Hubbell Modular Panel Products
Surge Protective Devices (SPD)
The Hubbell Modular Panel Product Surge Protective Devices (SPD)
are designed to provide protection at the service entrance, branch
panels or other critical locations for today’s electrical equipment.
The Hubbell Modular Panel Product series units have a Maximum
Surge Current Rating of 160kA and 320kA per phase, (depending
on model), and provide options such as: Surge Counting, Integral
Switch and a selection of wiring configurations including Delta.
Compliant with UL 1449, edition 2.5 requirements
dated February 9, 2007.
160kA
320kA
Retain for future use.
8232-0081C
11/07
Page 2
2
Hubbell Modular Panel Surge Protective Device (SPD)
DANGER
Hubbell Modular Panel Surge Protective Device (SPD)
WARNING S
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
· Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices.
See NFPA 70E.
· This equipment must only be installed and serviced by qualified electrical personnel.
· Turn off all power supplying this equipment before working on or inside equipment.
· Always use a properly rated voltage sensing device to confirm power is off.
· Replace all devices, doors and covers before turning on power to this equipment.
Failure to follow these instructions will result in death or serious injury.
CAUTION
LOSS OF BRANCH CIRCUIT POWER AND SURGE PROTECTION
In the event that the surge protective elements of the SPD have been damaged (i.e. excessive surge
energy, power system anomaly, etc.), the surge protective elements can lose their ability to block
power system voltage and attempt to draw excessive current from the line. This SPD is equipped with
overcurrent and overtemperature protection that will automatically disconnect the surge protective
elements from the mains should the surge protective elements be damaged.
The effects of damaged surge protective elements and the subsequent operation of the automatic
overcurrent and overtemperature protection must be considered when applying a SPD, particularly
when critical loads requiring continuity of power or continuity of surge protection are present on the
power system. The following items should be considered when applying a SPD:
· Tripping of the branch circuit breaker feeding the SPD can occur when the surge protective
elements are damaged. Do not connect the SPD to a branch circuit feeding a load requiring
continuity of power (i.e. central computer or control systems, safety-critical equipment, critical
processes or systems, etc.) unless the branch circuit breaker trip characteristic has been
coordinated with the overcurrent protection inside the SPD.
· Periodic inspection of the state of the status indicator lights on the SPD should be made as part of
the preventive maintenance schedule. The SPD should be promptly serviced when an alarm
state exists.
· For unmanned, inaccessible, or critical installations, the dry contacts should be used to signal an
alarm state to the central supervisory system.
· In addition to the preceding items, the use of multiple SPDs to achieve redundancy should be
considered for critical applications.
Failure to follow these instructions can result in loss of power or loss of surge protection
that can cause injury or equipment damage.
· During installation into an electrical system, SPDs must not be energized until the electrical system
is completely installed, inspected, and tested. All conductors must be connected and functional,
including the neutral. The voltage rating of the device and system must always be verified before
energizing the surge protective device.
· Any factory or on-site testing of power distribution equipment that exceeds the normal operating
voltage, such as high-potential insulation testing, or any other tests where the suppression
components will be subjected to voltages higher than their rated turn-on voltage must be performed
with the suppressor disconnected from the power source. The neutral connection at the SPD must
also be disconnected prior to performing high-potential testing and then reconnected upon
completion of the test.
Failure to follow these instructions can result in equipment damage.
Hubbell Modular Panel Surge Protective Device (SPD)
3
8232-0081C
7/07
1-800-729-3406 | www.Hubbell-Wiring.com
Hubbell W iring Devices
Page 4
4
Hubbell Modular Panel Surge Protective Device (SPD)
Hubbell Modular Panel Surge Protective Device (SPD)
Hubbell Modular Panel Surge Protective Device (SPD)
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC
FLASH
· Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E.
· This equipment must only be installed and serviced by qualified
electrical personnel.
· Turn off all power supplying this equipment before working on or
inside equipment.
· Always use a properly rated voltage sensing device to confirm
power is off.
· Replace all devices, doors and covers before turning on power to this
equipment.
Failure to follow these instructions will result in death or
serious injury.
5
PRELIMINARY INSPECTION
UNPACKING AND
STORAGE
Proper installation is imperative to maximize the Hubbell Modular Panel
SPD’s effectiveness and performance. The installer should follow the
steps outlined in this instruction bulletin to ensure proper installation.
Read the entire instruction bulletin before beginning the installation. These
instructions are not intended to replace national or local electrical codes.
Check all applicable electrical codes to verify compliance. Installation
of surge suppressors should only be performed by qualified electrical
personnel.
NOTE: SPDs are designed for use on the load side of the service entrance
disconnect only.
Inspect the entire shipping container for damage or signs of mishandling
before unpacking the device. Remove the packing material and further
inspect the device for any obvious shipping damage. If any damage is
found and is a result of shipping or handling, immediately file a claim with
the shipping company.
The device should be stored in a clean, dry environment. Storage
temperature is -40 to +65 °C (-40 to +149 °F). All of the packaging
materials should be left intact until the device is ready for installation.
8232-0081C
7/07
1-800-729-3406 | www.Hubbell-Wiring.com
Hubbell W iring Devices
Page 6
6
Hubbell Modular Panel Surge Protective Device (SPD)
Hubbell Modular Panel Surge Protective Device (SPD)
IDENTIFICATION
IDENTIFICATION NAMEPLATE
The identification nameplate (see Figure 1) is located on the inside of the
door/cover.
Figure 1: SPD Nameplate Example
kA
SCCR: 200 kA
Enclosure Type
A
Suit able for us e on a circ uit ca pable of de liveri ng not more than 200,000 rms
symetrical Amperes, 240V Maximum. See installation guide for wiring information.
58J4
Made in USA
www.efinet.com
Tr
L-L / L-L / L-L
BC
SAFETY LABELS
SPD LOCATION CONSIDERATIONS
Environment
Audible Noise
Mounting
Service Clearance
Equipment Performance
English versions of all safety labels (danger, warning, caution) are provided.
The device is designed to operate in an ambient temperature range of
0 to +50 °C (+32 to +122 °F) with a relative humidity of 0 to 95% noncondensing. Refer to the product catalog for further details on enclosures.
All SPDs operate normally without reduction in performance when subjected
to shock and vibrations described in IEC 60721-3-3, Class 3M4.
The device background noise is negligible and does not restrict the location
of the installation.
This device is designed to be surface or flush mounted. Refer to the device
submittal drawings or the product catalog for typical mounting dimensions
and weight. Install the Hubbell Modular Panel SPD in a restricted access area.
The service clearance should meet all applicable code requirements.
To obtain the maximum system performance, locate the device as close as
possible to the circuit breaker to minimize the interconnecting wiring length.
For every foot in length of wire, approximately 175 volts per foot (6 kV/ 3 kA,
8/20 microsecond) is added to the suppressed voltage. The suppressed
voltage rating is located on the device nameplate and is measured 6 inches
Hubbell Modular Panel Surge Protective Device (SPD)
7
ELECTRICAL
Voltage Rating
Terminals, Wire Size and
Installation Torque
Prior to mounting the SPD, verify that the device has the same voltage
rating as the power distribution system in which it is installed by comparing
the nameplate voltage or model number on the SPD with the nameplate of
the electrical distribution equipment.
The specifier or user of the device should be familiar with the configuration
and arrangement of the power distribution system in which any SPD is to
be installed. The system configuration of any power distribution system is
based strictly on how the secondary windings of the transformer supplying
the service entrance main or load are configured. This includes whether
or not the transformer windings are referenced to earth via a grounding
conductor. The system configuration is not based on how any specific load
or equipment is connected to a particular power distribution system.
Terminals are provided for phase (line), neutral, and equipment ground
connections. The SPD terminals accept a range of #12 to #2 AWG (34
mm2) copper wire for phase, neutral, and ground connectors. Torque
connections to the following values.
Table 1: Installation Torque
Power ConnectionTerminal Torque
W/O DisconnectW/ Disconnect
AØ, BØ, CØ & N35 lb-in (4N·M)50 lb-in (5.7N·M)
Disconnect Means (External)
Ground50 lb-in (5.7N·M)
The use of fusible disconnects requires a fuse with a melting characteristic
2
greater than the per phase (Clearing) I
t of the SPD to prevent nuisance
operation of the disconnect fuses during a surge. (Refer to caution
statement “LOSS OF BRANCH CIRCUIT POWER AND SURGE
PROTECTION” on page 2 for further information)
8232-0081C
7/07
1-800-729-3406 | www.Hubbell-Wiring.com
Hubbell W iring Devices
Page 8
8
Hubbell Modular Panel Surge Protective Device (SPD)
WARNING
Hubbell Modular Panel Surge Protective Device (SPD)
E LECTRIC A L
UNDERSIZED WIRING
(USE ONLY CONDUCTORS RATED 30 A OR GREATER.)
· The Hubbell series SPD is designed for connection to a 30 A (or greater) circuit breaker.
· The circuit breaker is the intended disconnect means for the SPD without integral disconnect
option and provides overcurrent protection for the connecting conductors.
· The circuit breaker maximum rating should not exceed the ampacity of the connecting conductors.
Failure to follow these instructions will result in death or serious injury.
Turn off all power supplying this equipment through the Panel Circuit
Breaker or Primary Disconnect before working on or inside the equipment.
INTEGRAL SWITCH
LOCATION OF SPD
The integral switch is a second mechanical means for qualified
maintenance personnel to isolate the entire surge suppressor to service
the device’s components. The integral switch opens the phase and neutral
connections to the SPD for additional protection.
Turn integral switch handle to the OFF position prior to opening the
door of the unit. With the handle in the OFF position, the SPD will be
disconnected from the circuit and the circuit will not be protected from
surges. Maintenance may now be performed on the Hubbell module and
associated parts. Upon completion of repairs, close the door of the unit
and turn the handle to the ON position. Close the Panel Circuit Breaker or
Primary Disconnect to power SPD.
Install SPDs on the load side of the main overcurrent protection to comply
with UL 1449 and the NEC.
Locate the SPD as close as possible to the circuit breaker being protected
to minimize the wire length and optimize SPD performance. Avoid long wire
runs so that the device will perform as intended. To reduce the impedance
that the wire displays to surge currents, the phase, neutral, and ground
conductors must be routed within the same conduit and tightly bundled or
twisted together to optimize device performance. Avoid sharp bends in the
conductors. See Figure 2.
Hubbell Modular Panel Surge Protective Device (SPD)
CAUTION
SYSTEM GROUNDING
· SPD must be installed on solidly grounded power systems.
· Verify that the service entrance equipment is bonded to ground in
accordance with all applicable codes.
· Verify that the neutral terminals are grounded to system ground in
accordance with all applicable codes.
Failure to follow these instructions can result in equipment
damage.
An equipment ground conductor must be used on all electrical circuits
connected to the SPD. For the best performance, use a single-point
ground system where the service entrance grounding electrode system
is connected to and bonded to all other available electrodes, building
steel, metal water pipes, driven rods, etc. (for reference, see IEEE STD
142-1991). The ground impedance measurement of the electrical system
should be as low as possible, and in compliance with all applicable
codes, for electronics and computer systems.
When metallic raceway is used as an additional grounding conductor,
an insulated grounding conductor should be run inside the raceway and
sized in accordance with all applicable codes.
9
WARNING
INADEQUATE RACEWAY ELECTRICAL CONTINUITY
· Ground impedance must be as low as possible and in compliance with
all applicable codes for electronic and computer systems.
· Install an insulated grounding conductor inside a metallic raceway when
the raceway is used as an additional grounding conductor. Size the
conductor in accordance with all applicable codes.
· Maintain adequate electrical continuity at all raceway connections.
· Do not use isolating bushings to interrupt a metallic raceway run.
· Do not use a separate isolated ground for the SPD.
· Verify proper equipment connections to the grounding system.
· Verify ground grid continuity by inspections and testing as part of a
comprehensive electrical maintenance program.
Failure to follow these instructions can result in death or
serious injury.
8232-0081C
7/07
1-800-729-3406 | www.Hubbell-Wiring.com
Hubbell W iring Devices
Page 10
10
Hubbell Modular Panel Surge Protective Device (SPD)
INSTALLATION
Hubbell Modular Panel Surge Protective Device (SPD)
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC
FLASH
· Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E.
· This equipment must only be installed and serviced by qualified
electrical personnel.
· Turn off all power supplying this equipment before working on or
inside equipment.
· Always use a properly rated voltage sensing device to confirm
power is off.
· Replace all devices, doors and covers before turning on power to this
equipment.
Failure to follow these instructions will result in death or
serious injury.
INSTA L L ATION
CONDUIT LOCATION AND
RECOMMENDATIONS
SPECIAL ENCLOSURE
CONSIDERATIONS
Removing and Reconnecting
the Communication
Patch Cables
NEMA 3R Applications
The recommended conduit entry is at the bottom of the device enclosure.
Use a conduit seal that is appropriate for the enclosure rating.
The communication patch cables are marked with matching phase
connections. If any of the cables are removed, reconnect the cables as
marked.
Remove screws from the bottom of the enclosure to create drain holes.
Hubbell Modular Panel Surge Protective Device (SPD)
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
· Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices.
See NFPA 70E.
· This equipment must only be installed and serviced by qualified electrical personnel.
· Turn off all power supplying this equipment before working on or inside equipment.
· Always use a properly rated voltage sensing device to confirm power is off.
· Replace all devices, doors and covers before turning on power to this equipment.
Failure to follow these instructions will result in death or serious injury.
11
WIRING
Note: Prior to mounting the SPD, verify that the device has the same voltage
rating as the power distribution system in which it is installed by comparing
the nameplate voltage or model number on the SPD with the nameplate of
the electrical distribution equipment.
Follow steps 1–5 to make wiring connections.
1. Turn off all power supplying this equipment through the Panel Circuit
Breaker or Primary Disconnect before working on or inside the
equipment. (For additional protection, an integral switch may be used)
2. Mount the SPD as close as possible to the panelboard being protected.
3. Connect the SPD to the panelboard using an approved wiring method.
The connecting wires should be twisted together and kept as short as
possible to enhance the performance of the device. See page 8 for the
recommended wire size and installation torque. For wiring diagrams,
see figures 3 thru 12.
a. Connect the ground wire to the GROUND bus of the distribution panel.
Where applicable, connect ground to the SPD module.
b. Where applicable, connect the neutral wire to the SPD module.
c. Be sure the circuit breaker is open (OFF) prior to making any connections
of any kind. If a circuit breaker or circuit breaker space is not available,
connect to the electrical panel bus and then to an integral disconnect
utilizing the 3M or 10ft tap rule. (See NEC 240.21(B)(1)(4)). Be sure the
disconnect is open (OFF) and the circuit is de-energized before making
any connections. Connect a wire (in conduit) to each phase (HOT)
terminal on the LOAD side of a circuit breaker. Refer to the markings
on the device when connecting the phase, neutral, and ground
conductors. Fuses are not recommended for protection unless the
fuses are specifically designed for use in an SPD application.
NOTE: On a high-leg delta installation, the high-leg of the power
system must be connected to phase B of the SPD.
4. After all connections have been made, reinstall any barriers that have
been removed, close the door or replace the cover.
5. Restore power to the equipment as required. If the SPD is properly installed
and functioning, the green LED indicators on the display will be lit.
If you have any questions pertaining to the installation, contact your Hubbell
representative.
NOTE: Always install the SPD on the LOAD side of the main disconnect.
8232-0081C
7/07
1-800-729-3406 | www.Hubbell-Wiring.com
Hubbell W iring Devices
Page 12
12
Hubbell Modular Panel Surge Protective Device (SPD)
Hubbell Modular Panel Surge Protective Device (SPD)
WIRING D I A G R A M S
WIRING DIAGRAMS WITHOUT INTEGRAL DISCONNECT
Figure 3: Single-Phase, 3-Wire, GroundedFigure 4: Three-Phase, 3- or 4-Wire,
Grounded Wye
Chasis Ground
Chasis Ground
Figure 5: Three-Phase, 3- or 4- Wire,
High-Leg Delta
Figure 14: Three-phase, 3- or 4-Wire, Grounded Wye Installation
NOTE: The neutral conductor is not present on 3-wire, grounded neutral power systems. For these systems tie the
neutral and ground lugs together.
AØ
BØ
CØ
ØC ØABØ N
Custom er Connec tions 160kA
Custom er Connec tions 320k A
Figure 15: Three-phase, 3- or 4-Wire, High-Leg Delta Installation
NOTE: The high-leg of the power system must connect to phase B of the SPD. The neutral conductor is not present
on 3-wire, grounded neutral power systems. For these systems tie the neutral and ground lugs together.
Figure 17: Three-phase, 3- Wire, Delta, Corner Ground Delta Installation with Integral Disconnect
15
Custom er Connec tions 160kACustom er Connec tions 320k A
Figure 18: Single-phase, 3- Wire, Grounded Installation with Integral Disconnect
N
AØ
CØ
Custom er Connec tions 160kA
8232-0081C
7/07
1-800-729-3406 | www.Hubbell-Wiring.com
Custom er Connec tions 320k A
Hubbell W iring Devices
Page 16
16
ØCØABØ N
Customer Connections 120 kA - 240 kA
ØCØABØ N
Customer Connections 120 kA - 240 kA
Hubbell Modular Panel Surge Protective Device (SPD)
Hubbell Modular Panel Surge Protective Device (SPD)
Figure 19: Three-phase, 3- or 4-Wire, Grounded Wye Installation with Integral Disconnect
NOTE: The neutral conductor is not present on 3-wire, grounded neutral power systems.
For these systems tie the neutral and ground lugs together.
PA N E L D I AGR A M S
AØ
BØ
CØ
Custom er Connec tions 160kA
ØC ØABØ N
Custom er Connec tions 320k A
Figure 20: Three-phase, 3- or 4-Wire, High-Leg Delta Installation with Integral Disconnect
NOTE: The high-leg of the power system must connect to phase B of the SPD. The neutral conductor is not
present on 3-wire, grounded neutral power systems. For these systems tie the neutral and ground lugs together.
Hubbell Modular Panel Surge Protective Device (SPD)
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
· Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices.
See NFPA 70E.
· This equipment must only be installed and serviced by qualified electrical personnel.
· Turn off all power supplying this equipment before working on or inside equipment.
· Always use a properly rated voltage sensing device to confirm power is off.
· Replace all devices, doors and covers before turning on power to this equipment.
Failure to follow these instructions will result in death or serious injury.
17
OPERATION AND
LED STATUS INDICATORS
The SPD display panel shows the status of the Hubbell module with
diagnostically controlled green/red LEDs. If a unit is operating correctly,
all the phase LEDs will be illuminated green. To test the integrity of the
diagnostics for each phase, push the button below the phase LEDs on the
diagnostic display. The green LED will turn red and the alarm will sound, if
the alarm is enabled. Releasing the test button will complete the test; the
red LED will turn green and the alarm will shut off.
If an inoperable condition occurs on any phase, the audible alarm sounds
and the corresponding phase LED on the diagnostic display panel is
illuminated red. This indicates that the device needs service by qualified
electrical personnel. The audible alarm can be silenced, until a qualified
person is able to evaluate and service the SPD by pressing the alarm
enable/disable button. The alarm will silence and the green alarm LED
will not be lit. The red phase LED will continue to be illuminated until the
inoperative condition had been cleared.
On wye and split phase configuration SPD modules (see Figure 21), if the
left green LED is not lit, it indicates a loss of suppression from line-toground for that phase. If the right green LED is not lit, it indicates a loss of
suppression from line-to-neutral for that phase. If both green LEDs are not
lit and the diagnostic display panel has power, then power has been lost to
that phase or module is bad and should be replaced.
Figure 21: SPD Module LEDs (Wye and Split Phase configurations)
8232-0081C
7/07
Left green LED lit:
Unit is operating
correctly
Left green LED not lit:
Loss of surge suppres-
sion from L·G
Right green LED lit:
Unit is operating correctly
Right green LED not lit:
Loss of surge
suppression from L·N
When power is applied to the SPD and one or more of the display LEDs
are red, and one or more SPD module LEDs are out, the appropriate
module should be replaced. Refer to “Maintenance and Troubleshooting”
on page 19 for proper troubleshooting procedures.
1-800-729-3406 | www.Hubbell-Wiring.com
Hubbell W iring Devices
Page 18
18
Hubbell Modular Panel Surge Protective Device (SPD)
Hubbell Modular Panel Surge Protective Device (SPD)
OPERAT I O N
SPD MODULE (DELTA
CONFIGURATIONS)
AUDIBLE ALARM
SURGE COUNTER
On a delta configured SPD, the module inside the panel does not contain
any status LEDs. Instead, there is a blue status LED which is located on
the panel backplane directly adjacent to the corresponding module. If the
blue LED is not lit, it indicates a loss of suppression from line-to-line for that
phase. If the blue LED is not lit and the diagnostic display panel has power,
then power has been lost to that phase or the module is bad and should
be replaced.
Push the alarm enable/disable button to enable or disable the alarm. If the
green alarm LED is lit the alarm is enabled. If the green alarm LED is not lit,
the alarm is disabled.
The surge counter displays the number of transient voltage surges since
the counter was last reset. The counter is battery powered to retain
memory in the event of a power loss to the diagnostic display panel.
To reset the surge counter remove all power and press the small switch
located inside the unit on the underside of the diagnostic circuit board
(near the communication connectors). This will reset the counter to zero.
Figure 22: Three-Phase Display Panel with Surge Counter
Note: Phase B is not present
on single-phase applications.
Description of
phase LEDs
Surge counter
Alarm enable/disable
push buttons
Alarm LEDs
DRY CONTACTS
SPIKESHIELD
Push-to-Test / Botón de prueba / Bouton pousser pour vérifier
= OK
SURGE PROTECTIVE DEVICE
= Replace Module / Sustituya el módulo / Remplacer le module
Counter /
Contador /
Compteur
AØ
Phase LEDs
On-Line diagnostic
push buttons
Enable Alarm
CØ
Disable Alarm
Surge counter
reset switch
www.hubbell.comMade in USA / Hecho en E.U.A. / Fabriqué aux É.-U.
8232-0011A
(on diagnostic
circuit board)
The Hubbell Hardwired series SPD is provided with dry contacts. The
connection for the dry contacts is located on the back of the diagnostic
display panel (lower right corner). The dry contacts are 3-position, Form
“C” type with Normally Open, Normally Closed and Common connections.
The unpowered state shall be closed between terminals NC and COM.
This is also the alarm condition. The opposite state, closed between
terminals NO and COM, indicates that power is on to the unit and that
no alarm condition exists (See Table 3). These contacts can be used for
remote indication of the SPD’s operating status to a computer interface
board or emergency management system. Also, these contacts are
designed to work with the SPD remote monitor option described below.
The contacts are designed for a Maximum voltage of 24 VDC and a
maximum current of 2 A. Higher energy applications may require additional
relay implementation outside the SPD. Damage to the SPD’s relay caused
by use with energy levels in excess of those discussed in this instruction
bulletin are not covered by warranty. For application questions, contact
your Hubbell representative.
Hubbell Modular Panel Surge Protective Device (SPD)
Care must be taken in installing the dry contact wiring because the
terminals are on a moving door. Avoid the door hinge, any disconnect
switches, and the high voltage areas of the enclosure when routing the
wiring. To avoid the door hinge, tie wrap any dry contact wiring to the
existing cable harness which crosses the hinge. Once the dry contact
wiring is secured on a non-moving point of the enclosure, it is the user’s
responsibility to maintain separation between dry contact wiring and the
power wiring in the enclosure.
Table 2: Dry Contact Configuration
Alarm Contact
Terminals
Contact State with Power Removed
NCNormally closed
COMCommon
NONormally open
19
MAINTENANCE AND
TROUBLESHOOTING
Preventive Maintenance
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC
FLASH
· Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E.
· This equipment must only be installed and serviced by qualified
electrical personnel.
· Turn off all power supplying this equipment before working on or
inside equipment.
· Always use a properly rated voltage sensing device to confirm
power is off.
· Replace all devices, doors and covers before turning on power to this
equipment.
Failure to follow these instructions will result in death or
serious injury.
Inspect the SPD periodically to maintain reliable system performance and
continued transient voltage surge protection. Periodically check the state of
the display LED status indicators. Routinely use the built-in diagnostics to
inspect for inoperative modules.
8232-0081C
7/07
1-800-729-3406 | www.Hubbell-Wiring.com
Hubbell W iring Devices
Page 20
20
START
Possible diagnostic
display board failure.
Replace diagnostic
display panel.
Is
power
being supplied
to the
SPD?
Green phase LED(s)
not lit. And, no
Red LED(s) lit and
no Alarm on.
Energize SPD
and verify proper
connection.
NO
YES
START
YES
NO
Red phase
LED(s) lit.
Check the power
utility feed and
verify voltage
levels.
Replace module(s)
that do not have
LEDs lit.
Energize SPD
and verify proper
connection.
Possible diagnostic
display board failure.
Replace diagnostic
display panel.
Alarm
on?
Is alarm
Enable/Disable
LED on?
Press
alarm Enable/
Disable switch.
Is alarm
on?
Is alarm
LED on?
All module
LEDs on?
Check
patch cable
connections. Is
Red LED(s)
on?
Check
the voltage
on each phase.
Is the voltage
correct?
NO
YES
YES
YES
YES
NO
NOYES
NO
NO
NO
Hubbell Modular Panel Surge Protective Device (SPD)
Hubbell Modular Panel Surge Protective Device (SPD)
TROUBLES HOOT I N G
Troubleshooting
Figure 23: Troubleshooting Flowcharts
Refer to Figure 23 below for troubleshooting procedures.
Replacement parts are available. For ordering information refer to the
product catalog.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by
Hubbell Wiring for any consequences arising out of the use of this material.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.