Hunter VSX Operating Manual

VSX Programming and Operations Manual
VSX OPERATING MANUAL
®
VSX OPERATING MANUAL

Table of Contents

FCPs (Field Controller Programs)........................................................................................................ 5
System Programs .................................................................................................................................. 5
VSX Option & Settings Displays ......................................................................................................... 6
Programming & Operations.................................................................................................................. 7
Emergency Functions ..................................................................................................................... 7
Rain Shutdown ......................................................................................................................... 7
Controller Setup.................................................................................................................................... 8
Field Controller Options....................................................................................................................... 9
Edit FC Settings.............................................................................................................................. 9
Set Address ................................................................................................................................... 10
Set Time........................................................................................................................................ 10
Set Date ........................................................................................................................................ 11
Set Main % Scale.......................................................................................................................... 11
Set Schedule Length ..................................................................................................................... 12
Set Schedule Day.......................................................................................................................... 12
Set Day Change ............................................................................................................................ 13
Set FCP Inhibit ............................................................................................................................. 13
Set Response................................................................................................................................. 14
Set MR Runtime ........................................................................................................................... 14
Set MR Pump ............................................................................................................................... 15
Set PINS ....................................................................................................................... ................ 15
Writing a Field Controller Program.................................................................................................... 16
Naming a Program........................................................................................................................ 16
Typing Instructions ................................................................................................................. 16
Assigning a Schedule.................................................................................................................... 17
Daily ....................................................................................................................................... 17
Day of Week ........................................................................................................................... 17
Assigning a Start Time ................................................................................................................. 20
Stations, Run Times & Events...................................................................................................... 21
Station Options ....................................................................................................................... 25
Delete an Event.................................................................................................................26
Cluster Events................................................................................................................... 26
Move an Event .................................................................................................................. 28
Insert an Event .................................................................................................................. 29
®
Program Advanced Options ................................................................................................................ 30
Set Program % Scale .................................................................................................................... 30
Cycles .......................................................................................................................................... 31
Cycle Delay .................................................................................................................................. 31
Skip Days...................................................................................................................................... 32
Pump .......................................................................................................................................... 33
Manual Starts...................................................................................................................................... 34
Semi-automatic Program Operation ................................................................................................... 35
Presets................................................................................................................................................. 36
Field Controller Advanced Options.................................................................................................... 37
Remove a Program ....................................................................................................................... 37
Remove Preset .............................................................................................................................. 38
Edit Decoders ............................................................................................................................... 38
Serial Number......................................................................................................................... 38
Power Factor........................................................................................................................... 38
V iew SYS Events.......................................................................................................................... 39
Remove SYS Events..................................................................................................................... 40
Radio Xmit Test............................................................................................................................ 40
Maintenance Radio Operations .......................................................................................................... 40
TRNR radio .................................................................................................................................. 41
Sending a Maintenance Radio Command .................................................................................... 42
MR Command Table..................................................................................................................... 43
Display Messages (Status, Errors and other Conditions) ................................................................... 44
OVERLOAD................................................................................................................................. 44
COLD START (Erase All)............................................................................................................ 45
VSX Series Specifications.................................................................................................................. 47
The VSX controller may be used as a standalone controller for up to 60 stations, or 103 stations in a decoder system. It may also be part of a central system, connected to a central computer via radio or hardwire com­munications. You can upgrade a standalone VSX controller to a networked controller at any time, by adding communications kits and connecting it to a central computer.
Two Controllers in One: The VSX actually has two different “brains” for storing and running two different kinds of irrigation programs. The keypad on the controller can create and run Field Controller Programs in one brain. An optional central control sys­tem, with a computer and communications, can create and transmit System Programs to the other brain.

Field Controller Programs

VSX OPERATING MANUAL
Field Controller Programs (FCPs) are the Programs numbered 1 through 64, which you can write from the keypad or the central com­puter. You can change them in the field at any time. They will run at the start times you specify and do exactly what you tell each one to do. They can also be remote-controlled from the VSX Express central computer software, if a central is installed.
Most of this manual is concerned with config­uring and operating FCPs through the keypad.

System Programs

System Programs are calculated by the Sur­veyor or Vista control software, and down­loaded from the central computer to each field controller. They are often based on automatic calculation from local weather conditions (ET, or evapo-transpiration), and they are almost always Flow Optimized. You can view the System Programs in each Field Controller, but you may not edit them there. You can also delete the System Program information from a Field Controller, but you must replace it with FCPs or the controller will not irrigate.
Generally, FCPs are used as the primary irrigation programs during grow-in (when there may not be a central computer), and are used later on for special purposes, after the central computer has taken over the primary daily irrigation. They can be used to germinate seed in repair areas, or for other special cases where the superintendent desires absolute control over each irrigation event.
Computerized System Programs are designed to operate the largest systems, more or less automatically. The superintendent can modify their general parameters at any time, but they handle the details of irrigation events inter­nally. Computerized System Programs do not need to be micro-managed (station by station); they only need to be adjusted in groups of similar stations (All Greens, Hole 14 Tee, etc.).
Detailed instructions on System Programs are provided in the software manual for the central software.
Why two different kinds of Programs?
Different superintendents manage their irriga­tion in different ways, and irrigation systems go through many different phases in their annual cycle. The VSX Field Controller is equipped to handle every phase of irrigation, including grow-in, seasonal changes, overseeding, winter­ization, and special applications like fertiliza­tion, frost control, and dew wipe.
5
®

VSX Option & Settings Displays

Options
(Press Options button from time/date display)
Pause W atering List FC Settings Edit FC Settings Block Programming
Create Edit Remove
Remove Program Remove Preset Edit Decoders (decoder controllers only) V iew SYS Events Rem SYS Events Radio Xmit Test (Radio controllers only)
Edit FC Settings
(From Options, Edit FC Settings)
Address Time Date Main % Scale Schedule Length Schedule Day Day Change FCP Inhibit? Response MR Runtime MR Pump PINs
Program Options
(Options when a Program or Preset name is selected)
Edit Program Name Set Program % Scale Cycles Cycle Delay Skip Days Pump
Schedule Options
(Options when Schedule is selected)
Daily (up to 31-day schedule) Day of Week (SMTWTFS)
Station Options
(Options when a Station is selected)
Remove Event Cluster Events Move Event Insert Event
1. Stops all irrigation; enables and disables Rain Shutdown.
2. Sets run times and order for stations and Blocks.
3. Accesses multiple options and controller settings. Different sets of options appear, depending on mode controller is in (with other keys).
4. Saves field inputs and edits.
5. Selects between fixed choices in the display, and selects Rain Shutdown yes/no when Off is pressed.
6. Alphanumeric buttons for data entry.
7. Clears display error messages; erases Program Name in Edit mode.
6
8. Determines type of schedule and actual water days On/Off for the selected Program
9. Navigate backward/forward through displays, Programs, and Option choices.
10. Defines Start Time for automatic Programs; launches Preset programs immediately..
11. Starts one or more stations immediately.
12. Cycles through available Preset names, allows access for creation or editing, or immediate start with Start button.
13. Cycles through available Program names, allows access for creation or editing, or immediate start with Start button.
14. Escapes current function and exits to next highest level.

Programming & Operations

VSX OPERATING MANUAL
Note: The VSX keypad display has a built-in timer, and will automatically exit any pro­gramming mode after 3 minutes if left un­touched. If you are using the password protection feature, you will be required to log back in, once this has happened. Any data not saved will be lost if the controller auto-exits.
Emergency Functions (OFF and Pause):
OFF: If you need to stop all irrigation at a controller immediately, press the OFF button to the right of the display. You may see a brief message, STOPPING ALL IRRIGATION, followed by:
Rain Shutdown: Rain Shutdown turns off all automatic functions, permanently, until a human operator manually removes the con­troller from the Rain Shutdown mode (from the VSX keypad or a central computer). If you want to enter the Rain Shutdown mode, press ENTER. The display will show:
If you do NOT want to enter Rain Shutdown, press the OFF button again (upper right of the keypad) or any other button except ENTER. This will simply shut down all current irrigation until the next scheduled Start Time. Note that if another automatic Program was scheduled to start one minute later, the controller will begin irrigating again in one minute.
To turn off Rain Shutdown (and restore the controller to automatic operations): When the display shows RAIN SHUTDOWN!, press OFF. The display will show:
Press ENTER, and the controller will return to the automatic mode.
Pause: The VSX controller features dynamic pause, which will suspend all irrigation at the controller temporarily. This will apply to manual, semi-automatic, automatic, and Preset Programs. The irrigation will remain paused until resumed by a human operator or until 30 minutes have elapsed. The controller will resume irrigating where it left off.
You will have to remember to place the controller back into automatic operation when irrigation is required again.
Note that Pause will cause the end of the “water window” to be ignored – the end time of the paused Program will be pushed back for the duration of the Pause.
7
®
To Pause a controller: Press OPTIONS. The display will show:
Press ENTER to select this Option. The display will show:
“YES” will be capitalized. To Pause the controller, press ENTER. The display will then show:
To Resume watering, press ENTER while the display says Resume Watering? The display will then show:
the controller into Pause, it will automatically resume after 30 minutes.
(The “no” selections will be in lower case. Press the TOGGLE button to switch between YES and NO. If you do not want to pause/ resume the irrigation, TOGGLE to NO and press ENTER, or simply press EXIT.)

Controller Setup

When you start up a brand new VSX controller, or if you have erased the controller memory and are reprogramming from scratch, you must set up some basic operating information first.
Press the OPTIONS button. The display will show “Pause Watering?” Press the OPTIONS button again. The display will show “List FC Settings?” Press ENTER. The display will automatically sequence the current information for the field controller in the following format:
Press ENTER with YES capitalized, and the controller will resume irrigating where it left off when you paused it. No irrigation will be missed. After 3 minutes, the Resume W atering? display will disappear, but the display will continue to flash PAUSE with the amount of time left to automatic resume. Press OPTIONS to return to the Resume Watering? display.
Note that if the controller was paused for 20 minutes, the currently active and any subsequent stations will be moved back in time 20 minutes. If the Program would normally have ended at 5:30 AM, it would now end at 5:50 AM.
If you forget to Resume irrigation after placing
Version number: The version of field control­ler software installed in the VSX. Time: On start up, this may be incorrect, but it will show the time of day that VSX thinks it is. Date: On start up, this may be incorrect, but it will show the day of week and year that VSX thinks it is. Size: This will show how many stations the VSX can operate, and in conventional systems it will either be 20, 30, 40, 50, or 60. You may expand the VSX controller hardware in incre­ments of 10 stations at any time, up to a maxi­mum of 60 stations. In decoder systems, the Size will always be 103. AC: Shows the frequency of the incoming AC power . This is a very important setting, since the VSX uses the AC power frequency to count time. North American systems are generally set to 60 Hz (Hertz). Many international systems are set to 50 Hz. If you are not sure which
8
VSX OPERATING MANUAL
VSX Field Controller Options:
setting to use, consult a local licensed electri­cian for the correct value. Refer to the installation instructions if you need to change this setting. Address: The unique identification number for a particular VSX controller in a central system. If your controller is a standalone, you may leave this set to “0” unless you plan to use it with Maintenance Radio. Main Scale: Indicates that the controller will operate each station for 100% of its scheduled Run Time. Cur Sch Len: A VSX may be programmed on a multiple day schedule (from 1 to 31 days). This shows the actual schedule length of the controller. Cur Sch Day: This shows which day (of the schedule in the previous setting) that the con­troller thinks it is – in this case, day 1 of a 1-day schedule. Day Change: The time at which the schedule day changes. The default is midnight, but you may change the time of day-change to any hour of the day. Inhibit is OFF: This setting is only meaningful in central systems, and shows the status of the Field Controller Programs (FCPs). If they have been inhibited, they will not run. Response: This setting is only meaningful in central systems, and shows how much commu­nicating the VSX controller will perform with the central computer. MR Run Time: This is the default time-out for stations started with Maintenance Radio with­out a run time specified. If you forget to turn the station off, VSX will turn it of f for you in 30 minutes. MR Pump: This specifies whether the Pump output turns on whenever a station is started by a Maintenance Radio command. Current ET Day: This is only used in central systems which calculate “look ahead” sched­ules based on evapo-transpiration rates, and download them to the controller. This display will indicate which day of the ET schedule you are on.
When the controller has finished sequencing through the FC Settings, it will show the current day and time. There may be a “POWER OUTAGE” message flashing in the display. Press the CLEAR button to clear this message.
If you continue to press the OPTIONS button, you will cycle through all of the available controller options:
Pause Watering? Stops irrigation temporarily; restarts where it left off. List FC Settings? Automatically displays vital Field Controller settings. Edit FC Settings? Allows you to change vital Field Controller settings. Block Prgraming? Allows you to group multiple stations into a single “block” for programming purposes. See Blocks on page 23. Remove Program? Allows you to delete a single program, including all station run times. Remove Preset? Allows you to delete a single Preset, including all station run times. Edit Decoders? Allows setup and/or changes to decoder/station assignments. View SYS Events? Allows you to view the downloaded System Program events. Del SYS Events? Allows you to delete the downloaded System Program events. Radio Xmit Test? (Radio controllers only) Generates a 5-second test tone for diagnostics. Edit FC Settings: Of all the Field Controller options, this is the most vital to set up on a new installation. Many of the powerful features of VSX will not work, or will not
9
®
work as intended, until these settings are made.
Press OPTIONS 3 times and the display will show “Edit FC Settings?” In this menu, you are able to change many of the settings dis­played in the “List FC Settings” menu above. Press ENTER, and the display will show “Set
Address?”
You may now press ENTER, to set or change the Address, or press OPTIONS again, to view further settings. You can also use the BACK and NEXT buttons to move backward and forward through the settings. Whenever the display shows a setting you want to change, press ENTER to edit it.
Set Address: Your VSX Field Controller cannot communicate with Maintenance Radio or a central system until it has an Address. Each controller must have a unique 3-digit number, so that the central interface and/or Maintenance Radio can direct communications to the correct controller. In central systems you will also need to make sure that a list of correct Field Control­ler addresses is configured in the central software.
If your VSX controller is a standalone, and you are not using Maintenance Radio, the Address is not necessary.
bered. However, each controller must have a unique address. If more than one controller has the same numeric address, the system will become confused and errors will occur.
Once the address is set, you may use the OPTIONS, BACK, or NEXT buttons to view more options, or you may press EXIT to leave the Edit Settings mode.
The other changeable settings are:
Set Time?: To set the time, press ENTER. The display will show:
Type the correct time (1:15, for example, in hour, then minute format), and press ENTER. The display will show:
The current am/pm selection will be capital­ized. The other selection will be in lower case. Press the TOGGLE button to switch between AM and PM. When it is correct, press ENTER. The display will show:
When the display shows “Set Address?”, press ENTER. The display will show:
Type the address you want with the number buttons on the keypad and press ENTER. The display will show “SAVED! Address = 2”. The address is now saved. You can use any 3­digit number, and controllers in a central system do not need to be sequentially num-
10
Press ENTER to set the time. The display will briefly show SAVED! and the time you have set. After a moment, the display will revert to:
VSX OPERATING MANUAL
You may now press the OPTIONS, BACK, or NEXT buttons to view more options, or you may press EXIT to leave the Edit Settings mode.
Set Date: To set the Date, press ENTER at this display. The display will then show:
Note: VSX dates are always shown in North American format (month/day/year).
T ype the number for the correct month (1-12), in this case “3” for March, and press ENTER (you can also use the BACK/NEXT buttons to move around in the Date). The display will then show:
You may now press the OPTIONS, BACK, or NEXT buttons to view more options, or you may press EXIT to leave the Edit Settings mode.
Set Main % Scale: “% Scale” allows you to reduce or increase all of the Run Times in the controller by the selected percentage (from 1 to 250%, in 1% increments). This enables you to quickly adjust the amount of irrigation for weather or other conditions without changing the basic programs. At 50%, each Run Time will only run half as long, and at 150%, each Run Time will run one-and-half times as long.
Note: In the Program Options, you can also scale individual Programs separately. The effects of % scaling are cumulative. See Set Program % Scale on page 30.
To set the Main % Scale from the Edit FC Settings mode, press ENTER at this display. The display will then show:
Type the number for today’s date (“8” in this example), and press ENTER. The display will show:
Type the correct year, and press ENTER. The display will show:
Press ENTER to set the date. The display will briefly show SAVED! and the date you have set. After a moment, the display will revert to:
Type the percentage you want with the number buttons on the keypad, and press ENTER. The display will briefly show “SAVED!” and the new % Scale amount. After a moment, the display will revert to:
You may now press the OPTIONS, BACK, or NEXT buttons to view more options, or you may press EXIT to leave the Edit Settings mode.
Note that, whenever the controller is scaled up or down (to any value other than 100%), a “+” or “-” sign will appear as a reminder in the upper left corner of the status display (before the Day and Time information).
11
®
Once the Main % Scale has been changed, the scaled run times for all stations will be dis­played when the Stations button is pressed in any Program. To return to the original (or base) run times, repeat the procedure above and change the Main % Scale to 100%.
Set Schedule Length: The Schedule Length is the number of days in a complete VSX watering period, and allows the controller to track pro­grams which do not water every day. If you only water a certain plant type every other day, for example, you could enter a 2-day Schedule, and schedule that program to water on just one of the days. The Schedule Length is tracked for the entire controller. To set the watering Sched­ule for individual programs, go to the individual Program and press SCHEDULE (see Schedule on page 16).
If you are not sure what schedule you need, start out with a 7-day schedule (so that it matches the number of days in a calendar week). You can always change it later.
If you always water everything every day , you can also just set a 1-Day schedule.
To set the Schedule Length: Press ENTER at the “Set Sched Len?” display. The display will then show:
You may now press the OPTIONS, BACK, or NEXT buttons to view more options, or you may press EXIT to leave the Edit Settings mode.
Set Schedule Day: The Schedule Day shows which day of the Schedule the controller thinks it is. For example, if you had set a 7-day sched­ule for a Schedule Length (above), you could tell the controller that today is Day 1 of the 7­Day Schedule, meaning Sunday. If today happens to be Wednesday, you could tell it that today is Day 4 (of the 7-day schedule).
Another example would be if most of your irrigation occurred every day, but a few pro­grams only run every other day (regardless of the day of the week). You could set up a 2-day Schedule Length, and then tell the controller which of the two days today is (1 or 2). In the Program Schedule (see Schedule on page 17) you can specify which days the individual Programs will water .
To set the Schedule Day (for today): Press ENTER at the “Set Sched Day?” display. The display will then show:
The default Schedule Length is 14 days: the maximum is 31 days. Type the number of the new Schedule Length with the number buttons on the keypad, and press ENTER. The display will briefly show “SAVED!” and the new Schedule Length selection. After a moment, the display will revert to:
12
Type the number of the new Schedule Day with the number buttons on the keypad, and press ENTER. The display will briefly show “SAVED!” and the new Schedule Day selec­tion. After a moment, the display will revert to:
You may now press the OPTIONS, BACK, or NEXT buttons to view more options, or you may press EXIT to leave the Edit Settings mode.
VSX OPERATING MANUAL
Set Day Change: The programmable Time of Day Change option allows you to tell the controller at what time one day changes into another, when using the Daily Schedule option.
The default is, of course, midnight (12am). However, this occurs right during the middle of many irrigation cycles. If you water a certain Program every other day, and the irrigation spans across midnight with multiple cycles, you may lose the portion of the irrigation which technically falls on a non-irrigation day.
To prevent this and similar confusion, you may specify a different hour for your irrigation days to change. Usually this is done after all irriga­tion is completed. If your night’s irrigation is completed by 7 in the morning, you might wish to set the Day Change to 8:00am. Then, all of your irrigation will fall within a single irrigation day.
Note: Time of Day Change only applies to Daily schedules. Day of Week schedules always change at midnight.
You may only set the Day Change to an exact hour (no minutes).
To set the Day Change: Press ENTER at the “Set Day Change?” display. The display will then show:
The current selection will be capitalized. Other selections will be in lower case. Press the TOGGLE button to switch between AM and PM. When it is correct, press ENTER. The display will show:
Press ENTER to set the Day Change. The display will briefly show SAVED! and the time of Day Change hour you have set. After a moment, the display will revert to:
You may now press the OPTIONS, BACK, or NEXT buttons to view more options, or you may press EXIT to leave the Edit Settings mode.
Set FCP Inhibit?: FCPs (Field Controller Programs) are the Programs numbered from 1 through 64 in the Field Controller. The control­lers may also irrigate with a master system program from the central computer, which is independent of the FCPs, and both types of programs may run at the same time.
FCP Inhibit will prevent all of the numbered FCPs from running, so that the only irrigation will be that sent out by the central computer’s master system program.
Type the number for the Day Change hour (8, in this example) with the number buttons on the keypad, and press ENTER. The display will show:
Remember that FCP Inhibit ON means the FCPs will NOT run. FCP Inhibit set to OFF means the FCPs will run normally.
13
®
T o set FCP Inhibit: Press ENTER at the “Set FCP Inhibit?” display . The display will then show:
The current selection will be capitalized (de­fault is OFF). The “on” selection will be in lower case. Press the TOGGLE button to switch between OFF and ON. When it is correct, press ENTER. The display will flash “SAVED!” and your selection. After a moment, the display will revert to:
The current selection will be capitalized (default is PARTIAL). The “full” selection will be in lower case. Press the TOGGLE button to switch between PARTIAL and FULL. When it is correct, press ENTER. The display will flash “SAVED!” and your selection. After a moment, the display will revert to:
You may now press the OPTIONS, BACK or NEXTbuttons to view more options, or you may press EXIT to leave the Edit Settings mode.
Set Response?: This will set the level of Field Controller response to the central computer (if it is present and communicating). In the Partial Response setting, the field controller will report any alarm conditions (such as Fuse Open, Overload, Power Outage, etc.) if they occur .
In the Full Response setting, the Field Control­ler will report all events as they occur, includ­ing every station start and station stop, as well as alarms. Full Response will also continuously update the Station Status Display on the central computer.
If full reports are not desired, or cause too much communications “chatter”, you can set this to Partial.
You may now press the OPTIONS, BACK, or NEXT buttons to view more options, or you may press EXIT to leave the Edit Settings mode.
Set MR Runtime?: MR = Maintenance Radio. This determines the time-out timer setting for stations started by Maintenance Radio without specified Run Times.
If you simply start a station with Maintenance Radio without a specific run time (see Sending a Maintenance Radio command on page 41) and forget to turn it off, this setting will auto­matically shut it off after the time shown, to prevent flooding and damage. The default value is 30 minutes. You may select a longer or shorter setting, from 1 minute to 18 hours, for this safety feature.
To set MR Runtime: Press ENTER at the “Set MR Runtime?” display. The display will then show:
To set Response: Press ENTER at the “Set
Response?” display . The display will then show:
14
Type the number for the default Maintenance Radio timer (example: 20 minutes) with the
VSX OPERATING MANUAL
number buttons on the keypad, and press ENTER. The display will show:
Press ENTER to set the MR Runtime. The display will briefly show SAVED! and the MR Runtime you have set. After a moment, the display will revert to:
You may now press the OPTIONS, BACK, or NEXT buttons to view more options, or you may press EXIT to leave the Edit Settings mode.
Set MR Pump?: MR = Maintenance Radio. This determines whether the Pump output in the Field Controller will be activated whenever Maintenance Radio starts stations. If you are using the Pump output to activate a Pump Start Relay or a Master Valve, you can choose to have that output come on whenever a Mainte­nance Radio command starts a station.
You may now press the OPTIONS, BACK, or NEXT buttons to view more options, or you may press EXIT to leave the Edit Settings mode.
Set PINS: The VSX controller has 2 levels of optional password protection: The Supervisor level can perform all program­ming functions. The Operator level can perform basic functions (START and STOP commands) which do not affect the automatic programs and their options.
Each level of access can be protected by a 4-digit Personal Identification Number (PIN).
To set PINs: Press ENTER at the “Set PINs?” display. The display will then show:
T ype any 4 digits (there must be exactly four, from 0001 to 9999) which you will be able to remember, and press ENTER. The display will show:
To set MR Pump: Press ENTER at the “Set MR Pump?” display. The display will then show:
The current selection will be capitalized (de­fault is YES). The “no” selection will be in lower case. Press the TOGGLE button to switch between YES and NO. When it is correct, press ENTER. The display will flash “SAVED!” and your selection. After a moment, the display will revert to:
T ype exactly the same PIN number again and press ENTER. The display will show “SAVED!”.
If you fail to enter the same number the second time, the display will show ERROR! You will then need to reenter the PIN and enter the confirmation a second time.
Once the PIN has been entered correctly, the display will show:
15
®
Writing a Field
Repeat the sequence above to enter an Operator’s PIN number. You are not required to enter a second level of password protection. If you do not want an Operator level, simply press ENTER at this display without entering anything.
If the second (verification) entry of either Supervisor or Operator level PINs results in an error, no PIN has been created.
You may change the passwords at any time, but you must first log on to the controller with the existing Supervisor-level PIN. If you forget your PIN, you can clear the password settings. Contact your distributor or Hunter Field Ser­vices for help to clear the password settings.
When you press the EXIT button at any time on the keypad, it will exit the function you are in and return to the next-highest level in the controller . After you exit all the way back to the normal time/date display , and press EXIT again, the display will show “LOGGED OFF”. This means that a valid PIN must be entered to log back on before any programming or operations take place (if PINs are enabled). If you do not log off when finished, the controller will log off automatically after 3 minutes of no activity .
When the PIN settings are complete, press ENTER. The display will flash “SAVED!” and your selection. After a moment, the display will revert to:
You may now press the OPTIONS, BACK, or NEXT buttons to view more options, or you may press EXIT to leave the Edit Settings mode.
Controller Pr ogram
Press the PROGRAM SELECT button. The display will show:
This indicates that you are in Program # 1, with 0 out of 64 total Programs in use. The numbers may vary if there are already pro­grams in the controller’s memory. There may already be a program name in place of the dashes. You can edit any Program at any time. For now, we will work on Program 1 as the controller came “out of the box”.
Naming a Program:
Press the OPTIONS button. The display will show “Edit Prg Name”? Press ENTER. The bottom line of the display will show “Alpha entry mode”, and the cursor will be flashing on the first space. Use the buttons on the keypad to type in a name for the Program. You may mix letters and numbers to create accurate names for each Program (up to 10 total characters long).
Typing Instructions:
Each number button also has a series of letters of the alphabet assigned to it. While the display says “Alpha entry mode” the buttons will type letters only. Press the button rapidly to display the letter you want. If you release the button for more than about 1 second, the letter will be selected and the cursor will advance to the next position.
16
To type the word “TEE”, for example, press the “T” button (#8) once, and wait for a sec­ond. You may hear a faint beep, and the cursor will advance to the next space.
Loading...
+ 32 hidden pages