HUBBELL CIRCUIT -LOCK
U.S. Patent No. 5,298,701
GENERAL INFORMA TION
1. NOTICE: For installation by a qualified electrician in
accordance with national and local electrical codes and
the following instructions.
2. CAUTION: RISK OF ELECTRIC SHOCK. Disconnect
power before installing. More than one disconnect
switch may be required to de-energize this
equipment before servicing. Disconnect ALL
power supplies to enclosure before exposing
interior.
3. NOTICE: Separate overcurrent protection must be
provided in accordance with National Electrical Code
Article 220 or Canadian Electrical Code, Section B, as
appropriate. Overcurrent protection MUST NOT exceed
the ampere rating of the receptacle [ref.: National
Electrical Code® section 430-42(c) or Canadian
Electrical Code, Part 1, Rule 28-602(3)(c)(i)].
4. Suitable for use on a circuit capable of delivering not
more than 10,000 rms symmetrical amperes at the
voltage rating of the receptacle.
5. This enclosure includes a lockout provision to isolate
the receptacle and connected equipment from the
power supplied to the enclosure as a method of
compliance to OSHA Lockout/Tagout Regulation 29,
CFR Part 1910.147. The ON-OFF control knob (in the
OFF position) accepts up to 5/16 inch (8 mm)) diameter
shackle of a suitable padlock or Lockout device. This
feature does NOT isolate the power supplied to the
enclosure during internal servicing of the enclosure.
6. NOTICE: This enclosure must NOT be used as a
junction box for feed-through connections.
7. The pilot contact (if installed) is rated A600 pilot duty,
600 VAC 10A.
8. WARNING: RISK OF ELECTRIC SHOCK. Bonding
between conduits must be provided.
A.Mounting Instructions:
1. This enclosure must always be mounted vertically with receptacle end down.
2. This enclosure may be mounted for top, bottom or back conduit entrances. Bottom feed is recommended whenever
possible. Figs M1 & M2. Back feed is permitted in Type 4X applications only. Fig. M4.
3. For Type 4X and Type 12 applications, enclosure must be mounted by means of mounting feet. DO NOT drill, punch or
nail mounting holes through the enclosure.
4. Mount the feet to the enclosure using the screws provided. Tighten to 10-12 lb•in (1.2 - 1.4 N•m).
5. Mounting feet will accept up to 5/16 inch (8 mm) diameter screws (not provided). Mounting pattern is shown in Fig. M1.
6. Remove the four (4) cover mounting screws and remove cover. Switch handle must be in “OFF” position to remove cover.
7. Drill or punch hole at the desired conduit entry location:
a. 1-3/8 inch (34.9 mm) diameter for 1 inch trade size conduit hub (30 Amp).
b. 1-3/4 inch (44.4 mm) diameter for a 1-1/4 inch trade size conduit hub (60 & 100 Amp).
Molded drill spots on the outside top, bottom and back surface show the locations. Fig. M4.
TM
30, 60 & 100 AMP PIN & SLEEVE MECHANICAL INTERLOCK
English
BOTTOM FEED
(RECOMMENDED METHOD OF ENTRY)
6.87
[174.50]
4.75
[120.65]
Dimensions in inches [mm]
6.87
[174.50]
4.75
[120.65]
•
®
10.12
[257.05]
•
•
[279.40]
8.00
[203.20]
11.00
UNIT RATING
11.87
[301.50]
•
GROUNDING
(BONDING)
PLATE
•
7.75
[196.85]
FIG. M1 • 30 AMP
•
MOUNTING FEET
ADJUST TO ANY 1
OF 3 POSITIONS
CONDUIT HUB
•
•
7.75
[196.85]
[323.85]
9.75
[247.65]
OPTIONAL
CENTER
LOCATION
FOR 3 POINT
MOUNTING
12.75
FIG. M2 • 60 & 100 AMP
INSTALLATION INSTRUCTIONS
8. Use ONLY Listed/Certified conduit hub rated for Type 4X and Type 12 applications (one supplied) such as:
RACO #1704 for 1 inch trade size (30 Amp)
RACO #1705 for 1¼ inch trade size (60 & 100 Amp)
9. Install the conduit hub. Be sure that the “O” ring is properly seated in its groove.
10. Install the grounding (bonding) plate under the conduit nut. Tighten nut securely for a watertight seal and grounding continuity.
11. Any unused conduit entrance holes must be sealed with Listed/Certified closure plugs rated Type 4X and type 12. (Hubbell
Cat. No. MICPK30 for 30A, Cat. No. MICPK60 for 60A and 100A).
12. NOTE: The metal closure plug must be grounded (bonded) back to the inside green & yellow grounding buss. Grounding
(bonding) wire connection required.
13. Use of user-installed conduit entrances above the switch are not recommended in applications where condensation may be
present in the conduit (high humidity and extreme temperature change locations). When using the top feed conduit entrance,
drip loops must always be formed as indicated in fig. M3.
Wiring Device-Kellems
Hubbell Incorporated (Delaware)
185 Plains Road
Milford, CT 06460-8897
(203) 882-4800
PD1788 (SHEET 1 of 3 • Page 1) PRINTED IN U.S.A. 8/06

INSTALLATION INSTRUCTIONS (CONTINUED)
B. Wiring Instructions
1. Select conductors having 90°C or higher rated insulation and sufficient ampacity in accordance
with the 60°C column (for 30 Amp and 60 Amp devices) or the 75ºC column (for 100 Amp
devices) of the National Electrical Code® Table 310-16 or Canadian Electrical Code Table 2.
2. CAUTION: USE COPPER CONDUCTORS ONLY.
3. DO NOT TIN CONDUCTORS.
4. Make sure the connected equipment rating does not exceed the rating of this device. See
General Information #4 regarding overcurrent protection.
5. Terminal capacity as indicated in Table 1
6. Strip conductor insulation ½ inch (13 mm).
7. Select proper wiring diagram. Loosen terminal screws. Insert conductors fully into proper terminal.
8. Tighten terminal screws to torque indicated in Table 2:
9. TAKE CAUTION THAT THERE ARE NO STRAY WIRE STRANDS.
10. Tighten the grounding buss mounting screw to 10-12 lb•in (1.2-1.4 N•m).
11. Reinstall the cover. The handle must be in the OFF position. Make sure the rope gasket is
properly seated in the groove. Tighten the four cover screws to 10-12 lb•in (1.2-1.4 N•m).
12. Consult factory for auxiliary contact availability.
FIG. M3 • TOP FEED
30 AMP
•
PROVIDE
CONDENSATE
DRIP LOOP
AS SHOWN
•
60 & 100 AMP
MOLDED IN DRILL POINT
(ONE TOP, ONE BACK,
ONE BOTTOM)
GROUNDING
(BONDING)
PLATE
TABLE 1
30A 60A 100A
Switch #4 to #12 AWG #2 to #10 AWG #2 to #10 AWG
Ground #6 to #16 AWG #4 to #10 AWG #4 to #10 AWG
Neu t r al #8 to #22 AWG #4 to #14 AWG #1/0 to #14 AWG
Auxiliary
contact
#14-18 AWG #14-18 AWG #14-18 AWG
Pilot #12-18 AWG P12-18 AWG
TABLE 2
30A 60 & 100A
Switch 27 lb•in (3.0 N•m) 50 lb•in (5.7 N•m)
Ground 16-18 lb•in (1.8-2.0 N•m) 22 lb•in (2.5 N•m)
Neut ral 13-15 lb•in (1.5-1.7 N•m) 22 lb•in (2.5 N•m)
Auxiliary
contact
10-12 lb•in (1.2-1.4 N•m) 10-12 lb•in (1.2-1.4 N•m)
Pilot 20 lb-in (2.5 N•m)
FIG. M4 • BACK FEED
(TYPE 4X INSTALLATIONS ONLY)
30 AMP 60 & 100 AMP
•
•
THIS DEVICE CARRIES A MAXIMUM RATING OF:
CA T . NOS. AMPS RATING HORSEPOWER USE PIN & SLEEVE WIRE
HBL330MI4W 30 120VAC 2 [1.5] HBL330P4W W1
HBL330MI6W 30 240VAC 3 (208-240VAC) [2.25] HBL330P6W W2
HBL330MI7W 30 480VAC 7.5 [5.62] HBL330P7W W2
HBL430MI5W 30 600VAC 3Ø 20 [15] HBL430P5W W3
HBL430MI7W 30 480VAC 3Ø 15 [11.25] HBL430P7W W3
HBL430MI9W 30 240VAC 3Ø 7.5 [5.62] HBL430P9W W3
HBL430MI12W 30 120 / 240VAC 3 (208-240VAC, L-L) [2.25] HBL430P12W W4
HBL432MI3W 32
HBL530MI5W 30 347 / 600VAC 3ØY 20 [15] HBL530P5W W5
HBL530MI7W 30 277 / 480VAC 3ØY 15 [11.25] HBL530P7W W5
HBL530MI9W 30 120 / 208VAC 3ØY 5 [3.75] HBL530P9W W5
HBL360MI4W 60 120VAC 3 [1.5] HBL360P4W W1
HBL360MI6W 60 240VAC 7.5 (208-240VAC) [5.62] HBL360P6W W2
HBL360MI7W 60 480VAC 20 [15] HBL360P7W W2
HBL460MI5W+ 60 600VAC 3Ø 40 [30] HBL460P5W W3
HBL460MI7W 60 480VAC 3Ø 30 [22.5] HBL460P7W W3
HBL460MI9W 60 240VAC 3Ø 15 [11.25] HBL460P9W W3
HBL460MI12W 60 120 / 240VAC 7.5 (208-240VAC, L-L) [5.62] HBL460P12W W4
HBL560MI5W 60 347 / 600VAC 3ØY 40 [30] HBL560P5W W5
HBL560MI7W 60 277 / 480VAC 3ØY 30 [22.5] HBL560P7W W5
HBL560MI9W 60 120 / 208VAC 3ØY 15 [11.25] HBL560P9W W5
HBL3100MI4W* 1 00 120VAC 5 [3.75] HBL3100P4W W1
HBL3100MI6W 10 0
HBL3100MI7W* 1 00 480VAC 30 [22.5] HBL3100P7W W2
HBL4100MI5W 1 00 600VAC 3Ø 50 [37.5] HBL4100P5W W3
HBL4100MI7W 1 00 480VAC 3Ø 50 [37.5] HBL4100P7W W3
HBL4100MI9W 1 00 240VAC 3Ø 25 [18.75] HBL4100P9W W3
HBL4100MI12W*100
HBL5100MI5W* 1 00 347 / 600VAC 3ØY 50 [37.5] HBL5100P5W W5
HBL5100MI7W* 1 00 277 / 480VAC 3ØY 50 [37.5] HBL5100P7W W5
HBL5100MI9W 100 120 / 208VAC 3ØY 20 [15] HBL5100P9W W5
380VAC 3Ø 50 Hz
440VAC 3Ø 60Hz
240VAC 15 [11.25]
208VAC 10 [7.5]
120/240VAC 15 [11.25]
208VAC 10 [11.25]
15 (440VAC 3 Ø 60 Hz) [11.25] HBL432P3W W3
* Consult factory for availability
[kW] PLUG CAT . NO. PER FIG .
HBL3100P6W W2
HBL4100P12W W4
GROUNDING
(BONDING)
PLATE
2 POLE 3 WIRE
SINGLE PHASE
FIG. W1
L
L1 L2 L3
T1 T2 T3
G
GREEN/YELLOW
N
WG
N
G
•
•
GROUND
BUSS
(GRN/YEL)
NEUTRAL
BUSS
(BLUE)
GROUNDING
(BONDING)
PLATE
2 POLE 3 WIRE
SINGLE PHASE
FIG. W2
L
L1 L2 L3
T1 T2 T3
G
GREEN/YELLOW
LG
L+
PD1788 (SHEET 1 of 3 • PAGE 2) PRINTED IN U.S.A. 8/06
G
•
GROUND
BUSS
(GRN/YEL)
GROUNDING
(BONDING)
PLATE
GREEN/YELLOW
3 POLE 4 WIRE
3 Ø
FIG. W3
X
L1 L2 L3
T1 T2 T3
G
L3
YZ
L2
G
G
GROUND
BUSS
•
(GRN/YEL)
L1
Pilot contact (if installed)
GROUNDING
(BONDING)
PLATE
GREEN/YELLOW
3 POLE 4 WIRE
EDISON SYSTEM
FIG. W4
L
L1 L2 L3
T1 T2 T3
G
L2
WIRING DIAGRAMS
LGW
GROUNDING
(BONDING)
G
N
GROUND
BUSS
•
•
(GRN/YEL)
NEUTRAL
BUSS
(BLUE)
N
L1
PLATE
4 POLE 5 WIRE
3 Ø Y
FIG. W5
X
L1 L2 L3
T1 T2 T3
G
GREEN/YELLOW
L3
N
YZ
L2
L1
WG
G
N
•
•
GROUND
BUSS
(GRN/YEL)
NEUTRAL
BUSS
(BLUE)