Huawei UPS2000-G-1KRTS, UPS2000-G-1KRTL, UPS2000-G-2KRTS, UPS2000-G-2KRTL, UPS2000-G-3KRTS Quick Manual

...
0
HUAWEI TECHNOLOGIES CO., LTD.
UPS2000-G-(1 kVA-3 kVA)
Quick Guide
Issue: 05 Date: 2017-07-21
1
UPS2000-G-1KRTS
1 K
-standard model-rack
mounted
-IEC
10.7 kg 88 mm x 438 mm x 310 mm
UPS2000-G-1KRTL
1 K
-long backup time
model
-rack mounted-IEC
5.9 kg 88 mm x 438 mm x 310 mm
UPS2000-G-2KRTS
2 K
-standard model-rack
mounted
-IEC
18.5 kg 88 mm x 438 mm x 410 mm
UPS2000-G-2KRTL
2 K
-long backup time
model
-rack mounted-IEC
8.6 kg 88 mm x 438 mm x 410 mm
UPS2000-G-3KRTS
3 K
-standard model-rack
mounted
-IEC
27. 9 kg 88 mm x 438 mm x 630 mm
UPS2000-G-3KRTL
3 K
-long backup time
model
-rack mounted-IEC
9.2 kg 88 mm x 438 mm x 410 mm
1
Introduction
UPS2000-G-1KRTS
UPS2000-G-1KRTL
UPS2000-G-2KRTS
UPS2000-G-2KRTL
(1) Mains input socket
(C14)
(2) Input circuit breaker
(3) Universal serial bus
(USB) port (security protection mechanism supported)
(4) RS232 port
(5)
Optional card slot
(6) Output socket (C13)
(7) External battery
connector (only for long backup time models)
Copyright © Huawei Technologies Co., Ltd. 2017. All rights reserved.
(1) Mains input socket
(C14)
(2) Input circuit breaker
(3)
USB port (security protection mechanism supported)
(4) RS232 port
(5)
Optional card slot
(6) Output socket (C13)
(7) External battery
connector (only for long backup time models)
2
UPS2000-G-3KRTS
UPS2000-G-3KRTL
(1) Mains input socket
(C20)
(2) Input circuit breaker
(3)
USB port (security protection mechanism supported)
(4) RS232 port
(5)
Optional card slot
(6) Output socket (C13)
(7
) Output socket (C19)
(8) External battery
connector (only for long backup time models)
UPS2000-G Rack-mounting Installation
Scenario 1
1. Before installation, read the UPS2000-G-(1 kVA-3 kVA) User Manual to get familiar with UPS information and safety precautions. UPS is short for uninterruptible power system.
2. Use fully insulated tools during installation and operations.
3. Only engineers certified by the manufacturer or its agents are allowed to perform UPS installation, commissioning and maintenance. Otherwise, personal injury or equipment damage may occur, and the resulting UPS faults are beyond warranty scope.
1. Install mounting brackets on UPS.
2. Install guide on the Cabinet. Then place the UPS on the guide rails. For details about how to install guide and UPS on the cabinet, see the UPS2000-G-(1 kVA-3 kVA) Rail Assembly Quick
Installation Guide.
NOTICE
2
Installing a Single UPS
UPS2000-G Tower-mounting Installation
Scenario 2
To tower-mount a UPS, perform the following steps:
1. Remove the UPS front panel.
2. Rotate the control panel 90 degrees clockwise.
3. Rotate the logo 90 degrees clockwise on the front panel. Reinstall the front panel.
4. Assemble support bases. The minimum distance between two support bases should be 150 mm.
5. Place UPS on the support bases in sequence.
6. Adjust the UPS and the support bases to be horizontally.
UPS load
UPS2000-G-1KRTS
UPS load
UPS2000-G-1KRTL
UPS load
UPS2000-G-2KRTS
3
3
Installing Cables
For socket-type output, connect loads to the UPS output sockets
Installing the UPS Output Power Cables
3.1
4
Connect the battery cable delivered with the long backup time model to an external battery pack. (This step is optional for the long backup time model. The standard model contains batteries and provides no battery port.) The installation method for 1 kVA UPS, 2 kVA UPS, and 3 kVA UPS is the same. The figures
below are based on the 3 kVA UPS.
For details, see the UPS2000-G-(1 kVA-3 kVA) Battery Pack Quick Installation Guide.
Installing the UPS Battery Cable (Only for UPS with Long Backup Time)
3.2
UPS load
UPS2000-G-3KRTS
UPS2000-G-3KRTL
UPS load
UPS2000-G-2KRTL
UPS load
1. If the 1 kVA UPS with long backup time needs to connect to external battery strings, each battery string must consist of three 12 V batteries connected in series. If the 2 kVA UPS with long backup time needs to connect to external battery strings, each battery string must consist of six 12 V batteries connected in series. If the 3 kVA UPS with long backup time needs to connect to external battery strings, each battery string must consist of eight 12 V batteries connected in series.
2. The UPS with long backup time provides a charge current of 4 A and the current is not configurable. If the UPS needs to connect to battery packs or battery strings, the total battery capacity must exceed 18 Ah. Otherwise, batteries may be damaged. If the capacity of external battery packs or battery strings to be connected exceeds 40 Ah, it is recommended that an external charger be purchased to increase the charge current. If an external chargers is not purchased, the charge time will be long.
3. The battery pack (ESS-36V12-9*2AHBPVBB01) for 1 kVA UPS with long backup time contain
two group battery strings. The battery pack (ESS-72V12-9AHBPVBB01) for 2 kVA UPS with
long backup time only contain one group battery strings. The battery pack (ESS-96V12­9AHBPVBB02) for 3 kVA UPS with long backup time only contain one group battery strings.
4. The 1 kVA UPS with long backup time is allowed a maximum of two battery packs (ESS-36V12­9*2AHBPVBB01) in parallel. The 2 kVA UPS with long backup time is allowed a maximum of four battery packs (ESS-72V12-9AHBPVBB01) in parallel. The 3 kVA UPS with long backup time is allowed a maximum of four battery packs (ESS-96V12-9AHBPVBB02) in parallel.