Huawei UPS2000-G-1KRTS, UPS2000-G-1KRTL, UPS2000-G-2KRTS, UPS2000-G-2KRTL, UPS2000-G-3KRTS Quick Manual

...
Page 1
0
HUAWEI TECHNOLOGIES CO., LTD.
UPS2000-G-(1 kVA-3 kVA)
Quick Guide
Issue: 05 Date: 2017-07-21
Page 2
1
UPS2000-G-1KRTS
1 K
-standard model-rack
mounted
-IEC
10.7 kg 88 mm x 438 mm x 310 mm
UPS2000-G-1KRTL
1 K
-long backup time
model
-rack mounted-IEC
5.9 kg 88 mm x 438 mm x 310 mm
UPS2000-G-2KRTS
2 K
-standard model-rack
mounted
-IEC
18.5 kg 88 mm x 438 mm x 410 mm
UPS2000-G-2KRTL
2 K
-long backup time
model
-rack mounted-IEC
8.6 kg 88 mm x 438 mm x 410 mm
UPS2000-G-3KRTS
3 K
-standard model-rack
mounted
-IEC
27. 9 kg 88 mm x 438 mm x 630 mm
UPS2000-G-3KRTL
3 K
-long backup time
model
-rack mounted-IEC
9.2 kg 88 mm x 438 mm x 410 mm
1
Introduction
UPS2000-G-1KRTS
UPS2000-G-1KRTL
UPS2000-G-2KRTS
UPS2000-G-2KRTL
(1) Mains input socket
(C14)
(2) Input circuit breaker
(3) Universal serial bus
(USB) port (security protection mechanism supported)
(4) RS232 port
(5)
Optional card slot
(6) Output socket (C13)
(7) External battery
connector (only for long backup time models)
Copyright © Huawei Technologies Co., Ltd. 2017. All rights reserved.
(1) Mains input socket
(C14)
(2) Input circuit breaker
(3)
USB port (security protection mechanism supported)
(4) RS232 port
(5)
Optional card slot
(6) Output socket (C13)
(7) External battery
connector (only for long backup time models)
Page 3
2
UPS2000-G-3KRTS
UPS2000-G-3KRTL
(1) Mains input socket
(C20)
(2) Input circuit breaker
(3)
USB port (security protection mechanism supported)
(4) RS232 port
(5)
Optional card slot
(6) Output socket (C13)
(7
) Output socket (C19)
(8) External battery
connector (only for long backup time models)
UPS2000-G Rack-mounting Installation
Scenario 1
1. Before installation, read the UPS2000-G-(1 kVA-3 kVA) User Manual to get familiar with UPS information and safety precautions. UPS is short for uninterruptible power system.
2. Use fully insulated tools during installation and operations.
3. Only engineers certified by the manufacturer or its agents are allowed to perform UPS installation, commissioning and maintenance. Otherwise, personal injury or equipment damage may occur, and the resulting UPS faults are beyond warranty scope.
1. Install mounting brackets on UPS.
2. Install guide on the Cabinet. Then place the UPS on the guide rails. For details about how to install guide and UPS on the cabinet, see the UPS2000-G-(1 kVA-3 kVA) Rail Assembly Quick
Installation Guide.
NOTICE
2
Installing a Single UPS
UPS2000-G Tower-mounting Installation
Scenario 2
To tower-mount a UPS, perform the following steps:
1. Remove the UPS front panel.
2. Rotate the control panel 90 degrees clockwise.
3. Rotate the logo 90 degrees clockwise on the front panel. Reinstall the front panel.
4. Assemble support bases. The minimum distance between two support bases should be 150 mm.
5. Place UPS on the support bases in sequence.
6. Adjust the UPS and the support bases to be horizontally.
Page 4
UPS load
UPS2000-G-1KRTS
UPS load
UPS2000-G-1KRTL
UPS load
UPS2000-G-2KRTS
3
3
Installing Cables
For socket-type output, connect loads to the UPS output sockets
Installing the UPS Output Power Cables
3.1
Page 5
4
Connect the battery cable delivered with the long backup time model to an external battery pack. (This step is optional for the long backup time model. The standard model contains batteries and provides no battery port.) The installation method for 1 kVA UPS, 2 kVA UPS, and 3 kVA UPS is the same. The figures
below are based on the 3 kVA UPS.
For details, see the UPS2000-G-(1 kVA-3 kVA) Battery Pack Quick Installation Guide.
Installing the UPS Battery Cable (Only for UPS with Long Backup Time)
3.2
UPS load
UPS2000-G-3KRTS
UPS2000-G-3KRTL
UPS load
UPS2000-G-2KRTL
UPS load
1. If the 1 kVA UPS with long backup time needs to connect to external battery strings, each battery string must consist of three 12 V batteries connected in series. If the 2 kVA UPS with long backup time needs to connect to external battery strings, each battery string must consist of six 12 V batteries connected in series. If the 3 kVA UPS with long backup time needs to connect to external battery strings, each battery string must consist of eight 12 V batteries connected in series.
2. The UPS with long backup time provides a charge current of 4 A and the current is not configurable. If the UPS needs to connect to battery packs or battery strings, the total battery capacity must exceed 18 Ah. Otherwise, batteries may be damaged. If the capacity of external battery packs or battery strings to be connected exceeds 40 Ah, it is recommended that an external charger be purchased to increase the charge current. If an external chargers is not purchased, the charge time will be long.
3. The battery pack (ESS-36V12-9*2AHBPVBB01) for 1 kVA UPS with long backup time contain
two group battery strings. The battery pack (ESS-72V12-9AHBPVBB01) for 2 kVA UPS with
long backup time only contain one group battery strings. The battery pack (ESS-96V12­9AHBPVBB02) for 3 kVA UPS with long backup time only contain one group battery strings.
4. The 1 kVA UPS with long backup time is allowed a maximum of two battery packs (ESS-36V12­9*2AHBPVBB01) in parallel. The 2 kVA UPS with long backup time is allowed a maximum of four battery packs (ESS-72V12-9AHBPVBB01) in parallel. The 3 kVA UPS with long backup time is allowed a maximum of four battery packs (ESS-96V12-9AHBPVBB02) in parallel.
Page 6
5
Connect the UPS to the RS232 or USB port on a PC. Then you can monitor the UPS status using the PC as long as you have installed the monitoring software. The installation method for 1 kVA
UPS, 2 kVA UPS, and 3 kVA UPS is the same. The figures below based on the 3 kVA UPS.
Installing the UPS Communication Cable
3.3
1. The USB channel supports a serial data communications protocol between the UPS and the PC.
2. If you connect a DB9 connector to the RS232 port, the UPS can communicate with the PC over
serial data.
3. The UPS support either USB or RS232.
4. To monitor the UPS over a PC, also need to install the monitoring software iManager NetEco 1000U. For details about how to install and use the iManager NetEco 1000U, see the iManager NetEco 1000U User Manual. The software and the user manual are available at
http://support.huawei.com or http://support.huawei.com/enterprise.
PC
PC
UPS2000-G-3KRTS
PC PC
UPS2000-G-3KRTL
Battery pack
UPS2000-G-3KRTL
Installing the UPS Input Cable
3.4
Mains input
UPS2000-G-1KRTS
Take out input power cable from the fitting bag, and connect mains input power cable to the UPS.
UPS2000-G-1KRTL
Mains input
Page 7
6
UPS2000-G-3KRTS
Mains input
For the installation procedure, see the RMS-SNMP01B SNMP Card User Manual, RMS-RELAY01B
User Manual, RMS-MODBUS01B User Manual. The installation method for 1 kVA, 2 kVA UPS, and
3 kVA UPS is the same. The figures below are based on the 3 kVA UPS.
4
Installing the Optional Card to the UPS
No. Item Acceptance Criterion
1 Cable routing Cable routing meets engineering requirements. 2 Cable connections Power cables and battery cables are tightened to
specified torques using a torque wrench, connected correctly, and free of damage.
3 Cable connections for USB ports and
network ports
Cables to USB ports and network ports are connected correctly and securely.
4 Labels Labels are neatly attached to both ends of each
cable, and the information on the labels is concise and understandable.
5 Ground cable connection and
upstream circuit breaker for the UPS
The ground cable is securely connected to the ground bar in the equipment room. An upstream circuit breaker of proper specifications is installed on the UPS input end.
6 Distances between cable ties Distances between cable ties are the same, and
no burr exists.
7 Operating environment Clean the conductive air and other sundries.
Verifying the Installation
5
Optional Card
UPS2000-G-3KRTS UPS2000-G-3KRTL
Optional Card
UPS2000-G-3KRTL
Mains input
Mains input
UPS2000-G-2KRTS UPS2000-G-2KRTL
Mains input
Page 8
7
Operations
6
ON/MUTE SELECT OFF/ENTER
Setting Key UPS Parameters
6.1
1. The 1 kVA UPS with standard backup time have two built-in batteries, the 2 kVA UPS with
standard backup time have four built-in batteries, the 3 kVA UPS with standard backup time
have six built-in batteries.
2. If the 1 kVA UPS with long backup time needs to connect to external battery strings, each battery string must consist of three 12 V batteries connected in series. If the 2 kVA UPS with long backup time needs to connect to external battery strings, each battery string must consist of six 12 V batteries connected in series. If the 3 kVA UPS with long backup time needs to connect to external battery strings, each battery string must consist of eight 12 V batteries connected in series.
3. The UPS with long backup time provides a charge current of 4 A and the current is not configurable. If the UPS needs to connect to battery packs or battery strings, the total battery capacity must exceed 18 Ah. Otherwise, batteries may be damaged. If the capacity of external battery packs or battery strings to be connected exceeds 40 Ah, it is recommended that an external charger be purchased to increase the charge current. If an external charger is not purchased, the charge time will be long.
4. For the UPS with standard backup time, the battery capacity has a fixed value of 9 Ah and the
charge current has a fixed value of 1 A. Set the battery capacity to the total capacity of all batteries actually connected. Set the battery capacity for the long backup time model based on site requirements. The default value is 7 Ah. For example, if eight batteries (9 Ah, 12 V) are connected in series to form a battery string, and two of such battery strings are connected in parallel and then to the UPS, set battery capacity to 18 Ah (9 Ah + 9 Ah). This parameter affects the backup time calculation. Incorrect setting will cause incorrect display of the backup time on the LCD.
5. When the battery pack/batteries connect to the Long back-up UPS for the first time, you must do a battery self-check manually, in order to confirm the battery connection is normal. The method is: hold down ON/MUTE on the front panel for 5 seconds, then the UPS transfer to battery mode to do a shallow discharge test, after 10 seconds it automatically back to line mode.
6. Charge the batteries used for the first time for 5 hours. Otherwise, the battery discharge time will decrease.
NOTICE
Page 9
8
If this is the initial startup, set system parameters such as output voltage, output frequency, and battery parameters as required.
1. After power on the UPS, hold down SELECT for 5 seconds. The UPS enters the preset mode.
2. In the preset mode, press SELECT for more than 3 seconds is used to select the next option, press ON/MUTE for more than 3 seconds is used to select a previous option, and press OFF/ENTER for more than 3 seconds is used to confirm your selection. The meaning of LCD display character see the 7.1 Character Display Description in page 9. Set voltage level to 200
V, 208 V, 220 V, 230 V (default), or 240 V. Set output frequency level to 50 Hz, 60 Hz, and AUT
(default). The battery capacity for the UPS with standard backup time cannot be changed. The default value of battery capacity is 7 Ah for the UPS with long backup time, and the value can range from 0 Ah to 999 Ah.
For more parameters setting information, see the UPS2000-G-(1 kVA-3 kVA) User Manual.
1. In the preset mode, LCD will return to the main page with 10 seconds of no operation.
2. If the long backup time model is not connected to an external battery pack, the buzzer keeps
buzzing.
3. The UPS performs a battery self-check automatically once a week. If batteries are faulty, an
alarm is generated.
Starting the UPS to Inverter Mode
6.2
When the UPS is connected to the Mains Input, it is no output. Hold down ON/MUTE on the front panel for over 5 seconds to make it transfer to inverter mode output. The default output of inverter mode is 230 V.
Shutting down the UPS
6.3
Normal Mode: If the UPS is originally in normal mode, hold down OFF/ENTER for over 2 seconds will enable the UPS to enter the standby mode or bypass mode (if set or enabled before).
Battery mode: Hold down OFF/ENTER for over 2 seconds to turn off the UPS in battery mode.
Page 10
9
Acronym
Display
Description
Acronym
Display
Description
ENA
Enable
FRE
Frequency
DIS
Disable
BVU
Bypass overvoltage
ESC
Escape
BVL
Bypass undervoltage
CF
Frequency conversion
CAP
Capacity
TP
Temperature
DT
Discharge time
CH
Charging
ECO
ECO mode
FU
Bypass frequency unstable
VU
High voltage
EE
EEPROM error
VL
Low voltage
VOT
Voltage
AUT
Constant-frequency
mode
BUZ
Buzzer off
AST
Automatic startup
Alarm
type
Buzzer alarm tone
Battery mode
Beeps once every 4 seconds.
Minor alarm
Beeps once every second.
Overload
Beeps twice every second.
Critical alarm
Buzzes continuously.
Bypass mode
Beeps once every 10 seconds.
7
FAQ
Character Display Description
7.1
Buzzer Alarm Tone Description
7.2
Page 11
10
Symptom
Possible Cause
Measures
The main power is
normal, but no indicator
turns on and the buzzer generates no tone.
The mains input power cable is
disconnected.
Check the input power cable.
The mains input power cable is incorrectly connected to the UPS output end.
Correctly connect the mains input power cable to the UPS input terminal.
and blink on the
LCD and the buzzer beeps once every second.
The external or internal batteries are incorrectly connected.
Check that all batteries are connected correctly.
and blink on the
LCD and the buzzer beeps twice every second.
The UPS is overloaded.
Remove surplus load from the UPS output end.
The UPS is overloaded and supplying power to devices in bypass mode.
Remove surplus load from the UPS output end.
The UPS is overloaded server times
within a short period of time. The
UPS is locked in bypass mode and loads are directly connected to the main power source.
Remove surplus load from the UPS
output end, and then shut down
and restart the UPS.
The battery backup time is shorter than the time given in specifications.
Batteries are not fully charged.
Charge batteries for at least 5 hours and then check the battery capacity. If the battery capacity is still insufficient, contact the dealer.
Batteries are faulty.
Contact the dealer to replace batteries.
8
Troubleshooting
Page 12
11
For more alarm handling, see the UPS2000-G-(1 kVA-3 kVA) User Manual.
Ala rm ID
Ala rm Cau se
ID
Alarm Name
Alarm
Sever ity
Alarm Clear Mode
Trigger Condition
Impact on the System
Repair Proposal
10 1 Bypass
voltage abnorm al
Minor This
alarm is automatic ally cleared.
The bypass voltage is outside the scope.
The UPS remains in the current state. If the UPS works in
bypass mode,
it transfers to standby mode and has no output.
Possible causes: The bypass input voltage is abnormal. Measures: Check
whether the bypass
input voltage exceeds the
configured range. If
yes, change the range or wait until the bypass input recovers.
2 Bypass
frequen cy abnorm al
Minor This
alarm is automatic ally cleared.
The bypass frequency is outside the bypass frequency
range.
The UPS remains in the current state. If the UPS works in bypass mode,
it transfers to
standby mode and has no output.
Possible causes: The bypass input frequency is abnormal. Measures: Check
whether the bypass
input frequency
exceeds the
configured range. If
yes, change the range or wait until the bypass input recovers.
22 1 Battery
disconn ected
Minor This
alarm is automatic ally cleared.
Batteries are not connected, connected improperly, or damaged.
The power supply from the UPS is not affected.
Possible cause: No batteries are connected.
Measure:
Connect batteries.
Possible cause:
The batteries
are in poor contact.
Measure
: Check
the battery cable connection. If battery cables are loose, connect them securely.
9
Alarm Handling
Page 13
12
Ala
rm ID
Ala
rm Cau se ID
Alarm
Name
Alarm
Severit y
Alarm
Clear Mode
Trigger
Conditi on
Impact on the
System
Repair Proposal
25 1 Battery
overvol tage
Critical This
alarm must be manu ally cleare d.
The voltage of each battery
exceeds
15 V (when
the UPS
is started).
This alarm is generated because there are more batteries than required. The impact is as follows:
If battery packs are connected before the
startup, the UPS
fails to start.
If battery packs are connected during the
running of the
UPS, the UPS transfers to bypass mode.
Possible cause: The actual number of batteries does not meet requirements. Measure: Check that the actual number of batteries meets requirements.
Possible cause: The charger is abnormal.
Measure: Check
that the charger voltage is normal immediately after the batteries are disconnected.
Minor This
alarm is autom aticall y cleare
d after
the UPS transf ers to batter y mode.
The voltage of each battery
exceeds
14.7 V.
The UPS automatically transfers to battery mode. When the battery undervoltage alarm is generated, the
UPS automatically
transfers to normal
mode and starts the
charger for charging.
26 1 Battery
underv
oltage
Critical This
alarm
must
be manu ally cleare d.
The voltage
of each
battery is lower
than 5 V
(when
the UPS
is started).
This alarm is generated because
there are more
batteries than required. The impact is as follows:
If battery packs are connected before the
startup, the UPS
fails to start.
If battery packs are connected during the running of the UPS, the UPS transfers to
bypass mode.
Possible cause: The actual
number of
batteries does not meet requirements. Measure: Check that the actual number of batteries meets requirements.
Possible cause: The mains is
abnormal, and the
batteries are overdischarged.
Measure: Connect
to the mains in
non-battery test state.
Page 14
13
Ala rm ID
Ala rm Cau
se
ID
Alarm Name
Alar m Seve
rity
Alarm
Clear Mode
Trigger Condition
Impact on the System
Repair Proposal
26 1 Battery
underv oltage
Minor This
alarm is autom aticall y cleare d.
The voltage of
each battery is
lower than
11.28 V.
The power supply
from the UPS is not affected.
Possible cause: The actual number of batteries does not meet requirements.
Measure: Check
that the actual number of batteries meets
requirements.
Possible cause: The mains is abnormal, and
the batteries are
overdischarged.
Measure:
Connect to the mains in non­battery test state.
29 1 Battery
requirin
g mainte nance
Minor This
alarm
is autom aticall y cleare d.
The battery
voltage is
lower than the battery replacement voltage (11 V)
when batteries
are in self­check mode.
The power supply
from the UPS is
not affected.
Possible cause:
The actual
number of batteries does not meet requirements.
Measure: Check
that the actual number of batteries meets requirements.
Possible cause: The battery is damaged.
Measure:
Contact the
dealer or Huawei technical support to replace batteries.
Minor This
alarm is autom aticall y cleare d.
The voltage of
each battery is
lower than 5 V, or is higher than 15 V (when the UPS is not started).
The UPS remains
in the current state and cannot start.
Page 15
14
Ala rm ID
Ala rm Cau se ID
Alarm Name
Alar m Seve rity
Alarm
Clear Mode
Trigger Condition
Impact on the System
Repair Proposal
42 17
Internal
fault
CriticalThis
alarm must be manu ally cleare d.
The bus voltage is higher than 450 V.
If this alarm is generated during the running of the UPS, the UPS transfers to bypass mode.
Possible cause: The mains has experienced a transient high voltage. Measure: Rectify the fault and restart the UPS.
Possible
cause: The
output supplies power to special loads such as the inductive and rectification loads.
Measure:
Check that the
load types are supported by the UPS.
Possible
cause: The hardware is damaged.
Measure:
Contact the dealer or Huawei technical support.
For more information, refer to the channels provided on the following page.
Page 16
Scan here for more documents:
You can also log in to Huawei technical support website: http://support.huawei.com/enterprise http://support.huawei.com
SupportSupport-E WeChat
Apple Store
Google Play
Scan here for technical support (enterprise):
Scan here for technical support (carrier):
Apple Store
Google Play Huawei App Store
Huawei App Store
HUAWEI TECHNOLOGIES CO., LTD.
Huawei Industrial Base, Bantian, Longgang
Shenzhen 518129
People's Republic of China
www.huawei.com
Loading...