Hubbell Electric Heater DF1000 Installation Manual

Page 1
OPERATING AND MAINTENANCE MANUAL FOR
POWER BURNER SERIES FORCED DRAFT
COMMERCIAL WATER HEATER

ELECTRIC HEATER COMPANY

BASE MODEL “ DF ”
Page 2
HUBBELL ELECTRIC HEATER COMPANY
P.O. BOX 288
STRATFORD, CT 06615
PHONE: (203) 378-2659 FAX: (203) 378-3593
INTERNET: http://www.hubbellheaters.com/
-- IMPORTANT --
Always reference the full model number and serial number when calling the factory.

WARNING / CAUTION

¾ Do not use or store gasoline or any other flammable vapors, liquids, or materials in the
vicinity of this or any other appliance.
¾ Due to the rigors of transportation, all connections should be checked for tightness before heater
is placed in operation.
¾ Safety relief valve must be installed in tapping provided.
¾ KEEP AWAY FROM LIVE ELECTRICAL CIRCUITS.
Do not perform any maintenance, make any adjustments, or replace any components inside the control panel with the high voltage power supply turned on. Under certain circumstances, dangerous potentials may exist even when the power supply is off. To avoid casualties, always turn the power supply safety switch to off, turn the charge or ground the circuit before performing any maintenance or adjustment procedure.
¾ Installation and service must be performed by a qualified installer, service agency or the gas
supplier. City, state, and national codes governing installation of commercial water heaters must be followed and take precedence over recommendations in this manual.
¾ The manufacturer’s warranty on this water heater is in effect only when the water heater is
installed and operated in accordance with these instructions and local codes and ordinances or, in the absence of local codes and ordinances, the National Fuel Gas Code (the latest ANSI Z223.1). In Canada, installation should conform to the latest CAN/CGAB149 installation codes and/or local codes. The manufacturer of this water heater will not be held liable for any damage from failure to comply with these installation and operating instructions.
2
Page 3

FOR YOUR SAFETY

WHAT TO DO IF YOU SMELL GAS

¾ DO NOT try to light any appliance.
¾ DO NOT touch any electrical switch.
¾ DO NOT use any phone in the building.
¾ Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's
instructions. If you cannot reach your gas supplier, call the fire department.
¾ WARNING: If these instructions are not followed exactly, a fire or explosion may result
causing property damage, personal injury or death.

PRECAUTIONS

TANK LINING - DAMAGE PREVENTION
The water heater lining has been electronically inspected for continuity prior to final assembly. It was found to be free of defects. In order to protect the lining, do not apply heavy blows or weld to the exterior pressure vessel. Damage to the interior lining will void the warranty and ASME HLW stamp.
TANK MAINTENANCE - REMOVAL OF SEDIMENT AND SCALE To keep the water heater efficient and in good working condition, inspect and clean two weeks after installation to remove any piping system debris that may have accumulated. Do not acidize this unit. Monthly inspections should be performed to determine a time span for removing any sediment within the unit. This should become the basis for a routine maintenance schedule. It is recommended that high-pressure water be used to purge any accumulation of sediment through the drain valve opening or the hand hole.
ANODE MAINTENANCE
The water heating industry knows that many water heaters are installed in areas where the water supply can be abnormally corrosive due to low pH or an excessive amount of dissolved oxygen. Because of our commitment to provide clear water in all areas, an anode has been provided to help counteract the effects of these factors. Periodic inspection and, if necessary, replacement is required to assure the anodes effectiveness.
WATER QUALITY - pH LEVEL Materials used in the water heater to prevent corrosion have been selected for their compatibility with most domestic water supplies. However, significantly alkaline water (pH 7.5 or higher) or acidic water (pH 6.5 or lower) can result in abnormal scale formation or seriously attack these materials and cause premature corrosion. If the pH of incoming supply water does not fall between 6.5 and 7.5, it must be treated to prevent damage to internal water heater surfaces and other building plumbing components.
3
Page 4
SAFETY TEMPERATURE AND PRESSURE RELIEF VALVE (T&P) A listed and properly rated combination temperature and pressure relief valve shall be installed in the opening provided and marked for this purpose at the time of installation. Local codes shall govern installation of relief devices. The pressure rating of the relief valve must not exceed the working pressure shown on the rating plate affixed to the front of the water heater. The BTU/H rating of the relief valve must equal or exceed the water heater input shown on the rating plate. The relief valve discharge line must terminate 6 inches above the floor drain or externally to building. The discharge line must be able to withstand water temperature in excess of 210°F.
¾ DO NOT install a valve between tank and the relief valve.
¾ DO Install a discharge line directly to an adequate open drain. The discharge line must be
shielded, secured and plumbed to an appropriate drain to prevent scald injury.
¾ DO NOT install a reducing coupling or other restriction in the discharge line.
¾ DO NOT install the discharge line where it may be subject to blocking, plugging or freezing.
¾ DO NOT allow water from discharge line to contact any live electrical part.
Failure to install a listed and properly rated temperature and pressure relief valve could result in hazard to life, bodily injury or property damage and will release the manufacturer of this water heater from any claim which might result from excessive water temperature or pressure.

CAUTION

KEEP CLEAR OF DISCHARGE LINE OUTLET. It is hot enough to cause scald injury, is under pressure and may splash.
IMPORTANT
¾ Periodically check combustion products to assure that carbon monoxide is kept below 0.02%
(200 PPM) or that the CO
¾ Drain the water heater for 5 minutes every day to help prevent accumulation of sediment and
scale. Periodically check for the presence of scale and sediment. If present, physically loosen and flush using high-pressure water.
¾ All startup, periodic tuning and service must be performed by a trained technician familiar
with the water heater and forced draft burner. It is mandatory that the startup test report, contained in the burner installation and operation manual, be completed and a copy returned to the factory. It is also important that an operating log be maintained to provide a history of water heater performance.
is kept between 9 & 9 ½%.
2
4
Page 5

TABLE OF CONTENTS

SECTION TITLE PAGE #
I GENERAL DESCRIPTION 9
II INSTALLATION 10
III START UP AND OPERATION 16
IV SCHEDULED MAINTENANCE AND SERVICING 18
V TROUBLESHOOTING 25
VI MISCELLANEOUS CHARTS AND FORMULAS 26
5
Page 6
6
Page 7
7
Page 8
8 9
Page 9
SECTION I - GENERAL DESCRIPTION
GENERAL DESCRIPTION
This is a commercial storage water heater designed and constructed in accordance with UL and ASME requirements. Its thermal efficiency and standby loss exceed the levels established by ASHRAE 90.1 and incorporated by federal EPACT legislation. Given a reasonable amount of maintenance, this water heating product will perform reliably for many years. Its basic design is well proven over time, and operating components have been selected for their reliability and widespread use in the water heating industry. This philosophy also promotes availability of both parts and trained service personnel. It is essential that all aspects of installation, maintenance, routine servicing, troubleshooting and repair be planned with safety as the primary consideration. If the installer or service technician has any questions about this water heater's operation, the factory should be contacted immediately. It is also very important to properly maintain this water heater to obtain long life and maintain its high efficiency.
Page 10
SECTION II – INSTALLATION
WARNING / CAUTION
For protection against excessive pressures and temperatures, local codes require the installation of a temperature-and-pressure (T&P) relief valve certified by a nationally recognized laboratory that maintains periodic inspection of production of listed equipment of materials, as meeting the requirements for Relief Valves and Automatic Gas Shutoff for Hot Water Supply Systems. ANSI Z21.22-1971.
The National Fuel Gas Code, (ANSI Z223.1 and Can 1 -Bl 49.1 or Bl 49.2), expressly prohibits the following:
1. Installation of water heater in a bathroom, bedroom, or any occupied room normally kept closed.
2. Installation of a water heater in a garage unless the unit is installed so that the burner and ignition devices are at least eighteen (18) inches above floor level and protected to avoid damage by a moving vehicle.
If unit is painted or insulated on the job site, care should be taken not to paint or insulate over the A.S.M.E. nameplate. This plate should be accessible and legible at all times to inspectors, and information from this plate must be used when ordering parts from the factory.
HANDLING
Some models have been constructed with lifting lugs to permit lifting with a crane. Fork lift movement (rear access only) is also acceptable.
To lift with a crane, remove flue outlet adapter and connect a lifting cable to the two lifting lugs attached to the top tubesheet. Be sure lifting cable and crane can support the shipping weight as shown on Bill of Lading.
The skids are compatible with the forks of most fork lift equipment. When moving a heater into place, pick water heater up from rear (do not pick up from front or sides) with forks inside the skids. Picking up heater on outside of skids may allow forks to puncture bottom of combustion chamber.
INSPECTION
Inspect the water heater and burner for possible damage that may have occurred in shipping or during storage. Check rating plate on the water heater and burner for compliance with specifications. Be sure the electrical supply, gas and/or oil supply lines are adequate for the installation.
10
Page 11
LOCATION
NOTE: Do not run uninsulated water pipes in front of or directly above a fresh air opening. If an
exhaust fan is installed in the mechanical room, the combustion air inlet must allow for the fan's exhaust air volume. An undersized opening may cause down drafts resulting in poor combustion, sooting and carbon monoxide.
1. Position the water heater in a clean and dry location as close as possible to the greatest use of hot water (and the oil storage tank if used). Minimum clearances for servicing are listed on a label near the burner. Greater clearances may be required by local code.
2. An adequate uncontaminated air supply for combustion is needed. If air is directly obtained
1
from outdoors, a free area of 1 square foot per 1,000 CF/Hr
of input is required. If air is obtained from an adjacent indoor area, 1 square inch per 1,000 BTU/Hr of input is required. If oil-fired, 1 gallon per hour equals 140,000 BTU/Hr. Combustion air inlets should be located on an outside wall, away from prevailing winds, and be sized to accommodate all fuel burning equipment located in the mechanical room. Combustion air calculations should assume simultaneous operation of all fuel burning equipment in the equipment room.
3. The water heater should not be installed in an area where combustible liquids or vapors may be present that could be ignited by the burner. The installation area should not contain air contaminated with chlorinated hydrocarbons, perchlorethylene or any strong oxidizing agent. Combustion air containing these agents will seriously damage the burner and vessel parts thus voiding all warranties. If required, combustion air should be ducted from outside the building to avoid such contaminants. Burners require special construction for outside combustion air applications. Consult factory for details.
4. The water heater should be located on a pitched floor near a suitable drain, or other provisions must be made to prevent damage to areas of the building subject to water damage should the heater or plumbing leak. A drain is required for relief valve discharge as well as routine cleaning and flushing of the tank. The heater must be installed in a level position. Shim under skids if necessary.
WATER CONECTIONS
NOTE:
The most effective means for preventing deterioration from accelerated corrosion due to
galvanic and stray current is the installation of dielectric fittings/unions. The installation of these fittings is the responsibility of the installing contractor.
Water connections are made to the cold water inlet and hot water outlet as shown on the supplied water heater drawing. Dielectric fittings are provided to minimize the formation of galvanic corrosion (some jurisdictions require the use of dielectric fittings). Shut-off valves and unions should
1
1,000 CF/Hr of Gas = 1,000,000 BTU/Hr = 7.14 GPH of #2 fuel oil
11
Page 12
be installed so the heater may be disconnected for servicing if necessary. Hot water and return circulation lines should be insulated. The cold water supply line should be insulated if subjected to freezing temperatures. When a check valve is installed in the cold water line to the water heater, a diaphragm type expansion tank suitable for potable water shall be installed in the system.
PIPING MULTIPLE WATER HEATERS
A parallel connection, see the following diagram, allows heated water from multiple heaters to flow into the system to serve peak loads that can occur in a short time period. Pressure drop is reduced and total storage capacity is available for immediate use.
12
Page 13
ELECTRICAL CONNECTIONS
Electrical connections to the water heater should conform to the National Electrical Code or the code legally authorized in your locality. A fused disconnect switch should be used in the burner control circuit. The contractor shall run the properly sized electrical service to the terminals indicated on burner wiring diagram. Refer to burner manufacturer's manual for specific electrical requirements.
VENTING
This non-condensing water heater is designed to exhaust into its own independent vent or into an existing vent system that serves other appliances. In all cases, a negative pressure must be maintained within the venting system to prevent the leakage of combustion products.
Several basic venting rules must always be followed.
1. The vent must be independently supported so its weight does not bear on the water heater's flue collector.
2. The vent must never be sized smaller than the flue collector outlet. It can be up to two sizes larger but, in all cases, must be sized in accordance with National Fuel Gas Code Requirements given the particular installations vent configuration and water heater input rate.
3. When a relatively high negative draft occurs in a vent, a draft regulator sized to the vent diameter should be installed and adjusted to begin opening at a negative draft of -0.1 in. W.C. A draft regulator should be installed no further than two feet away from the water heater flue outlet.
4. A vent must never be welded to the flue collector outlet.
5. All vents must be constructed in accordance with the National Fuel Gas Code and terminated on the outside of the building using a UL listed vent cap. Horizontal venting through an outside wall is acceptable, but an induction blower may be needed to maintain a negative draft in the vent.
If the water heater is vented into an existing overhead vent (or breaching), it is recommended the vent be designed for positive pressure in case there is positive pressure in the overhead vent.
13
Page 14
GAS CONNECTION PIPING FOR GAS AND COMBINATION GAS/OIL BURNERS
WARNING / CAUTION
LP UNITS; liquefied petroleum (L.P.) gas is heavier than air and will remain at floor level if there is a leak. Basements, crawl spaces, closets and areas below ground level will serve as pockets for accumulation of leaking L.P gas. Before operating the water heater, sniff at floor level. IF YOU
SMELL GAS, follow applicable instructions on cover page. DO NOT OPERATE APPLIANCE UNTIL LEAKAGE IS CORRECTED AND AREA IS PURGED OF ANY GAS ACCUMULATION.
Be sure gas supply lines have been cleaned of all debris which could enter the regulators or the burner system and cause malfunctions or unsafe conditions. Pipe connection compounds must be used AT ALL TIMES. DO NOT use Teflon tape as a thread sealant.
1. The gas supply line must be sized, considering pressure drop, to furnish gas at a pressure necessary for the burner to develop rated capacity and the CFH to handle all fuel burning equipment attached to the line. A drip leg should be installed ahead of the burner piping connection. See burner manufacturer's manual for piping detail.
2. Piping or tubing from regulator vents shall be routed outside the building and must be the same diameter as the regulator venting ports. Provide no traps in the vent lines and terminate away from all doors, windows and air intakes serving HVAC equipment. Vent termination shall face downward with a screen mesh cover to prevent insects and debris from entering. If regulator vents are combined, use tubing or pipe equal to the total cross sectional area of the individual vents. Normally open vent valves must be separately vented.
NOTE:
pilot regulators. Termination of vents shall be the same as for regulators.
OIL TANK AND PIPING
High and low gas pressure switches must be vented separately from those of the main and
3. Before gas is turned on, be sure the gas line has been checked for leaks. Check to see that there are no open fittings and that the burner main manual valve and pilot manual valve are closed.
1. Tank construction and installation must meet all local codes and should meet the specifications recommended by Underwriters Laboratories.
2. REFER TO YOUR BURNER STARTUP MANUAL FOR OIL PUMPING AND PIPING DETAILS.
14
Page 15
3. A Rule of Thumb to determine total suction for suction line sizing is to add 10% to suction determined from the burner manufacturer's instruction manual.
4. It is good practice to size the oil pump return-line (to the tank) the same size as the selected suction line.
PRESSURE AND TEMPERATURE SAFETY RELIEF VALVE
1. Install the combination temperature and pressure safety relief valve in the tapping provided. Note that this is required by law for safety considerations.
Outlet to floor drain
Install into provided tapping
Manual Release Lever
Temperature Probe
2. Install a relief valve overflow pipe to a nearby floor drain. CAUTION: No valve of any type should be installed between the relief valve and tank or in the drain line.
15
Page 16
SECTION III – START UP AND OPERATION
WARNING / CAUTION
Temperatures above 130ºF (54º C) can cause scalding. Scalding temperatures are especially hazardous to young children, aged or handicapped persons. A serious or disabling injury can occur. Note that a mixing valve installed at the hot water outlet can reduce the risk of scalding at such points of use as lavatories, sinks and bathing facilities
Excessively hot water may suggest that the upper operating thermostat has failed. If you determine an operating control thermostat has failed, it should be replaced IMMEDIATELY by a qualified service technician.
If the burner turns on and off every 3 to 4 minutes on a regular basis, the lower control thermostat setting may have to be decreased. Such a "short cycling" condition accelerates wear of burner components which can lead to early failure.
IMPORTANT
THE MANUFACTURER'S START UP REPORT MUST BE COMPLETED AND RETURNED. FAILURE TO DO SO WILL VOID THE WARRANTY.
ALWAYS CONTACT A TRAINED SERVICE TECHNICIAN TO PERFORM START UP. SHOULD FACTORY ASSISTANCE BE REQUIRED, PLEASE HAVE THE WATER HEATER SERIAL NUMBER AVAILABLE.
Combination gas/oil burners require a supply of oil for oil pump lubrication even when operating on gas.
Some oil burners require a supply of either natural or L.P gas to operate the pilot. Check burner construction for the presence of gas pilot tubing and a pilot gas pressure regulator.
START UP
1. Fill water heater and drain to remove any residue that may have accumulated during the installation process. Remove hand hole cover and remove any material not flushed through drain. Reinstall hand hole cover, fill with water and open a nearby hot water faucet to bleed out any entrapped air. Be sure all tank connections are tight. Leaking water causes corrosion and insulation damage.
16
Page 17
2. The burner manufacturer's installation and operation manual, included with this manual, contains a detailed start up procedure that should be studied and followed precisely.
NOTE: Rated gas input for this water heater can be established by adjusting manifold gas pressure to the value listed on the burner data plate. Rated oil input can be established by adjusting oil pressure to the burner at 300 psi (pressure may have to be slightly reduced to obtain clean, smoke­free combustion).
TEMPERATURE ADJUSTMENT
The upper operating control thermostat shuts off the burner when its temperature setting is reached. The lower operating control thermostat can be adjusted to vary the temperature that activates the burner. The unit is also equipped with a high limit safety control preset at 180°F. For energy efficient operation of your water heater, the recommended upper temperature setting is approximately 130°F. Facilities with small children or invalids may require a 120°F or lower temperature setting to reduce the risk of scald injury. Some states require a lower temperature setting. Check with your gas supplier for local requirements governing the temperature setting.
Remember that no water heating system will provide an exact temperature at all times. Allow a few days of operation to determine the correct temperature setting consistent with your needs.
A lower temperature setting can cause condensation, but that does not mean your tank is leaking. Many reported tank leaks on installation are proven to be condensation. To avoid unnecessary inconvenience and expense, make sure the tank is leaking before calling a service person.
17
Page 18
SECTION IV - SCHEDULED MAINTENANCE AND SERVICING
WARNING / CAUTION
Before performing any maintenance procedure, turn off the water heater main disconnect switch before performing any cleaning or service. Also close both the pilot and main manual shutoff valves.
Keep the equipment room clean. Clean the burner at regular intervals. The blower inlet can collect dust and debris from the air during operation. Clean blower wheel and flame scanner when necessary. The burner should be cleaned each year according to the burner manufacturer's recommended procedures. A DIRTY BLOWER WHEEL WILL REDUCE EFFICIENCY AND
MAY CAUSE POOR COMBUSTION, SOOTING OR THE PRODUCTION OF CARBON MONOXIDE.
IMPORTANT
A preventive maintenance program should be established to help assure a long, trouble-free water heater life. AN ANNUAL INSPECTION SHOULD BE PERFORMED AND DOCUMENTED.
A COPY OF THE INSPECTION REPORT MUST BE FORWARDED TO THE MANUFACTURER. FAILURE TO DO SO WILL VOID THE WARRANTY.
18
Page 19
RECOMMENDED PERIODIC INSPECTION
DAILY
1. Inspect area around water heater for moisture. If present, determine if cause is condensation or leakage.
a. If cause is condensation - May be due to very cold incoming water. Consider
installation of intra-tank circulator; contact manufacturer for details.
b. If cause is leakage - May be due to leaking fitting; repair as soon as possible. If tank
leak is suspected, contact manufacturer.
2. Inspect vent for corrosion. If present, replace corroded vent section as soon as possible. Determine if cause is low temperature of combustion products (less than 280º F net flue temperature), or the presence of contaminated combustion air. Correct either condition immediately.
MONTHLY
1. Drain heater, remove hand hole cover and inspect for sediment accumulation. Remove any sediment and inspect more frequently to determine an appropriate schedule for sediment removal. NOTE: FAILURE OF THE WATER HEATER DUE TO SEDIMENT OR SCALE ACCUMULATION IS NOT COVERED BY THE WARRANTY.
2. Test combustion products for the presence of carbon monoxide (CO) above a 200 ppm concentration. If necessary, adjust burner to reduce CO concentration.
19
Page 20
RECOMMENDED PERIODIC TESTING
TESTING ITEM
Gauges, monitors and operating log Daily Operator Make visual inspection and record readings
Instrument and equipment settings Daily Operator Make visual check against recommended
Firing rate
Flue, vent, stack or outlet dampers Monthly Operator Make visual inspection of linkage; check for
Igniter
Fuel valves: pilot and main (primary and secondary)
Pilot and main gas or oil train Annually Service Tech Perform leakage tests - refer to instructions Combustion safety controls (flame
failure)
Flame signal strength
Pilot turndown test
Low-water fuel cutoff and alarm Daily/weekly
High limit safety thermostat control Annually Service Tech Refer to instructions Operating thermostat control Annually Service Tech Refer to instructions Vent draft fan, and air pressure
switches High and low gas pressure interlocks Monthly Operator Refer to instructions High and low oil pressure interlocks Monthly Operator Refer to instructions Fuel valve interlock switch Annually Operator Refer to instructions Low fire start interlock Annually Operator Refer to instructions Automatic changeover control (dual
fuel)
T&P valves
Inspect Burner Components Semiannually Operator Refer to burner instructions
HOW
OFTEN
Weekly Operator Verify factory settings
Semiannually Service Tech Verify factory settings
Annually Service Tech Check with combustion test
Weekly Operator Make visual inspection, check flame signal
Weekly Operator Operate burner. Using a manometer or pressure
Weekly Operator Close manual fuel supply for the pilot and main
Weekly Operator With flame signal meter installed, read and log
As required /
annually
Semiannually
Monthly Operator Refer to instructions
At least
annually
As required Operator In accordance with procedure in Section VI
COMPLETED
BY
Service Tech Required after any adjustment to flame scanner
Operator
Service Tech Under supervision of gas utility
REMARKS
specifications
proper operation
strength if meter-fitted (see "Combustion Safety Controls")
gauge, check pressure to the burner as required on rating label.
fuel valve(s); check safety shutdown timing; log result.
for both pilot and main flames. Notify service organization if readings are very high, very low or fluctuating. Refer to instructions for nominal values
mount or pilot burner; verify annually - refer to instructions.
Refer to instructions and perform a slow drain test.
ASME Boiler and Pressure Vessel Code, Recommended Rules for Care and Operation of Heating Boilers.
20
Page 21
SCALE AND SEDIMENT REMOVAL
THE MANUFACTURER CANNOT CONTROL USE OF THE WATER HEATER, WATER CONDITIONS OR MAINTENANCE. THE WATER HEATER WARRANTY DOES NOT COVER POOR PERFORMANCE, STRUCTURAL FAILURE OR LEAKING DUE TO AN EXCESSIVE ACCUMULATION OF SCALE.
The tank should be flushed to remove accumulated sediment at intervals depending on water conditions. To flush, turn off electrical disconnect to heater. Open drain valve and allow water to flow through the tank until it runs clear of sediment. Close the drain valve and turn electrical disconnect on.
Scale can form during operation and will accumulate on the bottom of the tank. Scale is formed from natural chemicals in the water which precipitate out during heating cycles. Some water supplies contain more scaling chemicals than others. The rate of scale accumulation increases as the temperature of stored water increases.
Sediment and scale accumulation in a tank reduce the water heater's ability to heat water. When heating energy cannot be effectively transferred to the water, tank metal can overheat. Overheating can cause the metal to lose its structural strength which can result in tank leakage.
The tank has a hand hole for inspection and cleaning. Remove hand hole cover on a regular basis and inspect tank for scale buildup. If scale is present, it can be loosened with a high pressure stream of water. Smaller flakes can be flushed through the drain, but larger flakes can be removed by hand through the hand hole. The frequency of inspection should be determined by the rate of scale buildup.
FIRETUBE CLEANING
The water heater contains a turbulator in each firetube, which increases flue gas velocity against the tube wall. This increased velocity does two things.
1. Transfers more heat into the water thus reducing fuel cost.
2. Helps in maintaining a cleaner tube wall should combustion adjustment change (which can produce sooting).
By maintaining the burner, and keeping CO2 in the 9.0 to 9.5% range (gas), or 13.5% (#2 oil), you will help reduce sooting. This will also keep fuel cost down.
To check for and remove sooting, remove the top pan and turbulators and wire brush each tube. Clean all soot from turbulators and reinstall into the firetubes.
After tube cleaning, remove the burner, clean combustion head internals and vacuum the combustion chamber before placing water heater back into service.
21
Page 22
BURNER SERVICE
IMPORTANT
IT IS HIGHLY RECOMMENDED THAT REPLACEMENT PARTS OR ASSEMBLIES BE OBTAINED FROM THE WATER HEATER OR BURNER MANUFACTURER.
The enclosed burner installation and operation manual contains a service suggestion (troubleshooting) section and a periodic checklist that recommends a variety of component tests designed to help maintain the water heater's reliable, efficient and safe operation.
For additional assistance, contact the burner manufacturer's customer service department.
Availability of spare parts varies from area to area. The burner material list provides the part number you require for obtaining replacements. If the item is not available locally, contact the service department at the location listed on the cover page.
WATER HEATER SERVICE
Serviceable water heater components include the control and high limit thermostats, the temperature and pressure relief valve(s), the drain valve and , low water cut off. Optional components such as a temperature and pressure gauge may also be installed. Replacement instructions for some of these items are listed below.
For additional assistance, contact the water heater manufacturer's customer service department.
22
Page 23
RELIEF VALVE
1. Disconnect power from unit.
2. Shut off incoming water and boiler water supply.
3. Lift test lever on relief valve to relieve pressure in tank.
4. Disconnect overflow piping.
5. Unscrew relief valve, remove assembly and replace with new one.
6. Connect overflow piping.
7. Turn on incoming water supply and check for leaks.
8. Turn safety switch to ON position.
Test Lever
Overflow Piping Outlet
Tank Connection
Temperature Probe
23
Page 24
IMMERSION TEMPERATURE HIGH LIMIT CUT-OFF, HIGH, OR LOW THERMOSTAT
1. Disconnect power from unit.
2. Remove access cover.
3. Remove high limit cover screw and cover.
Cover
Cover Screw
Reset Tab (High Limit Only)
4. Disconnect the two (2) 14 gauge wires.
Wires Capillary Tube
5. Remove capillary tube and bulb from thermowell
6. Remove two (2) mounting screws.
Mounting Screws
7. Remove control and install new high limit switch by performing above steps in reverse order. (Note: Be sure to place capillary tube into slot in base prior to installing cover.)
24
Page 25

Symptom Probable Cause Corrective Action / Remedy

No hot water.
SECTION V – TROUBLESHOOTING
(See separate component O&M for additional details.)
Flame safeguard locked out. Reset flame safeguard. Manual gas valve closed. Open gas valve and reset flame
safeguard. Blown control circuit. Replace fuse. No power. Reset circuit breaker.
Water not hot enough.
Water temperature too hot.
Gas odors.
Gas pressure too high or too low. Operating control thermostat set too low.
Recovery rate too low for demand.
Operating control thermostat failed. Operating control thermostat set too high. Temperature and pressure safety relief valve not closed. If leakage source cannot be determined.
Possible gas leak. Shut off gas supply and call the gas
Improper combustion. Call serviceman. Blower wheel dirty. Call serviceman. Down draft in vent. Call serviceman. Gas train vents not vented outdoors. Blower wheel running backward.
Reset gas pressure switch and reset
flame safeguard.
Increase control thermostat setting to
a higher temperature. Note: Higher
water temperatures increase the
danger of scalding.
Input rate too low/not operating at
peak efficiency.
Call serviceman to check input rate
and efficiency.
Check firetubes for soot. Inspect and
clean for scale and sediment build-up.
Call serviceman to replace control
thermostat.
Adjust operating control thermostat to
lower temperature.
Replace valve. Water leaks.
Shut off fuel and electrical supply,
close cold water inlet valve, and call
serviceman.
company.
Call serviceman.
Call serviceman.
25
Page 26
SECTION VI – MISCELLANEOUS CHARTS AND FORMULAS
TORQUE VALUES
BOLT SIZE
4-40 4-48 6.6 5.4 6.1 3.6 6.9 6.7 5-40 7.7 6.3 7.1 4.2 8.1 7.8 5-44 9.4 7.7 8.7 5.1 9.8 9.6 6-32 9.6 7.9 8.9 5.3 10.1 9.8 6-40 12.1 9.9 11.2 6.6 12.7 12.3 8-32 19.8 16.2 18.4 10.8 20.7 20.2
8-36 22.0 18.0 20.4 12.0 23.0 22.4 10-24 22.8 18.6 21.2 13.8 23.8 25.9 10-32 31.7 25.9 29.3 19.2 33.1 34.9
1/4-20 75.2 61.5 68.8 45.6 78.8 85.3
1/4-28 94.0 77.0 87.0 57.0 99.0 106.0 5/16-18 132 107 123 80 138 149 5/16-24 142 116 131 86 147 160
3/8-16 236 192 219 143 247 266
3/8-24 259 212 240 157 271 294 7/16-14 376 317 349 228 393 427 7/16-20 400 327 371 242 418 451
1/2-13 517 422 480 313 542 584
1/2-20 541 443 502 328 565 613 9/16-12 682 558 632 413 713 774 9/16-18 752 615 697 456 787 855
5/8-11 1110 907 1030 715 1160 1330
5/8-18 1244 1016 1154 798 1301 1482
3/4-10 1530 1249 1416 980 1582 1832
3/4-16 1490 1220 1382 958 1558 1790
7/8-9 2328 1905 2140 1495 2430 2775
7/8-14 2318 1895 2130 1490 2420 2755
1-8 3440 2815 3185 2205 3595 4130
1-14 3110 2545 2885 1995 3250 3730
18-8 S/S
IN.-LBS.
5.2 4.3 4.8 2.9 5.5 5.3
BRASS
IN.-LBS.
SILICON
BRONZE
IN.-LBS.
ALUMINUM
2024-T4
IN.-LBS.
316 S/S
IN.-LBS.
MONEL
IN.-LBS.
26
Page 27
METRIC CONVERSIONS
27
Loading...