HUBBELL ELECTRICAL PRODUCTS
INSTALLATION, OPERATION & MAINTENANCE DATA SHEET
SPECIAL COND ITIONS FOR SAFE USE
For use in enclosures with maximum internal volume of 9,764 cubic in; (160,000 cubic cm)
Application: For use in Hazardous Locations where gas
Preparation for Installation:
wall connection Tube connection
A Division of HUBBELL INCORPORATE D (Delaware )
3940 Martin Luther King Drive
FOR USE IN CLASS I, GROUPS B,C,D, CLASS II, GRPS E,F,G; CLASS III, HAZARDOUS (CLASSIFIED) LOCATIONS
St. Louis, Missouri 63113 USA
Flame Arrestors For use in Explosive Atmospheres
KB1FA25, KB1F AM16: IECEx: Ex d IIB+H2 Gb IP66 ATEX: IIGD Ex d IIB+H2 Gb Ex tb IIIC IP66
KBM20FA25, KBM20FAM16: IECEx: Ex d IIB+H2 Gb IP65 ATEX: IIGD Ex d IIB+H2 Gb Ex tb IIIC IP65
Do not use this product in explosive atmospheres containing acetylene gas.
analyzers and electro/pneumatic/hydraulic equipments are
installed within an explosion proof enclosure. The flame
arrestors provide through-the-wall connections for NPT and
Metric style threads.
Caution: Before installing, make sure you are compliant
with area classifications, failure to do so may result in bodily
injury, death and property damage. Do not attempt
installation until you are familiar with the following
procedures. All installatio n must comply with the applicable
Electrical Code.
Make sure that the circuit is De-energized before starting
installation or maintenance.
Verify that the installation is grounded . Failur e to ground will
create electrical shock hazards, which can cause serious
injury and or death.
Important: Please read these instructions carefully
before installing or maintaining this equipment. Good
electrical practices should be followed at all times and this
data should be used as a guide only.
Pressure Drop and Flow Rate Chart
1.) For thru-wall connection of 1/2-14 NPT, gauge the
opening from flush to 2 turn pass the notch.
1.) For thru-wall connection of M 20x1.5 6g , gauge the
opening with GO and NO-GO gauges for proper fit.
Operating Temperature:
KB1/KBM20 series operating temperature: (-50° to +60°C).
Thread designation for Connections
Series Thru-
KB1FA25 1/2-14 NPT 1/4-18 NPT
KB1FAM16 1/2-14 NPT M16x1.5 6g
KBM20FA25 M20x1.5 6g 1/4-18 NPT
KBM20FAM16 M20x1.5 6g M16x1.5 6g
Material Suffix:
Aluminium: (blank)
Stainless 303: SS
Stainless 316: SS6
Ni plated Brass: BS
Primary Pressure Secondary Pressure SCFH
Installation and Maintenance:
Before installing, apply lubricant (such as Killark’s LUBG-6 thread lubricant) to the threads. Install fitting in the proper
threaded opening and wrench tighten.
DO NOT use wrench or socket on the end hex-nut for removal; use the mid section hex-body.
If the pressure drop or flow rate is not reasonably within the above data, the flame arrestor element within the unit has
been partially clogged with fluid contaminant. To function properly the flame arrestor must be replaced.
P/N KIL00921368 FORM NO. K1368 R7/17 ECO-8-037-17