Hubbell GFRST20BKB Specifications

Ground Fault Products
Commercial Standard GFCI Receptacles
Features
Patented AUTOGUARD® self test technology
Internal back wiring clamp and guide for quick and secure termination
Alarm version provides audible notification of a trip condition
Ordering Information
Description Catalog Number UPC Color
20A, 125V, Style Line®, AUTOGUARD® self test GFCI receptacle, alarm, flush face, back and side wired,
Listings
UL Listed - Canadian and U.S. Meets ADA Standards Meets all NEC® requirements CSA Certified NEMA® WD-6 Compliant
GFRST20BKB 883778228094 GFRST20BKB
Specifications
Face Nylon Base Nylon Power Contacts Brass Ground Contacts Brass Mounting Strap Zinc plated steel Mounting Screws Zinc plated steel
Performance
Electrical
Amperage 15A/20A, 20A Feed Thru Current Interrupting Certified for current interrupting at full rated current Dielectric Voltage Withstands 1,500V minimum Frequency 60 Hz Maximum Interrupting
Capacity Trip Level 4 to 6 mA Trip Time .025 second nominal Voltage 120V AC +10% - 15% (102V to 132V)
Mechanical
Product Identification Ratings are a permanent part of the device Terminal Accommodation #14-#10 AWG copper stranded or solid conductor only Terminal Identification Terminals identified in accordance with UL 498 and CSA
Environmental
Flammability UL 94V-2 Operating Temperature -35°C to 66°C or -30°F to 150°F
10,000A
Accessories
Wallplates for duplex openings
Online Resources
eCatalog
Dimensions in Inches (mm)
Specifications subject to change without notice.