This manual must only be used by a qualied installer / service technician. Read all instructions in this manual before installing.
Perform steps in the given order. Failure to do so could result in substantial property damage, severe personal injury, or death.
HTP reserves the right to make product changes or updates without notice and will not be held liable for typographical errors
in literature.
NOTE TO CONSUMER: PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE.
272 Duchaine Blvd.New Bedford, MA 02745www.htproducts.com
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 2
2
The following dened terms are used throughout this manual to
bring attention to the presence of hazards of various risk levels or to
important product information.
DANGER indicates an imminently hazardous situation which, if not
avoided, will result in serious personal injury or death.
WARNING indicates a potentially hazardous situation which, if not
avoided, could result in personal injury or death.
CAUTION indicates a potentially hazardous situation which, if not
avoided, may result in moderate or minor personal injury.
CAUTION used without the safety alert symbol indicates a
potentially hazardous situation which, if not avoided, may result in
property damage.
NOTICE is used to address practices not related to personal injury.
Foreword
This manual is intended to be used in conjunction with other literature
provided with the SuperStor Indirect Fired Water Heater. This includes
all related control information. It is important that this manual, all
other documents included in this system, and additional publications
including the Code for the Installation of Heat Producing Appliances
(latest version), be reviewed in their entirety before beginning any
work.
Installation should be made in accordance with the regulations of
the Authority Having Jurisdiction, local code authorities, and utility
companies which pertain to this type of water heating equipment.
Authority Having Jurisdiction (AHJ) – The Authority Having Jurisdiction
may be a federal, state, local government, or individual such as a re
chief, re marshal, chief of a re prevention bureau, labor department
or health department, building ocial or electrical inspector, or others
having statutory authority. In some circumstances, the property owner
or his/her agent assumes the role, and at government installations, the
commanding ocer or departmental ocial may be the AHJ.
NOTE: HTP reserves the right to modify product technical specications
and components without prior notice.
For the Installer
This water heater must be installed by qualied and licensed personnel.
The installer should be guided by the instructions furnished with the
water heater, and by local codes and utility company requirements.
Installations Must Comply With:
Local, state, provincial, and national codes, laws, regulations, and
ordinances.
Table of Contents
Part 1 - General Safety Information 2
A. When Servicing the Water Heating System 3
B. Heater Water 3
C. Freeze Protection 3
D. Water Temperature Adjustment 3
Part 2 - Prepare the Water Heater 3
A. Locating the Water Heater 4
B. Performance and Sizing Guidelines 6
C. Reduced Boiler Input Sizing Guide 7
D. Water Chemistry Requirements 8
Part 3 - Piping 8
A. Plumbing 8
B. Boiler Connections 8
C. Domestic Piping Inlet 8
D. Temperature and Pressure Relief Valve 9
E. Scalding 9
F. Potable Expansion Tank 10
G. Pressure Drop Sizing For Circulator 10
H. Applications 10
Part 4 - Heater Control and Wiring 15
A. Control 15
B. Wiring 15
C. Wiring Diagrams 15
Part 5 - Start-Up and Operation 19
Part 6 - Maintenance and Troubleshooting 20
Limited Warranty 22
Customer Installation Record Form 24
Part 1 - General Safety Information
This water heater is approved for indoor installation only and is not
intended for use as a pool heater. Clearance to combustible materials:
0” top, bottom, sides, and back. Heater must have room for service:
24” front, 6” top, and 0” sides are recommended service clearances. (A
combustible door or removable panel is acceptable front clearance.)
This water heater has been approved for closet installation and
installation on combustible ooring. Do not install directly on
carpeting. Install the water heater in a location where temperature
and pressure relief valve discharge or a leak will not result in damage
to the surrounding area. If such a location is not available, install an
auxiliary catch pan.
Installer - Read all instructions in this manual before installing.
Perform steps in the given order.
User - This manual is for use only by a qualied heating installer
/ service technician. Have this water heater serviced / inspected
annually by a qualied service technician.
FAILURE TO ADHERE TO THE GUIDELINES ON THIS PAGE
CAN RESULT IN SUBSTANTIAL PROPERTY DAMAGE, SEVERE
PERSONAL INJURY, OR DEATH.
NOTE: Obey all local codes. Obtain all applicable permits before
installing the water heater.
NOTE: Install all system components and piping in such a manner
that does not reduce the performance of any re rated assembly.
NOTE: If the heater is exposed to the following, do not operate
until all corrective steps have been made by a qualied serviceman:
1. Fire
2. Damage
3. Water
Failure to follow this information could result in property damage,
severe personal injury, or death.
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 3
3
High heat sources (sources generating heat 100oF / 37oC or
greater, such as stove pipes, space heaters, etc.) may damage
plastic components of the water heater as well as plastic vent
pipe materials. Such damages ARE NOT covered by warranty. It is
recommended to keep a minimum clearance of 8” from high heat
sources. Observe heat source manufacturer instructions, as well
as local, state, provincial, and national codes, laws, regulations
and ordinances when installing this water heater and related
components near high heat sources.
Do not use this water heater for anything other than its intended
purpose (as described in this manual). Doing so could result in
property damage and WILL VOID product warranty.
UNCRATING THE WATER HEATER - Any claims for damage or
shortage in shipment must be led immediately against the transportation company by the consignee.
A. When Servicing the Water Heating System
To avoid electric shock, disconnect electrical supply before
performing maintenance.
To avoid severe burns, allow water heater and associated equipment
to cool before servicing.
B. Heater Water
Do not use petroleum-based cleaning or sealing compounds in
a water heating system. Gaskets and seals in the system may be
damaged. This can result in substantial property damage.
Do not use “homemade cures” or “patent medicines”. Damage to the
water heater, substantial property damage, and/or serious personal
injury may result.
NOTICE FOR SINGLE-WALL HEAT EXCHANGER MODELS
Per the Uniform Plumbing Code:
Single-wall heat exchangers are permitted if they satisfy all of the
following requirements:
The heat exchanger medium is potable water or contains only
substances which are recognized as safe by the US Food and Drug
Administration (FDA).
The pressure of the heat exchanger medium is maintained less
than the normal minimum operating pressure of the potable water
system (steam systems must comply with this statement).
The equipment is permanently labeled to indicate that only
additives recognized as safe by the FDA shall be used as the heat
transfer medium.
Other heat exchanger designs may be permitted where approved
by the AHJ.
C. Freeze Protection
NOTE: Consider piping and installation when determining heater
location. Place the water heater as close to the boiler as possible, in
a location not prone to freezing.
Failure of the water heater due to freeze related damage IS NOT
covered by product warranty.
In water heaters with single wall heat exchangers, the heat
transfer uid must be water or nontoxic food grade glycol, FDA
rated “generally recognized as safe” (GRAS) and having a toxicity
rating or class of 1, as listed in Clinical Toxicology of Commercial
Products, 5th edition. Ensure the system is permanently labeled to
indicate any additives used in the heat transfer uid.
NEVER use any toxic chemical, including automotive, standard glycol
antifreeze, or ethylene glycol made for hydronic (non-potable)
systems. These chemicals can attack gaskets and seals in water
systems, are poisonous if consumed, and can cause personal injury
or death.
D. Water Temperature Adjustment
If the water heater is going to have a set temperature above 120oF, you
must use an ASSE 1017 rated mixing valve to avoid severe burns or
death from scalding temperatures.
Households with small children, disabled, or elderly persons may
require a 120oF or lower temperature setting to prevent severe
personal injury or death due to scalding.
Approximate Time / Temperature Relationships in Scalds
120oFMore than 5 minutes
125oF1 1/2 to 2 minutes
130oFAbout 30 seconds
135oFAbout 10 seconds
140oFLess than 5 seconds
145oFLess than 3 seconds
150oFAbout 1 1/2 seconds
155oFAbout 1 second
Table 1 - Approximate Time / Temperature Relationships in Scalds
Part 2 - Prepare the Water Heater
Remove all sides of the shipping crate to allow the heater to be moved
into its installation location.
COLD WEATHER HANDLING - If the water heater has been stored
in a very cold location (BELOW 0oF) before installation, handle with
care until the components come to room temperature. Failure to do
so could result in damage to the water heater.
A. Locating the Water Heater
High heat sources (generating heat 100oF / 37oC or greater, such as
stove pipes, space heaters, etc.) may damage plastic components
of the water heater as well as plastic vent pipe materials. Such
damages ARE NOT covered by warranty. It is recommended to keep
a minimum clearance of 8” from high heat sources. Observe heat
source manufacturer instructions, as well as local, state, provincial,
and national codes, laws, regulations, and ordinances when installing
this water heater and related components near high heat sources.
Locate the water heater where any leakage from the relief valve,
related piping, tank, or connections will not result in damage to
surrounding areas or lower oors of the building. The water heater
should be located near a oor drain or installed in a drain pan. HTP
WILL NOT be held liable for leakage damages.
This water heater must be installed upright in the vertical position as
described in this manual. DO NOT attempt to install this water heater
in any other orientation. Doing so will result in improper water heater
operation and property damage, and could result in serious personal
injury or death.
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 4
4
This water heater is certied for indoor use only. DO NOT INSTALL
OUTDOORS. Outdoor installations ARE NOT covered by warranty.
Choose a location for the water heater as centralized to the piping
system as possible. Also, locate the water heater and domestic water
piping where it will not be exposed to freezing temperatures. All
piping should be insulated. Additionally, place the water heater so that
the drain, controls, and inlets/outlets are easily accessible.
NOTE: To save on heating costs and improve energy eciency keep
the distance between the boiler and water heater to a minimum
to reduce heat loss from excess piping and keep friction loss at a
minimum. Ensure all piping between the boiler and water heater is
properly insulated to minimize heat loss.
The water heater may be located some distance from the boiler
provided the circulator meets ow requirements through the coil. The
greater the distance from the water heater to the boiler the longer the
response will be to a call for hot water.
This water heater must be installed vertical on a level surface.
NOTE: In the State of California, the water heater must be braced,
anchored, or strapped to avoid moving during an earthquake. Contact
local utilities for code requirements in your area. Visit http://www.dsa.
dgs.ca.gov or call 1-916-445-8100 and request instructions.
However, applicable local codes shall govern installation. For
residential water heaters of a capacity greater than 52 gallons, consult
the local building jurisdiction for acceptable bracing procedures.
NOTE: If you do not provide the minimum clearances shown in
Figure 1, it might not be possible to service the water heater without
removing it from the space.
NOTE: A combustible door or removable panel is acceptable front
clearance.
Figure 1 - Recommended Service Clearances
This water heater must not be located near ammable liquids
such as gasoline, butane, liqueed propane, adhesives, solvents,
paint thinners, etc., as the controls of this water heater could
ignite these vapors and cause an explosion resulting in property
damage, severe personal injury, or death.
Ensure the location can support the entire lled weight of the
water heater. Failure to properly support the water heater could
result in property damage, severe personal injury, or death.
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 5
5
Figure 2 - Dimensions
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 6
6
Table 2 - Specications
Continuous Flow Performance Calculation
First Hour Rating - (.75 X Tank Capacity) = Continuous Flow
Example: SSU-45C = 314 - (.75 X 45) = 280.25
B. Performance and Sizing Guidelines
NOTE: The table below describes the minimum BTU/H required to achieve the listed rst hour rating.
MODELGROSS BOILER OUTPUT
SSU-2084,000121140168
SSU-30102,000154180212
SSU-30LB113,000169198234
SSU-45141,000212248292
SSU-45C215,000314367414
SSU-60174,000266311370
SSU-60C245,000354414467
SSU-80212,000330386440
SSU-80C331,000490573647
SSU-119269,999423495564
SSU-119C425,000637745841
Table 3 - Water Heater Performance and Sizing Guidelines
140oF
90oF Δ T
127oF
77oF Δ T
115oF
65oF Δ T
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 7
C. Reduced Boiler Input Sizing Guide
NOTE: IT IS NOT RECOMMENDED TO REDUCE BOILER INPUT WHEN USING DOUBLE WALL TANKS.
MODEL
SSU-20
SSU-30
SSU-30LB
SSU-45
SSU-60
SSU-80
SSU-119
Table 4 - Describes Cold Start First Hour Ratings (A and B) and Boiler Size
406084100120140160180200220240260280300320
A73112152-
B5381110-
A83125160193-
B6090115140-
A84128166213-
B6092120154-
A94138180210242-
B68100130152175-
A-221244251258266287305-
B-160176181186192207220-
A-297305314367424489503-
B-216223230269311359370-
A-333384444457470543627645
B-216251290335345399460474
PRODUCT LINE CONSISTS OF VARIOUS MODELS AVAILABLE IN
DIFFERENT SIZES
CALL THE FACTORY FOR PRODUCT AND WARRANTY INFORMATION
“DW” (Double Wall Commercial Heat Exchanger) Models are available
in 45, 60, 80, and 119 US Gallon Sizes.
“C” (Commercial) Models with Two Heat Exchangers for dual systems
and commercial applications. Use one coil for a wood boiler, the
other for a solar system, etc. Models available in 45, 60, 80, and 119
US Gallon Sizes.
GROSS OUTPUT (x 1,000 BTU/HR)
DETERMINE THE AMOUNT OF DOMESTIC HOT WATER NEEDED. THEN
USE THE TABLE BELOW TO OPTIMIZE WATER HEATER AND BOILER
SIZING.
NOTE: FIRST DRAW AT 140oF AT 90oF Δ T. (FOR PERFORMANCE AT
115oF, MULTIPLY BY 1.56 FOR MINUTES OF WATER DRAW.)
LINE A GALLONS: LOW MASS BOILERS THAT TAKE LESS THAN 90
SECONDS TO HEAT TO TEMPERATURE.
LINE B GALLONS: HIGH MASS BOILERS THAT TAKE GREATER THAN 90
SECONDS TO HEAT TO TEMPERATURE.
7
MODEL2 GPM2.5 GPM3 GPM3.5 GPM4 GPM4.5 GPM5 GPM
SSU-20
SSU-30
SSU-30LB
SSU-45
SSU-45C
SSU-60
SSU-60C
A9.5875.54.543.5
B8.57.56.5543.53
A1613107.565.55
B1412975.554.5
A18141296.565.5
B171210865.55
A231814118.57.57
B181513107.57.56.5
A∞∞∞29201714
B45242618161310
A
B291912
A
B3021
∞∞∞∞
∞∞∞∞∞
363022
4629
SSU-80AB∞∞∞∞∞∞∞
SSU-80CAB∞∞∞∞∞∞∞
SSU-119AB∞∞∞∞∞∞∞
SSU-119CAB∞∞∞∞∞∞∞
Table 5 - NOTE: THIS INFORMATION IS BASED ON BOILER SIZE CONFORMING TO THE MINIMUM BTU/H REQUIRED TO ACHIEVE FIRST HOUR RATINGS,
OBTAINABLE FROM FIRST HOUR RATING TABLE. ∞ - Indicates continuous duty.
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 8
8
D. Water Chemistry Requirements
Chemical imbalance of the water supply may aect eciency and
cause severe damage to the appliance and associated equipment.
Water quality must be professionally analyzed to determine whether
it is necessary to treat the water. Various solutions are available to
adjust water quality. Adverse water quality will aect the reliability
of the system. In addition, operating temperatures above 135oF will
accelerate the build-up of lime scale and possibly shorten appliance
service life. Failure of an appliance due to lime scale build-up, low pH,
or other chemical imbalance IS NOT covered by the warranty.
The water must be potable, free of corrosive chemicals, sand, dirt,
and other contaminates. It is up to the installer to ensure the water
does not contain corrosive chemicals or elements that can damage
the heat exchanger. Potable water is dened as drinkable water
supplied from utility or well water in compliance with EPA secondary
maximum contaminant levels (40 CFR Part 143.3). If the water contains
contaminants higher than outlined by the EPA, water treatment is
recommended and additional, more frequent maintenance may be
required.
If you suspect that your water is contaminated in any way, discontinue
use of the appliance and contact an authorized technician or licensed
professional.
• Water pH between 6.5 and 8.5
• pH levels below 6.5 can cause an increase in the rate of
corrosion. pH of 8.5 or higher can potentially cause lime
scale build-up
• Maintain water pH between 6.5 and 8.5. Check with litmus
paper or have it chemically analyzed by a local water
treatment company.
• If the pH is not between 6.5 and 8.5, consult a local water
treatment company for solutions.
• Hardness less than 12 grains (200 mg/L) (Residential Use water temperatures below 140oF)
• Hardness less than 7 grains (120 mg/L) (Commercial Use water temperatures of 140oF and greater)
• Hardness levels above the required amounts can lead to lime
scale build-up throughout the system. Water below 5 grains/
gallon (85 mg/L) may be over softened.
• Consult local water treatment companies for unusually
hard water areas (above the required amounts) or for other
treatment solutions if water is being over softened (below 5
grains/gallon [85 mg/L]).
• Chloride concentration less than 100 ppm (mg/L)
• Do not ll appliance or operate with water containing
chlorides in excess of 100 ppm (mg/L).
• Using chlorinated fresh water should be acceptable as levels
are typically less than 5 ppm (mg/L).
• Do not connect the appliance to directly heat swimming
pool or spa water.
• Total Dissolved Solids (TDS) less than 500 ppm (mg/L)
• Total dissolved solids are minerals, salts, metals, and charged
particles that are dissolved in water.
• The greater the amounts of TDS present, the higher the
corrosion potential due to increased conductivity in the
water.
• If using softened water to ll the appliance, it is still possible
to have high TDS. This water can be corrosive. Consult local
water treatment companies for other treatment solutions to
reduce this aect.
*NOTE: To promote appliance service life, it is strongly
recommended to follow the maintenance procedures in this
manual.
Part 3 - Piping
A. Plumbing
It is mandatory that all plumbing be done in accordance with
federal, local, and state plumbing codes and practices. Failure to
properly install the water heater WILL VOID the warranty. It is also
necessary to use both thread tape and pipe dope on all mechanical
plumbing connections.
When lling the water heater, open a hot water tap to release air in
the tank and piping. Failure to do so could lead to improper water
heater operation and damage to components.
B. Boiler Connections
Use two wrenches when tightening water piping at the heater.
Use one wrench to prevent the heater return or supply line from
turning. Failure to prevent piping connections from turning could
cause damage to water heater components.
Use a 1” nominal minimum pipe size when piping with zone valves
or circulators.
On the water heater, the boiler supply connects to the outlet of the
circulator. The circulator inlet is to be connected to the hot outlet
side of the boiler. Be sure that the arrow on the circulator is facing
the correct ow direction. (See pressure drop sizing for circulator,
this manual.) On the tank, the boiler return connects to the return
side of the boiler. The return(s) from heating loop(s) should have
a ow check or swing check valve installed before the return pipe
from the tank.
In a steam boiler, the tank supply must be connected to the boiler
well below the minimum water level. A strainer and drain valve
should be installed at the boiler for periodic draining of scale and
sludge. Banging and steam bound traps will occur if the boiler water
supplied to the heat exchanger has steam or is slightly above the
low water cut-o.
Live Steam Applications are allowed ONLY on 80 and 119 gallon
SSU / SSU-C models. Using any other SSU model in live steam
applications will result in product failure and void the warranty.
Pressure of steam in the indirect heat exchanger MUST NOT
EXCEED 10 PSI. Failure to follow these instructions could result
in product failure, substantial property damage, severe personal
injury, or death, and WILL VOID product warranty.
C. Domestic Piping Inlet
Never use dielectric ttings or galvanized steel ttings on any
domestic water connections. Use only copper or brass ttings.
Failure to do so will result in premature water heater failure. Such
failure IS NOT covered by warranty.
Use both thread tape and pipe dope to connect an NPT brass tee.
On the run, install a brass drain valve. In the branch, install an NPT
male X 3/4” (minimum) pipe adapter. A shut-o valve between the
city water supply and tank inlet is recommended for ease of service.
It may be recommended to use a back ow preventer - check local
codes. If a back ow preventer or a no return valve is used, a thermal
expansion tank must be installed on the cold water supply between
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 9
the tank and valve. If the tank is replacing a tankless coil in the
boiler, disconnect coil plumbing and use the cold inlet pipe and hot
water outlet pipes for the water heater.
D. Temperature and Pressure Relief Valve
On SSU-80 and SSU-119 residential models, as well as all commercial
models, a 3/4” temperature and pressure (T&P) port and relief valve
are provided. On all other models, an appropriate T&P valve must
be supplied and installed as detailed in the piping diagrams in this
installation manual.
Use both thread tape and pipe dope to install an NPT brass T&P
relief valve for hot water heaters, as required by local codes but
not less than valves certied as meeting the requirements for relief
valves for hot water heaters (ANSI Z21.22 / CSA 4.4) by a nationally
recognized lab that maintains periodic inspection of production
listed equipment. Make sure the relief valve is sized to the BTU/Hour
capacity of the water heater. The T&P valve must be plumbed down
so discharge can exit at least 6” above the structural oor. The relief
line cannot be in contact with any live electrical parts. If the relief
valve constantly weeps install an expansion tank. See expansion
tank manufacturer’s instructions for suggestions.
To avoid water damage or scalding due to relief valve operation:
• Discharge line must be connected to relief valve outlet and
run to a safe place of disposal. Terminate the discharge line
in a manner that will prevent possibility of severe burns or
property damage should the relief valve discharge.
• Discharge line must be as short as possible and the same
size as the valve discharge connection throughout its
entire length.
• Discharge line must pitch downward from the valve
and terminate at least 6” above the oor drain, making
discharge clearly visible.
• The discharge line shall terminate plain, not threaded, with
a material serviceable for temperatures of 375oF or greater.
• Do not pipe discharge to any location where freezing could
occur.
• No valve may be installed between the relief valve and
heater or in the discharge line. Do not plug or place any
obstruction in the discharge line.
• Test the operation of the relief valve after lling and
pressurizing the system by lifting the lever. Make sure the
valve discharges freely. If the valve fails to operate correctly,
immediately replace with a new properly rated relief valve.
• Test T&P valve at least once annually to ensure the waterway
is clear. If valve does not operate, turn the heater “o” and
call a plumber immediately.
• Take care whenever operating relief valve to avoid scalding
injury or property damage.
FAILURE TO COMPLY WITH THE ABOVE GUIDELINES COULD
RESULT IN FAILURE OF RELIEF VALVE OPERATION, RESULTING
IN POSSIBILITY OF SUBSTANTIAL PROPERTY DAMAGE, SEVERE
PERSONAL INJURY, OR DEATH.
RE-INSPECTION OF T&P RELIEF VALVES: T&P valves should be
inspected AT LEAST ONCE EVERY THREE YEARS, and replaced if
necessary, by a licensed plumbing contractor or qualied service
technician to ensure that the product has not been aected by
corrosive water conditions and to ensure that the valve and
discharged line have not been altered or tampered with illegally.
Certain naturally occuring conditions may corrode the valve and
its components over time, rendering the valve inoperative. Such
conditions can only be detected if the valve and its components
are physically removed and inspected. Do not attempt to conduct an inspection on your own. Contact your plumbing
contractor for a re-inspection to assure continued safety.
9
Do not thread a cap or plug into the relief valve or relief valve line
under any circumstances! Explosion and property damage, serious
injury, or death may result.
FAILURE TO RE-INSPECT THE T&P VALVE AS DIRECTED COULD
RESULT IN UNSAFE TEMPERATURE AND/OR PRESSURE BUILD-UP
WHICH CAN RESULT IN PROPERTY DAMAGE, SERIOUS PERSONAL
INJURY, OR DEATH.
E. Scalding
An ASSE 1017 or ASSE 1070 temperature limiting or mixing valve is
recommended in installations servicing disabled or elderly persons,
or children. Mixing valves do not eliminate the risk of scalding.
To avoid scalding:
• Set the water heater set point temperature as low as possible.
• Feel water before bathing or showering.
• If thermostatic valves are required, use devices specically
designed for such purpose. Install these devices in accordance
with instructions provided by the manufacturer.
Failure to install a temperature limiting or mixing valve and follow
these instructions could result in property damage, severe personal
injury, or death due to scalds.
This water heater can
deliver scalding water. Be
careful whenever using
hot water to avoid scalding
injury. Certain appliances
such as dishwashers and
automatic clothes washers
may require increased water
temperatures. By setting the
thermostat on this heater to
obtain the increased water
temperature required by
these appliances you may
create the potential for scald
injury.
To protect against injury,
install a mixing valve in the
water system. This valve
will reduce point of use
discharge temperatures by
mixing cold and hot water
in branch supply lines. Such
valves are available from your local plumbing supplier.
The following table details the relationship of water temperature
and time with regard to scald injury and may be used as a guide in
determining the safest water temperature for your applications.
Approximate Time / Temperature Relationships in Scalds
120oFMore than 5 minutes
125oF1 1/2 to 2 minutes
130oFAbout 30 seconds
135oFAbout 10 seconds
140oFLess than 5 seconds
145oFLess than 3 seconds
150oFAbout 1 1/2 seconds
155oFAbout 1 second
Table 6 - Approximate Time / Temperature Relationships in Scalds
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 10
10
F. Potable Expansion Tank
A potable hot water expansion tank may be required to oset heated
water expansion. If there is a back ow preventer or any other type
of no return or check valve in the system a thermal expansion tank IS
MANDATORY. The expansion tank must be sized for the entire water
volume of the hot water system. A weeping relief valve indicates the
need for an expansion tank. See the Typical Expansion Tank example in
the Piping section for details.
G. Pressure Drop Sizing For Circulator
The boiler circulator ow rate must meet the requirements found in
the water heater specications, Part 2, this manual, or the published
ratings cannot be achieved. The following ow chart below represents
the pipe run, water heater, and heat exchanger ONLY and does not
include any ow checks, zone valves, or friction loss through the boiler.
That resistance must be added to the value found in the following
chart.
Pressure Drop for Pipe Length of 1” Copper,
Six 90o Elbows, and One Tee
Pipe Size20’30’40’50’60’
6 GPM8.638.939.239.539.8
7 GPM11.311.7712.2412.713.1
10 GPM10.2511.111.9512.813.66
12 GPM11.313.214.11516
14 GPM15.316.417.518.619.8
Pressure Drop for Pipe Length of 1 1/4” Copper,
Six 90o Elbows, and One Tee
Pipe Size20’30’40’50’60’
20 GPM10.911.712.613.414.3
22 GPM1415161718
24 GPM16.217.518.820.121.5
28 GPM20.42223.625.226.8
Table 7 - Pressure Drop through 1” and 1 1/4” Copper
Figure 4 - Expansion Tank Application
H. Applications
Figure 3 - Mixing Valve Installation
Figure 5 - Installation with High Eciency Boiler
NOTES:
1. Minimum pipe size should match connection size. Upsize pipe
accordingly if greater ow is required.
2. A thermal expansion tank suitable for potable water must be
sized and installed within this piping system between the backow
preventer and the cold water inlet.
3. All circulators should have an integral ow check.
4. Drains and check valve between the heating appliance and water
heater will assist in purging air from system.
5. This drawing is meant to demonstrate system piping only. The
installer is responsible for all equipment and detailing required by
local codes. In Massachusetts, you must install a vacuum relief valve
per 248 CMR.
6. Mixing valve application is optional, but recommended to help
prevent scalding. See Part 3, Section E for more information.
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 11
11
Figure 6 - Zoning with Zone Valves
Figure 7 - Installation with Storage Tank
Figure 8 - Zoning with Circulators
NOTES:
1. Minimum pipe size should match connection size. Upsize pipe accordingly if greater ow is required.
2. A thermal expansion tank suitable for potable water must be sized and installed within this piping system between the backow preventer
and the cold water inlet.
3. All circulators should have an integral ow check.
4. Drains and check valve between heating appliance and water heater will assist in purging air from system.
5. This drawing is meant to demonstrate system piping only. The installer is responsible for all equipment and detailing required by local
codes. In Massachusetts, you must install a vacuum relief valve per 248 CMR.
6. Mixing valve application is optional, but recommended to help prevent scalding. See Part 3, Section E for more information.
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 12
12
Figure 9 - Dual Purpose Application with Wood BoilerFigure 10 - Dual Purpose Application with Wood Stove
Figure 11 - Dual Purpose Application with Two Water Heaters
Figure 12 - Dual Purpose Application with Solar Panel
NOTES:
1. Minimum pipe size should match connection size. Upsize pipe
accordingly if greater ow is required.
2. A thermal expansion tank suitable for potable water must
be sized and installed within this piping system between the
backow preventer and the cold water inlet.
3. All circulators should have an integral ow check.
4. Drains and check valve between heating appliance and water
heater will assist in purging air from system.
5. This drawing is meant to demonstrate system piping only. The
installer is responsible for all equipment and detailing required
by local codes. In Massachusetts, you must install a vacuum relief
valve per 248 CMR.
6. Mixing valve application is optional, but recommended to help
prevent scalding. See Part 3, Section E for more information.
7. On multiple source applications, use a Honeywell L4081-A-1148,
which has two (2) limit settings. This allows the wood stove or
solar panel to operate on the tank high setting and the tank low
limit setting for conventional boiler back-up.
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 13
13
Figure 13 - Steam Boiler
Figure 14 - Live Steam Installation
NOTE: On Steam Boiler Applications, the indirect heat exchanger supply and return connections must be below the water line from the boiler
connection. The internal ow check or spring check must be used to avoid thermal siphoning from the connected boiler. A basket strainer
should also be used to avoid sludge and sediment getting into the pump or heat exchanger.
Live Steam Applications are allowed ONLY on 80 and 119 gallon SSU / SSU-C models. Using any other SSU model in live steam applications
will result in product failure and void the warranty. Pressure of steam in the indirect heat exchanger MUST NOT EXCEED 10 PSI. Failure to
follow these instructions could result in product failure, substantial property damage, severe personal injury, or death, and WILL VOID
product warranty.
Figure 15 - Multiple Tank Installation
NOTES:
1. Minimum pipe size should match connection size. Upsize pipe accordingly if greater ow is required.
2. A thermal expansion tank suitable for potable water must be sized and installed within this piping system between the backow preventer
and the cold water inlet.
3. All circulators should have an integral ow check.
4. Drains and check valve between heating appliance and water heater will assist in purging air from system.
5. This drawing is meant to demonstrate system piping only. The installer is responsible for all equipment and detailing required by local
codes. In Massachusetts, you must install a vacuum relief valve per 248 CMR.
6. Mixing valve application is optional, but recommended to help prevent scalding. See Part 3, Section E for more information.
7. All piping in parallel used for large dumps of hot water, high usage, and short duration.
8. Massachusetts requires a limit of four (4) tanks per mechanical room. Consult with your local inspector.
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 14
14
CAUTION
CAUTION
Part 4 - Heater Control and Wiring
A. Control
Install control element into the control well and tighten into place with screws on the control body. Thermal conductive paste is recommended.
Once the control is operational, it is important to make sure the control is maintaining the desired operating temperature.
NOTE: DO NOT attempt to remove the control well! The control well is welded to the water heater. Attempting to remove the control well
will result in product damage, leakage, and possible property damage. Such damages are not covered by product warranty.
B. Wiring
Wiring is to be done in accordance with all applicable local and state codes. Turn o all power related to the boiler before starting any wiring
procedures.It is recommended that a disconnect switch be installed between the boiler control and the water heater.
When wiring the water heater and controls be sure to label all wires to ease future maintenance. Wiring errors can cause improper and
dangerous operation.
C. Wiring Diagrams
Figure 16 - Wiring with Circulators
Figure 17 - Wiring with Zone Valves
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 15
Figure 18 - Zoning with Circulators - R845A Relay
15
Figure 19 - Zoning with Circulators Using R8182D and DPST - No Relay Required
Figure 20 - Zoning with Circulators Using L8124 A, C, and R845A RelayFigure 21 - Zoning with Circulators Using L8124 A, C, and DPST Control -
No Relay Required
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 16
16
Figure 23 - Zoning with Circulators - R8182D and R845A Relay
Figure 25 - Zoning with Circulators Using L8124 E-F, and R845A RelayFigure 26 - Zoning with Circulators Using L8124 E-F, and DPST - No Relay
Figure 24 - Control with Built-In DPST Switch - No Relay Required
Required
Figure 22 - Using L8148A or L8152A Cold Start Boiler Control with Circulators
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 17
Figure 27 - Priority Zone with CirculatorsFigure 28 - Priority Zone with Zone Valves
17
Figure 29 - Using L8148A or L8152A Cold Start Boiler Control with Zone Valves
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 18
18
Part 5 - Start-Up and Operation
1. Fill the water heater by opening the cold water shut-o valve.
Purge air from the system by opening a hot water outlet at a xture
in a kitchen or bathroom. When water ows freely from the outlet, the
system is purged.
When lling the water heater, open a hot water tap to release air in
the tank and piping to ensure proper water heater operation. Failure
to ensure the water heater is full before turning on the system will
result in damage to the water heater, and could result in property
damage. Such damages ARE NOT covered by warranty.
2. Check the system for leaks.
Fix any leaks before continuing the installation. Failure to do so
could result in property damage or personal injury.
3. After ensuring there are no leaks within the system, ush the system
to clear any soldering residue. Many soldering uxes contain Zinc
Chloride, which can corrode stainless steel.
Draw at least three times the volume of the water heater to properly
ush the system.
4. Initiate a call for hot water. Ensure each zone valve or circulator
operates only when its thermostat calls for heat. Purge each zone of
air to ensure proper operation.
5. Set the water
heater to the desired
temperature. Boiler
high limit should
be set at least 20oF
higher than the heater
temperature. Set the
low limit of the boiler
control at the minimum
setting - this will call
the burner on only to
satisfy the tank control.
A water heater
temperature setting of
120oF is recommended.
However, a lower
temperature setting
may be required to
comply with local
and state codes for
normal operation. The
dierential should
be set at 10 to 15oF.
Installation conditions
may require a higher or lower temperature setting. A mixing valve in
conjunction with a high temperature setting may be used for high
demand applications (spas, hot tubs, whirlpools).
6. When the system is completely ushed, purged of air, and the
temperature is set, turn on the boiler. Observe operation. Ensure the
boiler shuts down after the indirect water heater set point is satised.
Figure 30 - Sealing the Water Heater for Sanitary Applications
Figure 31 - Replacement Parts
Item #Part #Description
T&P Relief Valve
TP1500
1
TP1400
Table 8 - Replacement Parts List
(Not Included with Water Heater)
(SSU-20 - SSU-60
and All DW Models)
T&P Relief Valve
(SSU-80, SSU-119,
and All C Models)
(Included with Water Heater)
Risk of scald injury increases as you increase water temperature.
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 19
19
Part 6 - Maintenance and Troubleshooting
Periodic maintenance should be performed by a qualied service technician to ensure all equipment is operating safely and eciently. The
owner should make necessary arrangements with a qualied heating contractor for periodic maintenance of the heater. Installer must also
inform the owner that the lack of proper water heater care and maintenance may result in hazardous conditions.
Annual Maintenance ActivitiesDate Last Completed
Piping1st Year2nd Year3rd Year4th Year
Near heater pipingCheck heater and system piping for any sign of leakage; make sure
pipes are properly supported.
System
VisualDo a full visual inspection of all system components. Ensure all
components (including boilers, water treatment systems, mixing
valves, circulators, etc.) are operating properly and have been
maintained.
FunctionalTest all functions of the system. Perform any maintenance required
by local codes. Verify system pressure is in the safe operating range.
TemperaturesCheck control for temperature accuracy.
*Verify safe settings on Mixing Valve (if installed in system).
Electrical
Smoke and CO
Detectors
Circuit BreakersCheck to see that the circuit breaker is clearly labeled. Exercise circuit
ConnectionsCheck wire connections. Make sure they are tight.
Relief and Drain Valve
Relief ValveLift and release the relief valve on the water heater. Make certain
Drain ValveOpen the drain valve and drain a few quarts of water from the bottom
Final Inspection
Check for
Combustibles
ChecklistVerify that you have completed the entire checklist. WARNING:
HomeownerReview what you have done with the homeowner.
Initial and Date after Inspection / Service. Continue Inspections Annually beyond the
Fourth Year.
Table 9 - Maintenance Activities Checklist - *If Applicable to System
*Verify devices are installed and working properly. Change batteries
if necessary.
breaker.
that the valve operates properly by allowing several gallons to ush
through the discharge line. Replace if valve is blocked or does not
operate properly.
NOTE: TAKE CAUTION WHEN OPERATING RELIEF VALVE. DISCHARGED
WATER MAY PRESENT A SCALD RISK.
of the tank to ush any hard water deposits. Replace if valve is blocked
or does not operate properly.
NOTE: TAKE CAUTION WHEN OPERATING DRAIN VALVE. DRAINED
WATER MAY PRESENT A SCALD RISK.
Check area around heater for combustible materials such as gasoline
or paint thinner. If combustible materials are found, move away from
the heater to a safe location.
FAILURE TO DO SO COULD RESULT IN SERIOUS INJURY OR DEATH.
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 20
20
ProblemReasonRemedy
Zone Valve Not OpeningOpen manually or replace
Circulator Not OperatingCheck or replace
Tank Control Set Too LowRaise tank temperature*
Boiler Control Set Too LowRaise boiler temperature
Zone valve restriction1” full bore replace zone valve
Circulator arrow reversedReverse circulator
Tank temperature too lowRaise tank temperature*
Boiler temperature too lowRaise boiler temperature
Boiler sized too small
Tank sized too small
Demand ow rate too highInstall mixing valve. Raise tank temperature
Air trap in loop
Check wiring or set indirect as priority over heating
Draw tank down and lower thermostat. Recheck.
Tank Temperature Too HighLower tank temperature
Water Expands When HeatedInstall expansion tank
Water Pressure Too HighInstall pressure reducing valve
Pressure Too LowCheck line pressure for restriction
Tank recovery slowSlow startup boiler. See chart
Boiler sized too small. See chart
Not enough hot water
Demand too great. Check ow rates and compare to chart. Install mixing
valve and/or ow restricting valve and raise tank and boiler temperature.*
Check ow rate. Compare to chart
Check sizing chart
Purge air
Install ow regulator
The risk of scald injury increases as you increase water temperature.
Use a water tempering or mixing valve and extreme caution when
using hot water to avoid scald injury. Consult codes for conformance.
Failure to follow the instructions in this warning statement could
result in serious personal injury or death from scalds.
lp-83 Rev. 006 Rel. 005 Date 12.18.17
If draining of the water heater is necessary, open the T&P valve or
a hot water tap to prevent vacuum buildup in the tank and piping.
Page 21
21
SSU Indirect Fired Water Heater / Solar Water Heater
Limited Warranty
For Residential and Commercial Use
HTP warrants each indirect red water heater to be free from defects
in materials and workmanship according to the following terms,
conditions, and time periods. UNLESS OTHERWISE NOTED THESE
WARRANTIES COMMENCE ON THE DATE OF INSTALLATION. This
limited warranty is only available to the original consumer
purchaser (hereinafter “Owner”) of the water heater, and is non-
transferable.
Residential Use Warranty
(Lifetime – Tank, One [1] year - Components)
“Residential” setting shall mean water heater usage in a single family
dwelling, or usage in a multiple family dwelling, provided that the
water heater services only one (1) dwelling in which the Owner
resides on a permanent basis and operating temperatures do not
exceed 140oF.
Commercial Use Warranty
(Seven [7] years – Tank, One [1] year - Components)
Water heaters used in a commercial setting shall mean any usage not
falling within the denition of a “residential” setting.
COVERAGE
A. During the rst year after the original date of installation in the
dwelling, HTP warrants that it will repair or replace, at its option,
any defective or malfunctioning component of the water heater.
Replacement components will be warranted for ninety (90) days.
B. Should a defect or malfunction result in a leakage of water from
the water heater within the above-stated warranty periods due to
defective material or workmanship, malfunction, or failure to comply
with the above warranty, with such defect or malfunction having
been veried by an authorized HTP representative, HTP will replace
the defective or malfunctioning water heater with a replacement of
the nearest comparable model available at the time of replacement.
The replacement water heater will be warranted for the unexpired
portion of the applicable warranty period of the original water heater.
C. In the event of a leakage of water of a replacement water heater
due to defective material or workmanship, malfunction, or failure to
comply with the above warranty, HTP reserves the right to refund
to the Owner the published wholesale price available at the date of
manufacture of the original water heater.
D. If government regulations, industry certication, or similar
standards require the replacement water heater or component(s)
to have features not found in the defective water heater or
component(s), the Owner will be charged the dierence in price
represented by those required features. If the Owner pays the price
dierence for those required features and/or to upgrade the size
and/or other features available on a new replacement water heater
or component(s), the Owner will also receive a complete new limited
warranty for that replacement water heater or component(s).
E. Residential Use ONLY - If at the time of a request for service the
Owner cannot provide a copy of the original sales receipt or the
warranty registration, the warranty period for the water heater shall
then be ten (10) years from the date of manufacture of the water
heater and NOT the date of installation of the water heater.
Commercial Use - If at the time of a request for service the Owner
cannot provide a copy of the original sales receipt or the warranty
registration, the warranty period for the water heater shall then
be deemed to have commenced thirty (30) days from the date of
manufacture of the water heater and NOT the date of installation of
the water heater.
F. This warranty extends only to water heaters utilized in heating
applications that have been properly installed by qualied
professionals based upon the manufacturer’s installation instructions.
G. It is expressly agreed between HTP and the Owner that repair,
replacement, or refund are the exclusive remedies of the Owner.
OWNER RESPONSIBILITIES
The Owner or Qualied Installer / Service Technician must:
1. Have a relief valve bearing the listing marks of the American
Society of Mechanical Engineers (ASME) installed with the water
heater assembly in accordance with federal, state, and local codes.
2. Have a vacuum relief valve certied to ANSI Z21.22 - Relief Valves
for Hot Water Supply Systems - installed with the water heater
assembly in accordance with federal, state, and local codes and in
installations prone to vacuum related damages.
3. Maintain the water heater in accordance with the maintenance
procedure listed in the manufacturer’s provided instructions.
Preventive maintenance can help avoid any unnecessary breakdown
of the water heater and keep it running at optimum eciency.
4. Maintain all related system components in good operating
condition.
5. Use the water heater in an open system, or in a closed system with
a properly sized and installed thermal expansion tank.
6. Use the water heater at water pressures not exceeding the working
pressure shown on the rating plate.
7. Keep the water heater free of damaging scale deposits.
8. Make provisions so if the water heater or any component or
connection thereto should leak, the resulting ow of water will not
cause damage to the area in which it is installed.
WARRANTY EXCLUSIONS
This limited warranty will not cover:
1. Any water heater purchased from an unauthorized dealer.
2. Any water heater not installed by a qualied heating installer
/ service technician, or installations that do not conform to ANSI,
CSA, and/or UL standards, as well as any applicable national or local
building codes.
3. Service trips to teach the Owner how to install, use, maintain, or
to bring the water heater installation into compliance with local
building codes and regulations.
4. Failure to locate the water heater in an area where leakage of the
tank or water line connections and the relief valve will not result in
damage to the area adjacent to the water heater or lower oors of
the structure.
5. Any failed components of the system not manufactured by HTP as
part of the water heater.
6. Water heaters repaired or altered without the prior written
approval of HTP.
7. Damages, malfunctions, or failures resulting from improper
installation, or failure to install the water heater in accordance
with applicable building codes/ordinances or good plumbing and
electrical trade practices; or failure to operate and maintain the water
heater in accordance with the manufacturer’s provided instructions.
8. Damages, malfunctions, or failures resulting from failure to operate
the water heater at pressures not exceeding the working pressure
shown on the rating label.
9. Failure to operate the water heater in an open system, or in a closed
system with a properly sized and installed thermal expansion tank.
10. Failure or performance problems caused by improper sizing of
the water heater, expansion device, or piping.
11. Damages, malfunctions, or failures resulting from vacuum
conditions.
12. Damages, malfunctions, or failures caused by operating the water
heater with modied, altered, or unapproved components, or any
component / attachment not supplied by HTP.
13. Damages, malfunctions, or failures caused by abuse, accident,
re, ood, freeze, lightning, acts of God and the like.
14. Tank failures (leaks) caused by operating the water heater in a
corrosive or contaminated atmosphere.
15. Damages, malfunctions, or failures caused by operating the water
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 22
22
heater with an empty or partially empty tank (“dry ring”), or failures
caused by operating the water heater when it is not supplied with
potable water, free to circulate at all times.
16. Failure of the heater due to the accumulation of solid materials
or lime deposits.
17. Any damages or failures caused by using any models other than
SSU / SSU-C 80 and 119 gallon models in live steam applications.
18. Any damages or failures caused by live steam pressures in excess
of 10 PSI in the indirect heat exchanger.
19. Any damage or failure resulting from improper water chemistry.
WATER CHEMISTRY REQUIREMENTS (RESIDENTIAL USE) – Water pH
between 6.5 and 8.5. Operating temperatures not exceeding 140oF.
Hardness less than 12 grains (200 mg/L). Chloride concentration less
than 100 ppm (mg/L). TDS less than 500 ppm (mg/L). (COMMERCIAL
USE) - Water pH between 6.5 and 8.5. Hardness less than 7 grains (120
mg/L). Chloride concentration less than 100 ppm (mg/L). TDS less
than 500 ppm (mg/L).
20. Any damages, malfunctions, or failures resulting from the use of
dielectric unions.
21. Production of noise, taste, odors, discoloration, or rusty water.
22. Water heaters replaced for cosmetic reasons.
23. Components of the water heater that are not defective, but must
be replaced during the warranty period as a result of reasonable
wear and tear.
24. Components of the water heater that are subject to warranties,
if any, given by their manufacturers; HTP does not adopt these
warranties.
25. Damages, malfunctions, or failures resulting from the use of any
attachment(s) not supplied by HTP.
26. Water heaters installed outside the fty states (and the District of
Columbia) of the United States of America and Canada.
27. Water heaters moved from the original installation location.
28. Water heaters that have had their rating labels removed.
LIMITATIONS OF YOUR HTP WARRANTY AND REMEDIES
THE FOREGOING WARRANTIES ARE EXCLUSIVE AND ARE GIVEN AND
ACCEPTED TO THE FURTHEST EXTENT UNDER APPLICABLE LAW IN LIEU
OF ANY AND ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING
WITHOUT LIMITATION THE IMPLIED WARRANTIES OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE AND ANY OBLIGATION,
LIABILITY, RIGHT, CLAIM OR REMEDY IN CONTRACT OR TORT, WHETHER
OR NOT ARISING FROM HTP’S NEGLIGENCE, ACTUAL OR IMPUTED. THE
REMEDIES OF THE OWNER SHALL BE LIMITED TO THOSE PROVIDED
HEREIN TO THE EXCLUSION OF ANY OTHER REMEDIES INCLUDING
WITHOUT LIMITATION, INCIDENTAL OR CONSEQUENTIAL DAMAGES,
SAID INCIDENTAL AND CONSEQUENTIAL DAMAGES INCLUDING, BUT
NOT LIMITED TO, PROPERTY DAMAGE, LOST PROFIT OR DAMAGES
ALLEGED TO HAVE BEEN CAUSED BY ANY FAILURE OF HTP TO MEET ANY
OBLIGATION UNDER THIS AGREEMENT INCLUDING THE OBLIGATION
TO REPAIR AND REPLACE SET FORTH ABOVE. NO AGREEMENT VARYING
OR EXTENDING THE FOREGOING WARRANTIES, REMEDIES OR THIS
LIMITATION WILL BE BINDING UPON HTP. UNLESS IN WRITING AND
SIGNED BY A DULY AUTHORIZED OFFICER OF HTP. THE WARRANTIES
STATED HEREIN ARE NOT TRANSFERABLE AND SHALL BE FOR THE
BENEFIT OF THE OWNER ONLY.
NO OTHER WARRANTIES
This warranty gives the Owner specic legal rights. The Owner may also
have other rights that vary from state to state. Some states do not allow
the exclusion or limitation of incidental or consequential damages so this
limitation or exclusion may not apply to the Owner.
These are the only written warranties applicable to the water heater
manufactured and sold by HTP. HTP neither assumes nor authorizes
anyone to assume for it any other obligation or liability in connection
with said water heaters.
HTP reserves the right to change specications or discontinue models
without notice.
PROCEDURES FOR WARRANTY SERVICE REQUESTS
Any claim for warranty assistance must be made promptly. Determine
if the water heater is “in-warranty” (that is, within the applicable
warranty period) by reviewing a copy of the original sales receipt or
warranty registration. The Owner must present a copy of the original
sales receipt or warranty registration for a warranty service request.
If the water heater is “in-warranty”, contact the retailer from whom
the water heater was purchased (or the installer) for assistance.
Be prepared to provide the retailer or installer with a copy of the
original receipt, complete model and serial numbers, and the date
of installation of the water heater, in addition to explanation of the
water heater problem.
Warranty coverage is subject to validation of “in-warranty” coverage
by HTP claims department personnel. All alleged defective or
malfunctioning components must be returned to HTP via the local
distribution channels where original purchase was made. NOTE: Any
components or heaters returned to HTP for warranty analysis
will become the property of HTP and will not be returned, even
if credit is denied. If all warranty conditions are satised, HTP will
provide replacement components to the retailer.
For questions about the coverage of this warranty, please contact HTP
at the following address or phone number: HTP, 272 Duchaine Blvd,
New Bedford, MA, 02745, Attention: Warranty Service Department,
1(800) 323-9651.
SERVICE, LABOR AND SHIPPING COSTS
This limited warranty does not extend to any shipping charges,
delivery expenses, or administrative fees incurred by the Owner
in repairing or replacing the water heater or component(s). This
warranty does not extend to labor costs beyond the coverage
specied in this warranty document. All such expenses are the
Owner’s responsibility.
lp-83 Rev. 006 Rel. 005 Date 12.18.17
Page 23
Customer Installation Record Form
The following form should be completed by the qualied installer / service technician for you to keep as a record of the installation in
case of a warranty claim. After reading the important notes at the bottom of the page, please also sign this document.
Customer’s Name
Date of Installation
Installation Address
Product Name / Serial Number(s)
Comments
23