Hubbell GF20LAMP Specifications

Ground Fault Products
20A, 125V
Circuit Guard® GFCI Receptacles
Features
Ground fault EOL indicator
No power at face if reverse wired
Automatic self-grounding staple makes installation ease
Ordering Information
Description Device Color UPC Catalog Number
Flush, nylon face, back Brown 883778379093 GF20LA
Listings
Meets UL498 for receptacles UL943 Class A for GFCIs UL File E41978 CSA Certified
Specifications
Trip Level 4 to 6 mA Trip Time .025 second nominal Frequency 60 Hz Codes Meets all NEC® and CEC
requirements
Performance
Electrical
Amperage 15A/20A, 20A Feed Thru Max. Interrupting Capacity 10,000A Voltage 120V AC +10% - 15% (102V to 132V)
Environmental
Maximum Humidity 0.95 Operating Temperature -35°C to 66°C or -30°F to 150°F.