Hunter 44905 Installation Sheet

Page 1
©2010 Hunter Fan Company 44049-01 R20100416
This thermostat is compatible with most conventional oil, gas, electric, hot water systems, single stage, and multi-stage heat pumps. This thermostat will not control line voltage systems.
You will need the following tools to complete your installation:
• Phillips Screwdriver (#2)
• Two 1.5V (AA) size alkaline batteries
• Read all installation instructions before beginning installation! If you still need assistance after reading this manual, call our
Technical Support at 1-888-830-1326.
• Do not disconnect the wires from your old thermostat until all wires have been properly labeled. You must label all wires properly because wire color may not indicate the function of the wire.
• All wiring must be done in accordance with local code and ordinances.
• Always turn power off to your furnace/compressor before the installation process. Failure to do so could result in damage to your thermostat and/or your heating and cooling system. Do not restore power until your installation is complete.
• This thermostat is designed for use with 24V AC/millivolt systems with a maximum of 1 amp. Higher amp or line voltage systems will cause damage to your system and increase the risk of fire.
44905 Touch Screen ermostat
Preparation
Gathering Tools and Warnings
1
Old ermostat Removal
1. Turn off power to your compressor and furnace.
2. Remove the cover to your existing thermostat. Some thermostats
may have screws or other locking devices that must rst be removed. Once the wallplate is exposed, locate the wire terminals and try to identify the wire designations. If the wire terminals are not visible, they may be connected to the back of the wallplate. Look for any additional screws, tabs, or locking devices to remove the wallplate. See Figure 1. If you are still unable to nd the terminals for the wires, it may be necessary to contact the manufacturer of the original thermostat.
3. Use the table in Figure 2. to write down your wire colors and
the letter designations on the old thermostat. This will allow you to keep a record of your old thermostat’s wiring conguration should you need to refer to it at a later time. This will also help our Technical Support Department determine your system type and proper wiring, should you need to contact them. Wire color does not indicate the function of the wire, this is being used only to help determine which wire has what letter designation.
Installation
2
Mounting the Wallplate
After writing down the wire colors and letters, use the terminal stickers to label the wires. Figures 3a and 3b will help you depending on system type; Conventional or Heat Pump. Not all terminals will be used, this will be determined by your system type.
To ensure wires do not fall back into the wall hole, you may tape them to the wall, or wrap them around a pencil.
Figure 4. may assist you if your old thermostat is a heat pump from one of the listed Manufacturers and your wire labels do not match. It is located on the back of this sheet. These tips will also help you in wiring:
• Only 1 reversing valve is needed to run a heat pump. If both “O” and “B” are present, “B” may be a common wire.
• Often, 2-wire heat only systems do not have terminal labels. Connect 1 wire to the Rh terminal and the other to W.
• If you have a 3-wire hot water system, the damper valve control wire will be labeled and attached to the “A” terminal.
• If you need further assistance with wiring, or determining your system type, you can contact our Technical Support Department. See the “Technical Support” section for information.
Wire Color Wire letter
Figure 2.
Figure 3b.
R, V
R
Y, Y1, M
Y
G, F
G
L, F, X
L
O, R
O
B
B
W2, E, X,
Aux
E
Y2
Y2
C, X, X1, B
C
Heat Pumps
W
G
Y
RH
C
Figure 6.
1. Remove the mounting plate by pulling it straight off the back of the Thermostat. Figure 5.
Figure 5.
2. Pull the wires through the back of the mounting plate, ensuring none of the wire labels are removed. Figure 6.
Figure 7.
bubble level
Figure 8.
W
G
Y
RH
C
3. Using a Phillips Screwdriver, Partially install 1 screw into the top hole of the thermostat. Ensure the thermostat is level using the bubble level on the mounting plate Figure 7., then install the other screw. Tighten both screws until secure. Figure 8.
Figure 11.
4. Check the charts on the back of this sheet and identify your system type. They are divided by Conventional and Heat Pump installations.
5. Raise all of the levers on the terminals you will be using. Heat Pump Installation labels are located on the left of the terminal blocks on the mounting plate and Conventional labels are on the right. If your installation does not call for the jumper, remove it now. It is located underneath the wire holes, between the RH and RC terminals on the conventional side. Figure 9.
6. If one of the terminals you need has a tab in front of it, use your nger to break the tab away. Figure 9.
Note: Only break tabs you know you will be using. Double
check your wiring conguration and make sure you are familiar with the terminals you will be using.
7. Insert the bare end of each wire all the way into the appropriate hole in the terminal block that matches the wire label then lower the lever. This will lock each of the wires in place. Tuck excess wire back into wall after they have been locked in the mounting plate.
Note: Do not insert the wires into the holes in the top of the
mounting block. The wires should be inserted into the front close to the hole in the mounting plate. See Figure 8.
8. Lay the ribbon across the battery compartment and install 2 (AA) Batteries into the back of the thermostat over it, Figure
10., and snap the thermostat on to the mounting plate. Refer to “Setup” on page 8 of your owner’s manual to continue setup, scheduling, and daily use.
If you have any additional questions or problems with your Hunter thermostat, please call:
USA: 1-888-830-1326
Canada: 1-866-268-1936
Hours of operation are from 7:00 am to 7:00 pm Monday - Friday and 8:00 am to 5:00 pm on Saturday, Central Time. You may also contact us over the Internet at www.hunterfan.com.
Technical Support
Installation Sheet
Conventional
RH
RH
RC, R
RC
Y, Y1
Y
G, F
G
W, W1
W
W2
W2
Y2
Y2
C
C
A
A
Figure 3a.
Figure 1.
Y
RC
G
W
Y
RC
G
W
ermostat Cover
Wallplate
ermostat Cover
Wallplate
W
G
Y
C
W G Y RC RH
RH
Tabs
Levers
Figure 9.
Jumper
Insert Wires
Labeling Your Wires
Page 2
HEAT PUMP
Hunter Carrier Coleman Comfortmaker Bryant, Payne Rheem Ruud
Trane,
Weathertron
York Lennox (1) Lennox (2)
R R R R R R R R R V-VR
Y Y or Y1 Y Y Y Y Y Y Y M
E W2 W2 W1 W2 W2 W W W1 Y
E E Jumper to W2 E E X2 Jumper to W2 E E
O O O O O O O R
B B B
G G G G G G G G G F
L L or F L L or X L L X L
C C X C, X, X1 C , X, X1 X B B C X
Figure 4.
CONVENTIONAL
4 Wire Heat / Cool
ermostat Mounting Plate
Wall
RH
RC
Y
G
W
W2
Y2
C
A
RH
Y
G
W
Jumper
Heat Power
Cool Contactor
Fan Relay
Heat Contactor
3 Wire Cool Only
ermostat Mounting Plate
Wall
RH
RC
Y
G
W
W2
Y2
C
A
RC
Y
G
Jumper
Cool Power
Cool Contactor
Fan Relay
2 Wire Heat Only
ermostat Mounting Plate
Wall
RH
RC
Y
G
W
W2
Y2
C
A
RH
W
Jumper
Heat Power
Heat Contactor
4 Wire with Common
ermostat Mounting Plate
Wall
RH
RC
Y
G
W
W2
Y2
C
A
RH
Y
G
W
C
Jumper
Heat Power
Cool Power
Cool Contactor
Fan Relay
Heat Contactor
Common
5 Wire Heat / Cool
ermostat Mounting Plate
Wall
RH
RC
Y
G
W
W2
Y2
C
A
Heat Power
Cool Power
Cool Contactor
Fan Relay
Heat Contactor
RH
RC
Y
G
W
3 Wire Heat Only
ermostat Mounting Plate
Wall
RH
RC
Y
G
W
W2
Y2
C
A
RH
G
W
Jumper
Heat Power
Fan Relay
Heat Contactor
3 Wire Hot Water with Damper Valve
ermostat Mounting Plate
Wall
RH
RC
Y
G
W
W2
Y2
C
A
RH
W
A
Jumper
Heat Power
Heat Contactor
Damper Valve
Conventional Multi-Stage
ermostat Mounting Plate
Wall
RH
RC
Y
G
W
W2
Y2
C
A
RC
Y
G
W
W2
Y2
Jumper
Heat Power
Cool Contactor
Fan Relay
Heat Contactor
Second Stage Heat Second Stage Cool
Single Stage Heat Pump
ermostat Mounting Plate
Wall
R
Y
G
L
O
B
Aux/E
Y2
C
R
Y
G
O
Jumper
Heat 24V Supply
Cool Contactor
Fan Relay
Cool Relay / Valve
ermostat Mounting Plate
R
Y
G
L
O
B
Aux/E
Y2
C
Single Stage Heat Pump W/Aux Heat
Wall
R
Y
G
O
E
C
Jumper
Heat 24V Supply
Compressor Contact
Fan Relay
System Monitor*
Cool Relay / Valve
Auxiliary Heat
Common*
* The common wire “C” and system monitor wire “L” may or
may not be present.
L
Single Stage Heat Pump W/Heat Reversing
ermostat Mounting Plate
Wall
R
Y
G
L
O
B
Aux/E
Y2
C
R
Y
G
B
C
Jumper
L
* The common wire “C” and system monitor wire “L” may or
may not be present.
E
Heat 24V Supply
Compressor Contact
Fan Relay
System Monitor*
Heat Relay / Valve
Auxiliary Heat
Common*
Multi-Stage Heat Pump
ermostat Mounting Plate
Wall
R
Y
G
L
O
B
Aux/E
Y2
C
R
Y
G
L
O
E
Y2
C
Jumper
* The common wire “C” and system monitor wire “L” may or
may not be present.
Heat 24V Supply
Compressor Contact
Fan Relay
System Monitor*
Cool Relay / Valve
Auxiliary Heat
Second-Stage Cool
Common*
Loading...