Hubbell RFHP-R, Geyser-R Installation Manual

Geyser-R
Heat pump water heater
Installation manual
1 Version 2.9
SAFETY INFORMATION
Please read carefully to prevent serious accidents or injury.
The Geyser-R Heat Pump Water Heater must be installed in the accordance with Local and
Disconnect all power before installing or servicing the Geyser-R.There is a discharge fan located on the unit. Extreme caution must be exercised to
ensure that any foreign objects including fingers and hands remain clear of the fan area.
Do not stand, sit or place any objects on or beside the unit (clearances are stated in the
installation manual).
Do not allow children to play on or near the unit.Make sure all power is disconnected and shut off before moving the unit.Cover should not be removed with power on.Internal components may be HOT. Please allow sufficient time for the unit to cool
completely before touching any internal components.
Ensure that the power receptacle for the Geyser-R is rated for 115 V. and at least 15 A.Ensure that the electrical supply has a properly rated fuse or breaker protection rated
for at least 15 amps. It is suggested to use a dedicated outlet.
Always wear eye protection during installation.Unit weight is approximately 70lbs. All lifting should be done with the handles located
on the side of the Geyser-R. Proper lifting should be used in the moving of the unit.
The Geyser-R must NOT be connected to an electric water heater with heating elements
larger than 240/5500 watts.
Please keep these instructions for reference!
2 Version 2.9
SYSTEM REQUIREMENTS
The Geyser-R should only be installed in a dry/covered location. The Geyser-R is not designed
to be installed outside where it can be exposed to adverse weather condition. The ambient air temperature in the installation area should not drop below 50°F (10°C). The cubic area of the space needs to be 1,000 cubic feet or greater for proper air flow and to avoid excessive cooling of the area. The Geyser-R can be installed in attics garages, or basements provided the above criteria are met for proper installation.
The Geyser-R connects to a typical household outlet, 115V, 15 Amp. While the device requires
approx. 12 Amps momentarily upon power-up, the device draws 5-8 Amps during normal operation. It is recommended that a dedicated 15 Amp Circuit be used to power the Geyser-R. The Geyser-R is recommended for installation on electric water tanks of 40gallons (151.4 liters) or greater.
A drain must be available to accommodate condensate generated during operation of the
Geyser-R. In high humidity environments, the Geyser-R is capable of generating as much as 50 pints (24 liters) per day. The condensate can be routed to a floor drain, sink, the house waste line, or to the outside by way of the drain hose (provided).
Check with the codes in your area for the proper way to dispose of the condensate. A
condensate pump may be required (not included).
Most electric water tanks utilize two heating elements, one at the top of the tank and one at
the bottom. The heating element at the top of the tank is called the quick recovery element. This is designed to heat water at the top of the tank if the temperature of the tank falls below the set point of the thermostat. The lower element provides most of the heating in a typical water heater.
The Geyser-R replaces the lower element in operation and provides the majority of the heating
requirements. The upper element is left on at the temperature you set it, and will only engage if there is a need for quick recovery. Therefore in normal operation the Geyser-R will provide all the hot water needed and the top element will not run.
The Geyser-R will remove moisture from the air. It is an efficient dehumidifier and many have
found that the unit provides all the necessary dehumidification for the space the Geyser-R is located.
Moisture may occasionally cause frost to form on the evaporator. When the frost builds up, the
Geyser-R will go into a defrost cycle. This could occur as often as every two hours in a cold humid environment. While in the defrost mode, a period of up to 6 minutes, the fan will continue to run and the tanks lower element will provide heating for the tank, when the defrost cycle is over the Geyser-R will resume heating the water.
3 Version 2.9
INSTALLATION PARTS
The Geyser-R comes with the following installation kit:
Qty Description
1 4”x ¾” Nipple
2 ¾” Tee
1 Dip tube
2 ¾”FH x ¾” FIPS, with washers.
4 ¾”PEX x ¾” MIP
1 Teflon Tape
1 Red Wire nut
1 Strain relief
6’ Condensate tubing
4 Version 2.9
You will need to provide the following components to complete the installation:
¾” Pex tubing.
Pex tubing crimps ¾”
Armaflex ¾” insulation (not split Rubatex)
Optional: 2 shut-off valves
Furthermore, a transfer pump is recommended to drain the tank.
This installation method is designed to bring the most efficiency for the system. Deviating from the following installation procedure will affect the efficiency of the unit. Deviation from the installation method could also damage the unit and void the warranty. PLEASE read and follow the installation instruction carefully.
It is recommended that the Geyser-R be installed as close as possible to the water heater. We recommend 4 feet if possible. This will ensure the most efficiency with the least amount of heat loss through the piping.
5 Version 2.9
INSTALLATION OF THE GEYSER-R
Note: The following installation instructions cover the installation of the Geyser-R in conjunction with an electric water heater. Alternate water tanks may require an alternative installation method not covered by this manual. It is recommended that you contact Hubbell Electric Heater Company office (203-378-2659) and speak with technical support to see if the Geyser-R can be used in a particular application other than an electric water heater.
Survey the area where the Geyser-R is to be installed. Make sure the area is clear of
obstructions, clear of debris, and clean of significant dust and dirt that can get into the unit or clog the filter.
Area should be at least 1,500 sq ft of open space.Ambient air temperature should be at least 50°F (10°C). Temperatures lower than this
will cause the unit to defrost constantly and reduce the efficiency. If the temperature in the space gets lower than 50°F (10°C), it is recommended that the unit be shut off until a constant temperature above 50°F (10°C) can be maintained.
When choosing the placement of the Geyser-R, make sure the fan is not blocked or close
to a wall or other object that would inhibit air flow.
The Geyser-R should be placed on the floor or set on vibration isolation pads. Make sure
the unit is higher than the drain and the drain line has an unobstructed path to the drain.
You can install the unit in an elevated position if desired. Make sure the unit is secure
and that the piping is not kinked or restricted in any way. The unit should not be installed higher than the top of the water heater.
Piping should be kept to a minimum and as short as possible to minimize heat loss. 4
feet is the recommended length.
Check the overall condition of the existing water heater.Make sure the drain is easily accessible.Be sure shut off valves are in good condition and are in working order.If unit is being installed in an attic it is recommended that both hard and soft foam be
placed on the joists to absorb any excess vibration.
Make sure there is an 115V outlet in close proximity to where the unit is going to be
installed.
DO NOT install the Geyser-R with an extension cord of any size.
6 Version 2.9
INSTALLATION INSTRUCTIONS
Turn off all power to the water heater at the circuit breaker in the electric panel.
Plumbing Installation
Turn off the cold water inlet at the service valve above the water heater.
Open one or more hot water faucets in the house to relieve the water pressure in the
hot water tank; leave these faucets open to allow air to freely enter the tank during draining.
Drain the tank completely.
7 Version 2.9
Remove the drain valve from the bottom of the tank and set aside for use in a later step.
Properly using thread seal tape, wrap all ¾” NTP* male threads.
*NTP fittings do not include fittings on Geyser front panel. These are standard hose thread fittings.
8 Version 2.9
Install 4”x ¾” brass nipple into the drain valve opening.
Do not over tighten.
9 Version 2.9
Loading...
+ 20 hidden pages