Commercial Specification Grade Receptacles
Specications
Part Standard Weather Resistant
Top Base
Double Wipe Power Contacts Wire Clamp
Finish
Mounting Strap
Ground Contact
Line Terminal Screws Ground Screw
Automatic Self-Grounding Staple
Mounting Screws
Certification
UL Listed
Fed. Spec. Certified to CSA
CRF15I BR15LA DR20I CR20TR
Nylon Nylon
.030 in. (.8) Brass .062 in. (1.6) Steel-Nickel Plated
.040 in. (1) Steel (Galvanized) .031 in. (.8) Brass #8-32 Plated Steel, Multiple Drive #8-32 Plated Steel, Multiple Drive
Stainless Steel
Zinc Plated Steel
UL498 WC596* C22.2, No. 42
Nylon (UV Rated)
Nylon
.030 in. (.8) Brass .062 in. (1.6) Steel-Nickel Plated
.040 in. (1) Steel (Galvanized) .031 in. (.8) Brass #8-32 Stainless Steel, Multiple Drive #8-32 Stainless Steel, Multiple Drive
Stainless Steel Stainless Steel
UL498 WC596* C22.2, No. 42
DR20GRYWR
Performance
Electrical
Dielectric Voltage Max. Working Voltage Current Interrupting
Temperature Rise
Mechanical
Terminal Identification
Terminal Accommodation
Product Identification
Environmental – Material
Flammability
Operating Temperature
Note: *Decorator and Commercial Tamper-Resistant devices are not Fe d. Spec. Listed.
Withstands 2,000V minimum. 125 V. Certified for current interrupting at full rated current. Max 30°C temperature rise at full rated
current after 100 cycles of overload at
150% of rated current.
Terminals identified in accordance with
UL 498 and CSA (Brass, White, Green). #14-10 AWG stranded or solid copper conductor only. Ratings are a permanent part of the device.
UL 94V-2. Maximum continuous 75°C; minimum -40°C (w/o impact).
Withstands 2,000V minimum. 125 V. Certified for current interrupting at full rated current. Max 30°C temperature rise at full rated
current after 100 cycles of overload at
150% of rated current.
Terminals identified in accordance with
UL 498 and CSA (Brass, White, Green). #14-10 AWG stranded or solid copper conductor only. Ratings are a permanent part of the device.
UL 94V-2. Maximum continuous 75°C; minimum -40°C (w/o impact).
®
Wiring Device-Kellems