Hubbell VE3Q2626E30 Installation Manual

Page 1
INSTALLATION, OPERATION &
MAINTENANCE DATA SHEET
(VEB/DEB/VEQ SERIES FLUORESCENT
EMERGENCY LIGHTING FIXTURES)
EMERGENCY LIGHTING FIXTURES
CAUTION:
Before installing, make sure you are compliant with area classications, failure to do so may result in bodily injury, death and property damage. Do not attempt installation until you are familiar with the following procedures. All installation must comply with the applicable Electrical Code.
Make sure that the circuit is de-energized before starting installation or maintenance.
Verify that the installation is grounded. Failure to ground will create electrical shock hazards, which can cause serious injury and or death.
Technical information, advice and recommendations contained in these documents is based upon information that Killark believes to be reliable. All the information and advice contained in these documents is intended for use only by persons having been trained and possessing the requisite skill and know-how and to be used by such persons only at their own discretion and risk. The nature of these instructions is informative only and does not cover all of the details, variations or combinations in which this equipment may be used, its storage, delivery, installation, check out, safe operation and maintenance. Since conditions of use of the product are outside of the care, custody and control of Killark, the purchaser should determine the suitability of the product for his intended use, and assumes all risk and liability whatsoever in connection therewith.
3940 Dr. Martin Luther King Drive St. Louis, MO 63113
P/N 00912293 FORM NO. K1207 Released 05/01
Page 1 of 4
Page 2
1. IMPORTANT SAFEGUARDS ­ READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
NOTE: Read this sheet carefully before beginning
installation.
Do not use this equipment for other than the intend use as specied on equipment nameplate. Turn off the supplying circuit before beginning installation, or performing any maintenance including revamping.
Do not install near gas or electric heaters.
Do not attempt to service battery. The
emergency ballast contains a sealed, no­maintenance battery. Contact manufacturer for information on replacements.
Batteries must be recycled or disposed of properly.
Servicing should be performed by qualied service personnel.
Do not use this equipment for other than intended use.
The use of accessory equipment not recommended by the manufacturer man cause an unsafe condition.
Equipment should be mounted in locations and at heights were it will not readily be subjected to tampering by unauthorized personnel.
The emergency ballast is for use with bi or quad pin uorescent lamps only.
3940 Dr. Martin Luther King Drive St. Louis, MO 63113
P/N 00912293 FORM NO. K1207 Released 05/01
2. INSTALLATION
CAUTION: To prevent high voltage on red
& yellow output leads prior to installation, inverter connector must be open. Join inverter
connector after installation, then turn power
ON. To reduce the risk of electrical shock, disconnect the AC input and inverter before servicing. The emergency ballast must be connected to an unswitched power source (120/277 V).
NOTE: All installations must comply with the applicable local and/or National Electrical Code.
IMPORTANT: Before installing, check the
xture nameplate to be sure you have the correct xture. Verify ground continuity in the electrical system.
Refer to nameplate for specic ambient and supply wire temperature rating.
Page 2 of 4
Page 3
FIG.2
1. Install splice box per Instruction Sheet K0451 supplied with the product.
2. Refer to Fig.1 for general guidance. Hang the xture on the splice box hinge.
3. Attach the green (ground) lead to the splice
box ground screw (provided).
4. For VEB/DEB Series connect the supply
common lead to marked “COM” & supply line voltage hot lead (120 or 277) to marked “LINE” at the terminal block. For VEQ series connect the supply common lead to marked “COM” & supply line voltage hot lead to marked “LINE” at the terminal block.
5. Mount the lamps on socket supplied with the xture.
6. Join the emergency ballast(s) inverter connector(s) as shown in Fig.2.
7. Close the ballast tank against the splice box and tighten the screw to secure it.
8. Install globe or refractor in the globe thread. Hand tighten.
9. Install globe guard (if required) over lugs on ballast tank, turn until stopped. Secure with screw.
10. To install reectors, back out (4) screws provided in ballast tank boxes enough to slip the reector over the screws and twist in place. Tighten screws to secure reector.
11. Turn ON the supply circuit to operate the xture.
NOTE: For push to test station installation use Killark control station catalog number FXCS_5B2 (e/push to test nameplate) or equivalent. Refer to Fig.3 for typical wiring diagram.
FIG.3
3940 Dr. Martin Luther King Drive St. Louis, MO 63113
P/N 00912293 FORM NO. K1207 Released 05/01
Page 3 of 4
Page 4
2. OPERATION:
When AC power is applied, the charging indicator light is illuminated, indicating that the batter is being charged. When power fails, the emergency ballast automatically provides at least 90 minutes of emergency lighting.
3. MAINTENANCE:
As routine maintenance, this emergency xture should be checked periodically to
ensure proper operation, The following
schedule is recommended.
1. Visually inspect the charging indicator light monthly. It must be illuminated.
2. Test operation of the circuit at 30 day intervals for a minimum of 30 seconds. The lamp should operate.
3. Conduct a 90 minute discharge test once a year. The lamp should operate for 90 minutes.
SAVE THESE INSTRUCTION SHEETS