Hubbell SWB-38 Installation Manual

Page 1
INSTALLATION, OPERATION &
MAINTENANCE DATA SHEET
TYPE SWB CONTROL STATIONS AND CONTROL
FOR USE IN CLASS I, DIV. 1 & 2, GROUPS C & D
CLASS I, ZONES 1 & 2, GROUPS IIB, IIA
CLASS II, DIV. 1 & 2, GROUPS E, F & G, CLASS III
TYPE SWB CONTROL STATIONS AND
CONTROL PANELS
CAUTION:
Before installing, make sure you are compliant with area classications, failure to do so may result in bodily injury, death and property damage. Do not attempt installation until you are familiar with the following procedures. All installation must comply with the applicable Electrical Code.
Make sure that the circuit is de-energized before starting installation or maintenance.
Verify that the installation is grounded. Failure to ground will create electrical shock hazards, which can cause serious injury and or death.
IMPORTANT:
Please read these instructions carefully before installing or maintaining this equipment. Good electrical practices should be followed at all times and this data should be used as a guide only.
Technical information, advice and recommendations contained in these documents is based upon information that Killark believes to be reliable. All the information and advice contained in these documents is intended for use only by persons having been trained and possessing the requisite skill and know-how and to be used by such persons only at their own discretion and risk. The nature of these instructions is informative only and does not cover all of the details, variations or combinations in which this equipment may be used, its storage, delivery, installation, check out, safe operation and maintenance. Since conditions of use of the product are outside of the care, custody and control of Killark, the purchaser should determine the suitability of the product for his intended use, and assumes all risk and liability whatsoever in connection therewith.
3940 Dr. Martin Luther King Drive St. Louis, MO 63113
P/N KIL00901308 FORM NO. K0569F ECO-3-011-12 R04/2012 FORMULE NO. K0569F R04/2012
Page 1 of 5
Page 2
FOR USE WITH SWB SINGLE AND MULTIPLE GANG BACK BOXES; SWB-1, -2, - 3, -4, -5, -6,, -7, -8, -9, -10, -11, -12, -17, -18,
-19, -20, -21, -31, -32, -34, -35, -36, -37, -38,-42, -45, -48 & -49.
COVER ASSEMBLIES (ONE REQUIRED PER GANG)
A) SNAP SWITCHES SERIES XS B )PUSHBUTTONS SERIES XCS C) SELECTOR SWITCHES SERIES XCS D) PILOT LIGHTS SERIES XCS E) MANUAL MOTOR STARTERS SERIES XSD F) RECEPTACLSE SERIES KRS-20, KRS-303, KRS-304 G) BLANK COVER SERIES X-10
ENSEMBLES DE COUVERCLE (UN PAR SECTION)
A) COMMUTATEURS A RESSORT SERIES XS B) BOUTONS-POUSSOIRS SERIES XCS C) COMMUTATEURS SELECTEURS SERIES XCS D) LAMPES TEMOINS SERIES XCS E) DEMARREURS MANUEL DE MOTEUR SERIES XSD F) PRISESDE COURANT SERIES KRS-20, KRS-303, KRS-304 G) PLAQUE COUVERCLE SERIES X-10
1. DIRECTIONS FOR INSTALLATION
1. Mount the back box by means of mounting lugs, install conduit nipple and sealing ttings one each to be installed on each conduit entrance or exit to the enclosure back box in Class l and Class ll areas (Reference: Article 500 NEC) thread conduit into sealing tting (Note: for Class l areas the
conduit should engage [5] full threads).
2. The conduit thread should be lubricated with a non-electrical insulating lubricant or pipe joint compound that will not promote corrosion or chemically attack aluminium.
3. After conduit system has been properly installed, pull the wires and make electrical connections as required. The electrical circuits and ground continuity should be checked with an instrument approved for the area. (Notice: connect only copper wire to this device).
4. All conduits entering or leaving the enclosure must be sealed within 18” of the enclosure with listed sealing ttings such as Killark “EY” or “EYS” sealing ttings.
5. Caution must be taken during installation to be sure that the ground ange ame joints of the cover and the box are not scratched, nicked or damaged.
6. Before assembly of the cover to the box, the mating ground surfaces of both the box and cover should be wiped clean to assure that the ground ame joint will be free of all foreign particles such as lint, dust or dirt.
7. After tightly bolting the cover assembly/assemblies to the enclosure all box to cover, ame joints should be checked with a 0.0015” thick feeler gauge such that the gauge will not enter the ame path more than 1/8” at any point.
3940 Dr. Martin Luther King Drive St. Louis, MO 63113
P/N KIL00901308 FORM NO. K0569F ECO-3-011-12 R04/2012 FORMULE NO. K0569F R04/2012
Page 2 of 5
Page 3
2. MAINTENANCE
All moving shafts should be lubricated occasionally to prevent binding. Only use a lubricant which is suitable for use with aluminium or stainless steel such as killark “LUBG” (general purpose) or “LUBT” (high temperature) lubricants. If devices are to be installed in corrosive areas
which will attack aluminium alloys containing less
than 0.4% copper (boxes and covers) and 303 stainless steel (mostly shafts), the device should be suitably protected from the corrosive material.
3. CAUTION
To prevent ignition of hazardous atmospheres, disconnect from the supply circuits before opening the enclosure; keep tightly closed while circuits are energized.
IDENT
NO.NOGANGS
7 2 SWB- 7 21 5 SWB-21
8 2 SWB- 8 30 4 SWB-31
9 2 SWB- 9 32 6 SWB-32
10 2 SWB- 10 33 8 SWB-33
11 2 SWB- 11 34 10 SWB-34
12 2 SWB- 12 35 6 SWB-35
17 2 SWB- 17 36 9 SWB-36
18 2 SWB- 18 37 12 SWB-37
19 3 SWB- 19 38 15 SWB-38
20 4 SWB- 20
BOX IDENTIFICATION
CAT.NO IDENT.NONO
GANGS
CAT.NO
3940 Dr. Martin Luther King Drive St. Louis, MO 63113
P/N KIL00901308 FORM NO. K0569F ECO-3-011-12 R04/2012 FORMULE NO. K0569F R04/2012
Page 3 of 5
Page 4
1. METHODE GENERALE D’INSTALLATION
1. Monter le boitier au moyen des oreilles de xation fournies. Installer le raccord et le raccord d’etancheite, un de chaque sorte a visser sur chaque entrée ou sortie de tube vers l’enceinte, dans les endroits de Class I et Classe II (Reference: Article 500 Du Cen).
(Note: Pour les endroits de Classe I, le tube doit
engager 5 lets complets).
2. Les lets du tube doivent etre lubries avec un lubrant isolant non-electrique, ou mastic pour joints de tuyaux qui n’encouragera pas la corrosion, ni n’attaquera chimiquement l’aluminium.
3. Apres que le systeme du tubes aura ete installe convenablement, tirer les ls et faites les raccords requis. il faut controller les circuits electriquess et l’uniformite de la mise a la terre au moyen d’un appareil approuve pour l’endroit. Note: Raccorder seulement des ls en cuivre a ce dispositif.
4. Tous les tubes entrant dans l’enceinte ou en sortant doivent etre fermes a 18” de l’enceinte avec des raccords. d’etancheite repertories tels que les raccords killark “ey” ou “eys”.
5. Il faut veiller pendant l’installation a ce que les joints a collet du couvercle et du boiter ne soient ni eraes, ni entailles, ni endommages. avant d’assembler le couvercle sur le boiter, il fout essuyer les surfaces de mise a la terre correspondantes pour etre sur que le joint sera exempt de toute particule etrangere, telle que poussiere, salete ou charpie.
6. Apres avoir bien boulonne les ensembles des couvercles sur l’enceinte, il faut verier tous les joints entre le boiter et le couvercle avec un calibre e’epaisseur de 0.0015” (de sorte que le calibre ne penetrera pas dans le joint de plus de 1/8” a n’ importe quel point).
3940 Dr. Martin Luther King Drive St. Louis, MO 63113
P/N KIL00901308 FORM NO. K0569F ECO-3-011-12 R04/2012 FORMULE NO. K0569F R04/2012
2. ENTRETIEN
Tous les arbes mobiles doivent etre lubries a l’occasion pour empecher tout coincage. Employer seulement un lubriant convenant a l’aluminium ou l’acier inoxydable, tel que Killark “lubg” (tout usage) ou “lubt” (hautes temperatures). Garder tous les collets propres et exempts d’eraures.
Si les dispositifs doivent etre installes dans des endroits corrosifs qui attaqueront les alliages d’aluminium contenant moins de 0.4% de cuivre (boiters et couvercles) et de l’acier inoxydable 303 (la plupart des arbres), il faut proteger le dispositif convenablement contre le materiau corrosif.
Page 4 of 5
Page 5
3. MISE EN GARDE
Pour empecher toute inammation des atmospheres dnagereuses, debrancher des circuits d’alimentation avat d’ouvrir l’enceinte. Garder bien ferme tant que les circuits sont sous tension.
IDENTIFICATION DU BOTHER
NO.
NO OF
D’IDE
SECTIONSCAT.DE NO.D’ID
NT
7 2 SWB- 7 21 5 SWB-21
8 2 SWB- 8 30 4 SWB-31
9 2 SWB- 9 32 6 SWB-32
10 2 SWB-10 33 8 SWB-33
11 2 SWB-11 34 10 SWB-34
12 2 SWB-12 35 6 SWB-35
17 2 SWB-17 36 9 SWB-36
18 2 SWB-18 37 12 SWB-37
19 3 SWB-19 38 15 SWB-38
20 4 SWB-20
ENT
NO OF SECTIONSCA.DE
3940 Dr. Martin Luther King Drive St. Louis, MO 63113
P/N KIL00901308 FORM NO. K0569F ECO-3-011-12 R04/2012 FORMULE NO. K0569F R04/2012
Page 5 of 5