Hubbell H-MOSS Operating Instructions Manual

H-MOSS® Motion Switching System
Passive Infrared / Ultrasonic Occupancy Sensors
Installation and Operating Instructions
DESCRIPTION
The H-MOSS® sensor is an intelligent self-adapting occupancy sensor that is designed to replace existing wall switches.
SPECIFICATIONS
• 1000 sq. ft. coverage area (Models: AP and AD)
• 400 sq. ft. coverage area (Models: AU)
• Single or Dual Circuit 120/277VAC, 50/60Hz operation
• Electrical Ratings: (Each Output Separately) 120VAC – 800W Incandescent, 1000W Ballast, 1/4 HP 277 VAC – 1800W Ballast, 1/4 HP
• Adjustable Time Delay: 4-30 minutes, self-adapts based on
occupancy
• Light Level Adjustment (Circuit B output on Dual Circuit versions): 10 to 500FC
• UL, cUL Listed
PRECAUTIONS CAUTION: RISK OF ELECTRICAL SHOCK. Turn power off at service panel before beginning installation. Never wire energized electrical components. CAUTION: USE COPPER CONDUCTOR ONLY
Read and understand all instructions before beginning installation. NOTICE: For installation by a licensed electrician in accordance with National and/or local Electrical Codes and the following instructions.
NOTICE: For indoor use only.
Conrm device ratings are suitable for application prior to installation. Use of device in applications beyond its specied ratings or in applications other than its intended use may cause an unsafe con­dition and will void manufacturer’s warranty.
NOTICE: Do not install if product appears to be damaged. NOTICE: Connect to eld wiring rated for 60°C or greater. INSTALLATION
1.Turn power OFF at the service panel.
2.Remove the old switch(es) if applicable.
3.Wire as shown in the WIRING DIAGRAMS section. Figures 1 and 2 denote wiring method for Leakage to Ground Sensors (NOTE: A secure ground is required for proper operation). Figures 3 and 4 denote wiring method for Neutral Wiring Sensors.
4.Install sensor in wall box using mounting screws provided.
5.Restore power to the sensor and allow it to initialize
6.Sensor is factory congured to provide the most energy savings. If additional adjustments are required, see the ADJUSTMENTS
section.
7.If daylight harvesting is desired, calibrate the sensor’s photocell as described in the PHOTOCELL CONTROL section.
8.Install a decorator style wall plate (not included).
TEST MODE
1.Make sure lights are ON
2.Press and hold the ON/OFF button. Lights will cycle OFF then back ON. Release the ON/OFF button.
• For dual circuit sensors, press and hold the ON/OFF button for Circuit A.
• For sensors without buttons, remove the cover (see ADJUSTMENTS section) and press and hold the Test Button.
3.Sensor is now in Test Mode (NOTE: While in Test Mode the sensor will operate in Automatic ON/Automatic OFF mode). Vacate room; lights should turn OFF after 5 seconds. Wait 5 seconds after turn OFF before re-entering space. Step back into room, lights will turn back ON. Repeat walk test as necessary to conrm sensor is operating and detecting in the area as desired. Sensor will ash red and/or green LED while moving to indicate Passive Infrared (PIR) or Ultrasonic occupancy detection respectively. NOTE: Sensors with ultrasonic technology can be very sensitive and may require more than 5 seconds of no movement before turning lights off.
4.To exit Test Mode, press any button.
NOTE:
Sensor will automatically exit Test Mode after sixty (60)minutes.
(up to 2 minutes).
COVER RELEASE CATCH
LINE CIRCUIT BLACK
PHOTOCELL PUSH BUTTON
GROUND CONNECTION
COVER RELEASE CATCH
LINE CIRCUIT BLACK
PHOTOCELL PUSH BUTTON
GROUND CONNECTION
COVER RELEASE CATCH
LINE CIRCUIT BLACK
PHOTOCELL PUSH BUTTON
NEUTRAL WHITE
GROUND CONNECTION
COVER RELEASE CATCH
LINE CIRCUIT BLACK
PHOTOCELL PUSH BUTTON
NEUTRAL WHITE
WIRING DIAGRAMS
RED
LOAD 1
BUTTON A (TEST BUTTON)
BUTTON B
BLUE
LOAD 2
RED
LOAD
BUTTON A (TEST BUTTON)
RED
LOAD 1
BUTTON A (TEST BUTTON)
BUTTON B
BLUE
LOAD 2
RED
LOAD
(TEST BUTTON LOCATED UNDER COVER)
English
FIGURE 1
MULTI-TECH, DUAL CIRCUIT, GROUND CONNECTION
FIGURE 2
MULTI-TECH, SINGLE CIRCUIT, GROUND CONNECTION
FIGURE 3
ULTRASONIC, DUAL CIRCUIT, NEUTRAL CONNECTION
FIGURE 4
PASSIVE INFRARED, SINGLE CIRCUIT, NO BUTTON, NEUTRAL CONNECTION
Wiring Device-Kellems Hubbell Incorporated (Delaware) Shelton, CT 06484 1-800-288-6000 www.hubbell-wiring.com
PD2611 Page 1 04/15
GROUND CONNECTION
®
MANUAL OVERRIDE
Press button(s) to toggle lights ON or OFF. Lights will remain in the last state determined by the buttons while occupancy is detected. Sensor will return to the programmed mode of operation when the sensor times out. NOTE: Sensors with no buttons always operate in the Automatic ON/Automatic OFF mode and cannot be manually turned off.
PHOTOCELL CONTROL
The photocell is used to detect if other light sources such as
sunlight, are sufcient to illuminate the space without turning on the controlled lights. For Dual Circuit sensors, only Circuit B is controlled by the photocell. The sensor is shipped from the factory with the photocell control disabled. If use of the photocell is desired, calibrate the photocell set point as follows:
1.With the light level at the desired level where the controlled lights should be off, PRESS and RELEASE the photocell set button using the end of a paper clip or small bladed screwdriver.
2.Step back from the sensor to avoid changing ambient light levels in the room. During calibration the sensor will turn the lights OFF then back ON.
3.After the calibration process, the sensor will return to its programmed mode of operation. During occupancy, the sensor will turn lighting OFF sixty (60) seconds after reaching or exceeding the set point level. When the lighting level drops below the set point level, the sensor will turn the lights ON.
ADJUSTMENTS
The following switch adjustments require that the sensor’s cover be removed. Remove the cover by inserting a small blade screwdriver
into the catch at the top of the sensor and gently pry the cover off. Set
the adjustment switches as desired (see
CONFIGURATION
is all switches OFF. To re-install cover, place cover directly over the sensor and align the cover’s four (4) catches with the recesses in the sensor housing. Snap cover onto housing making sure that all catches
are securely in place.
CONFIGURATION SWITCH SETTINGS – BANK A Switch 1 – Sensor Operation Relay 1 (Default – Manual ON/Auto­matic OFF) Note: This switch is disabled for 2001 series vacancy sensors.
Programs the sensor for either Manual ON/Automatic OFF operation or Automatic ON/Automatic OFF operation. When set to Manual ON/Automatic OFF mode, lights are turned ON by manually pressing the ON/OFF button. If the sensor times out and turns the lights OFF in the Manual ON/Automatic OFF mode while the space is still occupied, any motion detected within thirty (30) seconds will automatically turn the lights back ON, without requiring the user to press the ON button.
Switch 2 – Dual Circuit Relay 2 (Default – Manual ON/ Automatic OFF) Note: This switch is disabled for 2001 series vacancy sensors.
Programs the sensor for either Manual ON/Automatic OFF operation or Automatic ON/Automatic OFF operation. When set to Manual ON/Automatic OFF mode, lights are turned ON by manually pressing the ON/OFF button. If the sensor times out and turns the lights OFF in the Manual ON/Automatic OFF mode while the space is still occupied, any motion detected within thirty (30) seconds will automatically turn the lights back ON, without requiring the user to press the ON button.
SWITCH SETTINGS
section). Factory default
Switch 3 – Adaptive or Fixed Timer (Default – Adaptive)
Controls selection between Adaptive Timer Mode and Fixed Timer Mode. In Adaptive Timer Mode, the sensor automatically self-adjusts its timeout delay to optimize energy savings. The sensor will initialize its timer value to eight (8) minutes. If the Bank B Timer Select 0 and Timer Select 1 switches have been set to four (4) minutes, this will be the smallest timer value used. In Fixed Timer Mode, the sensor’s self­adapting timer functions are disabled and the sensor’s timeout delay is set according to the Bank B Timer Select 0 and Timer Select 1 switch
settings.
Switch 4 – Adaptive Reset (Default – Off)
The sensor is equipped with Hubbell patented self-adaptive Intelli­DAPT® technology which automatically adjusts the sensor’s sensitiv­ity and timer settings to optimize performance based on occupancy patterns. The sensor constantly learns and adjusts appropriately. If the learned settings need to be reset (e.g. when relocating sensor to an­other area), toggle the switch ON then OFF. The adaptive timer is reset according to the Bank B Timer Select 0 and Timer Select 1 switches. The adaptive sensitivity (both PIR and Ultrasonic as applicable) are
reset to factory default. The photocell sensor settings are also reset to
factory default (disabled) such that the sensor will turn on the light(s) in response to occupancy regardless of ambient light levels in the lighted space. NOTE: Adaptive reset can also be achieved by pressing and holding the photocell set button for ten (10) seconds.
Switch 5 – Relay Bypass (Default – Off)
If it is necessary to service the controlled circuits without de-energizing them at the breaker panel (NOTE: this is not recommended as a stan­dard procedure), perform the following steps:
1.With the lights ON, set the relay bypass switch to the ON
position.
2.Push the button(s) to turn the lights OFF.
3.Push the button(s) again to verify override (lights should not come back on). The relay bypass switch will now interrupt sensor operation, preventing output(s) from turning ON again, regardless of occupancy or pushbutton conditions. To return the sensor to normal operation, ip the relay bypass switch to the OFF position. To conrm sensor is operating normally, lights should now turn ON and OFF when the button(s) are pressed.
CONFIGURATION SWITCH SETTINGS – BANK B Switches 1 and 2 – Timer Settings (Default – 8 min)
Sets the length of time lights will remain ON after last motion is de­tected. The timeout value can be set to 4, 8, 16 or 30 minutes. See
Bank A – Switch 3 - Adaptive or Fixed Timer section for additional
information.
Switches 3 and 4 – Sensing Technology Enable/Disable (De­fault – Enable)
Enables or disables the occupancy sensing technologies used by the
sensor.
Switch 5 – Sensitivity (Default – High)
Sets the sensor’s initial Passive Infrared (PIR) and/or Ultrasonic sensi­tivity level. Sensitivity can be set to either High or Low.
Switch Bank A Function OFF (Default) ON
1 Sensor Operation Relay 1 Manual ON / Automatic OFF Automatic ON / Automatic OFF
2 Dual Circuit Relay 2 Manual ON / Automatic OFF Automatic ON / Automatic OFF
3 Timer Mode Adaptive Fixed
4 Adaptive Reset Enable Adaptation Restore Factory Defaults
5 Relay Bypass Normal Operation Relay Override
Switch Bank B Function OFF ON
1 Timer Select 0
2 Timer Select 1
Æ Å Å Æ
Å Å Æ Æ
Time 4 min 8 min 16 min 30 min
3 Passive Infrared Enabled Disabled
4 Ultrasonic Enabled Disabled
5 Sensitivity High Low
PD2611 Page 2 04/15
Loading...
+ 4 hidden pages