Hubbell 67L Installation Instructions Manual

INSTALLATION INSTRUCTIONS
AIRCRAFT
FEED
CABLE
FIXTURE LENGTH MINUS .75"
AIRCRAFT CABLE
.38" TYP
MOUNTING TYPE: AIRCRAFT CABLES
PAGE: 1 OF 3
CEILING REFERENCE
FEED
.38" TYP
END CAP
AIRCRAFT CABLE
END CAP
SIDE VIEW - INDIVIDUALLY MOUNTED
FIXTURE LENGTH MINUS .75"
AIRCRAFT CABLE
AIRCRAFT CABLE
END CAP FIXTURE LENGTH
(24", 36", 48", 72", OR 96")
AIRCRAFT CABLE
FIXTURE LENGTH
AIRCRAFT CABLE
END CAP
2.00"
3.69"
BELL LENS SHOWN
SIDE VIEW - ROW MOUNTED
GENERAL NOTES: (READ SHEETS COMPLETELY BEFORE STARTING)
1. LEAVE PROTECTIVE WRAPPING ON FIXTURE(S) UNTIL START OF INSTALLATION.
2. FIXTURES ARE SUPPLIED WITH FACTORY-INSTALLED BRANCH CIRCUIT WIRING. REFER TO SUPPLEMENTAL INSTRUCTION SHEET WEHN MAKING CONNECTIONS.
3. APPROXIMATE WEIGHT OF FIXTURE IS 2 LBS PER FOOT OF LENGTH.
4. REFER TO PAGE 3 FOR LENS INSTALLATION/REMOVAL INSTRUCTIONS.
DO NOT MODIFY OR ALTER THIS PRODUCT IN ANY WAY, OR INSTALL IN ANY FASHION WHICH IS CONTRARY TO THE INSTRUCTIONS CONTAINED HEREIN.
litecontrol.com
IF YOU HAVE ANY QUESTIONS REGARDING THIS PRODUCT OR THE INSTALLATION OF IT, PLEASE CALL LITECONTROL ENGINEERING AT 781-294-0100.
TOOLS REQUIRED
- SCREWDRIVER/DRILL
- 11/32" NUT DRIVER
3.56"
CROSS SECTION VIEW
SUPPLIED BY INSTALLER
DRAWING: 510641 REV / DATE: 0 / 1/16/2019
INSTALLATION INSTRUCTIONS
REMOVE LENS, REFERRING TO PAGE 3. LOCATE AIRCRAFT CABLES ALONG
1
STRAIGHT LINE IN CEILING PER DIMENSIONS SHOWN ON PAGE 1. REFER TO CABLE INSTRUCTION SHEET 510541 FOR ATTACHMENT TO CEILING.
FIXTURE SERIES: 67L
2
MOUNTING TYPE: AIRCRAFT CABLES
PAGE: 2 OF 3
INSERT FLAT STRAP INTO CHANNEL IN HOUSING (MARKED IN BLUE). INSERT CABLE GRIPPER THROUGH HOUSING AND THREAD INTO FLAT STRAP. REPEAT AT EACH CABLE LOCATION.
AT END OF FIXTURE, INSERT FLAT STRAP COMPLETELY INTO HOUSING SUCH THAT CABLE GRIPPER IS THREADED INTO HOLE A. AT FIXTURE JOINT, INSERT FLAT STRAP PARTIALLY SUCH THAT HOLE B IS USED.
IF INSTALLING INDIVIDUAL FIXTURE: LEVEL
3 4
FIXTURE BY SLIDING CABLE GRIPPERS UP/DOWN. SKIP TO STEP 5.
FLAT STRAP
CABLE GRIPPER
B
FLAT STRAP
A
RAISE FIXTURE (1ST FIXTURE OF ROW) UP TO CEILING. ATTACH TO AIRCRAFT CABLE
REMOVE 5/8" PLUG BUTTON AT FEED LOCATION. INSERT UNIVERSAL BUSHING INTO FEED HOLE AND ROUTE FEED CORD THROUGH BUSHING INTO FIXTURE WIREWAY. MAKE ELECTRICAL CONNECTIONS.
5
#8 SMS
FEED CORD
BUSHING
5/8" FEED HOLE (PLUG REMOVED)
END CAP
1/4-20 MS
RAISE NEXT FIXTURE IN ROW; ATTACH TO AIRCRAFT CABLE IN CEILING. ROUTE WIRING THROUGH FIXTURE JOINT AS SHOWN. INSERT PROTRUDING FLAT STRAP OF PREVIOUS FIXTURE INTO CHANNEL OF NEW FIXTURE. SECURE BY INSERTING 1/4-20 MACHINE SCREW THROUGH HOUSING TOP AND FLAT STRAP.
litecontrol.com
DO NOT MODIFY OR ALTER THIS PRODUCT IN ANY WAY, OR INSTALL IN ANY FASHION WHICH IS CONTRARY TO THE INSTRUCTIONS CONTAINED HEREIN. IF YOU HAVE ANY QUESTIONS REGARDING THIS PRODUCT OR THE INSTALLATION OF IT, PLEASE CALL LITECONTROL ENGINEERING AT 781-294-0100.
NUT
(LED REFLECTOR MODULES HIDDEN
8-32 MS
SECURE JOINT USING (2) 8-32 MACHINE SCREWS AND NUTS. DO NOT TIGHTEN UNTIL FIXTURES ARE ALIGNED; LEVEL BY SLIDING CABLE GRIPPERS UP/DOWN. REPEAT STEPS 3-4 FOR EACH ADDITIONAL FIXTURE IN ROW.
FOR CLARITY.)
ATTACH END CAP AT BOTH ENDS OF FIXTURE OR ROW OF FIXTURES USING (2) #8 X 1/4" LONG SHEET METAL SCREWS. ENSURE END CAP IS FLUSH WITH HOUSING WALLS.
CLEAN FIXTURE EXTERIORS WITH GENERAL WINDOW CLEANER. REATTACH LENS PER PAGE 3.
DRAWING: 510641 REV / DATE: 0 / 1/16/2019