: You can perform a Cold Start on the Field
Controller at the keypad, if you want to completely erase its memory and start over. The
sequence for this is to press CLEAR, SCHEDULE, 0, ENTER. This will clear the controller
memory, although the Time, Address, and PINs
(passwords) are retained.
Events at Max: This indicates that the
System Program station event buffer is full.
This area of the controller can hold up to 1000
events. Pressing the ‘CLEAR’ key will clear
this message.
Max Sta Running: The VSX controller can
operate a maximum of 20 stations at a time.
This message indicates that scheduled or
manual programs are attempting to operate
more than 20 stations simultaneously. Pressing
the ‘CLEAR’ key will clear this message.
PINs Reset!: This indicates that the
controller’s Personal Identification Numbers
have been reset to the factory defaults, and the
controller is no longer password protected.
Pressing the ‘CLEAR’ key will clear this
message. You will need to reprogram passwords (PINS) if you want to restore password
protection.
RAIN SHUTDOWN!: This states that the
controller will not run any automatic programs.
A command from a central computer or by
pressing OFF on the keypad will toggle this
feature on and off. See Rain Shutdown on
page 7.
SUSPEND W A TERING: This indicates that
the controller has stopped all irrigation (but event
timers continue to time on any stations that are
scheduled to run). This mode is only initiated by
the central computer . It can be cleared at the
controller keypad, using the same procedure as
“Resume” after a Pause command (See Pause on
page 7). To clear, press OPTIONS once. The
display will then show:
POWER OUTAGE: This indicates that power
has been lost in the recent past. Pressing the
‘CLEAR’ key will clear this message.
45
Page 45
®
Press ENTER. The display will then show:
Press ENTER with YES capitalized, and the
controller will return to Auto Operational
status. If irrigation is scheduled to be running
when you Resume, it will begin irrigating. It is
technically possible (though unlikely) for a
controller to be in both “Suspend” and “Pause”
at the same time. If that is the case, repeat the
above procedure to clear first the Suspend, then
the Pause.
PAUSE mm:ss togo: This indicates that
controller has stopped irrigation and all event
timers have been stopped. When a thirtyminute Pause timer expires, or a Resume
command is entered, all events will resume
where they left off. This feature can be turned
on or off from the central computer control,
through the Field Controller Options selection
at the keypad, or via Maintenance Radio. See
Pause on page 7.
Comm is muted: This indicates that the
controller will not initiate any communication
to a central controller. This message is only
cleared by an internal five-minute timer or by a
command from a central computer. This mode
is started or stopped by the central computer
and cannot be changed or cleared at the controller keypad. Consult software documentation for details on this display.
No Network link: This indicates that the
controller has not been in communication with
a central computer for 30 minutes. This message is cleared by communicating with a
central computer, and may indicate power of f
at the central or a communications failure at
either device.
FCP AUTO INHIBIT: This indicates that the
controller will not start any internal scheduled
programs. This mode can be started or stopped
from the controller keypad (see Set FCP
Inhibit on page 13), or the central computer.
Consult software documentation for details on
enabling and disabling this mode from the
central computer.
46
Page 46
VSX Series Specifications
VSX OPERATING MANUAL
Dimensions:
Steel Pedestal:36in/92cm tall x 13.5in/35cm
wide x 10in/26cm deep
Plastic Pedestal: 35in/89cm tall x 17.5in/45cm
wide x 10.5in/27cm deep
A verage Weight
(depends on
configuration):56 lbs/25kg