Hubbell GFCI Sensing Module Catalog Page

Ground Fault Products
GFCI Sensing Module, 50A Maximum Rating - NEMA 4X
Typical Applications Include:
Power Generators, Spas, High Pressure Washers, Power Centers, Refineries and Mobile Power.
The sensing module functions interdependently with a magnetic branch circuit breaker. The module monitors the electrical circuit by use of an external differential current transformer. No direct load is present at the module. In the event of a ground fault, the load is interrupted by way of the hydraulic magnetic circuit breaker utilizing a shunt trip coil.
This line of Sensing Modules is rated from 1 to 50 Amps and circuit current-carrying conductors from 1 to 3 poles. Product is available with an automatic or manual “safe start” reset feature. The enclosure, when mounted with
the supplied gasket, achieves a UL NEMA 4X Rating. This module and breaker system is ideal for portable generator integration protecting all outlets on a generator. This system meets the proposed requirements for generators Underwriters Laboratory Standard 2201. UL/cUL 943 Listed, Class A 4-6mA trip level and UL 1053 Compliant.
GFCI Sensing Module – 50A Maximum
Description Catalog Number
120V AC Sensing Module Auto GFS M120A 120V AC Sensing Module Manual GFS M120M 240V AC Sensing Module Auto GFSM240A 240V AC Sensing Module Manual GFSM240M
GFSM120M
GFSMCB120401P
Wiring Schematics
Current carrying leads must be twisted as they go through the sensing module.
PART # AUTO GFSM120A MAUUAL GFSM120M
H N
120V AC IN
SINGLE PHASE 120VAC (HOT, NEUTRAL, GRND)
GROUND
GFCI Sensing Module, 50A Maximum Rating - NEMA 4X Ground Fault Products
120VAC GFCI SENSING MODULE
GFCI Sensing Module Circuit Breakers
Catalog Number Configurator - Example Catalog Number: GFSMCB120401P
GFSMCB 120 40 1P Ground Fault
Sensing Module Circuit Breaker
120 Volt
240 Volt 120/240 Volt
OtherExamples:
GFSMCB240502P: 240V 50A 2P GFSMCB240203P: 240V 20A 3P
GFSMCB120XX1P
CIRCUIT BREAKER
LOAD
NO C
LINE
WHITE BLACK YELLOW (SHUNT)
ORANGE SHUNT JUMPER
LOAD--->
Current carrying leads must be twisted as they go through the sensing module.
H
L1
N
L2
240V AC IN
SINGLE PHASE 240VAC (L1, L2, GRND)
G
GROUND
PART # AUTO GFSM240A MAUUAL GFSM240M
240VAC GFCI SENSING MODULE
1 thru 50 Amp
GFSMCB240XX2P
CIRCUIT BREAKER
LOAD
LINE
RED BLACK YELLOW (SHUNT)
1P
2P 3P
GFSMCB120XX2P
ORANGE SHUNT JUMPER
NO C
LOAD--->
Current carrying leads must be twisted as they go through the sensing module.
L1
L2
L2 L1
N 120/ 240 V AC IN
G
GROUND
PART # AUTO GFSM120A MAUUAL GFSM120M
120VAC GFCI SENSING MODULE
SPLIT PHASE 120/240VAC (L1, L2, N, GRND)
LOAD
LINE
CIRCUIT BREAKER
NO C
WHITE BLACK YELLOW (SHUNT)
ORANGE SHUNT JUMPER
LOAD--->
L2
L1
N
G
H-10 Dimensions in Inches (mm)