Hubbell Portable 30 Ampere GFCI Catalog Page

Ground Fault Products
Portable 30 Ampere GFCI - NEMA 4X
Applications
Pressure Washers Portable Electric Heaters Portable Power Tools De-icing Equipment Material Dryers Submersible Pumps Pipeline Heaters Automotive Garages Outdoor Signage
GFP1311
Circuit Guard® Portable 30A GFCI - UL Type 4X Rated
GFPIL30250LKM
3.37" (85.6)
Portable, manual set and automatic set GFCIs.
Note: All units above are stock items.
2' (60.9 cm) 120V AC GFP1301 GF P13 11 6' (182.9 cm) 120V AC GFP1305 GFP1315 25' (762.0 cm) 120V AC GFP1302 GFP1312 50' (1524.0 cm) 120V AC GFP1303 GFP1313 2' (60.9 cm) 240V AC GFP2301 GFP2311 25' (762.0 cm) 240V AC GFP2302 GFP2312 6' (182.9 cm) 120/240V AC GFP3305 GFP3315 6' (182.9 cm) 3Ø 250V AC GFP5305 GFP5315 6' (182.9 cm) 3Ø 120/208V AC GFP4305 GFP4315
Circuit Guard® 30A GFCI In Line GFCI – Locking
4.80"
(121.9)
L5-30 locking. 2' (60.9 cm) 120V AC GFPIL30125LKM GFPIL30125LK A L6-30 locking. 2' (60.9 cm) 250V AC GFPIL30250LKM GFPIL30250LKA
Plug and Connector Selector Chart (partial listing)
The chart below is a list of possible Hubbell plug and connector body products that can be used with the Hubbell Portable GFCIs.
Family Style Amps Voltage Hubbell Catalog Number
Dimensional Drawing
Insulgrip® Straight Blade 15 120V AC HBL5266C & HBL5269C Insulgrip® Twist-Lock® 30 240V AC HBL2621 & HBL2623 Watertight Safety-Shroud® Twist-Lock® 30 240V AC HBL2621SW & HBL2623SW IEC Pin & Sleeve Watertight Pin & Sleeve 30 240V AC HBL330P6W & HBL330C6W Insulgrip® Pin & Sleeve Insulgrip® Pin & Sleeve 30 240V AC HBL330PS2W & HBL330CS2W Hubbellock® Hubbellock® 20 120V AC HBL23035B & HBL23032B
Specifications
Electrical Ratings
Rated Voltage 120V AC, 240V AC, 120/240V AC, 3Ø 250V AC, 3Ø 120/208V AC. Operating Voltage Range 85% to 110%. Current Up to 30A or device rating. Frequency 60 Hz. Trip Level 4-6 mA. Response Time 25 mS Max. Dielectric Withstand 1500 VRMS across contact, 4000 VRMS between conductors and enclosure. Surge Withstand 6000V impulse, 0.5 microseconds rise time 100kHz ringing frequency with 40% decay per cycle. Let Go Line Voltage 60% of rated. Power Up Manual or Automatic reset.
Environmental Ratings
Housing Rating UL Type 4X. Construction Industrial grade design. Type Meets UL943 Class A GFCI. Operating Temperature -35°C to 66°C, -30°F to 150°F. Leakage Current @ 93% Humidity Zero.
Dimensions in Inches (mm)
Features
Life (Endurance) 10,000 cycles (6000 with load and 4000 without load). Open Neutral Protection Trips upon loss of neutral. Grounded Neutral Protection Trips if ground and neutral touch at load side. Power On Indicator Green light on. Power Off Indicator Red blinking light plus optional audible alarm. Wiring Application 3 Wire Single Phase (Hot, Neutral and Ground). 4 Wire Single Phase (Line 1, Line 2, Neutral and Ground). Switch interface Double Insulated. Latching Mechanism Electromagnetic.
Physical Specifications
Cord Type 2-50', 10/3 SJGOOW. 100', 8/3 SEOW. Unit Color Gray with black cover. Label Color on Portable Automatic reset: Yellow background with black and Hard Wired Units lettering. Manual reset: Black background with yellow lettering. Weight 2 ft. 1.8 lbs., 6 ft. 2.7 lbs., 25 ft. 6.8 lbs., 50 ft. 12.4 lbs.,100 ft. 23.3 lbs.
Related Code
Conned Space OSHA 29 CFR 1926.404 (b) (1) (ii)
OSHA 29 CFR 1926.405 (a) (2) (ii) (G) Construction Sites NEC 590.6 Commercial Garages NEC 511.12 Outdoor Signs N E C 6 0 0.10 Spas and Hot Tubs NEC 680.40 Bo at Ya rds NEC 555.3
K-18
®
Wiring Device-Kellems