Huawei UPS2000-G-6KRTS, UPS2000-G-6KRTL, UPS2000-G-10KRTS, UPS2000-G-10KRTL, UPS2000-G-15KRTL User Manual

...
Page 1
User Manual
Issue
10
Date
2017-01-19
HUAWEI TECHNOLOGIES CO., LTD.
Page 2
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
i
Copyright © Huawei Technologies Co., Ltd. 2017. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd.
Trademarks and Permissions
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS" without warranties, guarantees or representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the preparation of this document to ensure accuracy of the contents, but all statements, information, and recommendations in this document do not constitute a warranty of any kind, express or implied.
Huawei Technologies Co., Ltd.
Address:
Huawei Industrial Base Bantian, Longgang Shenzhen 518129 People's Republic of China
Website:
http://e.huawei.com
Page 3
UPS2000-G-(6 kVA-20 kVA) User Manual
About This Document
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
ii
About This Document
Purpose
This document describes the UPS2000-G-(6 kVA–20 kVA) in terms of features, performance, appearance, structure, working principle, installation, operation, and maintenance. UPS is short for uninterruptible power system.
Intended Audience
This document is intended for:
Sales Engineer
Technical Support Engineer
System Engineer
Hardware Installation Engineer
Commissioning Engineer
Data Configuration Engineer
Maintenance Engineer
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol
Description
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
Indicates a potentially hazardous situation which, if not avoided, could result in equipment damage, data loss, performance deterioration, or unanticipated results.
Page 4
UPS2000-G-(6 kVA-20 kVA) User Manual
About This Document
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
iii
Symbol
Description
NOTICE is used to address practices not related to personal injury.
Calls attention to important information, best practices and tips.
NOTE is used to address information not related to personal injury, equipment damage, and environment deterioration.
Change History
Changes between document issues are cumulative. The latest document issue contains all the changes made in earlier issues.
Issue 10 (2017-01-19)
Added the DHCP feature.
Added an external dry contact card.
The default value of Max. current parameter changed to 2.0 A.
Issue 09 (2016-10-10)
The software is upgraded.
Issue 08 (2016-01-06)
The software is upgraded.
Issue 07 (2015-03-30)
The alarm handling is upgraded.
Issue 06 (2014-10-09)
Added the shutdown delay parameter.
Issue 05 (2014-07-31)
Upgraded the Optional Components.
Issue 04 (2013-11-06)
Added the description of Checking Before Powering On the UPS
Issue 03 (2013-08-24)
Added the description of the UPS2000-G-15 kVA/20 kVA three-phase input single-phase output and single-phase input single-phase output.
Page 5
UPS2000-G-(6 kVA-20 kVA) User Manual
About This Document
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
iv
Issue 02 (2013-06-10)
The software is upgraded.
Issue 01 (2013-05-15)
This is the first release.
Page 6
UPS2000-G-(6 kVA-20 kVA) User Manual
Contents
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
v
Contents
About This Document .................................................................................................................... ii
1 Safety Precautions ......................................................................................................................... 1
1.1 General Safety .............................................................................................................................................................. 1
1.2 Electrical Safety ................................ ................................................................ ............................................................ 3
1.3 Operating Environment................................................................................................................................................. 6
1.4 Battery .......................................................................................................................................................................... 7
1.5 Mechanical Safety ........................................................................................................................................................ 9
1.6 Laying Out Cables ...................................................................................................................................................... 11
2 UPS2000-G-(6kVA-20kVA) Quick Introduction ................................................................... 12
2.1 Model Description ...................................................................................................................................................... 12
2.2 Working Principle ....................................................................................................................................................... 13
2.2.1 Conceptual Diagram ................................................................................................................................................ 13
2.2.2 Working Modes ........................................................................................................................................................ 13
2.3 Appearance ................................................................................................................................................................. 14
2.4 Optional Components ................................................................................................................................................. 18
3 Installation.................................................................................................................................... 25
3.1 Preparations ................................................................................................................................................................ 25
3.1.1 Site ........................................................................................................................................................................... 25
3.1.2 Tools ........................................................................................................................................................................ 27
3.1.3 Power Cables ........................................................................................................................................................... 28
3.1.4 Unpacking and Checking ......................................................................................................................................... 33
3.2 Single UPS/Parallel System Installation ..................................................................................................................... 34
3.3 Installing a Backfeed Protection Device ..................................................................................................................... 34
3.3.1 Feedback Prevention Connections (With Dry Contract Control) ............................................................................. 36
3.4 Check After Installation .............................................................................................................................................. 39
4 Control Panel ............................................................................................................................... 41
4.1 Introduction ................................................................................................................................................................ 41
4.2 Indicators .................................................................................................................................................................... 41
4.3 Functional Buttons ...................................................................................................................................................... 42
4.4 LCD ................................................................................................................................ ............................................ 43
4.5 LCD Startup Screens .................................................................................................................................................. 43
Page 7
UPS2000-G-(6 kVA-20 kVA) User Manual
Contents
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
vi
4.5.1 Starting the UPS in Normal Mode ........................................................................................................................... 45
4.5.2 Starting the UPS in Battery Mode ........................................................................................................................... 46
4.6 LCD Menu Hierarchy ................................................................................................ ................................................. 47
4.6.1 Status Screen ............................................................................................................................................................ 49
4.6.2 Alarms Screen .......................................................................................................................................................... 53
4.6.3 Settings Screen......................................................................................................................................................... 55
4.6.4 Control Screen ......................................................................................................................................................... 68
4.6.5 About Screen ............................................................................................................................................................ 71
5 Operations .................................................................................................................................... 73
5.1 Checking Before Powering On the UPS ..................................................................................................................... 73
5.2 Single UPS Operations ............................................................................................................................................... 73
5.2.1 Starting the UPS....................................................................................................................................................... 73
5.2.2 Shutting down the UPS ............................................................................................................................................ 76
5.2.3 Performing EPO ....................................................................................................................................................... 77
5.3 Parallel System Operations ......................................................................................................................................... 77
5.3.1 Starting the Parallel System ..................................................................................................................................... 78
5.3.2 Shutting down the Parallel System .......................................................................................................................... 81
5.3.3 Performing EPO ....................................................................................................................................................... 82
6 Communications ......................................................................................................................... 83
6.1 Optional Communications Components ..................................................................................................................... 83
6.2 SNMP Card ................................................................................................................................................................. 83
6.3 Modbus Card .............................................................................................................................................................. 84
6.4 Dry Contact Card ........................................................................................................................................................ 84
6.5 External Dry Contact Card ......................................................................................................................................... 84
7 Routine Maintenance ................................................................................................................. 85
7.1 UPS Maintenance ....................................................................................................................................................... 85
7.2 Battery Maintenance ................................................................................................................................................... 86
8 Troubleshooting .......................................................................................................................... 91
9 Technical Specifications ............................................................................................................ 93
9.1 Physical Specifications ............................................................................................................................................... 93
9.2 Environmental Specifications ..................................................................................................................................... 93
9.3 Mains Input Electrical Specifications ......................................................................................................................... 94
9.4 Bypass Input Electrical Specifications ........................................................................................................................ 95
9.5 Output Electrical Specifications ................................................................................................................................. 95
9.6 Battery Specifications ................................................................................................................................................. 96
9.7 ECO Feature ............................................................................................................................................................. 104
9.8 Parallel Feature ......................................................................................................................................................... 104
9.9 Safety Regulations and EMC .................................................................................................................................... 104
A Parallel Parameter List ............................................................................................................ 105
Page 8
UPS2000-G-(6 kVA-20 kVA) User Manual
Contents
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
vii
B LCD Menus and Parameters................................................................................................... 106
C Alarm Handling ........................................................................................................................ 118
D Alarm Handing of Battery Maintenance Notification ...................................................... 141
E Battery Shallow Discharge Test ............................................................................................. 143
F Capacity Test .............................................................................................................................. 146
G Acronyms and Abbreviations................................................................................................ 149
Page 9
UPS2000-G-(6 kVA-20 kVA) User Manual
1 Safety Precautions
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
1
1 Safety Precautions
1.1 General Safety
This section describes safety precautions to consider before installing, maintaining, and operating the UPS.
To minimize the risk of personal injury and damage to equipment, read and follow all the precautions in this document before performing any operation. The "DANGER", "WARNING", "CAUTION", and "NOTICE" statements in this document are only supplemental and do not represent all the safety instructions.
Only trained and qualified personnel are allowed to install, operate, and maintain Huawei equipment.
Follow the precautions and special safety instructions provided by Huawei when operating Huawei products. Huawei will not be liable for any consequences that are caused due to violations regarding general safety regulations and equipment design, production, and usage safety standards.
Declaration
Huawei does not take responsibilities for the following situations:
Operation under severe environments that are not specified in this document.
Installation or use in environments that are not specified in related international standards.
Unauthorized product changes and software code modification.
Operations not complying with the operation instructions and safety precautions in this document.
Damage caused by extreme natural environments.
Damage caused by using batteries provided by Huawei for non-Huawei UPSs.
Damage caused by using batteries not provided by Huawei.
Page 10
UPS2000-G-(6 kVA-20 kVA) User Manual
1 Safety Precautions
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2
Power Grid Requirements
A standard UPS can connect to a three-phase, five-wire (L1, L2, L3, N, PE) TT, TN-C, TN-S, and TN-C-S AC power distribution system (IEC60364-1).
Local Laws and Regulations
Equipment operations must comply with local laws and regulations. The safety instructions in this document are only supplemental to local safety regulations.
Personal Requirements
Only engineers certified by the manufacturer or its agents are allowed to perform UPS commissioning and maintenance. Otherwise, human injury or equipment damage may occur, and any resulting UPS faults will be beyond warranty scope.
Personnel who plan to install or maintain Huawei equipment must receive thorough training, understand all necessary safety precautions, and master the correct operation methods. Trained and qualified personnel, or personnel certified or authorized by Huawei are:
Allowed to install, operate, and maintain the equipment.
Allowed to remove safety facilities and inspect the equipment.
Allowed to replace or change the devices or components (including software).
Operation personnel must report faults or errors that might cause serious safety issues to related owners.
This product should be installed and used according to the installation and technical, specification requirements found in this manual. Otherwise, the product may be damaged, and the resulting product exceptions or component damage will be beyond the warranty scope.
Grounding Requirements
Devices to be grounded (excluding the energy storage unit) must meet the following requirements:
When installing a device, install the ground cable first. When removing a device, remove the ground cable at the very end.
Do not damage the ground conductor.
Do not operate devices if the ground conductor is not installed. Before operating a device, check the electrical connection of the device to ensure that it is securely grounded.
Personal Safety
Do not operate the product, or handle cables, during thunderstorms.
To avoid electric shocks, do not connect safety extra-low voltage (SELV) circuits to telecommunication network voltage (TNV) circuits.
Page 11
UPS2000-G-(6 kVA-20 kVA) User Manual
1 Safety Precautions
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3
Before operating a device, wear electrostatic discharge (ESD) clothes, ESD gloves, and an ESD wrist strap. Remove any conductors (such as jewelry or watches) before the operation to avoid electric shocks or burns.
In the case of fire, leave the building or the equipment room immediately, and turn on the fire alarm bell or make an emergency call. Never enter the building on fire in any case.
If the cabinet provides an ESD jack, wear an ESD wrist strap and insert the ground terminal of the ESD wrist strap into the jack.
Ensure all switches are turned to OFF during device installation.
Power on the UPS only after authorized engineers arrive at the site.
If a C2 UPS is used in residential areas, additional measures must be taken to prevent radio frequency interferences.
If the UPS is used for life-supporting medical apparatus and facilities such as lifts where adequate care has to be taken to ensure personal safety, discuss with the manufacturer in advance about the applicability, settings, management, and maintenance of the UPS, which require special considerations during design.
Device Safety
Before operation, ensure that the device is firmly anchored to the floor or other solid objects, such as a wall or an installation rack.
Ensure ventilation vents are unblocked while the system is operating.
Before powering on the device, ensure that all the screws inside it are securely tightened and will not fall off during operation.
After the installation, remove packing materials from the equipment area.
Replace warning labels that have worn out or are unreadable.
A UPS can be used to serve resistive-capacitive loads, resistive loads, and micro-inductive loads. It is recommended that a UPS not be used for pure capacitive loads, pure inductive loads, and half-wave rectification loads. It does not apply to energy feedback loads.
Do not alter the UPS internal structure or installation procedure unless consent from the manufacturer is given.
Never use water to clean electrical components inside or outside the UPS.
Do not drill holes into a cabinet.
1.2 Electrical Safety
High Voltage
Page 12
UPS2000-G-(6 kVA-20 kVA) User Manual
1 Safety Precautions
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4
The high voltage power supply provides power for the device operation. Direct or indirect contact with high voltage power sources may result in fatal injury.
Non-standard or incorrect high voltage operations may result in fire and electric shocks.
The personnel who install the AC facility must be qualified to perform high voltage and AC operations.
When selecting, connecting, and routing power cables, ensure compliance with local laws and regulations.
When installing the AC power supply facility, ensure compliance with local laws and regulations.
Before connecting cables to the UPS, ensure that the input power and mains power distribution switches and output power distribution switch are turned off.
Use only dedicated tools during high voltage and AC operations.
If the operation is performed in a damp environment, ensure that the device is dry. When water is found in the rack or the rack is damp, switch off the power supply immediately.
High Leakage Current
Ground a device before powering it on. Otherwise, personal injury or device damage may occur.
If a "high leakage current" tag is attached to the panel of the device, ground the protective ground terminal on the device enclosure before connecting the AC power supply to prevent electric shocks.
The UPS can generate high leakage currents. Using a circuit breaker that has the leakage current protection function is not recommended.
Power Cable
Do not install or remove power cables when the device is on. Transient contact between the core of the power cable and the conductor may generate electric arcs or sparks, which may cause fire or damage eyesight.
Before moving or reconnecting the UPS, disconnect the mains and batteries, open the output power distribution switch, and wait a period of at least 5 minutes after the UPS completely powers off. Otherwise, electric shocks may occur.
Before installing or removing the power cable, open the power switch.
Before connecting a power cable, check that its label is correct.
Page 13
UPS2000-G-(6 kVA-20 kVA) User Manual
1 Safety Precautions
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5
Fuse
If a fuse needs replacing, ensure the new fuse is of the same type and specifications so that the system runs safely.
Backfeed Protection Dry Contact
The UPS can be configured with a backfeed protection dry contact to work with an external automatic circuit breaker, preventing the voltage from flowing back to input terminals over static bypass circuits. If device installation and maintenance personnel do not need to use backfeed protection, paste labels on the external bypass input circuit breakers informing that the circuit is connected to the UPS. Disconnect the device from the UPS before performing operations on the circuit.
Electrostatic Discharge
Static electricity generated by human bodies may damage the electrostatic-sensitive components on boards, for example, the large-scale integrated (LSI) circuits.
To prevent damage to electrostatic-sensitive components, wear a pair of ESD gloves or a well-grounded ESD wrist strap when touching the device or handling boards or application-specific integrated circuits (ASICs).
When holding a board, hold its edge without touching any components, especially chips.
Package boards with ESD packaging materials before storing or transporting them.
Figure 1-1 shows how to wear an ESD wrist strap.
Page 14
UPS2000-G-(6 kVA-20 kVA) User Manual
1 Safety Precautions
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6
Figure 1-1 Wearing an ESD wrist strap
Liquid Prevention
Do not place the product under areas prone to water leakage, such as near air conditioner vents, ventilation vents, or feeder windows of the equipment room. Ensure that there is no condensation inside the product or equipment room. Ensure that no liquid enters the product. Otherwise, short circuits will occur and may result in serious injury or death.
If any liquid is detected inside the product, immediately disconnect the power supply and contact the administrator.
1.3 Operating Environment
Do not expose the equipment or perform any operations in an environment with flammable or explosive gas, or smoke.
Any operation on any electrical device in an environment that has flammable air can cause extreme danger. Strictly obey the operating environmental requirements specified in related use manuals when using or storing the device.
Do not places the UPS in the following environments:
Places where the temperature and humidity are beyond the range of 0–40°C and 0%–95% RH respectively.
Places in direct sunlight or near heat sources.
Places subject to vibrations or shocks.
Dusty places, or places exposed to corrosive substances or salts.
Marine environments or outdoor land environments (with simple shielding measures) near pollution sources. If a site is near a pollution source, it must be at most:
3.7 km away from saline water areas such as the ocean.
Page 15
UPS2000-G-(6 kVA-20 kVA) User Manual
1 Safety Precautions
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7
3 km away from serious pollution sources, such as metallurgic plants, coal mines,
and thermal power plants.
2 km away from secondary pollution sources, such as chemical, rubber, and
galvanization industries.
1 km away from light pollution sources, such as packing houses, tanneries, and
boiler rooms.
1.4 Battery
This section describes precautions for operating batteries.
Before operating batteries, carefully read the safety precautions for battery handling and connection.
To ensure battery security and efficient battery management, use the batteries delivered with the UPS. Huawei shall not be responsible for battery damage caused by using non-Huawei batteries for Huawei UPSs.
Handle lead-acid batteries according to local regulations.
Incorrect handling of batteries causes hazards. When operating batteries, avoid battery short circuits and electrolyte overflow or leakage.
Electrolyte overflow may damage the device. It will corrode metal parts and circuit boards, and ultimately damage the device and cause short circuits of circuit boards.
Short circuits caused by incorrect operations may cause serious injuries due to high power of batteries.
Do not reversely connect positive and negative battery terminals.
Use batteries of the specified type. Otherwise, the batteries may be damaged.
Check battery connections periodically to ensure that all screws are securely tightened.
Install or store batteries in clean, cool, and dry environments.
Do not decompose, transform, or damage batteries. Otherwise, battery short circuits, acid leaks, and even human injuries may result.
Page 16
UPS2000-G-(6 kVA-20 kVA) User Manual
1 Safety Precautions
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8
Technical Specifications
Table 1-1 Battery specifications
Battery Type
Minimum/Ma ximum Number of Batteries
Cell Float Voltage
Cell Equalized Voltage
Cell Minimum Voltage
Sealing lead-acid battery
Sixteen to twenty 12 V batteries
2.23–2.27 V/cell
2.3–2.4 V/cell
1.6–1.9 V/cell
Open lead-acid battery
Sixteen to twenty 12 V batteries
2.23–2.27 V/cell
2.3–2.4 V/cell
1.6–1.9 V/cell
A cell indicates a 2 V cell, each 12 V battery consists of six cells.
Preventative Measures
When installing and maintaining batteries, pay attention to the following points:
Use special insulation tools.
Take care to protect your eyes when operating batteries.
Wear rubber gloves and a protective coat in case of electrolyte overflow.
When moving a battery, ensure that its electrodes are upward. Leaning or reversing the battery is prohibited.
Switch off the power supply during installation and maintenance.
Short Circuit
Battery short circuits may cause human injuries. Although the voltage of ordinary batteries is low, the instantaneous high current caused by the short circuit releases a great deal of energy.
To avoid battery short circuits, do not maintain batteries in use.
Harmful Gas
Page 17
UPS2000-G-(6 kVA-20 kVA) User Manual
1 Safety Precautions
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9
Do not use unsealed lead-acid batteries. Place and secure lead-acid batteries horizontally to avoid inflammation or device corrosion due to flammable gases emitted from batteries.
The lead-acid batteries in use may emit flammable gases. Therefore, store the batteries in a place with good ventilation, and take precautions against fire.
Battery Temperature
High temperature may result in battery distortion, damage, and electrolyte overflow.
Install or store batteries far away from fire and heating sources, such as transformers. Never burn batteries.
When the temperature of the battery is higher than 60°C, check the battery for electrolyte overflow. If the electrolyte overflows, absorb and counteract the electrolyte immediately.
Acid Leakage
In the case of electrolyte leaks, counteract and absorb the leaking electrolyte immediately.
When moving or handling a battery whose electrolyte leaks, note that the leaking electrolyte may hurt human bodies. When you find the electrolyte leaks, use the following substances to counteract and absorb the leaking electrolyte:
Sodium bicarbonate (baking soda): NaHCO3
Sodium carbonate (soda): Na2CO3
When using substances to counteract and absorb electrolytes, strictly follow the guidelines provided by the battery supplier.
If your body meets the acid, wash the part that has met the acid with clean water immediately, or immediately call a doctor if the situation is serious.
1.5 Mechanical Safety
Moving Sharp Objects
Page 18
UPS2000-G-(6 kVA-20 kVA) User Manual
1 Safety Precautions
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
10
Wear protective gloves when moving sharp objects.
Moving Heavy Objects
Perform operations in accordance with all instructional symbols on the device.
Take caution to avoid injury when moving heavy objects.
When moving or lifting a device, hold the handle or bottom of the device.
When transporting a device using a pallet truck, the forks must be properly positioned to ensure that the device does not topple. No excessive tilt or jolt is allowed during the transportation, and the maximum tolerance of the tilting angle during loading and unloading is 15°. To avoid toppling, secure the device to the pallet truck by using ropes before moving, and assign persons to watch out the device during movement.
Move the cabinet with caution. Any bumping or falling may damage the device.
Figure 1-2 Tilting angle of a cabinet
Handling Fans
Do not insert fingers or boards into the operating fans until the fans are switched off, and have stopped running.
Page 19
UPS2000-G-(6 kVA-20 kVA) User Manual
1 Safety Precautions
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
11
1.6 Laying Out Cables
Binding Signal Cables
Signal cables must be bound separately from strong-current cables and high-voltage cables.
Laying Out Cables
When the temperature is low, a violent strike or vibrations may damage the cable sheathing. To ensure cable safety, comply with the following requirements:
Cables can be laid, or installed, only when the temperature is higher than 0°C (32°F). Handle cables with caution, especially at lower temperatures.
Before laying out cables that have been stored in temperatures lower than 0°C (32°F), move the cables to an environment that is at the requisite ambient temperature. Store them in this environment for at least 24 hours.
Do not drop the cables directly from the vehicle.
As the insulation layer of a cable may age, or be damaged from high temperatures, ensure a sufficient distance between cables and the DC busbars, shunts, and fuses. Cables prepared by the customer should be flame resistant. Cables must not be routed behind the air exhaust vent of the cabinet. The air exhaust vent should not be blocked by any object.
Before connecting a cable, ensure that the cable and cable label to be used meet the actual installation requirements.
Page 20
UPS2000-G-(6 kVA-20 kVA) User Manual
2 UPS2000-G-(6kVA-20kVA) Quick Introduction
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
12
2 UPS2000-G-(6kVA-20kVA) Quick
Introduction
2.1 Model Description
This document describes the following UPS models:
Model
Represented By
Remarks
UPS2000-G-6KRTS
UPS2000-G-6 kVA standard model
The two models are represented by UPS2000-G-6 kVA in the description of their common features and parameters.
UPS2000-G-6KRTL
UPS2000-G-6 kVA long backup time model
UPS2000-G-10KRTS
UPS2000-G-10 kVA standard model
The two models are represented by UPS2000-G-10 kVA in the description of their common features and parameters.
UPS2000-G-10KRTL
UPS2000-G-10 kVA long backup time model
UPS2000-G-15KRTL
UPS2000-G-15 kVA
The UPS2000-G-15KRTL has only a long backup time model.
UPS2000-G-20KRTL
UPS2000-G-20 kVA
The UPS2000-G-20KRTL has only a long backup time model.
Figure 2-1 shows a UPS model number.
Figure 2-1 Model number
Table 2-1 describes the model number.
Page 21
UPS2000-G-(6 kVA-20 kVA) User Manual
2 UPS2000-G-(6kVA-20kVA) Quick Introduction
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
13
Table 2-1 Model number details
No.
Item
Description
1
Product category
UPS
2
Product family
2000: Power ≤ 20 kVA
3
UPS subcategory
G: series name
4
Output capacity
6K: 6 kVA 10K: 10 kVA 15K: 15 kVA 20K: 20 kVA
5
UPS type
RT: rack- and tower-mounted unit RR: rack-mounted unit TT: tower-mounted unit TM: modular tower-mounted unit RM: modular rack-mounted unit
6
Built-in battery (optional)
S: standard model, which provides only a standard battery pack.
L: long backup time model. You need to use an external large-capacity battery pack.
2.2 Working Principle
2.2.1 Conceptual Diagram
Figure 2-2 shows the UPS conceptual diagram.
Figure 2-2 Conceptual diagram
2.2.2 Working Modes
The UPS has the following working modes:
Normal mode
Page 22
UPS2000-G-(6 kVA-20 kVA) User Manual
2 UPS2000-G-(6kVA-20kVA) Quick Introduction
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
14
When the mains is normal, the rectifier boosts the mains input voltage and converts the AC power into stable DC power for the inverter, and the mains charges batteries over a charger. Then the inverter converts the DC power into stable AC power, which is supplied to loads.
Battery mode When the mains is abnormal or disconnected, the DC-DC step-up transformer boosts the
DC power supplied from batteries. Then the inverter converts the DC power into stable AC power for powering loads.
Bypass mode The mains supplies power directly to loads after filtering. The UPS transfers to bypass
mode when overload, overtemperature, or faults occur. This mode does not provide battery backup capability.
Economy control operation (ECO) mode If the bypass voltage and frequency are in the specified range, the UPS supplies power to
loads over the bypass. If the bypass voltage and frequency are outside the range, the UPS transfers to normal or battery mode. ECO is short for economy control operation.
The UPS2000-G-15 kVA/20 kVA supports battery ECO mode only in the case of two mains inputs. In battery ECO mode, the bypass supplies power to the UPS, and batteries are used as backup power. If the bypass is abnormal, the UPS transfers to battery mode.
By default, ECO mode described in this document refers to mains ECO mode.
2.3 Appearance
Figure 2-3 shows the front and rear views of the UPS2000-G-6 kVA. Figure 2-4 shows the
front and rear views of the UPS2000-G-10 kVA. Figure 2-5 shows the front and rear views of the UPS2000-G-15 kVA/20 kVA.
Page 23
UPS2000-G-(6 kVA-20 kVA) User Manual
2 UPS2000-G-(6kVA-20kVA) Quick Introduction
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
15
Figure 2-3 Front and rear views of the UPS2000-G-6 kVA
(1) Control panel
(2) AC input port
(3) AC output ports (pL and sL)
(4) Output sockets
(5) Parallel ports
(6) Control area network (CAN) communications ports (MON1 and MON2)
(7) Optional card slot
(8) Battery temperature sensor port
(9) Universal Serial Bus (USB) port
(10) Emergency power-off (EPO) port
(11) Maintenance bypass port (MBS)
(12) Fuse base (13) Input circuit breaker
(14) Battery port
The total load current supported by the two output sockets (C13) cannot exceed 10 A.
The fuse used on the UPS2000-G-6 kVA meets the 250V-10A-IEC specifications.
Page 24
UPS2000-G-(6 kVA-20 kVA) User Manual
2 UPS2000-G-(6kVA-20kVA) Quick Introduction
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
16
Figure 2-4 Front and rear views of the UPS2000-G-10 kVA
(1) Control panel
(2) AC input ports
(3) AC output ports (pL and sL)
(4) Parallel ports
(5) CAN communications ports (MON1 and MON2)
(6) Optional card slot
(7) Battery temperature sensor port
(8) USB port
(9) EPO port
(10) Maintenance bypass port (MBS)
(11) Input circuit breaker
(12) Battery port
Page 25
UPS2000-G-(6 kVA-20 kVA) User Manual
2 UPS2000-G-(6kVA-20kVA) Quick Introduction
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
17
Figure 2-5 Front and rear views of the UPS2000-G-15 kVA/20 kVA
(1) Control panel
(2) AC input ports (mains and bypass)
(3) Battery terminals
(4) EPO port
(5) Maintenance bypass port (MBS)
(6) Parallel ports
(7) CAN communications ports (MON1 and MON2)
(8) USB port
(9) Battery temperature sensor port
(10) Optional card slot
(11) AC output ports (pL and sL)
Page 26
UPS2000-G-(6 kVA-20 kVA) User Manual
2 UPS2000-G-(6kVA-20kVA) Quick Introduction
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
18
2.4 Optional Components
Table 2-2 Optional components
Compone nt
Model
Function
Remarks
Parallel cable
DB15M, CC8P0.48B(S), DB15F
Connect UPSs in parallel.
A parallel cable is 1.5 meters long.
Battery temperature sensor
TE820E10B/W103-B02-L1
Measures the ambient temperature of the external power module and battery pack.
The temperature ranges from –40ºC to +80ºC.
The standard cable is 2 meters long. To increase the length, install a magnetic ring at the sensor plug. Table 2-3 lists the specifications of magnetic rings from three vendors.
Ambient temperature and humidity sensor
ENR1DETA MODULE
Measures the UPS ambient temperature and humidity. The ambient temperature ranges from 0–50ºC. The ambient humidity ranges from to 0%–100% RH.
It is used together with a Simple Network Management Protocol (SNMP) card.
SNMP card
RMS-SNMP01A
Monitors the UPS and the ambient temperatures and humidity (if required) and allows for Ethernet networking.
N/A
6 kVA output isolation transformer box
DGL-6/0.22
Provides isolation solutions for customer equipment. Compared with the output transformer on an industrial frequency UPS, the output transformer box provides isolation functions even in bypass mode. The isolation transformer is
The output isolation transformer box is 6 kVA, single-phase. It is used for the UPS2000-G-6 kVA.
10 kVA output isolation
DGL-10/0.22
The output isolation transformer box
Page 27
UPS2000-G-(6 kVA-20 kVA) User Manual
2 UPS2000-G-(6kVA-20kVA) Quick Introduction
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
19
Compone nt
Model
Function
Remarks
transformer box
a 2:1:1 industrial-frequency transformer. It converts one 220 V output voltage into two isolated 110 V outputs.
is 10 kVA, single-phase. It is used for the UPS2000-G-10 kVA.
Standard battery pack (7 Ah, 20 batteries)
ESS-240V12-7AhBPVBA01 ESS-240V12-7AhBPVBA02
Each battery pack consists of twenty 12 V, 7 Ah VRLA batteries connected in series. It is a standard configuration for the UPS2000-G-6 kVA. A maximum of four battery packs are connected in parallel.
The UPS2000-G-15 kVA/20 kVA uses at least two battery packs.
Standard battery pack (9 Ah, 20 batteries)
ESS-240V12-9AhBPVBA01 ESS-240V12-9AhBPVBA02
Each battery pack consists of twenty 12 V, 9 Ah VRLA batteries connected in series. It is a standard configuration for the UPS2000-G-10 kVA. A maximum of four battery packs are connected in parallel.
Modbus card
RMS-MODBUS01A
Provides two cascaded RJ45 ports to implement networking over the Modbus or YDN-23 protocol.
N/A
Dry contact card
RMS-RELAY01A
Provides six alarm dry contact outputs (normal mode, battery mode, bypass mode, low battery voltage, bypass backfeed, and UPS faults) and two dry contract control inputs (one is the shutdown signal input, and the other is reserved).
N/A
External dry contact card
RMS-RELAY02B
Provides four dry contact outputs (critical alarm, minor alarm, mains mode, battery mode, bypass mode, inverter on, battery undervolt.,bypass backfeed , high ambient tempreture, or UPS
Used together with an SNMP card.
Page 28
UPS2000-G-(6 kVA-20 kVA) User Manual
2 UPS2000-G-(6kVA-20kVA) Quick Introduction
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
20
Compone nt
Model
Function
Remarks
fault.) and two dry contract inputs (startup, shutdown).
iBAT 2.0
-
Consists of the communication interface module (CIM) and battery interface module (BIM). The CIM is an intelligent battery management module which collects wireless communication data of battery stauts from the downstream BIM groups, and uploads data to the SNMP card through the COM port.
Used together with an SNMP card.
Power distribution unit (PDU) (PDC-0038 V4ACIOA)
PDC-0038V4ACIOA
Controls and protects input and output power, increases output sockets, and distributes power for 1+1 parallel systems, and implements online maintenance.
The PDU is designed for a 1+1 UPS2000-G-15 kVA/20 kVA parallel system (three-phase input three-phase output).
PDU (PDC-0091 V2ACIOA)
PDC-0091V2ACIOA
The PDU is designed for a 1+1 UPS2000-G­15 kVA/20 kVA parallel system (three-phase input single-phase output and single-phase input single-phase output).
It can also be used in a UPS2000-G­6 kVA/10 kVA 1+1 parallel system and 2+0 parallel
Page 29
UPS2000-G-(6 kVA-20 kVA) User Manual
2 UPS2000-G-(6kVA-20kVA) Quick Introduction
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
21
Compone nt
Model
Function
Remarks
system.
Magnetic loop
DN85H, H38x22x15 (DMEGC)
E2F, 38x22x15 (FENGYI)
Optimizes the performance of the TN-C power distribution system in the parallel system scenario.
In a UPS2000-G-15 kVA/20 kVA parallel system using the TN-C power distribution system, install four magnetic rings on the PE cables on each UPS, bind the four magnetic rings together using binding tape, and secure them to the nearest place.
NOTE
The application scenarios of magnetic rings are described below.
Figure 2-6
and Figure
2-7 show the
magnetic ring installation method and position.
It is recommended that you install the battery temperature sensor (secured with an adhesive) on the surface of batteries in the middle of the battery rack.
In a UPS2000-G-15 kVA/20 kVA parallel system using the TN-C power distribution system, there are two scenarios for installing magnetic rings on the UPS mains input PE cables:
One is to install magnetic rings on branch PE cables (see Figure 2-6).
The other is to install a magnetic ring on the general PE cable (see Figure 2-7).
For magnetic ring specifications, see section Table 2-2.
Page 30
UPS2000-G-(6 kVA-20 kVA) User Manual
2 UPS2000-G-(6kVA-20kVA) Quick Introduction
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
22
Figure 2-6 Installing magnetic rings (numbered 1) on branch PE cables
Page 31
UPS2000-G-(6 kVA-20 kVA) User Manual
2 UPS2000-G-(6kVA-20kVA) Quick Introduction
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
23
Figure 2-7 Installing a magnetic ring (numbered 1) on the general PE cable
Perform the following operations in a parallel system using the TN-C power distribution system:
Short-circuit battery terminals N in the parallel system.
It is recommended that you connect AC loads and battery packs only to the UPS PE terminal.
If you have directly grounded AC loads and battery packs (as shown by PE1 and PE2 in Figure 2-6) and connected them to the UPS PE terminal, install magnetic rings 2 and 3 on the PE3, PE4, PE5, and PE6 ground cables. You need to purchase magnetic rings 2 and 3.
The recommended type for magnetic rings 1, 2, and 3 is DN85Hx4 or E2Fx4. For details, see Table
2-2.
Table 2-3 Specifications of magnetic rings from three vendors
Vendor
Magnetic Ring
DMEGC
R10K
TDK
HS10
TDG
TS10
Page 32
UPS2000-G-(6 kVA-20 kVA) User Manual
2 UPS2000-G-(6kVA-20kVA) Quick Introduction
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
24
The magnetic conductivity of manganese and zinc magnetic rings is greater than 10,000, and the recommended internal diameter of magnetic rings is greater than 10 mm (easy for wire coiling). The number of coiling circles is 5 or greater.
Page 33
UPS2000-G-(6 kVA-20 kVA) User Manual
3 Installation
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
25
3 Installation
3.1 Preparations
3.1.1 Site
Floor Bearing
The floor can bear the weight of the UPS and its optional components. In the case of rack installation, ensure that the floor can also bear the weight of the rack.
For the UPS weight, see section 9.1 Physical Specifications.
Environment
Do not install the UPS in an environment outside the specifications (see section 9.2
Environmental Specifications).
Keep the UPS far away from water, heat sources, and flammable and explosive substances. Install the UPS in an environment free of dust, volatile gas, salt, and corrosive materials. Avoid direct sunlight.
Do not install the UPS in environments with conductive metal scraps in the air.
The ideal operating temperature for batteries is 20–30ºC. Temperatures higher than 30ºC shorten the battery lifespan and temperatures lower than 20ºC reduces the backup time.
Page 34
UPS2000-G-(6 kVA-20 kVA) User Manual
3 Installation
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
26
UPS2000-G-6 kVA/10 kVA Dimensions
Figure 3-1 UPS2000-G-6 kVA/10 kVA installation dimensions
UPS2000-G-15 kVA/20 kVA Dimensions
Figure 3-2 UPS2000-G-15 kVA/20 kVA installation dimensions
Clearances
Page 35
UPS2000-G-(6 kVA-20 kVA) User Manual
3 Installation
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
27
The distance between UPS air vents and the wall or obstacle is greater than or equal to 500 mm.
Reserve a clearance of at least 500 mm respectively from the front and rear panels of the UPS to the wall or adjacent equipment to facilitate ventilation and heat dissipation, as shown in
Figure 3-3.
Figure 3-3 Reserved clearances
3.1.2 Tools
Get installation tools insulated to prevent electric shocks.
Table 3-1 lists the installation tools.
Table 3-1 Tools
Tools
Clamp meter
Multimeter
Label
Phillips screwdriver (PH 2 x 150 mm or PH 3 x 250 mm)
Page 36
UPS2000-G-(6 kVA-20 kVA) User Manual
3 Installation
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
28
Tools
Flat-head screwdriver (2 mm x 80 mm)
Torque screwdriver
Crimping tool
Diagonal pliers Wire stripper
Polyvinyl chloride (PVC) insulation tape
Cotton cloth
Brush Heat shrink tubing
Heat gun
Electrician's knife
Protective gloves
ESD gloves
Insulated gloves
Hydraulic pliers
Cable tie
3.1.3 Power Cables
Page 37
UPS2000-G-(6 kVA-20 kVA) User Manual
3 Installation
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
29
In the case of three-phase input, install a three-phase disconnector. In the case of single-phase input, you are advised to install a disconnector.
When used to power IT system, the UPS (three-phase output) should provide 4-pole disconnectors, and the UPS (single-phase output) should provide 2-pole disconnectors.
The UPS is a large leakage current device. Do not configure a circuit breaker that has the leakage current protection function. If you need leakage current protection function, use the earth leakage circuit breaker recommended.
The battery cable cannot be longer than 10 m.
You can install linked circuit breakers for both the N wire and L wire. No independent circuit breaker is allowed for only the N wire.
For 15 kVA/20 kVA model, use AC ground cables that have a cross-sectional area of 25 mm2 and M6 OT terminals that are 90° bent and have a cross-sectional area of 25 mm2.
For 15 kVA/20 kVA model, use battery ground cables that have a cross-sectional area of 16 mm2 and M6 OT terminals that are 90° bent and have a cross-sectional area of 16 mm2.
For 6 kVA model, use ground cables that have a cross-sectional area of 6 mm2 and M4 OT terminals and have a cross-sectional area of 6 mm2.
For 10 kVA model, use ground cables that have a cross-sectional area of 10 mm2 and M6 OT terminals and have a cross-sectional area of 10 mm2.
Table 3-2 lists the recommended power cable specifications.
Table 3-2 Recommended power cable specifications
Model
Wiri ng Term inal
Nu mbe r of Pha ses
Rated Voltage
Extern al Circui t Break er
Earth Leaka ge Circui t Break er (ELCB )
Cross­sectio nal Area
Termi nal Type
Torq ue for Tight ening Bolts
6 kVA
Input
1
220 V AC, 230 V AC, or 240 V AC
50 A (the charact eristics of D)
100 mA
6 mm2
6 mm2 M4 OT termina l
1.4 N·m
Outpu t
1
50 A (the charact eristics of D)
N/A
Batter y
N/A
240 V DC
50 A
N/A
6 mm2
N/A
10 kVA
Input
1
220 V AC, 230
63 A (the
100
10 mm2
10 mm2 M6 OT
2.8
Page 38
UPS2000-G-(6 kVA-20 kVA) User Manual
3 Installation
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
30
Model
Wiri ng Term inal
Nu mbe r of Pha ses
Rated Voltage
Extern al Circui t Break er
Earth Leaka ge Circui t Break er (ELCB )
Cross­sectio nal Area
Termi nal Type
Torq ue for Tight ening Bolts
V AC, or 240 V AC
charact eristics of D)
mA
termina l
N·m
Outpu t
1
63 A (the charact eristics of D)
N/A
Input
3
380 V AC, 400 V AC, or 415 V AC
63 A (the charact eristics of D)
100 mA
10 mm2
Outpu t
1
220 V AC, 230 V AC, or 240 V AC
63 A (the charact eristics of D)
N/A
Batter y
N/A
240 V DC
63 A
N/A
10 mm2
N/A
15 kVA (single-ph ase input single-pha se output)
One mains input
1
220 V AC, 230 V AC, or 240 V AC
100 A (the charact eristics of D)
300 mA
25 mm2
25 mm2 M6 OT termina l
4.8 N·m
Batter y
N/A
±240 V DC
63 A
N/A
16 mm2
16 mm2 M6 90° OT termina l
4.8 N·m
Outpu t
1
220 V AC, 230 V AC, or 240 V AC
100 A (the charact eristics of D)
N/A
25 mm2
25 mm2 M6 OT termina l
4.8 N·m
15 kVA (three-pha se input single-pha
Bypas s input
1
220 V AC, 230 V AC, or 240 V AC
100 A (the charact eristics
300 mA
25 mm2
25 mm2 M6 OT termina l
4.8 N·m
Page 39
UPS2000-G-(6 kVA-20 kVA) User Manual
3 Installation
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
31
Model
Wiri ng Term inal
Nu mbe r of Pha ses
Rated Voltage
Extern al Circui t Break er
Earth Leaka ge Circui t Break er (ELCB )
Cross­sectio nal Area
Termi nal Type
Torq ue for Tight ening Bolts
se output)
of D)
Mains input
3
380 V AC, 400 V AC, or 415 V AC
50 A (the charact eristics of D)
300 mA
10 mm2
10 mm2 M6 OT termina l
2.8 N·m
Batter y
N/A
±240 V DC
63 A
N/A
16 mm2
16 mm2 M6 90° OT termina l
4.8 N·m
Outpu t
1
220 V AC, 230 V AC, or 240 V AC
100 A (the charact eristics of D)
N/A
25 mm2
25 mm2 M6 OT termina l
4.8 N·m
15 kVA (three-pha se input three-phas e output)
Bypas s input
3
380 V AC, 400 V AC, or 415 V AC
50 A (the charact eristics of D)
300 mA
10 mm2
10 mm2 M6 OT termina l
2.8 N·m
Mains input
3
300 mA
Batter y
N/A
±240 V DC
63 A
N/A
16 mm2
16 mm2 M6 90° OT termina l
4.8 N·m
Outpu t
3
380 V AC, 400 V AC, or 415 V AC
50 A (the charact eristics of D)
N/A
10 mm2
10 mm2 M6 OT termina l
2.8 N·m
20 kVA (single-ph ase input single-pha se output)
One mains input
1
220 V AC, 230 V AC, or 240 V AC
125 A (the charact eristics of D)
Adjusta ble from 500 mA to 1000 mA
25 mm2
25 mm2 M6 OT termina l
4.8 N·m
Page 40
UPS2000-G-(6 kVA-20 kVA) User Manual
3 Installation
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
32
Model
Wiri ng Term inal
Nu mbe r of Pha ses
Rated Voltage
Extern al Circui t Break er
Earth Leaka ge Circui t Break er (ELCB )
Cross­sectio nal Area
Termi nal Type
Torq ue for Tight ening Bolts
Batter y
NA
±240 V DC
63 A
N/A
16 mm2
16 mm2 M6 90° OT termina l
4.8 N·m
Outpu t
1
220 V AC, 230 V AC, or 240 V AC
125 A (the charact eristics of D)
N/A
25 mm2
25 mm2 M6 OT termina l
4.8 N·m
20 kVA (three-pha se input single-pha se output)
Bypas s input
1
220 V AC, 230 V AC, or 240 V AC
125 A (the charact eristics of D)
Adjusta ble from 500 mA to 1000 mA
25 mm2
25 mm2 M6 OT termina l
4.8 N·m Mains input
3
380 V AC, 400 V AC, or 415 V AC
63 A (the charact eristics of D)
300 mA
10 mm2
10 mm2 M6 OT termina l
2.8 N·m
Batter y
N/A
±240 V DC
63 A
N/A
16 mm2
16 mm2 M6 90° OT termina l
4.8 N·m
Outpu t
1
220 V AC, 230 V AC, or 240 V AC
125 A (the charact eristics of D)
N/A
25 mm2
25 mm2 M6 OT termina l
4.8 N·m
20 kVA (three-pha se input three-phas e output)
Bypas s input
3
380 V AC, 400 V AC, or 415 V AC
63 A (the charact eristics of D)
300 mA
10 mm2
10 mm2 M6 OT termina l
2.8 N·m
Mains input
3
300 mA
Batter
N/A
±240 V
63 A
N/A
16 mm2
16 mm2 M6 90°
4.8
Page 41
UPS2000-G-(6 kVA-20 kVA) User Manual
3 Installation
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
33
Model
Wiri ng Term inal
Nu mbe r of Pha ses
Rated Voltage
Extern al Circui t Break er
Earth Leaka ge Circui t Break er (ELCB )
Cross­sectio nal Area
Termi nal Type
Torq ue for Tight ening Bolts
y
DC
OT termina l
N·m
Outpu t
3
380 V AC, 400 V AC, or 415 V AC
63 A (the charact eristics of D)
N/A
10 mm2
10 mm2 M6 OT termina l
2.8 N·m
If customers purchase input and output power cables by themselves, use the cables that comply with standards proposed by Underwriters Laboratories (UL) or International Electrotechnical Commission (IEC).
Two-mains-input scenarios are not supported on the UPS2000-G-15 kVA/20 kVA (single-phase input single-phase output).
3.1.4 Unpacking and Checking
Figure 3-4 shows the transportation safety requirements.
Figure 3-4 Transportation safety requirements
Page 42
UPS2000-G-(6 kVA-20 kVA) User Manual
3 Installation
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
34
Only trained personnel are allowed to move the UPS.
Do not move the UPS by holding its mounting brackets, front panel, terminal cover, or monitoring module.
At least two persons are required to move the battery pack and transformer because they are heavy. Exercise caution when moving them. Prevent the battery pack from falling over; otherwise, fire accidents may occur. Remove rings, watches, and other metal objects when you move the battery pack.
To prevent shocks or falls, move the UPS gently. After placing the UPS in the installation position, unpack it carefully to prevent scratches.
Procedure
Step 1 Visually inspect the UPS appearance for shipping damage. If any shipping damage is found,
report it to the carrier immediately.
Step 2 Move the UPS to the installation position. Step 3 Unpack the case. Step 4 Check the UPS packing.
1. Check the UPS bar code (which is at the rear panel of the UPS, near the air exhaust vent),
and ensure that it complies with the order.
2. If there is any discrepancy, contact your local Huawei office immediately.
----End
3.2 Single UPS/Parallel System Installation
UPS installation includes mechanical installation and cable connection. Installation modes include tower installation and rack installation. You can select an installation mode based on the site requirements.
For details, see the UPS2000-G-(6 kVA-10 kVA) Quick Guide and UPS2000-G-(15 kVA-20 kVA) Quick Guide.
The UPS2000-G-(6 kVA-10 kVA) Quick Guide and UPS2000-G-(15 kVA-20 kVA) Quick Guide delivered with the UPS.
3.3 Installing a Backfeed Protection Device
Page 43
UPS2000-G-(6 kVA-20 kVA) User Manual
3 Installation
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
35
The UPS has no built-in backfeed protection device. You can install a backfeed protection device on the input front side.
If you do no install a backfeed protection device on the input front side, attach a warning label to the main power isolation device. The label reads like this: "This circuit supplies power to the UPS. Before cable connection, disconnect the UPS, and check the voltage across wiring terminals."
When battery mode is unavailable or the mains fails, the UPS internal voltages or energy may flow back directly, or through a leakage path, to an input terminal. To minimize the risk of electric shocks, install a backfeed protection device on the input side.
Table 3-3 lists the rated voltages and currents for backfeed protection contactors on the UPSs.
Table 3-3 Rated voltages and currents for backfeed protection contactors
Model
Rated Voltage and Current
Recommended Contactor Models (Schneider contactors)
UPS2000-G-6KRTS
220/230/240 V AC, 40 A
LC1-D40A UPS2000-G-6KRTL
UPS2000-G-10KRTS
220/230/240 V AC, 65 A
LC1-D50A for single-phase input
LC1-DT60A for three-phase input
UPS2000-G-10KRTL UPS2000-G-15KRTL
(three-phase input)
220/230/240 V AC, 32 A
LC1-D80 for single-phase input
LC1-DT60A for three-phase input
UPS2000-G-20KRTL (three-phase input)
220/230/240 V AC, 40 A
UPS2000-G-15KRTL (single-phase input)
UPS2000-G-20KRTL (single-phase input)
220/230/240 V AC, 125 A
Table 3-4 Control relay parameters
Recommended Model
Parameters
HF18FF/012 (HONGFA control relay)
Dry contact: NC Breaking capability: 250 V AC, 5 A Coil: 12 V rated voltage; rated current of
less than 1 A
MY2N-J DC12V (OMRON control relay)
HJ2-L-DC12V (Panasonic control relay)
Page 44
UPS2000-G-(6 kVA-20 kVA) User Manual
3 Installation
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
36
3.3.1 Feedback Prevention Connections (With Dry Contract Control)
Figure 3-5, Figure 3-6, Figure 3-7 and Figure 3-8 show backfeed protection connections (with
dry contract control).
Figure 3-5 Bypass backfeed protection connections for the UPS2000-G-6 kVA/10 kVA/15 kVA/20 kVA (single-phase input single-phase output)
Page 45
UPS2000-G-(6 kVA-20 kVA) User Manual
3 Installation
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
37
Figure 3-6 Bypass backfeed protection connections for the UPS2000-G-10 kVA (three-phase input single-phase output)
Page 46
UPS2000-G-(6 kVA-20 kVA) User Manual
3 Installation
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
38
Figure 3-7 Bypass backfeed protection connections for the UPS2000-G-15 kVA/20 kVA (three-phase input three-phase output)
Page 47
UPS2000-G-(6 kVA-20 kVA) User Manual
3 Installation
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
39
Figure 3-8 Bypass backfeed protection connections for the UPS2000-G-15 kVA/20 kVA (three-phase input single-phase output)
3.4 Check After Installation
Table 3-5 lists the check items.
Table 3-5 Post-installation check items
No.
Item
Expected Result
1
Cable routing
Cable routing meets engineering requirements.
2
Cable connections
Input cables, output cables, and battery cables are tightened to specified torques using a torque wrench, connected correctly, and free of damage.
Page 48
UPS2000-G-(6 kVA-20 kVA) User Manual
3 Installation
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
40
No.
Item
Expected Result
3
Cable connections for USB ports and network ports
Cables to USB ports and network ports are connected correctly and securely.
4
Labels
Labels are neatly attached to both ends of each cable, and the information on the labels is concise and understandable.
5
Ground cable connection
The ground cable is securely connected to the equipment room ground bar. Measure the resistance between the UPS ground cable and the equipment room ground bar, which must be less than 1 ohm.
6
Distances between cable ties
Distances between cable ties are the same, and no burr exists.
7
Operating environment
Clean the conductive air and other sundries.
Page 49
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
41
4 Control Panel
4.1 Introduction
The control panel, located on the front panel of the UPS, controls UPS running, displays running data, and allows you to set parameters and view alarms. Figure 4-1 shows the control panel.
Figure 4-1 Control panel
(1) Mains indicator
(2) Battery indicator
(3) Bypass indicator
(4) Fault indicator/INFO button
(5) Startup/Enter/Battery Self-Check/Mute button
(6) Down button
(7) Up button
(8) Shutdown/Back button
4.2 Indicators
Table 4-1 describes the indicators on the control panel.
Page 50
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
42
Table 4-1 Indicator description
Indicator
Color
Status
Meaning
Mains indicator
Green On
The UPS is in normal mode.
Off
The UPS is not in normal mode.
Battery indicator
Yellow
On
The UPS is in battery mode.
Off
The UPS is not in battery mode.
Blinking
The remaining battery capacity is less than 25%.
Bypass indicator
Yellow On
The UPS is in bypass mode.
Off
The UPS is not in bypass mode.
Fault indicator/INFO button
Red
On
The UPS is faulty.
Red
Blinking
The UPS generates an alarm.
Green
On
The UPS is running properly.
The UPS is in ECO mode when the mains indicator and bypass indicator are both on.
4.3 Functional Buttons
The control panel provides five buttons to start and shut down the UPS and set parameters.
Table 4-2 describes the buttons.
Table 4-2 Button description
Butt on
Meaning
Description
ESC
Shutdown/Back
On the default screen, press ESC for more than 5 seconds. Release the button when you hear a beep sound. The inverter shuts down.
On any other screen, press ESC to return to the upper-level menu (the default screen is the upper-level screen for the main menu screen).
Up
Press ▲ or ▼ to scroll upward or downward. You can set a value by using the list or step increase
or decrease.
Down
Enter/Startup/Battery Self-Check/Mute
On the default screen in bypass mode, hold down
for more than 5 seconds. Release the button when you hear a beep sound. The UPS starts.
Page 51
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
43
Butt on
Meaning
Description
On the default screen, press . The main menu is displayed.
On any menu screen, press . The lower-level menu is displayed. If the menu is the last level, an information screen is displayed.
On the default screen in normal mode, hold down
for more than 5 seconds. Release the button when you hear a beep sound. The battery test starts.
When the buzzer buzzes, hold down for 2–5 seconds. The buzzer is muted when you release the button.
i
Fault indicator/INFO button
When an alarm is generated, press i to view the active alarm information.
When no alarm is generated, press i to return to the default screen.
Battery self-check: After the UPS starts in normal mode, it transfers to battery mode for 10 seconds to check that the battery status (if no battery is connected, No battery is displayed) and that the UPS can transfer to battery mode. The purpose is to prevent power backup failure when the UPS needs to transfer to battery mode.
If you do not press any button within 60 seconds, the default screen is displayed.
4.4 LCD
The LCD displays the UPS running data and alarm information, and allows you to set parameters and control operation. The backlight turns off if you do not press any button within 30 seconds.
4.5 LCD Startup Screens
Table 4-3 Symbol conventions
Symbol
Description
Press A.
Press B after you press A.
Indicates omitted screens.
Page 52
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
44
The symbol conventions apply to all chapters in this document.
The LCD figures in this document correspond to V100R001C10SPC802. The LCD updated without notice. If the LCD is updated, contact Huawei for the latest LCD figures.
The screen in this document based on the UPS2000-G-15 kVA/20 kVA. The parameter values in the menu pictures in this document are for reference only.
Figure 4-2 shows a startup screen.
Figure 4-2 Description of the startup screen
(1) Normal mode (The solid line indicates normal mode. The dotted line indicates non-normal mode.)
(2) Input voltage and frequency
(3) Load power
(4) Output voltage, current, and frequency
(5) Bypass mode (The solid line indicates bypass mode. The dotted line indicates non-bypass mode.)
(6) Battery voltage and capacity displayed during charge; Battery discharge time and capacity displayed during discharge.
(7) Battery mode (The solid line indicates battery in charge or discharge mode. The dotted line indicates non-battery mode.)
Table 4-4 describes the icons on the screen.
Page 53
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
45
Table 4-4 Icons on the screen
Icon
Meaning
Icon
Meaning
Mains input
Rectifier/Power factor correction (PFC) working
Inverter working
Bypass mode
Load power
Battery charging
Battery discharging
N/A
N/A
4.5.1 Starting the UPS in Normal Mode
Initial Startup
The settings wizard starts automatically when you start the UPS for the first time or when you restart the UPS after restoring factory settings, as shown in Figure 4-3. The settings wizard provides the Language, System Parameters, and Battery Parameters screens.
Figure 4-3 Settings wizard
After you complete the settings, press . The standby screen is displayed.
Page 54
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
46
Figure 4-4 Standby screen displayed after initial startup
Non-initial Startup
When the initialization is complete, the standby screen is displayed.
Figure 4-5 Standby screen displayed after non-initial startup
After the UPS starts, it enters normal mode. For the startup procedure, see chapter 5
Operations.
Figure 4-6 Normal mode
Press . The main menu screen is displayed.
4.5.2 Starting the UPS in Battery Mode
Initial Startup
The settings wizard starts automatically when you start the UPS for the first time or when you restart the UPS after restoring factory settings. The settings wizard provides the Language, System Parameters, and Battery Parameters screens.
After you complete the settings, press . The standby screen is displayed.
Page 55
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
47
Figure 4-7 Standby screen displayed after initial startup
Non-initial Startup
When the initialization is complete, the standby screen is displayed.
Figure 4-8 Standby screen displayed after non-initial startup
After the UPS starts, it enters battery mode. For the startup procedure, see 5 Operations.
Figure 4-9 Battery mode
Press . The main menu screen is displayed.
4.6 LCD Menu Hierarchy
Figure 4-10 Main Menu screen
Figure 4-11 shows the LCD menu hierarchy.
Page 56
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
48
Figure 4-11 LCD menu hierarchy
Page 57
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
49
For details about the menus, see appendix B LCD Menus and Parameters.
4.6.1 Status Screen
On the Main Menu screen, select Status, and press . The Status screen is displayed.
Mains Input Screen
Figure 4-12 shows the Mains Input screen.
Figure 4-12 Mains Input screen
Van, Vbn, and Vcn parameters Phase voltages displayed on the Mains Input screen (The parameter is Voltage in the
case of single-phase input.)
Frequency parameter Frequency displayed on the Mains Input screen.
Vab, Vbc, and Vca parameters Line voltages displayed on the Mains Input screen (The parameters are not displayed in
the case of single-phase input.)
Bypass Input Screen
Figure 4-13 shows the Bypass Input screen.
Figure 4-13 Bypass Input screen
Van, Vbn, and Vcn parameters Phase voltages displayed on the Bypass Input screen (The parameter is Voltage in the
case of single-phase input.)
Frequency parameter Frequency displayed on the Bypass Input screen.
Page 58
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
50
Battery Status Screen
Figure 4-14 shows the Battery Status screen.
Figure 4-14 Battery Status screen
Battery voltage Battery string voltage (positive and negative battery string voltages in the case of the
UPS2000-G-15 kVA/20 kVA)
Battery current Battery string current (positive and negative battery string currents in the case of the
UPS2000-G-15 kVA/20 kVA). + is displayed during battery charge, and – is displayed during battery discharge.
Status parameter The battery status is NA (battery not connected or reversely connected), Equalized
charging, Float charging, Hibernating, or Discharging.
Capacity parameter Remaining battery capacity
Backup time parameter Estimated backup time. The value is NA during battery charge.
Inverter Output Screen
Figure 4-15 shows the Inverter Output screen.
Figure 4-15 Inverter Output screen
Van, Vbn, and Vcn parameters Phase voltages displayed on the Inverter Output screen (The parameter is Voltage in
the case of single-phase input.)
la, lb, and lc parameters Phase currents displayed on the Inverter Output screen (The parameter is Current in
the case of single-phase input.)
Frequency parameter Frequency displayed on the Inverter Output screen.
Page 59
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
51
UPS Output Screen
Figure 4-16 shows the UPS Output screen.
Figure 4-16 UPS Output screen
Van, Vbn, and Vcn parameters Phase voltages displayed on the UPS Output screen (The parameter is Voltage in the
case of single-phase input.)
la, lb, and lc parameters Phase currents displayed on the UPS Output screen (The parameter is Current in the
case of single-phase input.)
Frequency parameter Frequency on displayed the UPS Output screen.
Local-UPS Load Screen
Figure 4-17 shows the Local-UPS Load screen.
Figure 4-17 Local-UPS Load screen
Single UPS Running screen A single UPS is running.
Sout_A, Sout_ B, and Sout_C parameters Phase A, B, and C apparent power displayed on the Local-UPS Load screen (The
parameter is Sout in the case of single-phase input.)
Pout_A, Pout_ B, and Pout_C parameters Phase A, B, and C active power displayed on the Local-UPS Load screen (The
parameter is Pout in the case of single-phase input.)
Load ratio_A, Load ratio_B, and Load ratio_C parameters
Page 60
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
52
Phase A, B, and C load ratio displayed on the Local-UPS Load screen (the parameter is Load ratio in the case of single-phase input.)
Parallel-System Load Screen
Figure 4-18 shows the Parallel-System Load screen.
Figure 4-18 Parallel-System Load screen
N+X Parallel-System screen A parallel system is running. X (value range: 0–3) indicates the number of redundant
UPSs (configurable on the LCD); N (value range: 1–4) indicates the number of requisite UPSs (total number of UPSs minus X). The total number of UPSs is automatically identified by the system.
Sys. Sout_A, Sys. Sout_ B, and Sys. Sout_C parameters System phase A, B, and C apparent power displayed on the Parallel-System Load
screen. The parameter is Sys. Sout in the case of single-phase input; the parameters are not displayed in single UPS mode.
Sys. Pout_A, Sys. Pout_ B, and Sys. Pout_C parameters System phase A, B, and C active power displayed on the Parallel-System Load screen.
The parameter is Sys. Pout in the case of single-phase input; the parameters are not displayed in single UPS mode.
Sys. Load ratio_A, Sys. Load ratio_B, and Sys. Load ratio_C parameters System phase A, B, and C load ratio displayed on the Parallel-System Load screen. The
parameter is Sys. Load ratio in the case of single-phase input, and the parameters are not displayed in single UPS mode.
System information is not displayed in single UPS mode.
Environment Monitoring Screen
Figure 4-19 shows the Environment Monitoring screen.
Page 61
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
53
Figure 4-19 Environment Monitoring screen
Ambient temp. parameter Temperature detected by the ambient temperature and humidity sensor (used together
with an SNMP card; if the sensor is not connected, NA is displayed.)
Ambient humidity Temperature and humidity sensor humidity (Install an SNMP card and a temperature and
humidity sensor; if they are not installed, NA is displayed.)
Internal temp. parameter Temperature in the UPS cabinet
Runtime Screen
Figure 4-20 shows the Runtime screen.
Figure 4-20 Runtime screen
Inv. runtime parameter Time during which the UPS runs in inverter output state
BPS runtime parameter UPS bypass running duration
4.6.2 Alarms Screen
On the Main Menu screen, select Alarms, and press . The Alarms screen is displayed.
When the buzzer buzzes, hold down for 2–5 seconds to mute it. The buzzer is muted when you release the button. When the buzzer is mute, it can not be buzzes again, until a new alarm is generated.
Active Alarms Screen
The Active Alarms screen displays the active alarm information, such as the alarm serial number, severity, ID, and name, as shown in Figure 4-21.
Page 62
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
54
Figure 4-21 Active Alarms screen
If an alarm is generated, press the INFO button on the default screen. On the Active Alarms screen, view the active alarms.
Historical Alarms Screen
The Historical Alarms screen displays the historical alarm information, such as the alarm serial number, severity, ID, and name, as shown in Figure 4-22.
Figure 4-22 Historical Alarms screen
Sort Alarms Screen
The Sort Alarms screen allows you to view alarms by occurrence time or severity, as shown in Figure 4-23.
Figure 4-23 Sort Alarms screen
Occurrence (latest first) parameter Alarms are sorted by occurrence time. The latest alarms are listed first.
Level (highest first) parameter Active alarms are displayed by severity. The most critical alarms are listed first.
√ is displayed next to a selected Sort Alarms.
Clear Alarms Screen
Clear the alarms that you can clear manually, as shown in Figure 4-24.
Page 63
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
55
Figure 4-24 Clear Alarms screen
4.6.3 Settings Screen
On the Main Menu screen, select Settings, and press . The Settings login screen is displayed. The preset password is 000001. After you enter a password, press . The
Settings screen is displayed, as shown in Figure 4-25.
Figure 4-25 Settings screen
Page 64
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
56
Basic Settings Screen
Figure 4-26 Basic Settings screen
Language parameter You can select Chinese, English (preset), Turkish, French, and Russian.
Change Password parameter You can change the password by choosing Settings > Basic Settings > Change
Password. The preset password is 000001. The password allows you to enter the Settings screen.
Change Feature Code parameter You can change the feature code by choosing Settings > Basic Settings > Change
Feature Code. The preset feature code is 999999. The feature code is used to restore the preset password.
Communication Card Screen
If an SNMP card is connected, set the following parameters:
Figure 4-27 SNMP card settings
IP alloc. parameter
Specifies the DHCP address allocating mode. The options include Manual and
Automatic. The default value is Manual. After the allocating mode is set to Automatic, an Allocating dialog box is displayed on the screen. If allocation
succeeds, the new IP address is displayed. If allocation fails, the IP address restores to the default one: 192.168.0.10. If the allocating mode is set to Automatic, you can only query the IP address but cannot set the IP address manually.
If the UPS monitor does not support the DHCP function, after the DHCP is selected for the SNMP card, you cannot set the IP address of the SNMP card on the UPS monitor. You are advised to update the version of the UPS monitor.
IP address parameter
Set an IP address for the SNMP card. The value ranges from 1.0.0.0 to
223.255.255.255. The default value is 192.168.0.10.
Subn. mask parameter
Page 65
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
57
Set a subnet mask for the SNMP card. The value ranges from 0.0.0.0 to
255.255.255.255. The default value is 255.255.255.0.
Gateway parameter
Set a gateway address for the SNMP card. The value ranges from 1.0.0.0 to
223.255.255.255. The default value is 192.168.0.1.
If a Modbus card is connected, the following parameters are displayed:
Figure 4-28 Modbus card settings
Comm. address parameter
Set a communications address for the Modbus card over the dual in-line package (DIP) switch on the Modbus card. The value cannot be changed on the LCD.
Baud rate parameter
Set a baud rate for the Modbus card over the DIP switch on the Modbus card. The value cannot be changed on the LCD.
If a dry contact card is connected, set the following parameters:
Figure 4-29 Dry contact card settings
Multiple statuses can be associated with one dry contact, but one status cannot be associated with multiple dry contacts.
Normal mode parameter
Set the output dry contact associated with normal mode. When the UPS is in normal or ECO mode, this dry contact is enabled. The value ranges from Dry contact1 to Dry contact6. The default value is Dry contact1.
Battery mode parameter
Set the output dry contact associated with battery mode. When the UPS is in battery or ECO mode, this dry contact is enabled. The value ranges from Dry contact1 to Dry contact6. The default value is Dry contact2.
Bypass mode parameter
Set the output dry contact associated with bypass mode. When the UPS is in bypass or ECO mode, this dry contact is enabled. The value ranges from Dry contact1 to Dry contact6. The default value is Dry contact3.
Batt. undervolt parameter
Page 66
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
58
Set the output dry contact associated with low battery voltages. When the system battery voltage is low, this dry contact is enabled. The value ranges from Dry contact1 to Dry contact6. The default value is Dry contact4.
BPS backfeed parameter
Set the output dry contact associated with bypass backfeed. When a bypass backfeed alarm is generated, this dry contact is enabled. The value ranges from Dry contact1 to Dry contact6. The default value is Dry contact5.
Faulty UPS parameter
Set the output dry contact associated with UPS faults. When a critical alarm is generated, this dry contact is enabled. The value ranges from Dry contact1 to Dry contact6. The default value is Dry contact6.
System Parameters Screen
Parallel screen
Figure 4-30 Parallel screen
Single/Parallel parameter
The values include Single and Parallel. The default value is Single. The parameter is configurable after the inverter shuts down.
Redundant UPSs parameter
Set the number of redundant UPSs. The value ranges from 0 to 3. The default value is 0. The parameter is configurable after the inverter shuts down.
Output screen
Figure 4-31 Output screen
The UPS supports 208 V output. In the case of 208 V output, the power is derated to 90%. For cable configurations and connections, see the details about 220 V output.
Output mode parameter
Set the system output mode. The value is not configurable on the UPS2000-G-6 kVA/10 kVA. The default value is Single-phase. The parameter is configurable on the UPS2000-G-15 kVA/20 kVA. The values include Single-phase and Three-phase. The default value is Three-phase. The input mode is identified automatically by the system. The parameter is configurable after the inverter shuts down.
Page 67
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
59
Voltage level parameter
Set the system output voltage level. The values include 220 V (default), 230 V, and 240 V on the UPS2000-G-6 kVA/10 kVA. The values include 220 V (default), 230 V, and 240 V on the UPS2000-G-15 kVA/20 kVA (single-phase output). The values include 380 V (default), 400 V, and 415 V on the UPS2000-G-15 kVA/20 kVA (three-phase output). After you change the voltage level, the upper thresholds for bypass voltages restore to default values 15%. The parameter is configurable after the inverter shuts down.
Frequency level parameter
Set the system output frequency level. The values include 50 Hz (default), 60 Hz, and Automatic. If the value is Automatic, the power-on bypass frequency ranges from 40 Hz to 55 Hz, and the system output frequency is 50 Hz; if the power-on bypass frequency ranges from 55 Hz to 70 Hz (excluding 55 Hz), and the system output frequency is 60 Hz. The parameter is configurable after the inverter shuts down.
Volt. adj. coef. parameter
You can adjust the inverter rated output voltage. The values include ±5%, ±4%, ±3%, ±2%, ±1%, and 0% (default). Press + or – to increase or decrease the output voltage. The parameter is configurable after the inverter shuts down.
If you set Converter mode to Enabled, the UPS cannot transfer to bypass mode or maintenance bypass mode. If you shut down the inverter, the loads power off.
Converter mode parameter
Determine whether to enable inverter mode. The values include Disabled and Enabled. The default value is Disabled. In converter mode, the output voltage and frequency are fixed at the specified values. The parameter is configurable after the inverter shuts down.
Bypass screen
Figure 4-32 Bypass screen
Max. voltage parameter
Upper threshold for the bypass voltage. If the difference between the bypass voltage and the rated output voltage exceeds this value, the system determines that the bypass voltage is abnormal and that the bypass is unavailable.
The Max. voltage parameter is associated with the system voltage level. The default value is 15%.
If the voltage system is 220 V (380 V in the case of three-phase outputs), the values include 10%, 15%, 20%, and 25%.
Page 68
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
60
If the voltage system is 230 V (400 V in the case of three-phase outputs), the values include 10%, 15%, and 20%.
If the voltage system is 240 V (415 V in the case of three-phase outputs), the values include 10% and 15%.
The parameter is configurable after the inverter shuts down.
Min. voltage parameter
Lower threshold for the bypass voltage. If the difference between the bypass voltage and the rated output voltage exceeds this value, the system determines that the bypass voltage is abnormal and that the bypass is unavailable. The values include 10%, 20% (default), 30%, 40%, 50%, and 60%. The parameter is configurable after the inverter shuts down.
Frequency range parameter
Bypass frequency range. When the difference between the bypass input frequency and the rated frequency is greater than this value, the system determines that the bypass frequency is abnormal and that the bypass is unavailable.
The frequency range must be greater than the ECO frequency range. The values include ±0.5 Hz, ±1 Hz, ±2 Hz (default), ±3 Hz, ±4 Hz, ±5 Hz, and ±6 Hz. The parameter is configurable after the inverter shuts down.
ECO screen
Figure 4-33 ECO screen
You can use the ECO function only if power grid conditions are good and the voltage and frequency fluctuation is within the specified ECO voltage and frequency range.
Max. voltage parameter
Upper threshold for the ECO voltage. In ECO mode, when the difference between the bypass voltage and the rated voltage is greater than this value, the system determines that the ECO voltage is abnormal and transfers to normal mode. The values include 5%, 6%, 7%, 8%, 9%, and 10% (default). The parameter is configurable after the inverter shuts down.
Min. voltage parameter
Lower threshold for the ECO voltage. In ECO mode, when the difference between the bypass voltage and the rated voltage is greater than this value, the system determines that the ECO voltage is abnormal and transfers to normal mode. The values include 5%, 6%, 7%, 8%, 9%, and 10% (default). The parameter is configurable after the inverter shuts down.
Frequency range parameter
ECO frequency range. In ECO mode, when the difference between the bypass frequency and the rated frequency is greater than this range, the system determines that the ECO frequency is abnormal and transfers to normal mode.
Page 69
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
61
The frequency range must be less than the current bypass frequency range. The values include ±0.5 Hz, ±1 Hz, ±2 Hz (default), and ±3 Hz. The parameter is configurable after the inverter shuts down.
Single UPS ECO parameter
Determine whether to support ECO mode on a single UPS (ECO mode is not supported in a parallel system). The values include Disabled and Enabled. The default value is Disabled. The parameter is configurable after the inverter shuts down.
Power Segment screen
Figure 4-34 Power Segment screen
In single UPS mode, primary loads connect to sL, and secondary loads connect to pL.
In single UPS mode, if power segment is enabled, pL is disconnected and sL continues with power output when an overload occurs.
In a parallel system, UPS AC output power cables connect to pL.
Dis. time. thres. parameter
pL terminal loading time in battery mode when power segment (not supported in a parallel system) is enabled. In battery mode, if the discharge time exceeds this value, the UPS disconnects from secondary loads. The value ranges from 0 Min to 999 Min, in units of minutes. The default value is 30 Min. The parameter is configurable in non-battery mode or non-battery ECO mode.
The UPS2000-G-15 kVA/20 kVA supports battery ECO mode only in the case of two mains inputs. In battery ECO mode, the bypass supplies power to the UPS, and batteries are used as backup power. If the bypass is abnormal, the UPS transfers to battery mode.
Dis. volt. thres. parameter
Set the lower threshold for the battery voltage when pL loading is allowed in battery mode when power segment (not supported in a parallel system) is enabled. In battery mode, if the battery voltage is less than this value, the UPS disconnects from secondary loads. The value ranges from 1.90 V/cell to 2.25 V/cell. The default value is 2.00 V/cell. The parameter is configurable in non-battery mode or non-battery ECO mode.
Power segment parameter
Determine whether to enable power segment in singe UPS mode (power segment is not supported in a parallel system). The values include Disabled and Enabled. The default value is Disabled. The parameter is configurable after the inverter shuts down.
Self-Load screen
Page 70
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
62
Figure 4-35 Self-Load screen
Output power ratio parameter
This parameter is used during the tests before shipment. The value ranges from 20% to 100%. The default value is 80%. The parameter is configurable after the inverter shuts down.
Self-load mode parameter
This parameter is used during the tests before shipment. The values include Disabled and Enabled. The default value is Disabled. The parameter is configurable after the inverter shuts down.
Others screen
Figure 4-36 Others screen
Recovery delay time parameter
Delay time that the UPS takes in transferring from battery mode to normal mode when the mains recovers. The value ranges from 0S to 900S. The default value is 5S. The parameter is configurable after the inverter shuts down.
If Recovery delay time is set to 0S, the actual recovery delay time is 1 second.
Max. BPS transfers parameter
Maximum number of bypass transfers within 30 minutes. The value ranges from 1 to 3. The default value is 3. When the number of bypass transfers exceeds the maximum, the UPS keeps running is bypass mode (in ECO mode, the UPS keeps running in normal mode). The parameter is configurable after the inverter shuts down.
Do not set the UPS to ECO mode when the system output connects to an isolated transformer.
Output transformer parameter
If an output transformer is connected, set the parameter to Enabled; otherwise, set it to Disabled. The values include Disabled and Enabled. The default value is Disabled. The parameter is configurable after the inverter shuts down.
Page 71
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
63
When you install a transformer on the output side, you must connect the load to the pL terminal and disable power segment.
Generator mode parameter
The values include Weak adaptability mode, Balance mode, and Strong adaptability mode. The default value is Balance mode. When the mains input voltage quality is good, select Weak adaptability mode; when the quality is average (for example, the mains input is from a high-performance generator or a common power grid), select Balance mode; when the quality is poor (for example, the mains input is from a common generator), select Strong adaptability mode. The parameter is configurable after the inverter shuts down.
Auto check bus capa. parameter
Determine whether to automatically check the bus capacitance upon power-on and generate capacitance failure warnings. The values include Disabled and Enabled. The default value is Enabled. If the value is Enabled, UPS startup takes additional 30–180 seconds. The parameter is configurable after the inverter shuts down.
Auto start parameter
Determine whether to automatically start inverter output after the UPS connects to the mains. The values include Disabled and Enabled. The default value is Disabled. The parameter is configurable after the inverter shuts down.
No battery alarm
This parameter is set to Enabled by default. If it is set to Disabled, the No battery alarm will not be reported. This parameter automatically changes to Enabled after
batteries are connected. It is configurable only when batteries are not connected.
If the batteries have been connected and you try to set this parameter, a message "Batteries have been connected. This parameter cannot be set." will be displayed.
Battery Parameters Screen
The configured number of batteries must match the actual number. When the actual number changes, change the configured number. If the configured number is less than the actual number, the battery lifespan is shortened. If the configured number is greater than the actual number, battery leakage may cause a fire.
Page 72
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
64
The UPS2000-G-6 kVA/10 kVA parallel system cannot shares a battery string.
If a UPS2000-G-15 kVA/20 kVA parallel system shares a battery string, set the same battery string capacity and charge current for each UPS.
Battery capacity (Ah) = Capacity of a single battery string x Number of parallel battery strings/Number of parallel UPSs sharing a battery string. Maximum charge current (Ah) =
0.1 x Capacity of a single battery string x Number of parallel battery strings/Number of parallel UPSs sharing a battery string. If the calculated maximum charge current is greater than 4 A, set it 4 A. Use two UPSs sharing a 65 Ah battery string as an example: If the calculated battery capacity is 65 x 1/2 = 32.5, set it to 32 Ah; if the calculated maximum current is 0.1 x 65 x 1/2 = 3.25, set it to 3.0 A.
If a single 15 kVA/20 kVA UPS connects to two battery packs, the maximum charge current must be less than or equal to 2.0 A.
Basic screen
Figure 4-37 Basic screen
Number of batteries/Positive batteries and Negative batteries parameters
Set the number of batteries. The value ranges from 16 to 20. The default value is 20. When the number of batteries N is less than 20, the system output power is derated to N/20 in battery mode. The parameter is configurable in non-battery mode or non-battery ECO mode. You need to set Number of batteries on the UPS2000-G-6 kVA/10 kVA, and set two battery strings (positive and negative) on the UPS2000-G-15 kVA/20 kVA.
Battery capacity parameter
Set the battery string capacity. The value ranges from 7 Ah to 1000 Ah. For the UPS2000-G-6 kVA, the default value is 7 Ah on a standard model and 40 Ah on a long backup time model; for the UPS2000-G-10 kVA, the default value is 9 Ah on a standard model and 65 Ah on a long backup time model; for the UPS2000-G-15 kVA/20 kVA, the default value is 65 Ah on a long backup time model. Battery capacity is the sum of all battery capacities, set the parameters based on the actual battery capacity. The parameter is configurable in non-battery mode or non-battery ECO mode.
Intelli. Hibernation
This parameter is set to disabled by default. When it is set to enabled, the intelligent battery hibernation function is enabled. The parameter is configurable in any mode.
Overtemp. thres. parameter
Set an alarm threshold for high battery temperatures. The value ranges from 45ºC to 55ºC. The default value is 50ºC. The parameter is configurable in any mode.
Undertemp. thres. parameter
Page 73
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
65
Set an alarm threshold for low battery temperatures. The value ranges from –30ºC to +5ºC. The default value is –5ºC. The parameter is configurable in any mode.
Overcurrent thres. parameter
Set an alarm threshold for battery overcurrent. On a standard model, the value ranges from 2.0 A to 4.0 A, and the default value is 3.0 A. On a long backup time model, the value ranges from 4.0 A to 8.0 A, and the default value is 6.0 A. The parameter is configurable in any mode.
Equalized Charge screen
Figure 4-38 Equalized Charge screen
Equalized charging parameter
Determine whether to enable equalized charging. The values include Disabled and Enabled. The default value is Enabled. The parameter is configurable in any mode.
Time interval parameter
Set the time interval for equalized charging. The value ranges from 30Day to 180Day. The default value is 60Day. The parameter is configurable in any mode.
Voltage parameter
Set the battery equalized voltage. The value ranges from 2.33 V/cell to 2.40 V/cell. The default value is 2.35 V/cell. The parameter is configurable in any mode.
Max. current parameter
Set the maximum equalized current. On a standard model, the value ranges from 1.0 A to 2.0 A, and the default value is 2.0 A. On a long backup time model, the value ranges from 1.0 A to 4.0 A, and the default value is 2.0 A. The parameter is configurable in any mode.
Max. time parameter
Set the maximum equalized charge time. The value ranges from 600Min to 999Min. The default value is 960Min. The parameter is configurable in any mode.
Float Charge screen
Figure 4-39 Float Charge screen
Voltage parameter
Set the battery float voltage. The value ranges from 2.25 V/cell to 2.30 V/cell. The default value is 2.25 V/cell. The parameter is configurable in any mode.
Temp. comp. coef. parameter
Page 74
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
66
Set a float voltage correction coefficient based on the battery temperature when a battery temperature sensor is connected. The value ranges from 0.0 mV/°C*cell to
6.0 mV/°C*cell. The default value is 3.3 mV/°C*cell. The parameter is configurable in any mode.
Discharge screen
Figure 4-40 Discharge screen
Max. time parameter
Set the maximum discharge time. When the discharge time reaches the value, the UPS powers off. The value ranges from 0Hour to 24Hour. The default value is 16Hour. If you set the value to 0Hour, the discharge time is not limited. The parameter is configurable in non-battery mode or non-battery ECO mode.
If you expect the battery discharge time to be greater than 24 hours, set Max. time to 0 hour. Otherwise, the system may power off.
If you set Max. time to 0 hour, the battery string may remain in the small-current discharge state according to the proportion of the battery capacity to the load power, which affects the battery lifecycle.
EOD mode parameter
Determine the power backup time. The values include Backup time first (ensures system running and has a long backup time, Table 4-5 shows the EOD setting values), Batt. protect first (protects batteries and extends the battery lifespan,
Table 4-6 shows the EOD setting values), and Balanced mode (Table 4-7 shows the
EOD setting values). The default value is Backup time first. The parameter is configurable in non-battery mode or non-battery ECO mode. EOD is short for end of discharge.
Table 4-5 Backup time first EOD setting values
Expected backup time
≤ 0.1 CA
0.1 CA to
0.5 CA
0.5 CA to 1 CA
1 CA to 3 CA
> 3 CA
Low voltage warning threshold (V/cell)
1.85
1.85
1.85
1.85
1.85 EOD threshold (V/cell)
1.75
1.67
1.60
1.60
1.60
Page 75
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
67
Table 4-6 Batt. protect first EOD setting values
Expected backup time
≤ 0.1 CA
0.1 CA to
0.5 CA
0.5 CA to 1 CA
1 CA to 3 CA
> 3 CA
Low voltage warning threshold (V/cell)
1.90
1.90
1.90
1.90
1.90 EOD threshold (V/cell)
1.85
1.85
1.83
1.75
1.67
Table 4-7 Balanced mode EOD setting values
Expected backup time
≤ 0.1 CA
0.1 CA to
0.5 CA
0.5 CA to 1 CA
1 CA to 3 CA
> 3 CA
Low voltage warning threshold (V/cell)
1.85
1.85
1.85
1.85
1.85 EOD threshold (V/cell)
1.80
1.75
1.70
1.67
1.65
EOD auto-start parameter
Determine whether to automatically start inverter output after the mains becomes normal. The values include Disabled and Enabled. The default value is Enabled. The parameter is configurable after the inverter shuts down.
Shutdown delay parameter
When the delay time reaches the value after UPS transfers to battery mode, the UPS powers off. The value ranges from 0S to 600S. The default value is 0S. The value interval is 30S. For example, the value can be 0S, 30S, 60S, and 90S. If the delay time is set to 0S, the shutdown delay function is disabled. If the delay time is set to other values, ensure that backup time is greater than shutdown delay time. Otherwise, the power supply to loads may be disconnected. The parameter is configurable in non-battery mode or non-battery ECO mode.
Shutdown delay parameters are asynchronous in a parallel system. When used in a parallel system, set the same shutdown delay parameter for different UPSs.
Shallow Discharge screen
Page 76
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
68
Figure 4-41 Shallow Discharge screen
Test notification parameter
Determine whether to periodically send shallow discharge test notifications. The values include Disabled and Enabled. The default value is Disabled. If the value is Enabled, the system sends shallow discharge test notifications. The parameter is configurable in any mode.
Time interval parameter
Set the time interval for shallow discharge tests. The value ranges from 30Day to 90Day. The default value is 60Day. The parameter is configurable in any mode.
Discharge ratio parameter
Set the proportion of the discharge capacity to the total discharge capacity. The value ranges from 10% to 50%. The default value is 20%. The parameter is configurable in any mode.
Restoring Factory Settings
You can restore factory settings after the inverter shuts down.
4.6.4 Control Screen
On the Main Menu screen, select Control, and press . The Control screen is displayed.
Startup Menu
The Startup menu allows you to restart the inverter.
Figure 4-42 Startup screen
Shutdown Menu
The Shutdown menu allows you to shut down the inverter.
Page 77
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
69
Figure 4-43 Shutdown screen
Replace Batteries Menu
If the batteries have been replaced for the system, set this parameter. The parameter is configurable in non-battery mode or non-battery ECO mode.
Figure 4-44 Replace Batteries screen
Maintain Batteries Menu
Shallow Discharge Test menu
Figure 4-45 Shallow Discharge Test screen
Capacity Test menu After you completely discharge batteries, the load ratio must be in the range of
20%–80%.
Stop Test menu
Figure 4-46 Stop Test screen
Stop the shallow discharge test or capacity test.
Manual EC for Pos. menu
Page 78
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
70
Figure 4-47 Manual EC for Pos. screen
Perform equalized charging on batteries forcibly. For the 6 kVA and 10 kVA UPSs, perform manual equalized charging. For the 15 kVA and 20 kVA UPSs, batteries in positive and negative groups are manually switched to equalized charging respectively.
Manual FC for Pos. menu
Figure 4-48 Manual FC for Pos. screen
Perform float charging on batteries forcibly. For the 6 kVA and 10 kVA UPSs, perform manual float charging. For the 15 kVA and 20 kVA UPSs, batteries in positive and negative groups are manually switched to float charging respectively.
Sync Paral. Param. Menu
The menu allows you to synchronize the parameters from one UPS to the other UPSs in the parallel system. The UPS running in inverter output state cannot be synchronized.
Figure 4-49 Sync Paral. Param. screen
For the parallel parameters that can be synchronized, see appendix A Parallel Parameter List.
Resetting the Password
Enter a feature code to restore the preset password.
Page 79
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
71
Figure 4-50 Resetting the password
Control Buzzer
Control Buzzer control the buzzer on/off. If the buzzer on, click Control Buzzer transfer to Buzzer off.
Figure 4-51 Buzzer off screen
If Control Buzzer is used for muting the alarm tone, the alarm tone should be unmuted by using Control Buzzer or power on the UPS again. Otherwise, when a new alarm is generated, it cannot buzz again.
If the buzzer off, click Control Buzzer transfer to Buzzer on.
Figure 4-52 Buzzer on screen
4.6.5 About Screen
On the Main Menu screen, select About, and press . The About screen is displayed, as shown in Figure 4-53.
You can view the UPS model, equipment serial number (ESN), and version number.
Figure 4-53 About screen
Page 80
UPS2000-G-(6 kVA-20 kVA) User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
72
MU1MSW1, PU1RSW1, PU1RSW2, PU1ISW1, and PU1ISW2 is the version for the component. When the component does not exist, NA is displayed for Version. PU1ISW1 and PU1ISW2 are not available for the UPS 6 kVA and UPS 10 kVA.
Model parameter The UPS model is 20K UPS.
ESN parameter This item provides the UPS ESN.
Version parameter This item provides the UPS version.
MU1MSW1 parameter This item provides the main monitoring software version.
PU1RSW1 parameter This item provides rectifier power software version.
PU1RSW2 parameter This item provides the rectifier logic software version.
PU1ISW1 parameter This item provides the inverter power software version.
PU1ISW2 parameter This item provides the inverter logic software version.
Page 81
UPS2000-G-(6 kVA-20 kVA) User Manual
5 Operations
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
73
5 Operations
5.1 Checking Before Powering On the UPS
AC power cable colors comply with local electrical regulations.
No short circuits occur in inputs and outputs.
Cables are securely connected.
Battery cables are correctly connected to battery terminals. The battery voltage meets the requirements.
Cables are properly connected between the UPS and batteries.
Input circuit breakers and load circuit breakers are OFF.
Power cables and signal cables are correctly identified.
The input phase sequence is correct.
Cables are neatly routed and securely bound.
Devices are installed and cables are routed in ways that facilitate modification, capacity expansion, and maintenance.
Parallel cables are properly connected.
The UPS is properly grounded.
The voltage between the neutral wire and the ground cable is less than 5 V AC.
The input voltage rang for the mains to start the UPS is 120–280 V AC (or 80–280 V AC after the UPS powers on). The battery voltage range is (Number of batteries x 10.8)–280 V DC.
5.2 Single UPS Operations
5.2.1 Starting the UPS
Page 82
UPS2000-G-(6 kVA-20 kVA) User Manual
5 Operations
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
74
The configured number of batteries must match the actual number. When the actual number changes, change the configured number. If the configured number is less than the actual number, the battery lifespan is shortened. If the configured number is greater than the actual number, battery leakage may cause a fire.
If the system uses three-phase input three-phase output, set Output mode to Three-phase. If the system uses three-phase input single-phase output or single-phase input single-phase output, set Output mode to Single-phase.
Set Voltage level and Frequency level based on the rated voltage and frequency. In the case of single-phase output, set Voltage level to 220 V (default), 230 V, or 240 V; in the case of three-phase output, set Voltage level to 380 V (default), 400 V, or 415 V.
Battery parameters are configurable in non-battery mode or non-battery ECO mode.
Set Positive batteries and Negative batteries. The value ranges from 16 to 20. The default value is 20.
Set Battery capacity to the total capacity of all batteries actually connected. The value ranges from 7 Ah to 1000 Ah. The default value is 65 Ah.
This section describes how to start the UPS2000-G-15 kVA/20 kVA.
Figure 5-1 Connecting cables to the UPS2000-G-15 kVA/20 kVA (three-phase input three-phase output, dual mains)
Page 83
UPS2000-G-(6 kVA-20 kVA) User Manual
5 Operations
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
75
Starting the UPS in Normal Mode
Step 1 Close the external battery circuit breaker (if there is), or connect battery cables. Step 2 Close the UPS mains input circuit breaker Km1 and bypass input circuit breaker Kb1.
The initialization screen is displayed.
Perform Step 2 when there are two mains inputs. In the case of one mains input, you need only to close the UPS mains input circuit breaker.
Step 3 The UPS enters bypass mode. The UPS sL delivers bypass voltages, and pL delivers no
voltage. When the initialization is complete, perform the following operations:
Initial startup On the Settings wizard screen, set the language (the preset language is English), system
parameters, and battery parameters. Press . The standby screen is displayed.
Non-initial startup When the initialization is complete, the standby screen is displayed. On the standby
screen, press to enter the main menu. Choose Main Menu > Settings > System Parameters > Output to view output settings: if the system uses three-phase input three-phase output, Output mode is set to Three-phase; if the system uses three-phase input single-phase output or single-phase input single-phase output, Output mode is set to Single-phase. Voltage level and Frequency level are set based on the rated voltage and frequency. Press ESC to return to the standby screen.
Step 4 Start the UPS in normal mode by using one of the following methods:
On the standby screen, hold down more than 5 seconds. Release the button when you hear a beep sound. The startup screen is displayed. If the UPS starts successfully, it enters normal mode.
On the standby screen, hold down to enter the main menu. Select Startup in the Control menu, and press . The Starting message is displayed. If the UPS starts
successfully, it enters normal mode.
The two methods in Step 4 are called "startup operations" in this section.
Step 5 When the UPS runs properly, close the UPS AC output circuit breaker Q1, and start the loads.
To prevent triggering overload protection, start the loads with higher power and then loads with lower power.
----End
Starting the UPS in Battery Mode
Step 1 Close the external battery circuit breaker (if there is), or connect battery cables.
Step 2 Press on the control panel.
The LCD starts. The initialization screen is displayed.
Page 84
UPS2000-G-(6 kVA-20 kVA) User Manual
5 Operations
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
76
Initial startup When the initialization is complete, the Settings wizard screen is displayed. Set the
language (the preset language is English), system parameters, and battery parameters, and press . The standby screen is displayed.
Non-initial startup When the initialization is complete, the standby screen is displayed. On the standby
screen, press to enter the main menu. Choose Main Menu > Settings > System Parameters > Output to view output settings: if the system uses three-phase input three-phase output, Output mode is set to Three-phase; if the system uses three-phase input single-phase output or single-phase input single-phase output, Output mode is set to Single-phase. Voltage level and Frequency level are set based on the rated voltage and frequency. Press ESC to return to the standby screen.
Step 3 Perform "startup operations" on the UPS. The UPS runs in battery mode. Step 4 When the UPS runs properly, close the UPS AC output circuit breaker Q1, and start the loads.
To prevent triggering overload protection, start the loads with higher power and then loads with lower power.
----End
5.2.2 Shutting down the UPS
Shutting down the Inverter
To shut down the inverter, perform any of the following operations:
On the default screen, hold down ESC for more than 5 seconds. Release the button when you hear a beep sound. The inverter shuts down, and the UPS transfers to bypass mode.
On the default screen, press to enter the main menu. Choose Shutdown to shut down the inverter. The UPS transfers to bypass mode.
The two methods are called "shutdown operations" in this section.
Shutting down the UPS
Step 1 Shut down the loads. Step 2 Perform "shutdown operations" on the UPS. The inverter shuts down. The UPS transfers to
bypass mode.
Step 3 Open the UPS mains input circuit breaker Km1, bypass input circuit breaker Kb1, and output
circuit breaker Q1.
Perform Step 3 when there are two mains inputs. In the case of one mains input, you need only to open the UPS mains input circuit breaker.
Step 4 Open the external battery circuit breaker (if there is), or disconnect battery cables.
----End
Page 85
UPS2000-G-(6 kVA-20 kVA) User Manual
5 Operations
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
77
5.2.3 Performing EPO
Turn on the EPO switch (provided by the customer). The UPS enters the EPO state. That is, the inverter shuts down, and the UPS will not transfer to bypass mode.
Figure 5-2 shows the EPO cable connection on a single UPS.
Figure 5-2 EPO cable connection on a single UPS
Connect an external switch to the EPO port on the UPS. After you turn on the switch, the inverter shuts down, and the UPS will not transfer to bypass mode. Output terminals completely power off, which meets the EPO purpose.
The external EPO switch (switch or dry contact signals controlled by a switch) is provided by the customer.
5.3 Parallel System Operations
This section describes operations on a UPS2000-G-15 kVA/20 kVA parallel system.
Page 86
UPS2000-G-(6 kVA-20 kVA) User Manual
5 Operations
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
78
Figure 5-3 Connecting cables to the UPS2000-G-15 kVA/20 kVA parallel system (three-phase input three-phase output, dual mains) equipped with no PDU
5.3.1 Starting the Parallel System
The configured number of batteries must match the actual number. When the actual number changes, change the configured number. If the configured number is less than the actual number, the battery lifespan is shortened. If the configured number is greater than the actual number, battery leakage may cause a fire.
Page 87
UPS2000-G-(6 kVA-20 kVA) User Manual
5 Operations
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
79
If a parallel system shares a battery string, set the same battery string capacity and charge current for each UPS.
Before you start the parallel system, ensure that UPS output circuit breakers are both ON.
Check that parallel parameters have been synchronized. For the parallel parameters to be synchronized, see appendix A Parallel Parameter List.
In a 4+0 parallel system, the four parallel cables must be of the same length (1 meter or longer), and connect to a remote junction box.
In the parallel system that uses the TN-C power distribution system, install four magnetic rings on the PE cable on each UPS, bind the four magnetic rings together using binding tape, and secure them in the nearest place. For the magnetic ring specifications, see Table
2-2.
Before starting a parallel system, ensure that all circuit breakers on the output side are OFF, and do not start loads.
To prevent triggering overload protection, start the loads with higher power and then loads with lower power.
Starting the Parallel System in Normal Mode
Perform the following steps to start the parallel system for the system to work in normal mode.
Step 1 Close the external battery circuit breakers (if there are), or connect battery cables. Step 2 Close the following circuit breakers in sequence: UPS mains input circuit breakers Km1 and
Km2, general mains input circuit breaker Km, bypass input circuit breakers Kb1 and Kb2, general bypass input circuit breaker Kb, and UPS AC output circuit breakers Q1 and Q2.
The initialization screen is displayed. The parallel system supplies no power.
Perform Step 2 when there are two mains inputs. In the case of one mains input, you need only to close the UPS mains input circuit breakers and general mains input circuit breaker.
If a PDU is configured, close the following circuit breakers: general mains input circuit breaker, general bypass input circuit breaker, mains input circuit breakers for all UPSs on the PDU, bypass input circuit breakers, and output circuit breakers for all UPSs on the PDU. The initiation screen is displayed.
Step 3 Perform the following operations on each UPS:
Initial startup a. Setting parameters on the Settings wizard screen
When the initialization is complete, the Settings wizard screen is displayed. Set the language, system parameters, and battery parameters, and press . The standby
screen is displayed.
b. Settings for transferring from single mode (preset) to parallel mode
On the standby screen, press . Choose Main Menu > Settings > System Parameters > Parallel > Single/Parallel to transfer from single mode to parallel mode. Press ESC to return to the standby screen.
Non-initial startup
Page 88
UPS2000-G-(6 kVA-20 kVA) User Manual
5 Operations
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
80
When the initialization is complete, the standby screen is displayed. On the standby screen, press to enter the main menu. Choose Main Menu > Settings > System
Parameters > Output to view output settings: if the system uses three-phase input three-phase output, Output mode is set to Three-phase; if the system uses three-phase input single-phase output or single-phase input single-phase output, Output mode is set to Single-phase. Voltage level and Frequency level are set based on the rated voltage and frequency. Press ESC to return to the standby screen.
Step 4 Perform "startup operations" on each UPS in the parallel system.
The parallel system transfers to normal mode.
After you perform "startup operations" on UPS 1 to UPS n one by one, UPS 1 to UPS n are starting. If you do not perform "startup operations" on the other UPSs in 5 minutes, UPS 1 to UPS n enter normal mode, and the other UPSs supply no power.
Step 5 When the parallel system runs properly, close the general output circuit breaker Q (provided
by the customer) and then branch output circuit breakers (provided by the customer), and start the loads.
----End
Starting the Parallel System in Battery Mode
Step 1 Close the external battery circuit breakers (if there are), or connect battery cables. Step 2 Close the AC output circuit breakers Q1 and Q2 for the parallel system.
Step 3 Press on each control panel.
The initialization screen is displayed on each LCD. On the standby screen, press to enter the main menu. Choose Main Menu > Settings > System Parameters > Output to view output settings: if the system uses three-phase input three-phase output, Output mode is set to Three-phase; if the system uses three-phase input single-phase output or single-phase input single-phase output, Output mode is set to Single-phase. Voltage level and Frequency level are set based on the rated voltage and frequency. Press ESC to return to the standby screen.
Step 4 Perform the following operations on each UPS:
Initial startup a. Setting parameters on the Settings wizard screen
When the initialization is complete, the Settings wizard screen is displayed. Set the language, system parameters, and battery parameters, and press The standby
screen is displayed.
b. Settings for transferring from single mode (preset) to parallel mode
On the standby screen, press . Choose Main Menu > Settings > System Parameters > Parallel > Single/Parallel to transfer from single mode to parallel mode. Press ESC to return to the standby screen.
Non-initial startup When the initialization is complete, the standby screen is displayed.
Step 5 Perform "startup operations" on each UPS.
Page 89
UPS2000-G-(6 kVA-20 kVA) User Manual
5 Operations
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
81
The parallel system transfers to battery mode.
After you perform "startup operations" on UPS 1 to UPS n one by one, UPS 1 to UPS n are starting. If you do not perform "startup operations" on the other UPSs in 5 minutes, UPS 1 to UPS n enter normal mode, and the other UPSs supply no power.
Step 6 When the parallel system runs properly, close the general output circuit breaker Q (provided
by the customer) and then branch output circuit breakers (provided by the customer), and start the loads.
----End
5.3.2 Shutting down the Parallel System
Shutting down a Single UPS in the Parallel System
Step 1 Perform "shutdown operations" twice on a single UPS within 30 seconds (for example, UPS 1
shown in Figure 5-3) in the parallel system. The UPS is shutting down. The other UPSs continue working.
The UPSs in the parallel system have shut down supply no power (the mains indicator, bypass indicator, and battery indicator are Off).
Step 2 Open the UPS mains input circuit breaker Km1, bypass input circuit breaker Kb1, and the AC
output circuit breaker Q1. After all indicators turn off and fans stop, the UPS shuts down.
Step 3 Open the external battery circuit breaker (if there is), or disconnect battery cables. The UPS
exits the parallel system.
To merely shut down the UPS, perform Step 1 only.
----End
Transferring the Parallel System to Bypass Mode
Perform "shutdown operations" on each UPS in the parallel system. All inverters shut down at the same time, and the parallel system transfers to bypass mode.
Shutting down the Parallel System
Step 1 Shut down the loads. Step 2 Perform "shutdown operations" on each UPS in the parallel system. All inverters shut down at
the same time. The parallel system transfers to bypass mode.
Step 3 Open the following circuit breakers in sequence for each UPS: UPS mains input circuit
breakers Km1 and Km2, general mains input circuit breaker Km, bypass input circuit breakers Kb1 and Kb2, general bypass input circuit breaker Kb, UPS AC output circuit breakers Q1 and Q2, and general AC output circuit breaker Q. After all indicators turn off and fans stop, the UPSs shut down, and the loads power off.
Page 90
UPS2000-G-(6 kVA-20 kVA) User Manual
5 Operations
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
82
Perform Step 3 when there are two mains inputs. In the case of one mains input, you need only to open the following circuit breakers in sequence for each UPS: UPS mains input circuit breakers, general mains input circuit breaker, UPS AC output circuit breakers, and general AC output circuit breaker.
Step 4 Open the external battery circuit breaker for each UPS or the general battery circuit breaker
(when all UPSs share a battery string). If no external battery circuit breaker is configured, disconnect battery cables from each UPS.
----End
5.3.3 Performing EPO
Turn on the EPO switches (provided by the customer). The parallel system enters the EPO state. That is, the inverters shut down, and the parallel system will not transfer to bypass mode.
Figure 5-4 shows the EPO cable connection in a parallel system.
Figure 5-4 EPO cable connection in a parallel system
Connect an external switch to the EPO port on the UPS. After you turn on the switch, the UPS stops inverter output and does not transfer to bypass mode. Output terminals completely power off, which meets the emergency power-off purpose.
The external EPO switch (switch or dry contact signals controlled by a switch) is provided by the customer.
Page 91
UPS2000-G-(6 kVA-20 kVA) User Manual
6 Communications
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
83
6 Communications
6.1 Optional Communications Components
The optional communications components include the SNMP card, Modbus card, and dry contact card.
6.2 SNMP Card
The SNMP card is an optional monitoring component of the UPS. It provides Simple Network Management Protocol (SNMP) agent and web management functions. The SNMP card allows users to remotely manage the UPS by using a network management system (NMS), NetEco, or a web browser on a computer network. A maximum of 16 SNMPv3 users and 1 SNMPv1&SNMPv2c user can manage the UPS. A maximum of 2 web users can manage the UPS online.
The SNMP card has an exquisite, advanced, and unique design, and features high performance and reliability. It has the following functions and features:
Supports UPS2000-G series and implements parallel system management using only one SNMP card.
Adapts to the 10 Mbit/s, 100 Mbit/s fast Ethernet (FE) by using an IP address that is configurable on the LCD.
Supports SNMP, Hypertext Transfer Protocol Secure (HTTPS), and Secure Shell (SSH).
Supports SNMP agent v1, v2c, and v3. The UPS MIB library can be downloaded from its own web page, instead of any CD-ROM.
Enables remote management on Windows or Linux using a web browser. The supported web browsers include Internet Explorer 8, Internet Explorer 9, Internet Explorer 10, Internet Explorer 11, and Firefox 33.1.
Provides an access security mechanism, assigns rights to users based on roles, and implements IP address control over HTTPS, SNMPv3, and SNMP access to prevent unauthorized access.
Provides comprehensive UPS management, such as producing a current diagram, displaying alarms, controlling UPS running, collecting performance data statistics, as well as allowing users to view, retrieve, and export historical alarms and operation logs.
Supports optional components such as temperature and humidity modules, AI/DI Module, iBAT 2.0, and external dry contact card.
Page 92
UPS2000-G-(6 kVA-20 kVA) User Manual
6 Communications
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
84
Works with NetShutdown, a computer and server security shutdown program developed by Huawei, to automatically shut down the computers and servers where NetShutdown is installed to protect customer data and reduce loss.
Works with RCCMD, a client shutdown software developed by Generex, to automatically and safely shut down the client that is installed with the RCCMD, thereby protecting customers' data and preventing loss.
Alarm information is sent to the specified user mailbox at the specified time.
For details about the SNMP card (old version, without USB port), see the RMS-SNMP01A V100R001 User Manual. For details about the SNMP card (new version, with USB port), see the RMS-SNMP01A V100R002 User Manual.
6.3 Modbus Card
The RMS-MODBUS01A provides an RS485 networking solution to remotely manage the UPS.
The card implements the following functions by setting the DIP switches:
Selects the Modbus protocol by using a DIP switch over the RS485 communications protocol.
Uses a DIP switch to select a two-wire or four-wire system.
Provides a DIP switch to select a build-out resistor.
Provides a DIP switch for setting the optional card address.
Supports hot swap.
For details about the Modbus card, see the RMS-Modbus01A User Manual.
6.4 Dry Contact Card
The RMS-RELAY01A is installed in an optional card slot and supports hot swap. The dry contact card provides six alarm dry contact outputs (normal mode, battery mode,
bypass mode, low battery voltage, bypass backfeed, and UPS faults) and two dry contract control inputs (one is the shutdown signal input, and the other is reserved).
For details about the dry contact card, see the RMS-RELAY01A User Manual.
6.5 External Dry Contact Card
The RMS-RELAY02B is connected to UPS together with SNMP card. The external dry contact card provides four dry contact outputs (critical alarm, minor alarm, mains mode,
battery mode, bypass mode, inverter on, battery undervolt.,bypass backfeed , high ambient tempreture, or UPS fault.) and two dry contract inputs (startup, shutdown).
For details about the dry contact card, see the RMS-RELAY02B Dry Contact Card User Manual.
The SNMP card, Modbus card, and dry contract card are optional communications components. If select it, the opration card maual delived with the optional components.
Page 93
UPS2000-G-(6 kVA-20 kVA) User Manual
7 Routine Maintenance
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
85
7 Routine Maintenance
7.1 UPS Maintenance
Only trained personnel are allowed to perform maintenance. Before performing operations on a device, wear electrostatic discharge (ESD) clothes, ESD gloves, and an ESD wrist strap. Do not wear jewelry or watches during the operation to avoid electric shocks or burns.
Use insulated tools when maintaining internal devices. Only trained personnel are allowed to perform maintenance.
Maintain UPSs regularly based on the following requirements. Otherwise, the UPSs may fail to operate properly and the lifespan may be shortened.
Table 7-1 Routine maintenance items for UPSs
Check Item
Expected Result
Troubleshooting
Maintenance Interval
Operating environment
Ambient temperature: 0–40°C
Humidity: 0–95% RH (non-condensing)
If the humidity and temperature are abnormal, check the air conditioner status.
If the input voltage is abnormal, check the power grid status and input cable connection.
Monthly
Control panel
Check that all units are operating properly by observing the status
If any alarm is present, rectify the fault by checking the device status and
Monthly
Page 94
UPS2000-G-(6 kVA-20 kVA) User Manual
7 Routine Maintenance
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
86
Check Item
Expected Result
Troubleshooting
Maintenance Interval
icons on the LCD, and no fault or alarm information is displayed in active alarm or historical alarms.
parameters. Cleanliness
Wipe the UPS surface using a white paper and the paper does not turn black.
Clean the dust, especially in the front panel.
Quarterly
Parameter
Check the output voltage level and frequency, the number of batteries and the actual battery capacity.
Reset the parameters.
Quarterly
Power cables and terminals (between the UPS and external power distribution equipment)
The insulation layers of cables are intact and terminals are free from noticeable sparks.
Replace the cables.
Secure the output terminals.
Quarterly
EPO (if configured)
Check the reliability of the EPO cable connection.
Secure the terminals.
Yearly
7.2 Battery Maintenance
Before installing batteries, read through the battery user manuals and pay attention to safety precautions and connection methods provided by battery manufacture.
When installing and maintaining batteries, pay attention to the following points:
Page 95
UPS2000-G-(6 kVA-20 kVA) User Manual
7 Routine Maintenance
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
87
Wrap tools with insulation tape to prevent electric shock.
Protect your eyes with relevant devices and apply other protective measures.
Wear rubber gloves and a protective coat in case of electrolyte overflow.
When moving batteries, avoid handling the battery upside down, handle batteries gently, and pay attention to personal safety.
Keep the battery switch off when installing or maintaining the batteries.
Precautions
Before battery maintenance, get the tools, such as handles, insulated. Do not place metal tools on exposed battery terminals.
Never use any organic solvent to clean batteries.
Never try to remove the safety valve or fill anything into batteries.
Never smoke or use fire around batteries.
After battery discharge, charge batteries to ensure a required battery capacity.
Only professionals are allowed to perform maintenance tasks.
If batteries have not been discharged for a long time, discharge and charge them in equalized mode at least once every three months to activate them. Each charge should last at least 4 hours.
Normally, discharge and charge batteries once every four to six months. Each charge should last at least 4 hours.
In high-temperature areas, discharge and charge batteries once every two months. Each charge should last at least 4 hours.
Do not overdischarge batteries. After discharging batteries, fully charge them within 24 hours.
Ensure that the battery discharge duration is 24 hours at most and 16 hours by default. If you set the value to 0 hour, the discharge time is not limited.
Routine maintenance items for batteries
Table 7-2 Routine maintenance items for batteries
Item
Expected Result
Measures
Maintenan ce Interval
Battery alarm
No battery alarm is generated.
Identify the cause based on the alarm information.
Monthly
Battery appearance
1. The surface is clean
and tidy without stains.
2. The battery
terminals are intact.
3. Batteries are free
from damage and cracks.
4. Batteries are free
from acid leakage.
If the battery appearance is abnormal, contact Huawei technical support.
Monthly
Page 96
UPS2000-G-(6 kVA-20 kVA) User Manual
7 Routine Maintenance
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
88
Item
Expected Result
Measures
Maintenan ce Interval
5. Batteries are not
deformed or bulged.
Battery operating temperature
1. The ambient battery
temperature is 25±5°C.
2. The battery
operating temperature is lower than battery temperature + 20°C.
3. Battery charge and
discharge conditions meet the requirements specified in the battery specifications.
1. Identify the cause of
the abnormal battery operating temperature.
2. If the fault persists,
contact Huawei technical support.
Monthly
Charge voltage of battery string
Equalized voltage
14.1 V x Number of batteries (tolerance ±1%)
Float voltage 13.5 V x Number of batteries (tolerance ±1%)
1. If the voltage drop
between the battery string output terminals and the battery input terminals at the UPS side is greater than 1% of the battery string voltage, check whether the cable between the battery string and the UPS is excessively long, or the cable diameter is excessively small.
2. Check whether the
equalized charging voltage and float charging voltage are correctly set for the UPS.
3. If the fault persists,
contact Huawei technical support.
Monthly
Battery temperature sensor measurement accuracy
The difference between the temperature measured by the temperature sensor and the temperature displayed on the LCD is less than 3°C.
1. Install the
temperature sensor in the correct position.
2. Replace the battery
temperature sensor.
Quarterly
Battery
The settings of battery
Set parameters correctly.
Quarterly
Page 97
UPS2000-G-(6 kVA-20 kVA) User Manual
7 Routine Maintenance
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
89
Item
Expected Result
Measures
Maintenan ce Interval
specifications
management parameters meet the requirements in the user manual.
Tightness of bolts on battery terminals
The location of the signs marked on battery terminals indicating tight connections does not change.
Take photos from multiple angles and contact Huawei technical support.
Quarterly
Cables between batteries
No cable deteriorates and the insulation layer does not crack.
Replace the faulty cable.
Quarterly
Battery voltage
Equalized charging voltage: 14.1 V ±
0.1 V
Float charging voltage: 13.5 V ±
0.1 V
1. Check whether the
equalized charging voltage and float charging voltage of a battery are normal.
2. If the charging
voltage of a battery exceeds the specifications requirement, perform a complete forcible equalized charging for the battery, and check again whether the voltage is normal.
3. If the fault persists,
contact Huawei technical support.
Quarterly
Shallow discharge test (recommended)
Conduct a shallow discharge test when the UPS is backed up to verify that the batteries can discharge normally.
1. Locate the cause
when an exception is identified.
2. If the fault persists,
contact Huawei technical support.
Quarterly
Capacity Test (recommended)
When the UPS is backed up, discharge a battery to the undervoltage alarm threshold, to refresh the capacity of the battery.
1. Locate the cause
when an exception is identified.
2. If the fault persists,
contact Huawei technical support.
Yearly
Battery connection reliability
1. Each battery
terminal is connected reliably. (When battery strings are powered off, check the reliability of each
1. Rectify any abnormal
connection.
2. If the fault persists,
contact Huawei technical support.
Yearly
Page 98
UPS2000-G-(6 kVA-20 kVA) User Manual
7 Routine Maintenance
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
90
Item
Expected Result
Measures
Maintenan ce Interval
terminal in the order from positive terminals to negative terminals.)
2. The tightening
torque of each battery screw meets the requirements of the battery manufacturer. (A torque wrench is used for checking the torque. After checking that the battery screws meet the requirements, mark the screws for later check.)
Page 99
UPS2000-G-(6 kVA-20 kVA) User Manual
8 Troubleshooting
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
91
8 Troubleshooting
When a UPS is faulty, alarm information is displayed on the LCD. Critical alarms must be processed before the UPS is powered on again. Otherwise, the fault may be extended, or the UPS may be damaged.
Table 8-1 lists the solutions to common faults.
Table 8-1 Solutions to common faults
No.
Symptom
Possible Cause
Measure
1
The mains switch is ON. The LCD does not display anything. The system does not perform self-tests.
The input power supply is not connected.
Check the input power cable connection.
The input voltage exceeds the limit.
Use a multimeter to check that the UPS input voltage meets specifications.
2
The mains is normal, but the AC input indicator is off. The UPS runs in battery mode.
The mains switch is OFF.
Turn on the mains switch.
The input power cable is not securely connected.
Check the input power cable connection.
3
The UPS does not report faults, but has no output voltage.
The output power cable is not securely connected.
Check the output power cable connection.
4
The UPS does not start after you press .
is not pressed long enough.
Press for more than 5 seconds until you hear a beep sound.
Page 100
UPS2000-G-(6 kVA-20 kVA) User Manual
8 Troubleshooting
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
92
No.
Symptom
Possible Cause
Measure
Overload occurs.
Disconnect all loads, and restart the UPS.
5
The Mains indicator is off.
The mains voltage or frequency exceeds the UPS input range.
Use a multimeter to check that the input voltage and frequency meet specifications.
6
The battery discharge time is much less than the standard time.
Batteries are not fully charged.
Charge batteries for more than 8 hours when the mains is normal. Test the discharge time again.
The battery performance deteriorates.
Contact local Huawei technical support to replace batteries.
7
Abnormal noises or smell is generated in the UPS cabinet.
The UPS is faulty.
Shut down the UPS immediately and cut off the input power supply. Contact local Huawei technical support.
8
The battery indicator is blinking yellow. The buzzer buzzes 1 second and then stops 1 second. The battery capacity is insufficient. The UPS is shutting down.
The remaining battery capacity is insufficient. The UPS is shutting down, and the loads are powering off.
Parameters settings of battery number or battery capacity is not correct.
Save load data immediately and power off critical loads.
Connect UPS input terminals to the backup AC power supply.
Set parameters of battery number and battery capacity correctly. For details, see battery parameters settings in
4.6.3 Settings Screen.
9
You forget the password.
N/A
If you forget only the LCD password (the preset password is 000001), use the feature code (the preset feature code is
999999) to activate the LCD password.
If you forget both the password and the feature code, contact local Huawei technical support.
Loading...