Ground Fault Products
GFCI Sensing Module, 50A Maximum Rating - NEMA 4X
Typical Applications Include:
Power Generators, Spas, High Pressure Washers, Power Centers, Refineries and Mobile Power.
The sensing module functions interdependently with a magnetic branch circuit breaker. The module monitors
the electrical circuit by use of an external differential current transformer. No direct load is present at the module.
In the event of a ground fault, the load is interrupted by way of the hydraulic magnetic circuit breaker utilizing a
shunt trip coil.
This line of Sensing Modules is rated from 1 to 50 Amps and circuit current-carrying conductors from 1 to 3 poles.
Product is available with an automatic or manual “safe start” reset feature. The enclosure, when mounted with
the supplied gasket, achieves a UL NEMA 4X Rating.
This module and breaker system is ideal for portable generator integration protecting all outlets on a generator.
This system meets the proposed requirements for generators Underwriters Laboratory Standard 2201.
UL/cUL 943 Listed, Class A 4-6mA trip level and UL 1053 Compliant.
GFCI Sensing Module – 50A Maximum
Description Catalog Number
120V AC Sensing Module Auto GFS M120A
120V AC Sensing Module Manual GFS M120M
240V AC Sensing Module Auto GFSM240A
240V AC Sensing Module Manual GFSM240M
GFSM120M
GFSMCB120401P
Wiring Schematics
Current carrying leads must
be twisted as they go through
the sensing module.
PART #
AUTO GFSM120A
MAUUAL GFSM120M
H
N
120V AC
IN
SINGLE PHASE 120VAC (HOT, NEUTRAL, GRND)
GROUND
GFCI Sensing Module, 50A Maximum Rating - NEMA 4X Ground Fault Products
120VAC GFCI
SENSING
MODULE
GFCI Sensing Module Circuit Breakers
Catalog Number Configurator -
Example Catalog Number: GFSMCB120401P
GFSMCB 120 40 1P
Ground Fault
Sensing Module
Circuit Breaker
120 Volt
240 Volt
120/240 Volt
OtherExamples:
GFSMCB240502P: 240V 50A 2P
GFSMCB240203P: 240V 20A 3P
GFSMCB120XX1P
CIRCUIT
BREAKER
LOAD
NO
C
LINE
WHITE
BLACK
YELLOW (SHUNT)
ORANGE
SHUNT
JUMPER
LOAD--->
Current carrying leads must
be twisted as they go through
the sensing module.
H
L1
N
L2
240V AC
IN
SINGLE PHASE 240VAC (L1, L2, GRND)
G
GROUND
PART #
AUTO GFSM240A
MAUUAL GFSM240M
240VAC GFCI
SENSING
MODULE
1 thru 50
Amp
GFSMCB240XX2P
CIRCUIT
BREAKER
LOAD
LINE
RED
BLACK
YELLOW (SHUNT)
1P
2P
3P
GFSMCB120XX2P
ORANGE
SHUNT
JUMPER
NO
C
LOAD--->
Current carrying leads must
be twisted as they go through
the sensing module.
L1
L2
L2
L1
N
120/
240 V AC
IN
G
GROUND
PART #
AUTO GFSM120A
MAUUAL GFSM120M
120VAC GFCI
SENSING
MODULE
SPLIT PHASE 120/240VAC (L1, L2, N, GRND)
LOAD
LINE
CIRCUIT
BREAKER
NO
C
WHITE
BLACK
YELLOW (SHUNT)
ORANGE
SHUNT
JUMPER
LOAD--->
L2
L1
N
G
H-10 Dimensions in Inches (mm)