Hunter 43007, 43018 Owner's Manual

SERVICE INSTRUCTIONS
CALIBRATION
Bimetal
FIG. 6. CALIBRATING THERMOSTAT
The thermostat is accurately calibrated before leaving the factory and no further calibration should be necessary. If the thermostat appears to be out of calibration or for any reason fails to function properly, a qualified serviceperson should proceed as follows:
1. The anticipator’s heat may adversely affect thermostat recalibration. To prevent this, disconnect electrical power power to the thermostat at the furnace, main fuse, or breaker box.
2. Move temperature adjustment lever to a setting about 5° above room temperature.
Arrow points to the
matched current rating
of the primary control.
FIG. 7. ANTICIPATOR ADJUSTMENT
41630-01 4/22/2003
Temperature
adjustment
lever
7/32” Calibration
wrench
HEAT ANTICIPATION ADJUSTMENT
Move this lever
to adjust heat
anticipator.
3. Remove thermostat cover. Slip 7/32” wrench onto hex nut beneath bimetal. While holding temperature adjustment lever stationary, turn hex nut clockwise until mercury shifts to the right end of the tube (fig. 7).
4. Move temperature adjustment lever to lowest setting.
5. Replace thermostat cover. Wait 10 min. for bimetal temperature to stabilize. Do not stand near the thermostat during this period, as your breath and body heat will affect bimetal temperature.
6. Move temperature adjustment lever to correspond to actual room temperature. Then remove thermostat cover.
7. Slip 7/32” wrench onto hex nut. While holding temperature adjustment lever stationary, turn hex nut counter-clockwise until mercury just barely shifts to the left end of the tube.
8. Replace thermostat cover and set temperature adjustment lever to desired temperature. Turn on electrical power to system.
Some heating installations require longer or shorter “ON”, “OFF” periods to maintain even temperatures. For average conditions, set the heat anticipator indicator to match the current rating of the primary heating control. Move indicator approximately 1/2 division in direction indicated by the arrows on the thermostat for longer “ON” cycles, or move lever in opposite direction for shorter “ON” cycles. Allow at least 24 hours to determine if setting provides satisfactory operation before making any further adjustments.
Climate Technology Corp. 2500 Frisco Avenue Memphis, TN 38114 A Hunter Fan Company
pg. 4
M E R C U R Y B U L B
MECHANICAL
CLIMATE
TECHNOLOGY
CORPORATION
CTC thermostats regulate 24 to 30 VAC single-stage heating-cooling systems. See the chart below
for specific models and applications.
THERMOSTAT MODELS AND APPLICATIONS
Tools needed for installation:
• Slotted Screwdriver • Electric Drill and 3/16” Bit
• Hammer • Level
ELECTRICAL DATA Switch Rating: 24VAC (30 VAC max.)
Heating - 0.2 to 1.2 amps Cooling - 0-1.5 amps
Switch Action: Sealed mercury switch Anticipator rating: Heating - Adjustable from 0.2 to 1.2 Amps
Cooling - Fixed 24 VAC
THERMAL DATA Temperature Range: 50ºF - 90ºF (10ºC - 32ºC)
WARNING!
Disposal Information
This product contains mercury
in a sealed tube. DO NOT place this
useful life.
contains mercury, DO NOT place the old product in the trash.
authority for instructions regarding recycling and the proper disposal of this product, or of and for any old control containing mercury in a sealed tube.
control in the trash at the end of its
If this product is replacing a control that
Contact your local waste management
INSTALLATION
When installing this product:
• Read these instructions thoroughly. Failure to follow them could damage the product or produce an unsafe condition.
• Check the ratings in these instructions and on the product to make sure the product is compatible with your application.
THERMOSTAT
SPECIFICATIONS
APPLICATIONS
This thermostat is designed for use with:
• Standard heating and cooling systems
• Electric heating and cooling systems
• Single stage heat pump systems
• Two-transformer systems
• Electronic air cleaners
• Humidifiers
• Zone Dampers This thermostat cannot be used with:
• Millivolt systems
• Multi-stage applications
To avoid electrical shock or equipment damage, make sure power is disconnected before installation.
• Installation must be performed by a trained, experienced service technician.
• Upon completion of the installation, verify the correct operation of the product as detailed in these instructions.
LOCATION
The thermostat should be located in an area with good air circulation at average temperature. It should be on an inside wall.
DO NOT place the thermostat where it can be affected by: – drafts or dead spots behind doors or in corners. – hot or cold air from ducts. – radiant heat from the sun, fireplaces, or appliances. – unheated (uncooled) areas behind the
thermostat, such as outside walls. This thermostat is a precision instrument and was carefully adjusted at the factory. Handle it
carefully.
ATTACH SUB-BASE TO WALL
LEVELING SURFACES
FACTORY INSTALLED JUMPER WIRE
YELLO
W
JUMPE
R
FIELD INSTALLED JUMPER WIRE
FA
CTORY INSTALLED JUMPER WIRE
Disconnect the power supply before beginning installation to prevent electric shock or equipment damage. All wiring must comply with local codes and ordinances.
To wire and mount the thermostat:
1. Remove cover from thermostat base by gripping the base in one hand. Use the other hand to pull gently at the top or bottom of the cover.
2. Carefully remove the protective packing.
3. Loosen the 4 screws holding the thermostat to the sub-base, then separate them. Refer to Figure 1.
4. Pull wires through opening near center of sub-base and connect wires beneath terminal screws (See figure 2-5 for typical wiring for each application, Also refer to the following subsections for special system configurations).
5. Push excess wiring into wall and plug hole with fire-resistant material (such as fiberglass insulation) to prevent drafts from affecting thermostat operation.
6. Position sub-base over hole in wall and mark mounting locations. Use any existing mounting holes if possible.
7. If the mounting screws will be going into drywall only, then drill 3/16” mounting holes for use with the included plastic anchors.
8. Fasten sub-base loosely to wall with two mounting screws. Place a level on the raised, flat surface near the bottom of the sub-base, adjust until level, then tighten the mounting screws. (Refer to Figure 2.)
An incorrectly leveled thermostat will cause the temperature control to deviate from the setpoint.
ATTACH THERMOSTAT TO SUB-BASE
1. Attach thermostat base to sub-base, being sure that 4 captive screws are tightnened snugly, since they serve as electrical connections between thermostat and sub­base.
2. Snap cover on thermostat and set switches and temperature lever to desired setpoint
3. Turn on power to the system.
SPECIAL APPLICATIONS
Electric Heat Furnaces
(Single Transformer Systems only)
The sub-base, as supplied, may not operate the fan correctly. If both the heating and the cooling system must operate the fan relay, remove the factory-installed jumper wire from the Y terminal and connect it to the A terminal. The fan should now cycle when the thermostat calls for either heat or cool.
Two-Transformer Systems
If two transformers are used, they must be in phase. Failure to do so may result in personal injury and/or property damage.
NOTE: Wire color does not indicate polarity. Polarity is obtained from an oscilloscope or voltmeter. Remove jumper between RC and RH terminals for two transformer systems.
This sub-base WILL NOT provide multi­stage heating or cooling operation. For single stage heat pump applications, install a short jumper wire across terminals W and Y. If the old thermostat has a terminal that is continuously energized, disconnect the wire from the old thermostat’s terminal and connect it either to the: 1) B terminal, if the reversing valve is energized on a call for heat; or to the 2) O terminal, if the reversing valve is energized on a call for cool. If the system heats on a call for cool, or vice versa, this wire has been connected to the wrong terminal. NOTE: RH and RC must be jumpered for single transformer heat pump systems.
The B and O terminals can provide switching for special functions other than heat pump operation. When the system switch is in the HEAT position, the B terminal is energized. When the system switch is in the COOL position, the O terminal is energized.
Heat Pump Applications
Special Application Terminals
TYPICAL WIRING DIAGRAMS
FIG. 3. SINGLE TRANSFORMER H/C SYSTEM
For electric heat-fan to cycle with either heat or cool, move yellow jumper from Y terminal to A
terminal (see dotted line at terminal A in illustration.)
FIG. 4. TWO TRANSFORMER H/C SYSTEM
Subbase
Thermostat
Cover
FIG. 1 ATTACH THERMOSTAT TO SUB-BASE
41630-01 4/22/2003
FIG.2. THERMOSTAT SUB-BASE
pg. 2 pg. 3
FIG. 5. SINGLE TRANSFORMER, SINGLE STAGE HEAT PUMP SYSTEM
Install jumper between W and Y terminals (see illustration.)
Loading...