HTP PH100-55, PH160-55, PH199-55, PH100-80, PH130-55 Installation Manual

...
Page 1
Phoenix Gas-Fired
This manual must be used by a qualified installer/service technician. Read all instructions in this manual damage, severe personal injury, or death.
Water Heater
INSTALLATION
START-UP
PARTS
Phoenix Water Heater Models* PH100-55 / 130-55 / 160-55 / 199-55 PH100-80 / 130-80 / 160-80 / 199-80
PH100-119 / 130-119 / 160-119 / 199-119
Phoenix Sanitizer Booster Models*
130-55SA / 199-55SA
*A suffix of “LP” denotes propane gas
*A suffix of “S” denotes solar model
before installing. Perform steps in the given order. Failure to comply could result in substantial property
NOTICE: HTP reserves the right to make product changes or updates without notice and will not be held liable for typographical errors in literature.
120 Braley Rd. P.O. Box 429 East Freetown, MA 02717-0429 www.htproducts.com
Page 2
IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION
provided by a qualified installer, service agency, or the gas supplier.
MAY RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE. DO NOT STORE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch.
Do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s
instructions.
If you cannot reach your gas supplier, call the fire department. Installation and service must be
2
Page 3
3
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important product information.
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious
injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
NOTE TO CONSUMER: PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE.
FOREWORD
This manual is intended to be used in conjunction with other literature provided with the Phoenix Gas­Fired Water Heater. This includes all related control information. It is important that this manual, all other documents included with this system, and additional publications including the National Fuel Gas Code, ANSI Z223.1-2002, be reviewed in their entirety before beginning any work.
Installation should be made in accordance with the regulations of the local code authorities and utility companies which pertain to this type of water heating equipment.
Page 4
This manual must only be used by a qualified heating installer/service technician. Read all instructions in personal injury, death or substantial property damage.
FOR THE INSTALLER
this manual before installing. Perform steps in the order given. Failure to comply could result in severe
This appliance must be installed by qualified and licensed personnel. The installer should be guided by the instructions furnished with the boiler, and with local codes and utility company requirements. In the absence of local codes, preference should be given to the National Fuel Gas Code, ANSI Z223.1-2002.
INSTALLATIONS MUST COMPLY WITH:
Local, state, provincial, and national codes, laws, regulations and ordinances. The latest version of the National Fuel Gas Code, ANSI Z223.1, from American Gas Association
Laboratories, 8501 East Pleasant Va lley Road, Cleveland, OH 44131. In Canada – CGA No. B149 (latest version), from Canadian Gas Association Laboratories, 55 Scarsdale
Road, Don Mills, Ontario, Canada M3B 2R3. Also, Canadian Electrical Code C 22.1, from Canadian Standards Association, 5060 Spectrum Way, Suite 100, Mississauga, Ontario, Canada L4W 5N6.
Code for the installation of Heat Producing Appliances (latest version), from American Insurance Association, 85 John Street, New York, NY 11038.
The latest version of the National Electrical Code, NFPA No. 70. NOTE: The gas manifold and controls met safe lighting and other performance criteria when undergoing
tests specified in ANSI Z21.10.3 – latest ed iti on.
4
Page 5
TABLE OF CONTENTS
PART 1 – GENERAL SAFETY INFORMATION .......................................................................................... 7
A. PRECAUTIONS .................................................................................................................................... 7
B. IMPROPER COMBUSTION.................................................................................................................. 7
C. GAS ....................................................................................................................................................... 7
D. WHEN SERVICING THE HEATER ...................................................................................................... 7
E. HEATER WATER .................................................................................................................................. 7
PART 2 – HOW THE HEATER OPERATES ................................................................................................ 8
PART 3 – PREPARE WATER HEATER LOCATION .................................................................................. 9
A. BEFORE LOCATING THE HEATER .................................................................................................... 9
B. LEVELING ............................................................................................................................................. 9
C. CLEARANCES FOR SERVICE ACCESS .......................................................................................... 10
D. RESIDENTIAL GARAGE INSTALLATION ......................................................................................... 10
E. EXHAUST VENT AND INTAKE AIR VENT ........................................................................................ 10
5
1. DIRECT VENT INSTALLATION OF EXHAUST AND INTAKE ....................................................... 11
2. INDOOR COMBUSTION AIR INSTALLATION IN CONFINED OR UNCONFINED SPACE .......... 11
F. PREVENT COMBUSTION AIR CONTAMINATION ........................................................................... 12
G. REMOVING A HEATER FROM A COMMON VENT SYSTEM.......................................................... 12
H. WATER CHEMISTRY ......................................................................................................................... 13
PART 4 – PREPARE THE HEATER .......................................................................................................... 14
PART 5 – HEATER PIPING ....................................................................................................................... 15
A. GENERAL PIPING INFORMATION ................................................................................................... 15
B. SCALDING .......................................................................................................................................... 15
C. TEMPERATURE AN D P R ES SURE RELIEF VALVE ......................................................................... 16
D. BACKFLOW PREVENTER ................................................................................................................. 16
E. POTABLE EXPAN SIO N T AN K ........................................................................................................... 16
F. WATER PIPING .................................................................................................................................. 17
G. AUXILIARY CONNECTIONS ............................................................................................................. 17
H. PIPING DIAGRAMS ............................................................................................................................ 18
PART 6 – ELECTRICAL CONNECTIONS ................................................................................................. 25
A. LINE VOLTAGE INPUT ...................................................................................................................... 25
B. LINE VOLTAGE CONDENSATE OUTPUT ........................................................................................ 25
C. LOW VOLTAGE OUTDOOR SENSOR INPUT .................................................................................. 25
PART 7 – GAS CONNECTIONS ................................................................................................................ 25
A. GAS PIPING ....................................................................................................................................... 26
Page 6
6
B. GAS TABLE ........................................................................................................................................ 26
C. GAS VALVE ........................................................................................................................................ 27
PART 8 – VENTING, COMBUSTION AIR AND CONDENSATE REMOVAL ........................................... 28
A. GENERAL ........................................................................................................................................... 28
B. APPROVED MATERIALS FOR EXHAUST AND INTAKE AIR VENTS ............................................. 28
C. EXHAUST AND INTAKE AIR VENT PIPE LOCATION ...................................................................... 29
1. DETERMINE EXHAUST VENT LOCATION.................................................................................... 29
2. DETERMINE AIR INTAKE VENT LOCATION ................................................................................ 29
D. EXHAUST AND INTAKE AIR VENT SIZING ...................................................................................... 30
E. LONGER VENT RUNS ....................................................................................................................... 31
F. EXHAUST VENT AND INTAKE AIR PIPE INSTALLATION ............................................................... 32
G. VENTING DRAWINGS ....................................................................................................................... 33
1. DIRECT VENT INSTALLATION OF EXHAUST AND INTAKE ....................................................... 33
2. INDOOR COMBUSTION AIR INSTALLATION IN CONFINED OR UNCONFINED SPACE .......... 38
H. CONDENSATE REMOVAL SYSTEM ................................................................................................ 41
PART 9 – START-UP PROCEDURE ......................................................................................................... 42
A. OPERATING INSTRUCTIONS ........................................................................................................... 42
B. OVERALL APPLIANCE AND CONTROL OPERATION ..................................................................... 42
C. STATUS MENU .................................................................................................................................. 43
D. OUTDOOR RESET ............................................................................................................................. 43
E. TEST MODE ....................................................................................................................................... 45
F. MAINTENANCE .................................................................................................................................. 45
G. INTERNAL WIRING ............................................................................................................................ 46
PART 10 – SHUTDOWN ............................................................................................................................ 47
A. SHUTDOWN PROCEDURE ............................................................................................................... 47
B. VACATION PROCEDURE .................................................................................................................. 47
C. FAILURE TO OPERATE..................................................................................................................... 47
PART 11 – TROUBLESHOOTING ............................................................................................................. 47
A. ERROR CODE .................................................................................................................................... 47
B. HEATER ERROR ................................................................................................................................ 47
C. LOCKOUT ........................................................................................................................................... 48
PART 12: MAINTENANCE ......................................................................................................................... 54
MAINTENANCE NOTES ............................................................................................................................ 57
HTP CUSTOMER INSTALLATION RECORD FORM ........................................................................ 58
Page 7
INSTALLER – Read all instructions in this manual before installing. Perform steps in the order given.
USER – This manual is for use only by a qualified heating installer/service technician. Refer to user’s technician annually.
FAILURE TO ADHERE TO THE GUIDELINES ON THIS PAGE CAN RESULT IN SUBSTANTIAL PROPERTY DAMAGE, SEVERE PERSONAL INJURY, OR DEATH.
NOTE: If the heater is exposed to the following, do not operate until all corrective steps have been made
company by the consignee.
NOTE: Do not obstruct the flow of combustion and ventilating air. Adequate air must be provided for safe operation.
PART 1 – GENERAL SAFETY INFORMATION
A. PRECAUTIONS
This appliance is for indoor installations only. Clearance to combustible materials: 0” top, bottom, sides and back. Unit must have room for service: 24” front and 12” sides are minimum recommended service clearances. (A combustible door or removable panel is acceptable front clearance.) This appliance has been approved for closet installation, and instal lat ion o n combustible flooring. Do not install this appliance directly on carpeting. Use only Category IV vent systems.
information manual for your reference. Have this heater serviced/inspected by a qualified service
7
by a qualified serviceman:
1. FIRE
2. DAMAGE
3. WATER Any claims for damage or shortage in shipment must be filed immediately against the transportation
DO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN UNDERWATER. Immediately call a qualified service technician. Replace any part of the control unit that has been und er water.
B. IMPROPER COMBUSTION
C. GAS
Should overheating or gas supply fail to shut off, turn off the manual gas control valve to the appliance.
D. WHEN SERVICING THE HEATER
To avoid electric shock, disconnect electrical supply before performing maintenance.
To avoid severe burns, allow heater to cool.
E. HEATER WATER
Do not use petroleum-based cleaning or sealing compounds in a heater system. Gaskets and seals in the system may be damaged. This can result in substantial property damage.
Do not use “homemade cures” or “heater patent medicines”. Substantial property damage, damage to heater, and/or serious personal injury may result.
Page 8
PART 2 – HOW THE HEATER OPERATES
Modulation Condensing Technology is an intelligent system that delivers highly efficient water heatin g, while maximizing efficiency by measuring the data parameters of your water heating system. Some of its features are:
Stainless Steel Water Storage Tank
The stainless steel water storage tank has a combustion chamber submerged into the tank water. When the water heater is fired, combustion gases heat the combustion chamber walls, transferring heat directly into the surrounding water. These hot gases are blown into secondary heat exchanger coils, where more heat is transferred into the water, removing even more heat from the gases.
Modulating Combustion System
Modulation during water heating operation is based on tank temperature. The control monitors the system to regulate burner output during operation to match system demand. This increase in efficiency allows for substantial fuel savings.
Gas Valve
The gas valve senses suction from the blower, allowing gas to flow only if the gas valve is energized and combustion air is flowing.
Upper Supply Tank Sensor
This sensor monitors the upper portion water temperature (system supply) of the water heater. The control module adjusts the burner firing rate so the outlet water temperature meets the set point.
Lower Return Tank Sensor
This sensor monitors the lower portion of the water heater inlet water temperature (system return). The control module reduces or increases input, depending on how close the water temperature is to the outlet water temperature set point.
Control
The integrated control system monitors upper and lower water temperature and regulates fan speed to regulate the unit’s energy output. This allows the unit to deliver the required amount of heated ener g y and nothing more.
Burner
Constructed of high grade stainless steel, the burner uses pre-mixed air and gas and provides a wide range of firing rates.
Condensate Drain Connection
This is a condensing high efficiency applianc e, and therefore has a condensate removal system. Condensate is nothing more than water vapor, derived from combustion products and similar to an automobile when it is initially starte d. It is ver y impor t ant that the condensate line slopes away from the water heater and down to a suitable inside drain.
If the condensate outlet on the heater is lower than the drain, you must use a condensate removal pump (kit p/n 554200 available from HTP.) In addition, local authorities may require a condensate neutralizer to neutralize the condensate. Condensate neutralizers are made up of lime crystals, marble or phosphate chips. Neutralizers c an be i ns tal led in the field by the installer and purchased from HTP (p/n 7450P-212).
It is also very important not to expose the condensate line to freezing temperatures or any type of blockage. Plastic tubing must be the only material used for the condensate line. Steel, brass, copper or other materia ls will be subject to corrosion or deterioration. A second vent may be necessary to prevent condensate line vacuum lock on a long horizontal run. Also, an increase in pipe size may be necessary to
8
Page 9
Water temperature over 125oF can instantly cause severe burns, or death, from scalds. Children,
valves are available.
Failure to keep heater area clear and free of combustible materials, liquids, and vapors can result in substantial property damage, severe personal injury, or death.
In order for the condensate to properly flow out of the collection system, the area where you locate the heater must be level. Location must also fully support the weight of the filled water heater.
allow condensate to dra in p roper ly. Support of the condensation line may be necessary to avoid blockage of the condensate flow.
Spark Ignition
The burner flame is ignited by applying high voltage to the system spark electrode. This causes a spark from electrode to ground.
disabled, and elderly are at the highest risk of being scalded. See instruction manual before setting temperature at water heater. Feel water before bathing or showering! Temperature limiting
PART 3 – PREPARE WATER HEATER LOCATION
Before considering locat ion , many factors need to be addressed. Piping, Ven tin g, and Cond ens at io n Removal are just a few of the issues that need attention prior to the installation of the heater. Please read the entire manual, as it could save time and money.
A. BEFORE LOCATING THE HEATER
Check for nearby connections to:
System water piping
Venting connections
Gas supply piping
Electrical power
Condensate drain
Check area around heater. Remove any combustible materials, gasoline, and other flammable liquids.
9
The heater gas control system components must be protected from dripping water during operation and service.
If replacing an existing heater, check for and correct any existing system problems, such as:
System leaks
Heater is located in a condition that could cause the system to freeze and leak.
Incorrectly-sized expansion tank
Clean and flush existing system when reinstalling a heater.
B. LEVELING
Page 10
The space must be provided with combustion/ventilation air openings correctly sized for all other
damage, severe personal injury, or death.
Failure to vent the water heater prope rly will result in serious personal injury or death.
C. CLEARANCES FOR SERVICE ACCESS
10
Figure 1
If you do not provide the minimum clearances shown, it might not be possible to service the heater without removing it from the space.
appliances located in the same space as the heater. The heater cover must be securely fastened to prevent the heater from drawing air form the heater room. This is particularly important if the heater is in a room with other appliances. Failure to comply with the above warnings could result in substantial property
D. RESIDENTIAL GARAGE INST AL LAT ION
PRECAUTIONS
If the heater is located in a residential garage, per ANSI Z223.1:
Mount the bottom of the heater a minimum of 18” above the floor of the garage, to ensure the burner and ignition devices are well off the floor.
When raising the heater, fully support the entire bottom of the appliance.
Locate or protect the heater so it cannot be damaged by a moving vehicle.
E. EXHAUST VENT AND INTAKE AIR VENT
The heater is rated ANSI Z21.10.3 Category IV (pres sur i zed vent, likely to form condensate in the vent) and requires a special vent system designed for pressurized venting.
NOTE: The venting options described here (and further detailed in Venting, Part 8 in this manual) are the lone venting options approved for this water heater. Failure to vent the water h eater in accordance with the provided venting instructions will void the warranty.
Page 11
11
Vents must be properly supported. Heater intake and exhaust connections are not designed to carry Heater must be readily accessible for visual inspection for the first 3’ from the heater.
adequate freeze protection.
heavy weight. Vent support brackets must be within 1’ of the heater and the balance at 4’ intervals.
1. DIRECT VENT INSTALLATION OF EXHAUST AND INTAKE
If installing a direct vent option, combustion air must be drawn from the outdoors directly into the appliance intake, and exhaust must terminate outside. There are three basic direct vent options detailed in this manual: 1. Sid e Wall Venting, 2. Roof Venting, and 3. Unbalanced Venting.
Be sure to locate the heater such that the air intake and exhaust vent piping can be routed through the building and properly terminated. Different vent terminals can be used to simplify and eliminate multiple penetrations in the building structure (see Optional Equipment in Venting Section). The air intake and exhaust vent piping lengths, routi ng and termination methods must all comply with the methods and limits given in the Venting section, Part 8 of this manual.
When installing a combustion air intake from outdoors, care must be taken to utilize uncontaminated combustion air. NOTE: To prevent combustion air contamination, see Table 1.
2. INDOOR COMBUSTION AIR INSTALLATION IN CONFINED OR UNCONFINED SPACE
This heater requires fresh, uncontaminated air for safe operation and must be installed in a mechanical room where there is adequate combustion and ventilating air. NOTE: To prevent combustion air
contamination, see Table 1.
Combustion air from the indoor space can be used if the space has adequate area or when air is provided through a duct or louver to supply suffic ient com bus tio n air based on the app li anc e input. Never obstruct the supply of combustion air to the appl iance. If the appliance is installed in areas where indoor air is contaminated (see Table 1) it is imperative that the appliance be installed as direct vent so that all combustion air is taken directly from the outdoors into the appliance intake connection.
Unconfined space is space with volume greater than 50 cubic feet per 1,000 Btu/hour (4.8 cubic meters per kW) of the total input rating of all fuel-burning appliances installed in that space. Rooms connected directly to this space, through openings not furnished with doors, are considered part of the space. See Figure 22, p. 40 for details.
Confined space is space with volume less than 50 cubic feet per 1,000 Btu/hour (4.8 cubic meters per kW) of the total input rating of all fuel-burning appliances installed in that space. Rooms connected directly to this space, through openings not furnished with doors, are considered part of the space.
When drawing combustion air from inside a conventionally constructed building to a confined space, such space should be provided with two permanent openings: one located 6” (15 cm) below the space ceiling, the other 6” (15cm) above the space floor. Each opening should have a free area of one square inch per 1,000 Btu/hr (22cm inches (645cm
2
/kW) of the total input of all appliances in the space, but not less than 100 square
2
).
If the confined space is within a building of tight construction, air for combustion must be obtained from the outdoors as outlined in the Venting section, Part 8 of this manual.
When drawing combustion air from the outside into the mechanical room, care must be taken to provide
Page 12
Do not attempt to vent this appliance by any means other than those described in this manual. Doing so will void the warranty, and may result in severe personal injury or death.
Failure to provide an adequate supply of fresh combustion air can cause poisonous flue gases to enter contamination, see Table 1.
Ensure that the intake air will not contain any of the contaminants below. Contaminated air will damage
from laundry facilities. These areas always contain contaminants.
PRODUCTS TO AVOID
AREAS LIKELY TO HAVE CONTAMINANTS
Spray cans containing fluorocarbons
Dry cleaning/laundry areas and establishments
Permanent wave solutions
Swimming pools
Chlorinated waxes/cleaners
Metal fabrication plants
Chlorine-based swimming pool chemicals
Beauty shops
Calcium chloride used for thawing
Refrigeration repair shops
Sodium chloride used for water softening
Photo processing plants
Refrigerant leaks
Auto body shops
Paint or varnish removers
Plastic manufacturing plants
Hydrochloric or Muriatic acid
Furniture refinishing areas and establishments
Cements and glues
New building construction
Antistatic fabric softeners used in clothes dryers
Remodeling areas
Chlorine-type bleaches, laundry detergents, and cleaning solvents
Garages and workshops Adhesives used to fasten building products
Do not install the heater into a common vent with any other appliance. This will cause flue gas spillage or appliance malfunction, resulting in possible substantial property damage, severe personal injury, or death.
Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe personal injury or death.
NOTE: DAMAGE TO THE HEATER CAUSED BY EXPOSURE TO CORROSIVE VAPORS IS NOT
living space, which could result in severe personal injury or death. NOTE: To prevent combustion air
F. PREVENT COMBUSTION AIR CONTAMINATION
Install intake air piping for the heater as described in the Venting Section. Do not terminate exhaust in locations that can allow contamination of intake air.
COVERED BY WARRANTY. (Refer to the limited warranty for complete terms and conditions).
12
the heater, resulting in possible substantial property damage, severe personal injury, or death. For example, do not pipe intake air vent near a swimming pool. Also, avoid areas subject to exhaust fumes
Table 1 – Contaminant Table
G. REMOVING A HEATER FROM A COMMON VENT SYSTEM
Page 13
13
Chemical imbalance of your water can cause severe damage to your water heater and associated
warranty.
Figure 3 - CO Warning Label Figure 2
When removing an existing heater, follow the steps below.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch to determine if there is blockage, leakage, corrosion or other deficiencies that could cause an unsafe condition.
3. If practical, close all building doors, windows and doors between the space in which the appliance remains connected to the common venting system and other spaces in the building. Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any exhaust fans,
such as range hoods and bathroom exhausts, at maximum speed. Do not operate a summer exhaust fan. Close all fireplace dampers.
4. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust the thermostat so the appliance will operate continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle or smoke from a cigarette.
6. After it has been determined that each appliance remaining connected to common venting system properly vents when tested as outlined, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous condition of use.
7. Any improper operation of the common venting system should be corrected to conform to the National Fuel Gas Code, ANSI Z223.1. When resizing any portion of the common venting system, the system should approach the minimum size as determined using the appropriate tables in Appendix G in the National Fuel Gas Code, ANSI Z 223.1.
H. WATER CHEMISTRY
equipment, and may also affect efficiency. You may have to have your water quality professionally analyzed to determine whether you need to install a water softener. Failure of a heat exchanger due to
lime scale build-up on the heating surface, low pH or other imbalance IS NOT covered by the
Water Hardness
Water hardness is mainly due to the presence of calcium and magnesium salts dissolved in the water. The concentration of these salts is expressed in mg/L, ppm or grains per gallon, as a measure of relative hardness of water. Grains per gallon is the common reference measurement used in the U.S. water heater industry. Hardness expressed as mg/L or ppm may be divided by 17.1 to convert to grains per gallon. Water may be classified as very soft, slightly hard, moderately hard, or hard based on its hardness
Page 14
14
UNCRATING HEATER – Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
COLD WEATHER HANDLING – If the heater has been stored in a very cold location (BELOW 0oF) before installation, handle with care until the plastic components come to room temperature.
number. The minerals in the water precipitate out when the water is heated and cause accelerated lime and scale accumulation on a heat transfer surface.
If the hardness of the water exceeds the maximum level of 25 grains per gallon, water should be softened to a hardness level no lower than 5 grains per gallon. Water softened as low as 0 to 1 grain per gallon may be under-saturated with respect to calcium carbonate, res u lting in water that is aggressive and corrosive.
pH of Water
pH is a measure of relative acidity, neutrality or alkalinity. Dissolved minerals and gases affect water pH. The pH scale ranges from 0 to 14. Water with a pH of 7.0 is considered neutral. Water with a pH lower than 7 is considered acidic. Water pH higher than 7 is considered alkaline. A neutral pH (around 7) is desirable for most potable water applications. Corrosion damage and heater failures resulting from water pH levels of lower than 6 or higher than 8 ARE NOT covered by the warranty. The ideal pH range for water used in a storage tank or a water heater system is 7.2 to 7.8.
Total Dissolved Solids
Total Dissolved Solids (TDS) is a measurement of all minerals and solids dissolved in a water sample. The concentration of total dissolved solids is usually expressed in parts per million (ppm).
Water with a high TDS concentration will greatly accelerate lime and scale formation in the hot water system. Most high TDS concentrations precipitate out of the water when heated. This can generate a scale accumulation on the heat transfer surface that will greatly reduce the service life of a water heater. This scale accumulation can also impede the ability of the heat exchanger to transfer heat into the water. A heat exchanger damaged or blocked by lime/scale accumulation must be replaced.
The manufacturer of the water heater has no control of water quality, especially TDS levels in your system. Total dissolved solids in excess of 2,000 ppm will accelerate lime and scale formation in the heat exchanger. Heat exchanger failure due to total dissolved solids in excess of 2,000 ppm is a non­warrantable condition. Failure of a water heater due to lime scale build up on th e heating surface IS
NOT covered by the warranty.
PART 4 – PREPARE THE HEATER
Remove all sides of the shipping crate to allow the heater to be lifted into its installation location.
Page 15
15
components.
The heater control module uses temperature sensors to provide both high limit protection and modulating the tank. Some codes/jurisdictions may require additional external controls.
Never use dielectric unions or galvanized steel fittings when connecting to a stainless steel storage tank or heater. Use only copper or brass fittings. Teflon thread sealant must be used on all connections.
APPROXIMATE TIME / TEMPERATURE
RELATIONSHIPS IN SCALDS
120oF
More than 5 minutes
125oF
1 ½ to 2 minutes
130oF
About 30 seconds
135oF
About 10 seconds
140oF
Less than 5 seconds
145oF
Less than 3 seconds
150oF
About 1 ½ seconds
155oF
About 1 second
Table 2
PART 5 – HEATER PIPING
A. GENERAL PIPING INFORMATION
Use two wrenches when tightening water piping at heater. Use one wrench to prevent the heater return or supply line from turning. Failure to prevent piping connections from turning could cause damage to heater
temperature control. The control module also provides low water protection by sensing the water level in
B. SCALDING
This heater can deliver scalding water. Be careful whenever using hot water to avoid scalding injury. Certain appliances, such as dishwashers and automatic clothes washers may require increased water temperature. By setting the thermostat on this heater to obtain the increased water temperature required by these appliances, you may create the potential for scald injury.
To protect against injury, you should install a mixing valve in the water system. This valve will reduce point of discharge temperature by mixing cold and hot water in branch supply lines. Such valves are available from your local plumbing supplier.
Table 2 details the relationship of water temperature and time with regard to scald injury and may be used as a guide in determining the safest water temperature for your applications.
Page 16
To avoid water damage or scalding due to relief valve operation:
SEVERE PERSONAL INJURY, OR DEATH.
Do not thread a cap or plug into the relief valve under any circumstances! Explosion and property damage, serious injury, or death may result.
C. TEMPERATURE AND PRESSURE RELIEF VALVE
Discharge line must be connected to relief valve outlet and run to a safe place of disposal. Terminate the discharge line in a manner that will prevent possibility of severe burns or property damage should the relief valve discharge.
Discharge line must be as short as possible and the same size as the valve discharge connection throughout its entire length.
Discharge line must pitch downward from the valve and terminate at least 6” above the floor drain, making discharge clearly visible.
The discharge line shall terminate plain, not threaded, with a material serviceable for temperatures of 375
Do not pipe discharge to any location where freezing could occur.
No shutoff valve may be installed between the relief valve and heater or in the discharge line. Do
not plug or place any obstruction in the discharge line.
Test the operation of the relief valve after filling and pressurizing the system by lifting the lever. Make sure the valve discharges freely. If the valve fails to operate correctly, immediately replace with a new properly rated relief valve.
Test T&P valve at least once annually to ensure the waterway is clear. If valve does not operate, turn the heater “off” and call a plumber immediately.
Take care whenever operating relief valve to avoid scalding injury or propert y damage.
FAILURE TO COMPLY WITH THE ABOVE GUIDELINES COULD RESULT IN FAILURE OF RELIEF VALVE OPERATION, RESULTING IN POSSIBILITY OF SUBSTANTIAL PROPERTY DAMAGE,
o
F or greater.
16
D. BACKFLOW PREVENTER
Use a backflow preventer specifically designed for water heater installations. This valve should be installed on the cold water fill supply line per local codes.
E. POTABLE EXPANSION TANK
A potable hot water expansion tank is required to offset heated water expansion. In most city plumbing systems, the water meter has a no return or back flow device built into the system to prevent back flowing of water into city mains. Some local codes require back flow preventers on all incoming water supplies. The hot water expansion tank must be listed for potable water use. The expansion tank should be located on the cold inlet piping close to the water heater.
EXPANSION TANK AND MAKE-UP WATER
1. Ensure that the expansion tank is sized to correctly handle heater and system water volume and temperature.
Page 17
17
Undersized expansion tanks cause system water to be lost from the relief valve, causing make-up water FAILURE IS NOT COVERED BY WARRANTY.
The expansion tank must be suitable for hot potable water.
Never use dielectric unions or galvanized steel fittings on any domestic water or auxiliary connections. Use only copper or brass fittings. Thread sealant must be use d on all connections.
Never connect auxiliary connections to any system that uses glycol or other solutio n s formulated Failure to follow this warning could result in serious injury or death.
to be added. Eventual heater failure can result due to excessive make-up water addition. SUCH
2. The expansion tank must be located as shown in the Heater Piping Details, or following recognized design methods. See expansion tank manufacturer’s instructions for details.
F. WATER PIPING
The domestic water connections must be installed in accordance to all local and national plumbing codes, or any applicable standard which prevails. The inlet and outlet ports are 1" on 55 gallon models, and 1 ½” on 80 and 119 gallon models.
On the cold inlet, install a 1" brass tee on 55 gallon models, or a 1 ½" tee on 80 and 119 gallon models. On the run of the 1" brass tee, install a 1" brass drain cock or equivalent with pipe sealant compound. In the branch of the 1" or a 1 ½" brass tee, install a copper male adapter to match your copper plumbing system. For convenience, you may install a sweat shut off valve and a union in the cold inlet piping to ease future servicing. If there is a back flow preventer or any type of a no return valve in the system, you must install an additional tee here, suitable for a potable hot water expansion tank.
In the hot outlet, install a suitable adapter to match the copper tubing of the plumbing system. A thermal trap or heat trap loop may be installed here to provide additional energy savings and prevent the thermal siphoning of domestic hot water.
G. AUXILIARY CONNECTIONS
The auxiliary connections are additional connections for air handlers, plate exchangers, or other devices that supply hot water. These connections must be installed in accordance with all local and national codes or any applicable standard that prevails. Auxiliary connections are 1" on all models. Never use dielectric unions or galvanized steel fittings. Use only copper or brass fittings. Sealant must be used on all connections. The top port is the supply outlet and the bottom port is the return inlet.
for hydronic systems. These auxil iary connections are to be used only in a potable water system.
Page 18
An ASSE 1017 thermostatic mixing valve MUST be installed when using outdoor reset. Failure to do so could result in substantial property damage, serious injury, or death.
H. PIPING DIAGRAMS
18
Figure 4 – LP-179-L - NOTE: This drawing is meant to demonstrate system piping only. The installer is responsible for all equipment and detailing required by local codes. In Massachusetts, you must install a vacuum relief valve per 248 CMR. With air handlers, outdoor reset is available with a n outdoor sensor. See Part 9, Section D.
Page 19
19
An ASSE 1017 thermostatic mixing valve MUST be installed when using outdoor reset. Failure to do so could result in substantial property damage, serious injury, or death.
PHOENIX WITH AIR HANDLER ON SIDE
Figure 5 – LP-179-M - NOTE: This drawing is meant to demonstrate system piping only. The installer is responsible for all equipment and detailing required by local codes. In Massachusetts, you must install a vacuum relief valve per 248 CMR. With air handlers, outdoor reset is available with an outdoor sensor. See Part 9, Section D.
Page 20
20
Figure 6 – LP-179-N - NOTE: This drawing is meant to demonstrate system piping only. The installer is responsible for all equipment and detailing required by local codes. In Massachusetts, you must install a vacuum relief valve per 248 CMR.
Page 21
21
Figure 7 – LP-179-U - NOTE: This drawing is meant to demonstrate system piping only. The installer is responsible for all equipment and detailing required by local codes. In Massachusetts, you must install a vacuum relief valve per 248 CMR.
Page 22
22
Figure 8 – LP-179-O - NOTE: This drawing is meant to demonstrate system piping only. The installer is responsible for all equipment and detailing required by local codes. In Massachusetts, you must install a vacuum relief valve per 248 CMR.
Page 23
23
An ASSE 1017 thermostatic mixing valve MUST be installed when using outdoor reset. Failure to do so could result in substantial property damage, serious injury, or death.
Figure 9 – LP-179-Z - NOTE: This drawing is meant to demonstrate system piping only. The installer is responsible for all equipment and detailing required by local codes. In Massachusetts, you must install a vacuum relief valve per 248 CMR. NOTE: For proper operation, it is important to pipe recirculation lines with thermostatic mixing valve as shown above.
Page 24
The standard Phoenix Water Heater does not meet the required temperature settings for sanitizer booster the booster must be supplied at 140oF.
applications. Use only the Phoenix Sanitizer Booster that delivers temperatures of 184oF. Inlet water to
PHOENIX SANITIZER BOOSTER INSTALLATION
p/n PH130-55SA / PH199-55SA
24
Figure 10 LP-179-SA - NOTE: In Massachusetts, you must install a vacuum relief valve per 248 CMR. For further energy savings, install the Phoenix Sanitizer Booster on the same electrical circuit as the dishwasher.
Page 25
25
Failure to follow all precautions could result in fire, explosion, severe injury or death!
It is of extreme importance that this unit be properly grounded. It is very important that the building system be turned on when the heater is completely filled with cold water.
PART 6 – ELECTRICAL CONNECTIONS
A. LINE VOLTAGE INPUT
The heater must be wired to a 120 volt circuit by a qualified electrician. It is recommended that the heater be wired on its own circuit to minimize the possibility of circuit failure due to outside causes. The heater requires a maximum of 8 amps at 120 volts in use.
B. LINE VOLTAGE CONDENSATE OUTPUT
The heater has the capability of supplying power to a condensate pump. The connection is 120 VAC +/­10% at a max of 2 amps. Power is supplied to the pump only when the heater is connected to power, and the power switch is in the on position.
C. LOW VOLTAGE OUTDOOR SENSOR INPUT
The heater has the capability of an outdoor reset. Connecting an outdoor sensor allows the heater to operate at optimum efficiency. HTP offers an outdoor sensor, p/n 7250P-319
The outdoor sensor must be a 12K NTC sensor. Use a minimum 22 AWG wire for runs of 100 feet or less and minimum 18 AWG wire for runs up to 150 feet. Instructions are included with the outdoor sensor to correctly mount the sensor on the exterior surface of the building. It is preferable to mount the sensor on the north side in an area that will not be affected by direct sunlight but will be exposed to varying weather conditions. Connect the outdoor sensor to terminals marked “Outdoor”.
Figure 11 – LP-179-Y
ground is inspected by a qualified electrician prior to making this connection. Electrical power must only
PART 7 – GAS CONNE CTION S
Page 26
Nominal
(Inches)
¾
.824
1
1.049
1 ¼
1.380
1,050
730
590
500
440
400
370
350
320
305
275
250
225
210
1 ½
1.610
Figure 12 LP-179-Q
The gas supply shall have a maximum inlet pressure of less than 14" water column (350 mm), ½ pound pressure (3.5 kPa), and a minimum of 3.5" water column. The entire piping system, gas meter and regulator must be sized properly to prevent pressure drop greater than 0.5" WC as stated in the National Fuel Gas Code. This information is listed on the rating plate.
It is very important that you are connected to the type of gas as noted on the rating plate: "LP" for liquefied petroleum, propane gas, or "Nat" for natural or city gas. All gas connections must be approved by the local gas supplier or utility, in addition to the governing authority, prior to turning the gas supply on.
Do not remove the adaptor in Figure 12! It is mandatory that this fitting is used for connection to a field fabricated drip leg per the National Fuel Gas Code. You must ensure that the entire gas line to the connection at the water heater is no smaller than ¾".
Once all inspections have been performed, the piping must be leak tested. If the leak test requirement is a higher test pressure than the maximum gas inlet pressure, you must isolate the heater from the gas line to continue leak testing. To do this, you must turn off the factory and field-installed gas cocks. This will
minimize the possibility of damaging the gas
valve. Failure to do so may damage the gas valve. In the event the gas valve is exposed to a pressure greater than ½ PSI, 14" water column, the gas valve must be replaced. Never use an open flame (match, lighter, etc.) to check gas connections.
26
A. GAS PIPING
Run the gas supply line in accordance with all applicable codes. Locate and install manual shutoff valves in accordance with local and state requirements.
B. GAS TABLE
Refer to the table below to size the supply piping to minimize pressure drop between meter or regulator and unit.
Maximum capacity of pipe in cubic feet of gas per hour for gas pressures of .5 psi or less and a pressure drop of .3 inch water column.
Iron Pipe
Size
Table 3 – Source – ANSI Z223.1
Internal
Diameter
(Inches)
10 20 30 40 50 60 70 80 90 100 125 150 175 200
278 190 152 130 115 105 96 90 84 79 72 64 59 55 520 350 285 245 215 195 180 170 160 150 130 120 110 100
1,600 1,100 890 760 670 610 560 530 490 460 410 380 350 320
Length of Pipe (Feet)
BTU’s
Per
Hour x
1,000
Page 27
27
Do not do a gas conversion on this water heater without an officially approved conversion kit and instructions supplied by HT P.
It is recommended that a soapy solution be used to detect leaks. Bubbles will appear on the pipe to indicate a leak is present. The gas piping must be sized for proper flow and length of pipe to avoid excessive pressure drop. Both the gas meter and the gas regulator must be properly sized for the total gas load. If you experience a pressure drop greater than 1" WC, the meter, regulator or gas line is undersized or in need of service. You can attach a manometer to the incoming gas drip leg by removing the cap. The gas pressure must remain between 3.5" WC and 14" WC during stand-by (static) mode and while in operating (dynamic) mode at full output.
If an in-line regulator is used, it must be a minimum of 10 feet from the heater. It is very important that the gas line is properly purged by the gas supplier or utility. Failure to prope rly purge the lines or improper line sizing will result in ignition failure. This problem is especially noticeable in
NEW LP installations and also in empty tank situations. This can also occur when a utility company shuts off service to an area to provide maintenance to their lines. The gas valve must not be replaced with a conventional gas valve under any circumstances. As an additional safety feature, the gas valve in this appliance has a flanged connection to the swirl plate and blower.
C. GAS VALVE
Figure 13 – Gas Valve LP-179-P
Page 28
28
Failure to provide a properly installed vent system will cause severe personal injury or death.
This vent system will operate with a positive pressure in the pipe. Do not connect vent connectors serving
damage, severe personal injury, or death.
APPROVED VENTING MATERIAL
Standards for Installation in:
United States
Canada
PVC schedule 40/80
ANSI/ASTM D1785
S636.
PVC-DWV
ANSI/ASTM D2665
PVC
ANSI/ASTM D2564
Cements & Primers
CPVC
ANSI/ASTM F493
Do not use Foam Core Pipe in any portion of the exhaust piping from this water heater. Use of Foam Core Pipe may result in substantial property damage, severe personal injury, or death.
PART 8 – VENTING, COMBUSTION AIR AND CONDENSATE REMOVAL
The heater must be vented as detailed in this Venting Section. Ensure exhaust and intake piping complies with these instructions regar di ng vent syst em.
Inspect finished combustion air intake and exhaust piping thoroughly to ensure all joints are well secured, airtight, and comply with all applicable code requirements , as well as with the ins truc tions prov id ed in this manual.
A. GENERAL
appliances vented by natural draft into any portion of mechanical draft systems operating under positive pressure.
Follow the venting instructions below carefully. Failure to do so may result in substantial property
1. Install the water heater venting system in accordance with these instructions and with the National Fuel Gas Code, ANSI Z223.1/NFPA 54, CAN/CGA B149, and/or applicable provisions of local building codes.
2. This water heater is a direct vent appliance and is listed as a Category IV appliance with Underwriters Laboratories, Inc. VENT AND INTAKE AIR VENT.
B. APPROVED MATERIALS FOR EXHAUST AND INTAKE AIR VENTS
Item Material
CPVC and PVC venting
must be ULC-S636
Vent or air pipe and
fittings
Pipe cement/primer
Table 4
CPVC schedule 40/80 ANSI/ASTM F441
Certified. IPEX is an
approved manufacturer in
Canada, supplying vent
material listed to ULC-
IPEX System 636
Page 29
C. EXHAUST AND INTAKE AIR VENT PIPE LOCATI ON
1. DETERMINE EXHAUST VENT LOCATION
a. The vent piping for this water heater is approved for zero clearance to combustible construction. b. See illustration within this section of clearances for location of exit terminals of direct-vent venting systems. c. This water heater vent system shall terminate at least 3 feet (0.9 m) above any forced air intake located within 10 ft (3 m). Note: this does not apply to the combustion air intake of a direct-vent appliance. d. Provide a minimum of 1 foot distance from any door, operable window, or gravity intake into any building. e. Provide a minimum of 1 foot clearance from the bottom of the exhaust above the expected snow accumulation level. Snow removal may be necessary to maintain clearance. f. Provide 4 feet horizontal clearance from electrical meters, gas meters, gas regulators, relief equipment, exhaust fans and inlets. In no case shall the exit terminal be above or below the aforementioned equipment unless the 4 foot horizontal distance is maintained. g. When adjacent to a public walkway, locate exit terminal at least 7 feet above grade. h. Do not locate the exhaust directly under roof overhangs to prevent icicles from forming. i. Provide 4 feet clearance from the inside corner of vertical walls, chimneys, etc., as well as horizontal corners created by roof overhangs.
29
2. DETERMINE AIR INTAKE VENT LOCATION
a. Provide 1 foot clearance from the bottom of the intake air vent and the level of maximum snow accumulation. Snow removal may be necessary to maintain clearances. b. Do not locate intake air vent in a parking area where machinery may damage the pipe. c. When venting with a two pipe system, maximum distance between intake air vent and exhaust vent is 6 feet (1.8 m). Minimum distance between exhaust vent and intake air vent on single water heater is 10” (0.255 m) center-to-center. Minimum distance between exhaust vents and intake air vents on multiple water heaters is 10” (0.255 m) center-to-center.
Page 30
30
Figure 14 – Venting
D. EXHAUST AND INTAKE AIR VENT SIZING
1. The exhaust and intake vent size is 2" for the PH100 and PH130 and 3" for the PH160 and PH199.
2. The total combined equivalent length of exhaust vent and intake air pipe should not exceed 85 feet.
Page 31
FRICTION LOSS EQUIVALENT IN PIPING AND FITTINGS
EQUIVALENT FEET
2”
3”
4”
90 DEGREE ELBOW*
5’
5’
3’
45 DEGREE ELBOW
3’
3’
1’
COUPLING
0’
0’
0’
AIR INLET TEE
0’
0’
0’
STRAIGHT PIPE
1’
1’
1’
CONCENTRIC VENT
KIT
V500 2’ VENT KIT
1’
N/A
N/A
V1000 3’ VENT KIT
N/A
1’
1’
V2000 4’ VENT KIT
N/A
1’
1’
VENT CONNECTION
REDUCING COUPLING
VENT TRANSITION
2”
3” X 2”
3”
3”
4” X 3”
4”
a. The equivalent length of elbows, tees, and other fittings are listed in the Friction Loss Table below:
FITTINGS OR PIPING
3’ 3’ N/A
Table 5 - *Friction loss for long radius elbow is 1 foot less.
b. For example: If the exhaust vent has two 90° elbows and 10 feet of PVC pipe we will calculate: Exhaust Vent Pipe Equivalent Length = (2x5) + 10 = 20 feet. Further, if the intake air vent pipe has two 90° elbows, one 45° elbow and 10 feet of PVC pipe, the following calculation applies: Intake Air Vent Pipe Equivalent Length = (2x5) + 3 + 10 = 23 feet. Finally, if a concentric vent kit is used we find: Total Combined Equivalent Length = 20 + 23 + 3 = 46 feet. Therefore, the total combined equivalent length is 46 feet which is well belo w the maximum of 85 feet. c. The intake air vent pipe and the exhaust vent are intended to penetrate the same wall or roof of the building. d. Effort should be made to keep a minimum difference in equivalent length between the intake air vent pipe and the exhaust vent.
3. The minimum combined equivalent length is 16 equivalent feet.
31
E. LONGER VENT RUNS
1. The maximum combined equivalent length can be extended by increasing the diameter of both exhaust vent and intake air vent pipe equally. However, the transitions should begin a minimum of 15 equivalent feet from the water heater.
a. The maximum equivalent length for increased diameter vent pipes is 125 feet. b. Transitions should always be made in vertical sections of pipe to prevent the condensate from pooling in the vent pipe.
Table 6 – Vent Run Transition
c. If the transition occurs at a distance greater than 15 equivalent feet from the water heater, the maximum equivalent length will be reduced.
Page 32
32
15
95
125
20
77-1/2
117-1/2
25
60-1/2
110-1/2
30
43
103
35
26
96
40
8-1/2
88-1/2
NONE
0
85
into living space.
DESCRIPTION
STOCK CODE
2” PVC CONCENTRIC VENT TERMINATION KIT
KGAVT0501CVT
3” PVC CONCENTRIC VENT TERMINATION KIT
KGAVT0601CVT
2” STAINLESS STEEL VENT TERMINATION KIT
V500
3” STAINLESS ST EEL VE N T TERMINATION KIT
V1000
4” STAINLESS STEEL VENT TERMINATION KIT
V2000
TRANSITION POINT (FT.
FROM WATER HEATER)
Table 7 – TEL = Total Equivalent Length *Oversized vent pipe diameter is 1” or greater than factory supplied connection.
TEL OF OVERSIZED VENT
PIPE (FT.)*
MAXIMUM TEL OF ALL VENT
PIPE (FT.)
F. EXHAUST VENT AND INTAKE AIR PIPE INSTALLAT ION
All joints of positive pressure vent systems must be sealed completely to prevent leakage of flue products
1. Use only solid PVC or CPVC pipe. FOAM CORE PIPING IS NOT APPROVED.
2. Remove all burrs and debris from joints and fittings.
3. All joints must be properly cleaned, primed, and cemented. Use only cement and primer approved for use with the pipe material. Cement must conform to ASTM D2564 for PVC and ASTM F493 for CPVC pipe.
4. Horizontal lengths of exhaust vent must slope back towards the water heater not less than ¼" per foot to allow condensate to drain from the vent pipe.
5. All piping must be fully supported. Use pipe hangers at a minimum of 4 foot intervals to prevent sagging of the pipe where condensate may form.
6. Do not use the heater to support any piping.
7. A screened straight coupling is provided with the heater for use as an outside exhaust termination.
8. A screened inlet air tee is provided with the heater to be used as an outside intake termination.
9. The following information on Table 5-8 lists optional intake air/exhaust vent terminations available from HTP.
Table 8
Page 33
33
G. VENTING DRAWINGS
1. DIRECT VENT INSTALLATION OF EXHAUST AND INTAKE
If installing a direct vent option, combustion air must be drawn from the outdoors directly into the appliance intake, and exhaust must terminate outside. There are three basic direct vent options detailed in this manual: 1. Side Wall Venting, 2. Roof Venting, and 3. Unbalanced Venting.
Be sure to locate the heater such that the air intake and exhaust vent piping can be routed through the building and properly terminated. Different vent terminals can be used to simplify and eliminate multiple penetrations in the building structure (see Optional Equipment in Venting Section). The air intake and exhaust vent piping lengths, routi ng and termination methods must all comply with the methods and limits given in the Venting section, Part 8 of this manual.
When installing a combustion air intake from outdoors, care must be taken to utilize uncontaminated combustion air. NOTE: To prevent combustion air contamination, see Table 1.
Figure 15 – LP-179-C - NOTE: This drawing is meant to demonstrate system venting only. The installer is responsible for all equipment and detailing required by local codes.
Page 34
34
Figure 16 – LP-179-D
NOTE: This drawing is meant to demonstrate system venting only. The installer is responsible for all
equipment and detailing required by local codes.
Page 35
35
Figure 17 – LP-179-E
NOTE: This drawing is meant to demonstrate system venting only. The installer is responsible for all
equipment and detailing required by local codes.
Page 36
36
Figure 18 – LP-179-F
NOTE: This drawing is meant to demonstrate system venting only. The installer is responsible for all
equipment and detailing required by local codes.
Page 37
37
Figure 19 – LP-179-G
NOTE: This drawing is meant to demonstrate system venting only. The installer is responsible for all
equipment and detailing required by local codes.
Page 38
38
Figure 20 – LP-179-AA
NOTE: This drawing is meant to demonstrate system venting only. The installer is responsible for all
equipment and detailing required by local codes.
2. INDOOR COMBUSTION AIR INSTALLATION IN CONFINED OR UNCONFINED SPACE
This heater requires fresh, uncontaminated air for safe operation and must be installed in a mechanical room where there is adequate combustion and ventilating air. NOTE: To prevent combustion air contamination, see Table 1 on page 12.
Page 39
Figure 21 – LP-325-X
Combustion air from the indoor space can be used if the space has adequate area or when air is provided through a duct or louver to supply sufficient combustion air based on the appliance input. Never
obstruct the supply of combustion air to the appliance. If the appliance is insta ll ed in areas
where indoor air is contaminated (see Figure 21) it is imperative that the appliance be installed as direct vent so that all combustion air is taken directly from the outdoors into the appliance intake connection.
Unconfined space is space with volume greater than 50 cubic feet per 1,000 Btu/hour (4.8 cubic meters per kW) of the total input rating of all fuel­burning appliances installed in that space. Rooms connected directly to this space, through openings not furnished with doors, are considered part of the space.
Confined space is space with volume less than 50 cubic feet per 1,000 Btu/hour (4.8 cubic meters per kW) of the total input rating of all fuel-burning appliances installed in that space. Rooms connected directly to this space, through openings not furnished with doors, are considered part of the space.
When drawing combustion air from inside a
conventionally constructed building to a confined space, such space should be provided with two permanent openings: one located 6” (15 cm) below the space ceiling, the other 6” (15cm) above the space floor. Each opening should have a free area of one square inch per 1,000 Btu/hr (22cm 100 square inches (645cm
2
).
2
/kW) of the total input of all appliances in the space, but not less than
If the confined space is within a building of tight construction, air for combustion must be obtained from the outdoors as outlined in the Venting section of this manual. See Figure 22
39
Page 40
40
Figure 22
Page 41
41
The condensate line must remain unobstructed. If allowed to freeze in the line or obstructed in any other
required by local codes.
H. CONDENSATE REMOVAL SYSTEM
This condensing high efficiency appliance has a condensate removal system. Condensate is water vapor derived from combustion products, similar to an automobile when it is initially started. It is very important that the condensate line is sloped down away from the heater and to a suitable drain.
If the heater condensate outlet is lower than the drain, you must use a condensate removal pump (kit p/n 554200 available from HTP). If required by local authorities , a condensate filter of lime crystals, marble, or phosphate chips will neutralize slightly acidic condensate. This can be installed in the field and purchased from HTP (p/n 7450P-212).
manner, condensate can exit from the water heater tee, resulting in potential water damage to property. When installing a condensate pump, select one approved for use with condensing heaters and furnaces.
The condensate pump should have an overflow switch to prevent property damage from spillage. Condensate from the heater will be slightly acidic (pH from 3.2 to 4.5). Install a neutralizing filter if
Figure 23
Page 42
42
Plastic pipe must be the only material used for the condensate line. Steel, brass, copper or other materials will be subject to corrosion or deterioration. A second vent may be necessary to prevent a condensate line vacuum lock if a long horizontal run is used. An increase in condensate line diameter may be necessary to allow condensate to drain properly. Support of the condensate line may be necessary to avoid blockage of the condensate flow.
PART 9 – START-UP PROCEDURE
FOR YOUR OWN SAFETY READ BEFORE OPERATING
1. This appliance does not have a pilot light. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.
2. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas suppliers' instructions.
If you cannot reach your gas supplier, call the fire department.
3. Turn on gas shutoff valve (located inside of the down near burner) so that the handle is aligned with the gas pipe. If the handle will not turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
4. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
5. The heater shall be installed so the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, condensate trap, control replacement, etc.)
A. OPERATING INSTRUCTIONS
If you smell gas, STOP. Follow listed safety instructions above. If you do not smell gas, follow the next steps.
1. Turn on all electric power to appliance. Make sure tank is full with cold water and purge all piping. To assure adequate purging, open all hot water faucets.
2. Adjust the temperature set point of the heater to the desired level. The factory default setting is 119 If changes are necessary, follow “Overall Appliance and Control Operation” in this section.
3. If the appliance fails to start, refer to the Troubleshooting section in the back of this manual.
B. OVERALL APPLIANCE AND CONTROL OPERATI ON
To adjust the temperature of stored water, press and hold {S3} for 2 seconds. The first item is: DU: Water Temperature Set Point – factory set at 119°F. Adjus t down by pressing {S1} to a temperature as low as 95°F. Adjust up as high as 160°F by pressing the {S2}. Press {S3} again to display DH, the differential which is factory set at 7°F and adjustable down to 1°F by pressing {S1} and up to 18°F by pressing {S2}.
o
F.
Page 43
43
Note: Due to the highly advanced control on this appliance, which compensates for varying inlet water temperature, the actual differential temperature may vary slightly from your setting. Press {S3} again to display the factory default temperature measurement in Fahrenheit. Change the default to Celsius by pressing {S1}. When finished, press {S3} one final time to place unit back into operation. The control automatically re-starts if no key is pressed for 2 minutes.
C. STATUS MENU
Installers are also able to check the current status of the heater parameters by pressing {S4} for 3 seconds. Once activated, the display will show |d1| alternating value of the actual upper supply tank temperature. Actual values are displayed for each function. To view the next value, simply press {S/4} to go to the next displayed value. Listed below are the values which can be displayed. These values cannot be changed. To exit this menu, press {S3} to resume normal operation.
Function Value |d1| — Actual temperature from upper tank sensor |d2| — Actual temperature from lower sensor |d3||0| (Not used) |d4||308| (Not used) |d5| — Outdoor sensor |d6| — Actual fan speed multiplied by 10 (Example: If fan speed displayed is |410| RPM x 10 = 4100
actual fan speed)
|d7| — Actual ionization current read from flame rectification probe |d8||0| (Not used) |d9| |1| (Not used) |d10| — Actual status of bus communication |co| = connected, |nc| = not connected |d11||32| (Not used) |d12| — Power on hours in thousands (display will not read until 100 hrs.) |d13| — Total water heatin g hours in thousands (display will not read until 100 hrs.) |d14||0| (Not used) |d15| — Passed ignition attempts in thousands
D. OUTDOOR RESET
This unit is supplied with outdoor reset wire connection terminals. When an outdoor sensor (p/n 7250P-
319) is connected, operation of the unit immediately changes. Refer to the following steps to properly set up the unit with an outdoor sensor.
Page 44
An ASSE 1017 thermostatic mixing valve MUST be installed when using outdoor r eset. Failure to do so could result in substantial property damage, serious injury, or death.
Function 11
Function 8
Function 10
1. Connect the outdoor sensor to the terminals marked “outdoor”.
2. Press and hold {S3}. You will see a flashing du and a temperature value. Set du to the maximum desired tank temperature (default 119oF). After you set the temperature; press {S3} until you exit the menu.
3. Setting the outdoor reset curve (change only the functions in the descriptions below):
a. Press and hold {S3} and {S4} together for 5 seconds b. Use {S1} and {S2} to adjust flashing |000| to code |975|. Press {S3} until you enter the menu. c. Use {S3} to scroll to Function 8 to adjust minimum outdoor temperature. Use {S1} and {S2} to adjust temperature to desired setting (Range: -49 d. Use {S3} to scroll to Function 9 to adjust maximum supply temperature. Use {S1} and {S2} to adjust temperature to desired setting (Ran ge: 77
o
F – 32oF / Default 5oF).
o
F – 160oF / Default 119oF). It is recommended that the du setting matches Function 9. e. Use {S3} to scroll to Function 10 to adjust maximum outdoor temperature. Use {S1} and {S2} to adjust temperature to desired setting (Ran ge: 32
o
F – 95oF / Default 68oF). f. Use {S3} to scroll to Function 11 to adjust minimum supply temperature. From the appliance, use {S1} and {S2} to adjust temperature to desired setting. It is recommended that this temperature is set to the minimum desired DHW temperature (Range: 32
o
F).
120
o
F – 160oF / Default
g. Use {S3} to scroll to Function 12 to adjust desired DHW temperature (minimum tank temperature). Use {S1} and {S2} to adjust temperature to desired setting. It is recommended that this is the same temperature set in Function 11 (Range: 32
o
F – 160oF / Default 120oF).
h. Press and hold {S4} to exit the menu.
44
Outdoor Reset Curve
145
140
135
130
125
120
Tank Temperature
115
0 20 40 60 80 100
Outdoor Temperature
Figure 24 - NOTE: The maximum tank temperature is 160oF, independent of all settings described above.
du setting
Function 12
Page 45
45
COMBUSTION SETTINGS
HIGH FIRING RATES and LOW FIRING RATES ON ALL MODELS
NATURAL GAS
PROPANE LP
Low
High
Low
high
Carbon Monoxide
(CO%)
Carbon Dioxide
(CO2%)
FAN SPEEDS
BTU
IGNITION
MIN
MAX
100,000
3000
2000
5400
130,000
3000
2000
6950
160,000
3000
2000
6850
199,000
3000
2000
8500
Failure
to do so VOIDS WARRANTY!
E. TEST MODE
This function is intended to simplify the gas valve adjustment if needed. Listed below are the recom­mended limits on each heater and the combustion settings. Automatic modulation does not take place when the controller is in Test mode, only temperature limitation based on the heater set point. The user will be allowed to increase or decrease the fan speed by pressing in either the {S1} or {S2} keys.
To activate the Test Mode simply press the {S2} and {S3} key together for 1 second. Once activated, you will see in the display {Ser} and the actual fan speed. The measurement of the combustion levels should always be taken at the highest and lowest fan speed. When in Test Mode, the heater’s limit will shut down the burner if temperature limit is exceeded. It is recommended to draw water out of the tank to lower temperature so tests can be performed.
After 10 minutes, Test Mode stops automatically. To exit Test Mode manually, press {S1} and {S2} key together for 1 second.
0 – 10 ppm 0 – 20 ppm 0 – 10 ppm 0 – 20 ppm
9 – 10.5% 9 – 10.5% 9.5 – 11% 9.5 – 11%
Table 9
Table 10
F. MAINTENANCE
The control system requires no periodic maintenance under normal conditions. However, in unusually dirty or dusty conditions, periodic vacuuming of the cover to maintain visibility of the display and indicators is recommended. In dirty environments, such as construction sites, care must be taken to keep the appliance burner cover in place and drywall or saw dust away from appliance.
In unusually dirty or dusty conditions, care must be taken to keep appliance burner door in place.
Page 46
G. INTERNAL WIRING
46
Figure 25
Page 47
47
PART 10 – SHUTDOWN
A. SHUTDOWN PROCEDURE
If the burner is not operating, disconnect the electrical supply. If the burner is operating, lower the set point value to 70
wait for the combustion blower to stop, so all latent combustion gases are purged from the system. This should take a maximum of 40 to 90 seconds.
B. VACATION PROCEDURE
If there is danger of freezing, change the set point to 70 danger of freezing, follow “Shutdown Procedure”.
C. FAILURE TO OPERATE
Should the burner fail to light, the control will perform two more ignition trials prior to entering a lockout state. Note that each subsequent ignition trial will not occur immediately. After a failed ignition trial, the blower must run for approximately 10 seconds to purge the system. Therefore, a time period of approximately 40 to 90 seconds will expire between each ignition trial.
If the burner lights during any one of these three ignition trails, normal operation will resume. If the burner lights, but goes off in about 4 seconds, check the polarity of the wiring. See electrical connection section.
If the burner does not light after the third ignition trial, the control will enter a lockout state. This lockout state indicates that a problem exists with the appliance, the controls, or the gas supply. Under such circumstances, a qualified service technician should be contacted immediately to properly service the appliance and correct the problem. If a technician is not available, depressing the {S4} button once will remove the lockout state so additional trials for ignition can be performed. The unit will try to re-light once every 6 minutes.
o
F and wait for the burner to shut off. Continue to
o
F. DO NOT turn off electrical power. If there is no
PART 11 – TROUBLESHOOTING
A. ERROR CODE
An error code may occur during installation of the heater. This condition may lead to a lock out condition of the controller, which will need to be manually reset b y pressing the {S4} button. These following will help the installer correct the problem before going into a lock out condition, which will require a manual reset.
B. HEATER ERROR
1. When an error condition occurs the controller will display an error code on the display module.
2. These error codes and several suggested corrective actions are included in Table 13.
3. In the case of |E00|, |E13|, and |E14| this error, if uncorrected, will go into a fault condition as described in Paragraph C.
Page 48
All electrical power is disconnected.
The electrical power is off.
Do not use this appliance if any part has been under water. Improper or dangerous operation may result. that has been under water.
servicing.
C. LOCKOUT
1. When a fault condition occurs the controller will illuminate the red “fault” indication light and display a fault code in the format (Example: |F00|) on the display module.
2. Note the fault code and refer to Table 12 for an explanation of the fault code along with several suggestions for corrective actions.
3. Press the reset key to clear the fault and resume operation. Be sure to observe the operation of the unit to prevent a recurrence of the fault.
When servicing or replacing any components of this water heater be certain that:
The gas is off.
When servicing or replacing components that are in direct contact with heater water, be certain that:
There is no pressure in the heater. Pull the release on the relief valve to relieve pressure in the heater.
Heater water is not hot.
48
Contact a qualified service technician immediately to inspect the heater and repair or replace any part
The appliance has wire function labels on all internal wiring. Observe the position of each wire before removing it. Wiring errors may cause improper and dangerous operation. Verify proper operation after
Page 49
49
Combustion
of expected.
Combustion
expected.
1. Be sure all air is bled from system. damage and repair if necessary.
Blocked Vent
present
1. Check line voltage. Must be between
board.
RESISTANCE TABLE FOR
SENSOR
HIGH/LOW
TEMP. (oF)
Table 11
Table 12
CODE DESCRIPTION DURATION CORRECTIVE ACTION
926 CONTROL BOARD ERROR CODES
SUPPLY TEMPERATURE
TEMP. SENSOR
32 32550 41 25340 50 19870 59 15700 68 12490 77 10000 86 8059
95 6535 104 5330 113 4372 122 3605 131 2989 140 2490 149 2084 158 1753 167 1481 176 1256 185 1070 194 915 202 786 212 667
RESISTANCE
(ohms)
Fan Speed Low. The
E131
E14
LEO
FLU
LOU 24 Volt L ow
heater combustion air fan speed less than 70%
Fan Speed High. The heater combustion air fan speed is more than 130% of
Water Level in Tank is Low
Pressure Switch o pen, Condensate cup Full, Condensate Cup not
60 Sec.
60 Sec.
Until
Corrected
Until
Corrected
Until
Corrected
1. Check the combustion air fan wiring.
2. Replace the combustion air fan.
3. Replace the control board.
1. Check the combustion air fan wiring.
2. Replace the combustion air fan.
3. Replace the control board.
2. Inspect low level switch and wiring for
1. Check the flue vent to be sure it is not blocked or damaged.
2. Check the blocked vent pressure switch operation by applying a jumper. (If the switch is not functioning properly, replace it.
100 – 128 volts.
2. If available, connect a PC and, using HTP service software, check the 24v supply display in the lower left corner of the screen. The number displayed here must be greater than 128 and should be greater than 250. Use this as a troubleshooting guide as you follow the steps below.
3. Remove 10 pin Molex connector from customer connection board. If LOU clears, then the problem is with external sensor wiring. Examine external sensor wiring for shorts to ground, repairing as necessary. If LOU code is still present and the boiler is so equipped, disconnect high gas pressure switch, then low gas pressure switch, then UL 353 low water cutoff in this order, one at a time, to see if LOU code clears. Replace faulty part. Check low voltage wire harness in heater for shorts to ground.
4. If LOU only occurs when burner tries to light, check gas valve for excessive current draw.
5. If LOU is present with the low voltage harness disconnected from the 926 control board, replace the 926 control
Page 50
926 Control Board FAULT
Code
Description
Remedy
1. Try reset. If F00 repeats, create a demand for hot water. (DANGER: Use caution to
1. Inspect all flue piping. If the flue is damaged or shows signs of overheating, repair or
7. If the flue temperature increases to over 190oF, consult HTP for further assistance.
Interrupted or shorted upper
temperature sensor.
1. Check the electrical connection to the appropriate temperature sensor. Interrupted or shorted lower
temperature sensor.
exceeds 194oF.
1. Watch the igniter through the observation window provided.
6. Check any flue blockage or condensate blocks.
1. Monitor the gas pressure to the unit while in operation.
6. If the flame rectifier probe continues to read low, replace it.
1. Turn the gas off to the unit at the service valve.
5. Turn the gas on at the service valve after corrective action is taken.
Combustion fan speed
60 seconds.
1. Check the combustion air fan wiring.
F00
F01
High temperature switch limit
exceeded 194
o
F.
Vent temperature limit
exceeded.
50
prevent burn injury. ) If water is above 194oF, test upper and lower temperature sensor with an ohmmeter. (Refer to resistance chart, this section.) Replace bad sensor. If water is below 194 closed at this point. If not, replace switch.
2. If unit did reset successfully, let the heater run and go into the status menu to check the upper and lower temperature sensor. If either reading displayed does not make sense, check appropriate sensor with ohmmeter. (Refer to resistance chart, this section.) Replace bad sensor. Do an OHMs reading on both sensors to check continuity.
replace the flue parts as necessary before proceeding.
2. If the flue piping system is intact, not damaged and there is no sign of the flue overheating (such as discoloration or melting), push the red reset button on the flue switch
3. Be sure the heater is connected to a water supply and full of water.
4. Push the RESET button on the heater control panel. The appliance should light. If the appliance lights, proceed to step 5. If the appliance does not light and the display again begins to flash F01, inspect the wiring to the flue switch, repairing or replacing as necessary. If the wiring is intact, replace the flue switch, using care to mount the new flue switch in the same position and mounting holes as the old one. If the display flashes a code other than F01, follow the troubleshooting guide for that code.
5. Observe operation for 5 minutes. Place the probe of an exhaust analyzer into the flue syst em within 6 feet of the heater. The exhaust temperature should not rise above 190 after several minutes of operation.
6. If the flue temperature is below 190 F01, replace the flue switch, using care to mount the new flue switch in the same position and mounting holes as the old one. If the display flashes a code other than F01, follow the troubleshooting guide for that code.
o
F, test high temperature switch and wiring with ohmmeter. Switch should be
o
F and the heater again goes into lockout displaying
o
F
F02
2. If connection is okay, replace bad sensor.
F03 F05 F06
Upper temperature sensor Lower temperature sensor
exceeds 194
o
F.
No flame detected – Heater
will make three attempts at
F09
ignition before the control
goes into this lockout
condition. Will reset in 1 hour.
Loss of flame signal – The
heater will relight 4 times
F10
before the control goes into
this lockout condition. Will
reset in 1 hour.
False flame signal – The
heater will lock out if it senses
F11F
a flame signal when there
should be none present.
incorrect – The heater will
F13
lock out if it senses that the
fan speed is less than 70% of
1. If water in tank is not greater than 194oF, check wiring. Repair if faulty.
2. If wiring is okay, check appropriate sensor with ohmmeter and compare to reading in resistance chart above. If reading does not agree with water temperature, replace bad sensor.
2. If there is no spark, check the spark electrode for the proper ¼” gap.
3. Remove any corrosion from the spark electrode and flame rectifier probe.
4. If there is a spark but no flame, check the gas supply to the heater.
5. If there is a flame, check the flame sensor.
2. Assure that the flame is stable when lit.
3. Check to see if the green light on the display module is out while the heater is running.
4. If the green light doesn’t come on or goes off during operation check the flame signal on the status menu.
5. If the signal reads less than 1 microampere, clean the flame rectifier probe.
2. If the flame signal is still present replace the igniter.
3. If the flame signal is not present after turning off the gas supply, check the gas valve electrical connection.
4. If there is no power to the gas valve, remove the valve and check for obstruction in the valve seat or replace the gas valve.
2. Replace the combustion air fan.
3. Replace the control board.
expected rate for more than
Table 13 NOTE: If you replace a part to remedy a fault, it is recommended that you cycle the unit at least three or four times to assure the fault has been resolved.
Page 51
51
Figure 26
Page 52
52
Figure 27 – LP-179-J
Page 53
53
Figure 28 – LP-179-H
Page 54
54
INSPECTION ACTIVITIES
DATE LAST COMPLETED
PIPING
1st YEAR
2nd YEAR
3rd YEAR
4th YEAR*
Near heater piping
Check heater and system piping for any sign of leakage; make sure they are properly supported.
Vent
Check condition of all vent pipes and joints.
Gas
Check Gas piping, test for leaks and signs of aging.
SYSTEM
Visual
Do a full visual inspection of all system components.
Temperatures
Verify safe settings on heater or Anti-Scald Valve
Temperatures
Verify programmed temperature settings
ELECTRICAL
Connections
Check wire connections. Make sure they are tight.
Smoke and CO detector
Verify devices are installed and working properly. Change batteries if necessary.
Circuit Breakers
Check to see that the circuit breaker is clearly labeled. Exercise circuit breaker.
CHAMBER/BURNER
Combustion Chamber
Check burner tube and combustion chamber coils. Vacuum combustion chamber.
Spark Electrode
Clean. Set gap at ¼”.
CONDENSATE
Neutralizer
Check condensate neutralizer. Replace if necessary.
Condensate hose
Disconnect condensate hose. Clean out dirt. Fill with
properly connected during final inspection.)
GAS
Pressure
Measure incoming gas pressure (3.5” to 14” W.C.)
Check gas pipe for
Check piping for leaks. Verify that all are properly
COMBUSTION
CO/CO2 Levels
Check CO and CO2 levels in Exhaust (See Start-up Procedures for ranges). Record at high and low fire.
SAFETIES
Upper/Lower Sensors
Check wiring. Verify through ohms reading.
FINAL INSPECTION
Check list
Verify that you have completed entire check list. SERIOUS INJURY OR DEATH.
Homeowner
Review what you have done with the homeowner.
PART 12: MAINTENANCE
Periodic maintenance should be performed once a year by a qualified service technician to assure that all the equipment is operating safely and efficiently. The owner should make necessary arrangements with a qualified heating contractor for periodic maintenance of the heater. Installer must also inform the owner that the lack of proper care and maintenance of the heater may result in a hazardous condition.
Make sure all pipes are properly supported.
Functional Test all functions of the system (Heat, Safeties)
Clean according to maintenance section of manual.
Flame Probe Clean. Check ionization in uA (d7 on status menu in
Pressure Drop Measure drop in pressure on light off (no more than 1”
leaks
ECO (Energy Cut Out)
Start-up Procedures). Record high fire and low fire.
water to level of outlet and re-install. (NOTE: Verify the flow of condensate, making sure that the hose is
W.C.) supported.
Check continuity on Flue and Water ECO. Replace if corroded.
WARNING: FAILURE TO DO SO COULD RESULT IN
Table 14 - *Continue annual maintenance beyond the 4th year as required.
Page 55
55
Page 56
56
Page 57
57
MAINTENANCE NOTES
Page 58
HTP CUSTOMER INSTALLATION RECORD FORM
The following form should be completed by the installer for you to keep as a record of the installation in case of a warranty claim. After reading the important notes at the bottom of the page, please also sign this document.
Customer’s Name:
Installation Address:
Date of Installation:
Installer’s Code/Name:
Product Serial Number(s):
58
Comments:
Installer’s Phone Number:1
Signed by Installer:
Signed by Customer:2
IMPORTANT: Customer: Please only sign after the installer has reviewed the installation, safety, proper operation and
maintenance of the system. In the case that the system has any problems, please call the installer. If you are unable to make contact, please contact your HTP Sales Representative.
Distributor/Dealer: Please insert contact details.
LP 179 REV. 8.25.10