This manual must only be used by a qualied installer / service technician. Read all instructions in this manual before installing.
Perform steps in the given order. Failure to do so could result in substantial property damage, severe personal injury, or death.
Improper installation, adjustment, alteration, service, or maintenance could void product warranty and cause property
damage, severe personal injury, or death.
California Proposition 65 Warning: This product contains chemicals known to the State of California to cause cancer, birth
defects, or other reproductive harm.
Heat Exchanger Bears the ASME “H”
Stamp
HTP reserves the right to make product changes or updates without notice and will not be held liable for typographical errors
in literature.
NOTE TO CONSUMER: PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE.
272 Duchaine Blvd.New Bedford, MA 02745www.htproducts.com
lp-666 Rev. 003 Rel. 004 Date 9.3.20
2
WARNING
!
WARNING: If the information in these instructions is not followed exactly, a re or explosion may result causing property
damage, personal injury or death.
• Do not store or use gasoline or other ammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
• Installation and service must be provided by a qualied installer, service agency or the gas supplier.
Improper installation, adjustment, alteration, service, or maintenance can cause injury, property damage, or death.
Refer to this manual. Installation and service must be performed by a qualied installer, service agency, or gas supplier.
lp-666 Rev. 003 Rel. 004 Date 9.3.20
SPECIAL ATTENTION BOXES
The following dened terms are used throughout this manual to
DANGER
!
WARNING
!
CAUTION
!
CAUTION
NOTICE
bring attention to the presence of hazards of various risk levels or
to important product information.
DANGER indicates an imminently hazardous situation which, if
not avoided, will result in serious personal injury or death.
3
Authority Having Jurisdiction (AHJ) – The AHJ may be a federal, state,
local government, or individual such as a re chief, re marshal, chief
of a re prevention bureau, labor department or health department,
building ocial or electrical inspector, or others having statutory
authority. In some circumstances, the property owner or his/her agent
assumes the role, and at government installations, the commanding
ocer or departmental ocial may be the AHJ.
NOTE: HTP reserves the right to modify product technical specications
and components without prior notice.
WARNING indicates a potentially hazardous situation which, if not
avoided, could result in personal injury or death.
CAUTION indicates a potentially hazardous situation which, if not
avoided, may result in moderate or minor personal injury.
CAUTION used without the safety alert symbol indicates a
potentially hazardous situation which, if not avoided, may result
in property damage.
NOTICE is used to address practices not related to personal injury.
Foreword
This manual is intended to be used in conjunction with other
literature provided with the boiler. This includes all related control
information. It is important that this manual, all other documents
included in this system, and additional publications including the
National Fuel Gas Code - ANSI Z223.1 (latest versions), be reviewed in
their entirety before beginning any work.
Installation should be made in accordance with the regulations of
the Authority Having Jurisdiction, local code authorities, and utility
companies which pertain to this type of water heating equipment.
For the Installer
This boiler must be installed by qualied and licensed personnel.
The installer should be guided by the instructions furnished with the
boiler, and by local codes and utility company requirements. In the
absence of local codes, preference should be given to the National Fuel Gas Code - ANSI Z223.1, latest version.
Installations Must Comply With:
Local, state, provincial, and national codes, laws, regulations, and
ordinances.
The latest version of the National Fuel Gas Code, ANSI Z223.1, from
American Gas Association Laboratories, 8501 East Pleasant Valley
Road, Cleveland, OH 44131.
In Canada - CGA No. B149 (latest version), from Canadian Gas
Association Laboratories, 55 Scarsdale Road, Don Mills, Ontario,
Canada M3B 2R3. Also, Canadian Electrical Code, C 22.1, from Canadian
Standards Association, 5060 Spectrum Way, Suite 100, Mississauga,
Ontario, Canada L4W 5N6.
The latest version of the National Electrical Code, NFPA No. 70.
NOTE: The gas manifold and controls met safe lighting and other
performance criteria when undergoing tests specied in ANSI Z21.13
- latest edition.
lp-666 Rev. 003 Rel. 004 Date 9.3.20
4
NOTICE
WARNING
!
The CSD-1 ASME Code, Section CW-400 requires that hot water
heating and supply boilers have a) a UL 353 temperature control
device, b) at least one (1) temperature-actuated control to shut
o the fuel supply when system water reaches a preset operating
temperature, c) a high temperature limit control that prevents
the water temperature from exceeding the maximum allowable
temperature by causing a safety shutdown and lockout, and d) its
own sensing element and operating switch.
The temperature control system integrated into the 928 control
provided with this heating appliance complies with the requirements
of CSD-1 Section CW-400 as a temperature operation control. The
control monitors the temperature dierence between the inlet
and the outlet sensor, which is aected by boiler water ow. If this
temperature dierence exceeds 55°F (typically because of low water
ow or very low heat load), the control will reduce the maximum fan
speed. If the temperature dierence exceeds 60°F, the control will
eectively sense there is little or no water ow or heat load and shut
the boiler down. The controller will restart automatically once the
temperature dierence has dropped below 55°F and the minimum
o time (anti-cycle time) has expired. In addition, if the control senses
that the outlet water temperature has reached 210°F, the boiler is put
into a hard lockout and requires manual reset to restart.
IMPORTANT
In accordance with Section 325 (f) (3) of the Energy Policy and
Conservation Act, HTP has provided this boiler with multiple
features designed to save energy by reducing the boiler water
temperature as heating load decreases.
These features include:
• A modulating combustion system that adjusts ring rate
based on heat demand.
• Adjustment of boiler set point based on inferred heat load
as determined by an outdoor sensor. The outdoor sensor
is supplied by HTP with this boiler.
• This boiler does not include a standing pilot.
• This boiler is designed and shipped to assure the highest
eciency operation possible. Such high eciency is
achieved by limiting heating circuit water temperature to
140°F when there is no anticipated heat load, based upon
the outdoor sensor and the Outdoor Reset Curve (sensor
response curve) in the boiler software.
• This feature may be over-ridden as described below in
specic installations:
• The boiler control is equipped with an outdoor sensor
override for use with building management systems or in
cascaded systems (for systems with total input of 300,000
BTU/hr or greater).
See statement below for an important notice on the use of the
override.
IMPORTANT
In accordance with Section 325 (f) (3) of the Energy Policy and
Conservation Act, this boiler is equipped with a feature that
saves energy by reducing the boiler water temperature as the
heating load decreases. This feature is equipped with an override
which is provided primarily to permit the use of an external
energy management system that serves the same function. THIS
OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE
FOLLOWING CONDITIONS IS TRUE:
• An external energy management system is installed that
reduces the boiler water temperature as the heating load
decreases.
• This boiler is not used for space heating.
• This boiler is part of a modular or multiple boiler system
having a total input of 300,000 BTU/hr or greater.
• This boiler is equipped with a tankless coil.
lp-666 Rev. 003 Rel. 004 Date 9.3.20
The hydronic supply and return connections of these products
are for installation in closed loop systems ONLY! Use of this
product in any manner other than described in this manual may
result in premature product failure, substantial property damage,
severe personal injury, or death. Damage or failure of this product
(or the system in which it is installed) due to unauthorized use IS
NOT COVERED BY WARRANTY.
Table of Contents
Part 1 - General Safety Information 5
A. Improper Combustion 6
B. Gas 6
C. When Servicing the Boiler 6
D. Boiler Water 6
E. Freeze Protection 6
F. High Elevation Installations 6
Part 2 - Before You Start 6
A. What’s in the Box 6
B. How the Boiler Operates 6
C. Optional Equipment 7
Part 3 - Prepare the Boiler 9
A. Locating the Boiler 9
B. Flooring 10
C. Leveling 10
D. Clearances for Service Access 10
E. Residential Garage and Closet Installations 11
F. Exhaust Vent and Intake Pipe 11
1. Direct Vent of Exhaust and Intake 11
2. Power Venting, Indoor Combustion Air in Conned or Unconned
Space 12
G. Carbon Monoxide Detectors 12
H. Prevent Combustion Air Contamination 12
I. Removing a Boiler from a Common Vent System 13
J. Water Chemistry Requirements* 13
K. Outdoor Installations 14
L. Technical Specications 16
Part 4 - Piping 17
A. General Plumbing Information 17
B. Relief Valve 17
C. Backow Preventer 17
D. Expansion Tank 17
E. Circulators 18
F. Hydronic Piping with Circulators, Zone Valves, and Multiple
Boilers 18
G. Circulator Sizing 19
H. Check / Control Water Chemistry 20
I. Plumbing 20
J. Fill and Purge Heating System 20
K. Freeze Protection Fluids 20
L. Zoning with Zone Valves 21
M. Zoning with Circulators 21
N. Multiple Boilers 21
O. Applications* 22
Part 5 - Venting 23
A. General 23
B. Approved Materials for Exhaust Vent and Intake Pipe 24
C. Additional Requirements for Installation in Canada 24
D. Exhaust Vent and Intake Pipe Location 25
E. Exhaust Vent and Intake Pipe Sizing 26
F. Exhaust Vent and Intake Pipe Installation 26
G. Applications 27
1. Direct Vent Installation of Exhaust and Intake 27
2. Power Venting, Room and Indoor Combustion Ventilation
Requirements 29
Part 6 - Condensate Removal 30
Part 7 - Wiring - 400 - 1500 Models 31
A. Installation Must Comply With 31
WARNING
!
B. Field Wiring 31
C. Line Voltage Wiring for Standard Boiler 32
D. Alarm Connections 32
E. Low Voltage Connections for Standard Boiler 32
F. Thermostat 32
G. Outdoor Sensor 32
H. Indirect Sensor 32
I. UL 353 Internal Low Water Cut-O (Factory Installed) 32
J. Wiring of Cascade System Communication Bus 32
K. Cascade Master System Pump and Sensor Wiring 33
L. Cascade Follower Pump and Sensor Wiring 33
M. Variable Speed Pumping 33
N. Optional 0-10 Volt Building Control Signal 34
O. Optional High Gas Pressure Switch 34
P. Optional Low Gas Pressure Switch 34
Q. Optional High Limit Manual Reset 34
Part 8 - Wiring - 2000 Models 38
A. Installation Must Comply With 38
B. Field Wiring 38
C. Line Voltage Wiring for Standard Boiler 38
D. Alarm Connections 38
E. Low Voltage Connections for Standard Boiler 39
F. Thermostat 39
G. Outdoor Sensor 39
H. Indirect Sensor 39
I. UL 353 Internal Low Water Cut-O (Factory Installed) 39
J. Wiring of Cascade System Communication Bus 39
K. Cascade Master Pump and Sensor Wiring 39
L. Cascade Follower Pump and Sensor Wiring 40
M. Variable Speed Pumping 40
N. Optional 0-10 Volt Building Control Signal 40
O. Optional High Gas Pressure Switch 40
P. Optional Low Gas Pressure Switch 41
Q. Optional High Limit Manual Reset 41
Part 9 - Gas Connections 45
A. Gas Piping 45
B. Gas Table 45
C. Check Inlet Gas Pressure 46
D. Boiler Gas Valve 47
Part 10 - Start-Up Preparation 48
A. Check / Control Water Chemistry 48
B. Check for Gas Leaks 48
C. Freeze Protection (When Used) 48
D. Fill and Test Water System 48
E. Check Thermostat Circuit(s) 49
F. Condensate Removal 49
G. Final Checks Before Starting Boiler 49
Part 11 - Start-Up Procedure 49
A. Control Overview 49
B. Navigation of the Touch Screen Display 50
C. Purge Air from the System 51
D. Single Boiler Initial Start-Up and Operation 51
E. Cascaded System Initial Start-Up and Operation 51
F. Lockout Condition - Cascade System 51
G. Cascade System Programming 52
H. Operating Instructions 52
I. Programming User Settings 53
J. Programming Installer Settings 56
K. Resetting the Maintenance Schedule 60
L. Service Mode - Setting and Verifying the Combustion Setting Testing the Internal LWCO 60
Part 12 - Boiler Monitoring 61
A. Status Screens 61
B. History Screens 64
C. Graphics Screen 66
D. Cascade Screen 66
5
Part 13 - Troubleshooting 68
A. Blocking 68
B. Fault (Lockout) 68
C. User Interface Display 68
Part 14 - Maintenance 74
A. Procedures 74
B. Combustion Chamber Coil Cleaning Instructions 74
C. Cleaning the Water Side of the Heat Exchanger 77
Part 15 - Shutdown 77
A. Shutdown Procedure 77
B. Failure to Operate 77
Part 16 - Replacement Parts 78
Part 17 - Installation Checklist 85
Part 18 - Maintenance Report 85
ELX Boiler Limited Warranty 87
Maintenance Notes 89
Customer Installation Record Form 90
Part 1 - General Safety Information
This boiler is approved for indoor or outdoor installations and is not
intended for use as a pool heater. Clearance to combustible materials:
0” top, bottom, sides, and back. Boiler must have room for service:
24” front, 24” right side, and 18” left side are minimum recommended
service clearances. (A combustible door or removable panel is
acceptable front clearance.) 400 - 1000 Models have been approved
for installation on combustible ooring. Do not install on carpeting.
1500 - 2000 MODELS ARE NOT APPROVED FOR INSTALLATION ON
COMBUSTIBLE FLOORING. Install the boiler in a location where
temperature and pressure relief valve discharge or a leak will not result
in damage to the surrounding area. If such a location is not available,
install an auxiliary catch pan. Use only Category IV vent systems.
Installer - Read all instructions in this manual before installing.
Perform steps in the given order.
User - This manual is for use only by a qualied heating installer /
service technician. Have this boiler serviced / inspected annually by
a qualied service technician.
FAILURE TO ADHERE TO THE GUIDELINES ON THIS PAGE
CAN RESULT IN SUBSTANTIAL PROPERTY DAMAGE, SEVERE
PERSONAL INJURY, OR DEATH.
DO NOT USE THIS BOILER IF ANY PART HAS BEEN SUBMERGED
IN WATER. Immediately call a qualied service technician. The
boiler MUST BE replaced if it has been submerged. Attempting to
operate a boiler that has been submerged could create numerous
harmful conditions, such as a potential gas leakage causing a re
and/or explosion, or the release of mold, bacteria, or other harmful
particulates into the air. Operating a previously submerged boiler
could result in property damage, severe personal injury, or death.
NOTE: Boiler damage due to ood or submersion is considered an
Act of God, and IS NOT covered under product warranty.
NOTE: Obey all local codes. Obtain all applicable permits before
installing the boiler.
NOTE: Install all system components and piping in such a manner
that does not reduce the performance of any re rated assembly.
NOTE: If the boiler is exposed to the following, do not operate.
Immediately call a qualied service technician.
1. Fire
2. Damage
3. Water
Failure to follow this information could result in property damage,
severe personal injury, or death.
Altering any HTP boiler with parts not manufactured by HTP WILL
INSTANTLY VOID the boiler warranty and could result in property
damage, personal injury, or death.
lp-666 Rev. 003 Rel. 004 Date 9.3.20
6
WARNING
!
WARNING
!
WARNING
!
NOTICE
CAUTION
WARNING
!
CAUTION
Due to low water content of the boiler, improperly sizing the boiler
in regard to heating load will result in excessive boiler cycling and
accelerated component failure. HTP DOES NOT warrant failures
caused by improperly sized boiler applications. DO NOT oversize the
boiler to the system. Modular boiler installations greatly reduce the
likelihood of boiler oversizing.
High heat sources (sources generating heat 100oF / 37oC or greater,
such as stove pipes, space heaters, etc.) may damage plastic
components of the boiler as well as plastic vent pipe materials. Such
damages ARE NOT covered by warranty. It is recommended to keep
a minimum clearance of 8” from high heat sources. Observe heat
source manufacturer instructions, as well as local, state, provincial,
and national codes, laws, regulations and ordinances when installing
this boiler and related components near high heat sources.
Do not use this boiler for anything other than its intended purpose
(as described in this manual). Doing so could result in property
damage and WILL VOID product warranty.
A. Improper Combustion
Do not obstruct the ow of combustion and ventilating air. Adequate
air is necessary for safe operation. Failure to keep the exhaust vent
and combustion air intake clear of ice, snow, or other debris could
result in property damage, serious personal injury, or death.
B. Gas
Should overheating or gas supply fail to shut o, turn o the manual
gas control valve to the boiler.
C. When Servicing the Boiler
E. Freeze Protection
NOTE: Consider piping and installation when determining boiler
location.
Failure of the boiler due to freeze related damage IS NOT covered
by product warranty.
NEVER use any toxic chemical, including automotive, standard
glycol antifreeze, or ethylene glycol made for hydronic (nonpotable) systems. These chemicals can attack gaskets and seals in
water systems, are poisonous if consumed, and can cause personal
injury or death.
NOTE: Loops Serving Indirect Water Heaters (IWHs)
Glycol used in IWH loops should be food grade propylene glycol,
FDA rated as “generally recognized as safe” (GRAS). If using a glycol /
potable water mix, the water chemistry must meet the requirements
in this manual. The glycol content of the liquid must not exceed 50%,
unless the manufacturer species a dierent ratio. Glycol should be
checked periodically to prevent it from becoming acidic. Please refer
to guidelines provided by the glycol manufacturer regarding glycol
maintenance.
NOTE: Glycol not recognized as GRAS may only be used in closed
loop CH applications.
NOTE: HTP DOES NOT WARRANT THE BOILER AGAINST FREEZERELATED DAMAGE.
The boiler control is equipped with freeze protection that activates
based on internal water temperature.
NOTE: Freeze protection will not be active if the boiler loses power.
F. High Elevation Installations
Be sure to disconnect electrical power before opening boiler cabinet
or performing service. Failure to do so could result in electrical shock,
property damage, serious personal injury, or death.
To avoid electric shock, disconnect electrical supply before performing
maintenance.
NOTE: When inquiring about service or troubleshooting, reference
the model and serial numbers from the boiler rating label.
To avoid severe burns, allow boiler and associated equipment to cool
before servicing.
D. Boiler Water
• If you have an old system with cast iron radiators, thoroughly
ush the system (without boiler connected) to remove
sediment. The high-eciency heat exchanger can be damaged
by build-up or corrosion due to sediment. HTP recommends
suction and/or magnetic strainers in this type of system.
• Do not use petroleum-based cleaning or sealing compounds
in boiler system. Gaskets and seals in the system may be
damaged, possibly resulting in substantial property damage.
• Do not use “homemade cures” or “boiler patent medicines”.
Substantial property damage, damage to boiler, and/or serious
personal injury may result.
• Continual fresh make-up water will reduce boiler life. Mineral
buildup in the heat exchanger reduces heat transfer, overheats
the stainless steel heat exchanger, and causes failure. Addition
of oxygen from make-up water can cause internal corrosion
in system components. Leaks in the boiler or piping must be
repaired at once.
Natural gas at high elevation might contain less heating value than
typical 1,000 BTU/cu ft and therefore can cause improper air / gas
mix leading to improper combustion. For natural gas installations
above 3,000 ft, call your gas provider to determine the heating
value of the supplied natural gas.
Part 2 - Before You Start
UNCRATING THE BOILER - Any claims for damage or shortage in
shipment must be led immediately against the transportation
company by the consignee.
A. What’s in the Box
Remove all sides of the shipping crate of the boiler.
Components included with the boiler:
Condensing technology intelligently delivers highly ecient
hydronic heating while maximizing eciency by measuring data
from the heating system. The following are features of the system
and how they operate.
lp-666 Rev. 003 Rel. 004 Date 9.3.20
7
Stainless Steel / Steel Heat Exchanger
The highly ecient heat exchanger is designed to use the cold
water return from the system and extract the last bit of heat before
it is exhausted.
Modulating Combustion System
The combustion system modulates the output of the burner during
operation to match system demand and achieve the control set
point while in operation. The set point can change by internal or
external signals to enhance the overall performance of the system.
Control
The integrated control system monitors the system and regulates
fan speed to control boiler output. This allows the boiler to deliver
only the amount of heat energy required and nothing more. The
system can be further enhanced by installing an indirect water
heater to provide domestic hot water.
The control can regulate the output of multiple boilers through
its cascade system function. The cascade system is capable of
connecting up to eight boilers together in such a way that they
function as one boiler system. This allows for greater turn down
ratios and provides systematic control of the multiple boilers in an
installation to minimize downtime and maximize eciency.
The cascade system works by establishing one boiler as the master
and the other connected boilers as followers. The master boiler
requires a cascade system sensor and a system pump in addition to
its own boiler pump. Each of the follower boilers will have its own
pump to provide maximum ow and control heat exchanger ow
rate.
Electronic Touchscreen Display with Status Indicators
Digital controls with full color resistive touchscreen technology. The
display allows the user to change system parameters and monitor
system operation.
Gas Valve
The gas valve senses suction from the blower, allowing gas to ow
only if powered and combustion air is owing.
Integrated Venturi
Controls air and gas ow into the burner.
Burner
The high grade stainless steel burner uses premixed air and gas to
provide a wide range of ring rates.
Spark Ignition
The burner is ignited by applying high voltage through the system
spark electrode. The spark from the electrode ignites mixed gas o
of the burner.
Dual Supply Water Temperature Sensor / High Limit Water ECO
This dual sensor monitors the boiler outlet water temperature
(System Supply). The control adjusts boiler ring rate so the supply
temperature will match the boiler set point. The dual sensor in
combination with the 928 control meets all requirements of a UL
353 water limiting control, eliminating the mechanical ECO and
increasing safety and reliability.
Return Water Temperature Sensor
This sensor monitors boiler return water temperature (System
Return).
Temperature and Pressure Gauge
Allows the user to monitor system temperature and pressure.
Electrical eld connections with terminal strips
The electrical cover allows easy access to the clearly marked line
voltage and low voltage terminal strips to facilitate wiring the boiler.
Supplied Condensate Collection System with Clean Out
This boiler is a high eciency appliance and will produce condensate.
The condensate collection system has a oat switch which monitors
condensate level and prevents condensate from backing up into
the combustion system. Inside the collection system is a built in trap
which seals the combustion system from the connected drain. This
condensate should be neutralized to avoid damage to the drainage
system or piping.
Flow Protection
The ow switch is designed to protect the boiler during low ow
conditions. The boiler control also monitors ow through the heat
exchanger by monitoring the return and supply sensors and will shut
down the burner before overheating occurs. The ow switch activates
at 4 GPM for 400 - 1000 Models; 9 GPM for 1500 - 2000 Models.
Outdoor Sensor
The control adjusts unit set point based on the outdoor temperature
measured by this sensor to provide greater eciency.
0-10 Volt Input
Allows the installer to connect a BMS (Building Management System)
to control the boiler.
0-10 Volt Output A (Congured through Control System)
0-10 Volt Output A is congured through the boiler’s control system.
0-10 Volt Output A is related to one of the following boiler values:
boiler power, cascade power, fan speed, alarm status, temperature
setting based on outdoor reset curve, ame, or pump.
0-10 Volt Output B (Congured through Control System)
0-10 Volt Output B is congured through the boiler’s control system,
and is related to one of the following boiler values: boiler power,
cascade power, fan speed, alarm status, temperature setting based on
outdoor reset curve, or ame.
UL 353 Internal Low Water Cuto (LWCO)
The supplied internal Low Water Cuto in conjunction with the 928
control meets UL 353 requirements to function as a safety, locking
out the boiler when water level is inadequate for safe operation. See
Service Mode, this manual, to test LWCO function.
Boost Timer Function
This function temporarily overrides the outdoor reset curve in order
to satisfy a thermostat setpoint in a short amount of time, especially
during a relatively warm day.
Flue Temperature Modulation
As an additional safety feature, if the ue temperature exceeds
200oF, the control will modulate the boiler down based on the
vent temperature, rather than the supply temperature. If the ue
temperature exceeds 210oF the control will lock out the boiler.
HTP Link
HTP Link allows the installer to connect the boiler to WiFi, providing
the user / installer with tools to remotely monitor the system, optimize
eciency, and aid in troubleshooting.
System Sensor (Optional)
This sensor is designed to be used in a cascade system. The system pipe
sensor measures the temperature of return water and communicates
with the control system to modulate the ring rate of the connected
boilers.
NOTE: When using a system sensor, pipe insulation must be wrapped
around it to improve temperature measurement accuracy and increase
overall system eciency.
Indirect Tank Sensor (Optional)
Monitors storage tank temperature.
C. Optional Equipment
Optional equipment available from HTP (and Part #):
• System Sensor (7250P-324)
• Indirect Tank Sensor (7250P-325)
• High and Low Gas Pressure Switch Kit with Manual Reset
(500 Model [7550P-999], 650 - 2000 Models [7550P-988])
Remove all sides of the shipping crate to allow the boiler to be moved
into its installation location. The boiler is heavy. At least two individuals
and special equipment (pallet jack, forklift, etc.) are needed to properly
handle the boiler. If surface ooring is rough, take care not to damage
the boiler when moving it into position.
9
• Never close existing ventilation openings
• Ensure a minimum 1” clearance around hot water and
exhaust vent pipes
NOTE: To prevent condensing in the fan, it is recommended to
avoid prolonged exposure to temperatures below 45oF
This boiler has a condensate disposal system that may freeze
if exposed to sustained temperatures below 32oF. Precautions
should be taken to protect the condensate trap and drain lines
from sustained freezing conditions. Failure to take precautions
could result in property damage, severe personal injury, or death.
2. Check for nearby connections to:
• System water piping
• Venting connections
• Gas supply piping
• Electrical power
• Condensate drain
3. Check area around boiler. Remove any combustible materials,
gasoline, and other ammable liquids.
COLD WEATHER HANDLING - If the boiler has been stored in a very
cold location (BELOW 0
the components come to room temperature. Failure to do so could
result in damage to the boiler.
Carefully consider installation when determining boiler location.
Please read the entire manual before attempting installation. Failure
to properly take factors such as boiler venting, piping, condensate
removal, and wiring into account before installation could result in
wasted time, money, and possible property damage and personal
injury.
o
F) before installation, handle with care until
A. Locating the Boiler
DO NOT INSTALL the Elite XL OUTDOORS without an optional
Outdoor Installation Kit. Follow the instructions included with
the optional Outdoor Installation Kit when installing the boiler
outdoors. Installing the boiler outdoors without an optional Outdoor
Installation Kit WILL VOID the warranty, and could result in property
damage, severe personal injury, or death.
Incorrect ambient conditions can lead to damage to the heating
system and put safe operation at risk. Ensure that the installation
location adheres to the information included in this manual. Failure
to do so could result in property damage, serious personal injury, or
death. Failure of boiler or components due to incorrect operating
conditions IS NOT covered by product warranty.
This boiler must be installed upright in the vertical position as
described in this manual. DO NOT attempt to install this boiler in any
other orientation. Doing so will result in improper boiler operation
and property damage, and could result in serious personal injury or
death.
1. Installation Area (Mechanical Room) Operating Conditions
• Ensure ambient temperatures are higher than 32oF / 0oC
• Prevent the air from becoming contaminated by the products,
places, and conditions listed in this manual
• Avoid continuously high levels of humidity
Failure to keep the boiler area clear and free of combustible
materials, liquids, and vapors can result in substantial property
damage, severe personal injury, or death.
High heat sources (generating heat 100oF / 37oC or greater, such
as boiler ue pipes, space heaters, etc.) may damage plastic
components of the boiler as well as plastic vent pipe materials.
Such damages ARE NOT covered by warranty. It is recommended
to keep a minimum clearance of 8” from high heat sources. Observe
heat source manufacturer instructions, as well as local, state,
provincial, and national codes, laws, regulations, and ordinances
when installing this boiler and related components near high heat
sources.
The service life of the boiler’s exposed metallic surfaces, such as
the casing, as well as internal surfaces, such as the heat exchanger,
are directly inuenced by proximity to damp and salty marine
environments. In such areas higher concentration levels of
chlorides from sea spray coupled with relative humidity can lead
to degradation of boiler components. In these environments,
boilers must not be installed using direct vent systems which draw
outdoor air for combustion. Such boilers must be installed using
room air for combustion. Indoor air will have a much lower relative
humidity, and hence potential corrosion will be minimized.
Failure of the boiler or components due to incorrect operating
conditions IS NOT covered by product warranty.
4. Gas control system components must be protected from dripping
water during operation and service.
5. If the boiler is to replace an existing boiler, check for and correct
any existing system problems, such as:
• System leaks
• Location that could cause the system and boiler to freeze
and leak
• Incorrectly sized expansion tank
6. Clean and ush system when reinstalling a boiler.
NOTE: When installing in a minimum clearance location, it may
not be possible to read or view some product labeling. It is
recommended to make note of the boiler model and serial number.
lp-666 Rev. 003 Rel. 004 Date 9.3.20
10
WARNING
!
WARNING
!
CAUTION
!
WARNING
!
Use extreme care not to drop the boiler or cause bodily injury
while lifting the boiler. Failure to follow these instructions could
result in property damage, severe personal injury, or death.
B. Flooring
400 - 1000 Models ONLY are approved for installation on
combustible ooring, but must never be installed on carpeting.
1500 - 2000 MODELS ARE NOT APPROVED FOR INSTALLATION
ON COMBUSTIBLE FLOORING. Failure to follow these instructions
could result in re, property damage, severe personal injury, or
death.
Ensure that the oor and structure of the installation location
are sucient to support the full installed weight of the boiler,
including water content of the heat exchanger and related piping.
Failure to ensure the oor and structure of the installation location
are structurally sound before installation of the boiler can result
in structural failure, substantial property damage, severe personal
injury, or death.
C. Leveling
In order for the condensate to properly ow out of the collection
system, the area where you locate the boiler must be level.
Location must also fully support the weight of the lled boiler. See
Figures 2 - 4.
INCORRECT
Figure 4 - Leveling - 1500 - 2000 Models
1500 - 2000 Models ONLY - After the boiler has been installed level
in the nal location the decorative skirts may be installed. These can
be found in the boiler cabinet. Use the included bolts to install the
front skirt (1) before proceeding to the side skirts (2). See Figure 5.
The space must be provided with combustion / ventilation air
openings correctly sized for all other appliances located in the same
space as the boiler. The boiler cover must be securely fastened to
prevent the boiler from drawing air from the boiler room. This is
particularly important if the boiler is in a room with other appliances.
Failure to comply with the above warnings could result in substantial
property damage, severe personal injury, or death.
NOTE: If you do not provide the minimum clearances shown in Figure
6 it might not be possible to service the boiler without removing it
from the space.
NOTE: A combustible door or removable panel is acceptable front
clearance.
NOTE: In multiple boiler installations, ensure an 18” minimum
clearance is maintained between boilers.
lp-666 Rev. 003 Rel. 004 Date 9.3.20
24"
CAUTION
CAUTION
WARNING
!
DANGER
!
WARNING
!
6"
18"
Figure 6 - Recommended Service Clearances
All boilers eventually leak. Locate the boiler where any leakage from
the relief valve, related piping, tank, or connections will not result
in damage to surrounding areas or lower oors of the building.
Any boiler should be installed in such a manner that if it should
leak the resulting ow of water will not cause damage to the area
in which it is installed. If the boiler is installed in a location where
a leak could cause damage, it is required to provide containment
measures. Such measures include but are not limited to: a properly
sized drain pan installed beneath the boiler and piped to an open
drain line, or installing the boiler on a concrete oor pitched to a free
owing drain. Failure to provide containment measures is the sole
responsibility of the owner and/or installer. Leakage damages ARE
NOT covered by warranty.
In addition, water leak detection devices and automatic water shuto
valves are readily available at plumbing supply houses. IT IS HIGHLY
RECOMMENDED BY THE MANUFACTURER TO INSTALL WATER LEAK
DETECTION DEVICES AND AUTOMATIC SHUTOFF VALVES IN ANY
BOILER INSTALLATION WHERE A LEAKAGE OF WATER COULD RESULT
IN PROPERTY DAMAGES.
24”
24"
LP-666-M
10/31/18
E. Residential Garage and Closet Installations
Check with your local Authority Having Jurisdiction for requirements
when installing the boiler in a garage or closet. Please read the
entire manual before attempting installation. Failure to properly take
factors such as venting, piping, condensate removal, and wiring into
account before installation could result in wasted time, money, and
possible property damage and personal injury.
Precautions
If the boiler is located in a residential garage, per ANSI Z223.1:
• Install the boiler burner and ignition devices a minimum of 18”
above the oor of the garage. This will ensure the burner and
ignition devices are well o the oor.
• When raising the boiler ensure the entire bottom and fully
lled weight of the boiler are fully supported.
• Locate or protect the boiler so it cannot be damaged by a
moving vehicle.
11
The space must be provided with correctly sized combustion/
ventilation air openings for all other appliances located in the
space with the boiler. For power venting installations using room
air for combustion, refer to the venting section, this manual, for
descriptions of conned and unconned spaces. Do not install
the boiler in an attic. Failure to comply with these warnings could
result in substantial property damage, severe personal injury, or
death.
F. Exhaust Vent and Intake Pipe
The boiler is rated ANSI Z21.13 Category IV (pressurized vent, likely
to form condensate in the vent) and requires a special vent system
designed for pressurized venting.
NOTE: The venting options described here (and further detailed
in the Venting section, this manual) are the lone venting options
approved for this boiler. Failure to vent the boiler in accordance
with the provided venting instructions will void the warranty.
Failure to vent the boiler properly will result in serious personal
injury or death.
Do not attempt to vent this boiler by any means other than those
described in this manual. Doing so will void the warranty and may
result in severe personal injury or death.
The exhaust discharged by this boiler may be very hot. Avoid
touching or other direct contact with the exhaust gases of the vent
termination assembly. Doing so could result in severe personal
injury or death.
Vents must be properly supported. Boiler exhaust and intake
connections are not designed to carry heavy weight. Vent support
brackets must be within 1’ of the boiler and the balance at 4’
intervals. Boiler must be readily accessible for visual inspection
for rst 3’ from the boiler. Failure to properly support vents could
result in property damage, severe personal injury, or death.
1. Direct Vent of Exhaust and Intake
If installing a direct vent option, combustion air must be drawn
from the outdoors directly into the boiler intake and exhaust must
terminate outdoors. There are three basic direct vent options
detailed in this manual: 1. Side Wall Venting, 2. Roof Venting, and 3.
Unbalanced Venting.
Be sure to locate the boiler such that the exhaust vent and intake
piping can be routed through the building and properly terminated.
Dierent vent terminals can be used to simplify and eliminate
multiple penetrations in the building structure (see Optional
Equipment in Venting Section). The exhaust vent and intake piping
lengths, routing, and termination methods must all comply with
the methods and limits given in the Venting Section, this manual.
When installing a combustion air intake from outdoors, care must
be taken to utilize uncontaminated combustion air. To prevent
combustion air contamination, see Table 1.
lp-666 Rev. 003 Rel. 004 Date 9.3.20
12
CAUTION
WARNING
!
WARNING
!
Conned space is space with volume less than 50 cubic feet per
1,000 BTU/hr (4.8 cubic meters per kW) of the total input rating of
all fuel-burning appliances installed in that space. Rooms connected
directly to this space through openings not furnished with doors are
considered part of the space.
When drawing combustion air from inside a conventionally constructed
building to a conned space, such space should be provided with two
permanent openings: one located 6” (15 cm) below the space ceiling,
the other 6” (15cm) above the space oor. Each opening should have a
free area of one square inch per 1,000 BTU/hr (22cm2/kW) of the total
input of all appliances in the space, but not less than 100 square inches
(645cm2).
If the conned space is within a building of tight construction, air for
combustion must be obtained from the outdoors as outlined in the
Venting section of this manual.
When drawing combustion air from the outside into the mechanical
room, care must be taken to provide adequate freeze protection.
Failure to provide an adequate supply of fresh combustion air can
cause poisonous ue gases to enter the living space, resulting
in severe personal injury or death. To prevent combustion air
contamination, see Table 1.
Figure 7 - Direct Vent Examples
2. Power Venting, Indoor Combustion Air in Conned or
Unconned Space
This boiler requires fresh, uncontaminated air for safe operation and
must be installed in a mechanical room where there is adequate
combustion and ventilating air. NOTE: To prevent combustion air contamination, see Table 1.
Combustion air from the indoor space can be used if the space has
adequate area or when air is provided through a duct or louver to
supply sucient combustion air based on the boiler input. Never
obstruct the supply of combustion air to the boiler. If the boiler is
installed in areas where indoor air is contaminated (see Table 1) it
is imperative that the boiler be installed as direct vent so that all
combustion air is taken directly from the outdoors into the boiler
intake connection.
Unconned space is space with volume greater than 50 cubic feet
per 1,000 BTU/hr (4.8 cubic meters per kW) of the total input rating of
all fuel-burning appliances installed in that space. Rooms connected
directly to this space through openings not furnished with doors are
considered part of the space. See Venting Section for details.
G. Carbon Monoxide Detectors
In the Commonwealth of Massachusetts and As Required by State
and Local Codes:
Installation of Carbon Monoxide Detectors: At the time of installation
or replacement of the vented gas fueled appliance, the installing
plumber or gas tter shall observe that a hard wired carbon monoxide
detector with an alarm and battery back-up is installed on the oor
level where the gas appliance is installed, unless the appliance is
located in a detached, uninhabitable structure separate from the
dwelling, building, or structure used in whole or in part for residential
purposes.
In addition, the installing plumber or gas tter shall observe that a hard
wired carbon monoxide detector with an alarm and battery back-up is
installed on each additional level of the dwelling, building, or structure
served by the vented gas appliance. It shall be the responsibility of the
property owner to secure the service of qualied licensed professionals
for the installation of hard wired carbon monoxide detectors.
a. In the event that the vented gas fueled appliance is installed in a
crawl space or attic, the hard wired carbon monoxide detector with
alarm and battery back-up shall be installed on the next adjacent
oor level.
b. In the event that these requirements cannot be met at the time of
completion of installation, the owner shall have a period of thirty (30)
days to comply with the above requirements; provided, however,
that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
Do not attempt to vent this appliance by any means other than those
described in this manual. Doing so will void the warranty and may
result in severe personal injury or death.
Approved Carbon Monoxide Detectors: Each carbon monoxide
detector as required in accordance with the above provisions shall
comply with NFPA 70 and be ANSI/UL 2034 listed and IAS certied.
H. Prevent Combustion Air Contamination
Install intake air piping for the boiler as described in the Venting
Section, this manual. Do not terminate exhaust in locations that can
allow contamination of intake air.
lp-666 Rev. 003 Rel. 004 Date 9.3.20
WARNING
!
Ensure that the intake air will not contain any of the contaminants
WARNING
!
DANGER
!
WARNING
!
in Table 1. Contaminated air will damage the boiler, resulting in
possible substantial property damage, severe personal injury, or
death. For example, do not pipe intake air near a swimming pool or
laundry facilities. These areas always contain contaminants.
Calcium chloride used for thawingRefrigeration repair shops
Sodium chloride used for water
softening
Refrigerant leaksAuto body shops
Paint or varnish removersPlastic manufacturing plants
Hydrochloric or Muriatic acid
Cements and gluesNew building construction
Antistatic fabric softeners used in
clothes dryers
Chlorine-type bleaches, laundry
detergents, and cleaning solvents
Adhesives used to fasten building
products
Table 1 - Products and Areas Likely to Have Contaminants
NOTE: DAMAGE TO THE BOILER CAUSED BY EXPOSURE TO
CORROSIVE VAPORS IS NOT COVERED BY WARRANTY. (Refer to
the limited warranty for complete terms and conditions.)
Areas Likely to Have
Contaminants
Dry cleaning / laundry areas
and establishments
Beauty shops
Photo processing plants
Furniture renishing areas
and establishments
Remodeling areas
Garages and workshops
I. Removing a Boiler from a Common Vent System
Do not install the boiler into a common vent with any other
appliance. This will cause ue gas spillage or appliance malfunction,
resulting in possible substantial property damage, severe personal
injury, or death.
Failure to follow all instructions can result in ue gas spillage and
carbon monoxide emissions, causing severe personal injury or death.
When removing an existing boiler, follow the steps below.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal
pitch to determine if there is blockage, leakage, corrosion, or other
deciencies that could cause an unsafe condition.
3. If practical, close all building doors, windows, and doors between the
space in which the boiler remains connected to the common venting
system and other spaces in the building. Turn on clothes dryers and
any appliances not connected to the common venting system. Turn
on any exhaust fans, such as range hoods and bathroom exhausts,
at maximum speed. Do not operate a summer exhaust fan. Close all
replace dampers.
4. Place in operation the appliance being inspected. Follow the lighting
instructions. Adjust the thermostat so the appliance will operate
continuously.
13
5. Test for spillage at the draft hood relief opening after 5 minutes of
main burner operation. Use the ame of a match or candle or smoke
from a cigarette.
6. After it has been determined that each appliance remaining
connected to the common venting system properly vents when
tested as outlined, return doors, windows, exhaust fans, replace
dampers, and any other gas burning appliances to their previous
condition of use.
7. Any improper operation of the common venting system should
be corrected to conform to the National Fuel Gas Code, ANSI Z223.1.
When resizing any portion of the common venting system, the
system should approach the minimum size as determined using the
appropriate tables in Appendix G of ANSI Z223.1.
Figure 8 - CO Warning Label
J. Water Chemistry Requirements*
Chemical imbalance of the water supply may aect eciency
and cause severe damage to the appliance and associated
equipment. It is important that the water chemistry on both the
domestic hot water and central heating sides are checked before
installing the appliance. Water quality must be professionally
analyzed to determine whether it is necessary to treat the water.
Various solutions are available to adjust water quality. Adverse
water quality will aect the reliability of the system. In addition,
operating temperatures above 135oF will accelerate the build-up
of lime scale and possibly shorten appliance service life. Failure of
an appliance due to lime scale build-up, low pH, or other chemical
imbalance IS NOT covered by the warranty.
Closed loop water must be free of corrosive chemicals, sand, dirt,
and other contaminates. It is up to the installer to ensure the water
does not contain corrosive chemicals or elements that can damage
the heat exchanger.
If you suspect that your water is contaminated in any way,
discontinue use of the appliance and contact an authorized
technician or licensed professional.
• Water pH between 6.5 and 8.5
• pH levels below 6.5 can cause an increase in the rate of
corrosion. pH of 8.5 or higher can potentially cause lime
scale build-up.
• Maintain water pH between 6.5 and 8.5. Check with litmus
paper or have it chemically analyzed by a local water treatment company.
• If the pH is not between 6.5 and 8.5, consult a local water
treatment company for solutions.
lp-666 Rev. 003 Rel. 004 Date 9.3.20
14
WARNING
!
WARNING
!
• Hardness between 5 and 12 grains (71.3 and 205 mg/L)*
• Hardness levels above the required amounts can lead to
lime scale build-up throughout the system. Water below 5
grains/gallon (71.3 mg/L) may be over softened.
• Consult local water treatment companies for unusually
hard water areas (above the required amounts) or for
other treatment solutions if water is being over softened
(below 5 grains/gallon [71.3 mg/L]).
• Chloride concentration less than 150 ppm (mg/L)
• Do not ll appliance or operate with water containing
chlorides in excess of 150 ppm (mg/L).
• Using chlorinated fresh water should be acceptable as
levels are typically less than 5 ppm (mg/L).
• Do not connect the appliance to directly heat swimming
pool or spa water.
• Total Dissolved Solids (TDS) between 100 and 450 ppm
(mg/L)*
• Total dissolved solids are minerals, salts, metals, and
charged particles that are dissolved in water.
• The greater the amounts of TDS present, the higher the
corrosion potential due to increased conductivity in the
water.
• If using softened water to ll the appliance, it is still
possible to have high TDS. This water can be corrosive.
Consult local water treatment companies for other
treatment solutions to reduce this aect.
*NOTE: The amount of Hardness ppm (mg/L) + TDS ppm (mg/L)
must be less than 450 ppm (mg/L) total. For Example:
WATER CHEMISTRY NOTES:
1. Avoid exposing the heat exchanger water tubes to oxygen to
prevent internal corrosion. System leaks and continuous makeup water will introduce oxygen into the system, increasing the
opportunity for internal corrosion and possibly reducing the life of
the heat exchanger and system components.
2. Leaks in the boiler or piping must be repaired at once to prevent
excessive make-up water. It is recommended to install a water
meter to regularly check the amount of make-up water entering the
system. Make-up water volume should not exceed 5% of the total
system volume per year. When make-up water is added, ensure
chemical additives (glycol, corrosion inhibitors, etc.) are added to
maintain the correct level.
3. Regularly monitoring pH, chlorides, TDS, and hardness levels can
prolong the life of the appliance by reducing mineral scale buildup,
corrosion, and erosion. Mineral buildup in the heat exchanger
reduces heat transfer, overheats the stainless steel heat exchanger,
and causes failure.
4. A corrosion inhibitor approved for use with stainless steel
heat exchangers (comparable to Sentinel X100 or Fernox F1) is
recommended at the correct concentration and in the manner
recommended by the manufacturer.
Elite XL outdoor models are intended for warm weather applications.
DO NOT install the Elite XL outdoors in areas prone to freezing (below
32oF / 0oC). Incorrect ambient conditions can lead to damage to
the heating system and put safe operation at risk. Ensure that the
installation location adheres to the information included in this
manual. Failure to do so could result in property damage, serious
personal injury, or death. Failure of Elite XL or components due to
incorrect operating conditions IS NOT covered by product warranty.
Exhaust vent adaptors are not designed as load-bearing devices,
and must not be used to support exhaust vent piping. All vent pipes
must be properly connected, supported, and the exhaust vent must
be pitched a minimum of 1/4” per foot back to the Elite XL to allow
drainage of condensate. Failure to properly support vent piping
and follow the information in this statement could result in product
damage, severe personal injury, or death.
General Outdoor Installation Guidelines
1. The Elite XL must not be installed outdoors in freezing climates.
Elite XLs installed outdoors must be vented with listed UV-resistant
vent materials per the following instructions and installed with
the optional factory-supplied Outdoor Installation Kit.
2. Keep venting areas free of obstructions, and combustible and
ammable materials. Keep the air intake and exhaust vent
terminations free of obstructions.
3. Do not install directly on the ground. Install on a concrete, brick,
block, or other non-combustible pad.
4. Install unit in a location that avoids opportunities for exhaust gas
recirculation.
5. Clearances around outdoor installations may change over
time. Make sure the growth or trees, shrubs, landscaping, etc. is
properly maintained.
6. Do not install in locations where building runo will spill onto the
unit.
7. Multiple unit installations require at least a 4’ (48 in.) clearance
between exhaust vents.
8. Locate unit at least 3’ (36 in.) away from any overhang.
9. Follow the outdoor kit instructions when locating / venting the
unit.
COUPLING
SCREEN
THE VENT MUST TERMINATE
AT LEAST 24" ABOVE THE
TOP OF THE UNIT
K. Outdoor Installations
DO NOT INSTALL the Elite XL OUTDOORS without an optional
Outdoor Installation Kit. Follow the instructions included with
the optional Outdoor Installation Kit when installing the VWH
outdoors. Installing the VWH outdoors without an optional
Outdoor Installation Kit WILL VOID the warranty, and could result
in property damage, severe personal injury, or death.
Minimum Ambient Temperature: Greater than 32oF (0oC)
70 – 185oF
160
50
100,000 /
1,000,000
150,000 /
1,500,000
3.5” to 10.5” WC (NG
ONLY)
WYE, 60Hz,
200,000 /
2,000,000
208/3PH
15A/Leg
Control Panel7” Full Color Touch Screen
Main Controller928 SIT Control
Connection Sizes
Materials
Safety Devices
Table 3 - Technical Specications
Supply / Return2” NPT2 1/2” Flange
Gas Inlet1” NPT1 1/4” NPT1 1/2” NPT2” NPT
CabinetPowder Coated Galvaneal Steel
Heat Exchanger316L Stainless Steel Water Tube
lp-666 Rev. 003 Rel. 004 Date 9.3.20
Flame Rectier Probe, Dual Water Supply Temperature Sensor / High Limit (210oF), Freeze Protection, Condensate
Trap with Float, Dual Flue Sensor (210oF), Blocked Vent Pressure Switch, Internal UL 353 Approved Low Water
Cut-O (LWCO), High Resolution Flow Switch
Part 4 - Piping
WARNING
!
CAUTION
CAUTION
WARNING
!
WARNING
!
CAUTION
CAUTION
WARNING
!
Failure to follow the instructions in this section WILL VOID the
warranty and may result in property damage, severe personal
injury, or death.
Dielectric unions or galvanized steel ttings must not be used in a
system with this boiler. Doing so WILL VOID the warranty. Use only
copper, brass, or stainless steel ttings. Teon thread sealant must
be used on all connections.
Plumbing of this product should only be done by a qualied, licensed
plumber in accordance with all local plumbing codes. The boiler
may be connected to an indirect water heater to supply domestic
hot water. HTP oers indirect water heaters in either stainless steel
or glass-lined construction.
A. General Plumbing Information
The building piping system must meet or exceed the piping
requirements in this manual.
The control module uses temperature sensors to provide both
high limit protection and modulating temperature control. The
control module also provides low water protection by sensing the
water level in the heat exchanger. Some codes/jurisdictions may
require additional external controls.
Use two wrenches when tightening water piping at boiler. Use one
wrench to prevent the boiler return or supply line from turning.
Failure to prevent piping connections from turning could cause
damage to boiler components.
NOTE: The addition of a high temperature limiting device is
important if the boiler is used to indirectly heat domestic hot water.
B. Relief Valve
Connect discharge piping to a safe disposal location by following
these guidelines.
Do not thread a cap or plug into the relief valve or relief valve line
under any circumstances! Explosion and property damage, serious
injury, or death may result.
RE-INSPECTION OF RELIEF VALVES: Valves should be inspected
AT LEAST ONCE EVERY THREE YEARS, and replaced if necessary,
by a licensed plumbing contractor or qualied service technician
to ensure that the product has not been aected by corrosive
water conditions and to ensure that the valve and discharge line
have not been altered or tampered with illegally. Certain naturally
occuring conditions may corrode the valve and its components
over time, rendering the valve inoperative. Such conditions can
only be detected if the valve and its components are physically
removed and inspected. Do not attempt to conduct an inspection on your own. Contact your plumbing contractor for a
re-inspection to assure continued safety.
FAILURE TO RE-INSPECT THE RELIEF VALVE AS DIRECTED
COULD RESULT IN UNSAFE TEMPERATURE AND/OR PRESSURE
BUILD-UP WHICH CAN RESULT IN PROPERTY DAMAGE,
SERIOUS PERSONAL INJURY, OR DEATH.
17
To avoid water damage or scalding due to relief valve operation:
• Discharge line must be connected to relief valve outlet and
run to a safe place of disposal. Terminate the discharge line
in a manner that will prevent possibility of severe burns or
property damage should the relief valve discharge.
• Discharge line must be as short as possible and the same
size as the valve discharge connection throughout its entire
length.
• Discharge line must pitch downward from the valve and
terminate at least 6” above the oor drain, making discharge
clearly visible.
• The discharge line shall terminate plain, not threaded, with
a material serviceable for temperatures of 375oF or greater.
• Do not pipe discharge to any location where freezing could
occur.
• No valve may be installed between the relief valve and boiler
or in the discharge line. Do not plug or place any obstruction
in the discharge line.
• Test the operation of the relief valve after lling and
pressurizing the system by lifting the lever. Make sure the
valve discharges freely. If the valve fails to operate correctly,
immediately replace with a new properly rated relief valve.
• Test relief valve at least once annually to ensure the waterway
is clear. If valve does not operate, turn the boiler “o” and call
a plumber immediately.
• Take care whenever operating relief valve to avoid scalding
injury or property damage.
FAILURE TO COMPLY WITH THE ABOVE GUIDELINES COULD RESULT
IN FAILURE OF RELIEF VALVE OPERATION, RESULTING IN POSSIBILITY
OF SUBSTANTIAL PROPERTY DAMAGE, SEVERE PERSONAL INJURY,
OR DEATH.
C. Backow Preventer
Use a backow preventer specically designed for hydronic boiler
installations. This valve should be installed on the cold water ll supply
line per local codes.
All piping methods in this manual use primary / secondary
connections to the boiler loop. This is to avoid the possibility of
inadequate ow through the boiler. For other piping methods,
consult your local HTP representative or refer to Applications in this
manual.
D. Expansion Tank
Expansion Tank and Make-Up Water
1. Ensure that the expansion tank is sized to correctly handle boiler
and system water volume and temperature.
Expansion tanks must be sized according to total system volume.
This includes all length of pipe, all xtures, boilers, etc. Failure to
properly size for system expansion could result in wasted time,
money, possible property damage, serious injury, or death.
Undersized expansion tanks cause system water to be lost from the
relief valve, causing make-up water to be added. Eventual boiler
failure can result due to excessive make-up water addition. SUCH
FAILURE IS NOT COVERED BY WARRANTY.
DO NOT install automatic air vents on closed type expansion tank
systems. Air must remain in the system and return to the tank to
provide an air cushion. An automatic air vent would cause air to leave
the system, resulting in improper operation of the expansion tank.
lp-666 Rev. 003 Rel. 004 Date 9.3.20
18
CAUTION
CAUTION
ModelHeat Exchanger Volume (Gallons)
4003.8
5004.3
6505.6
8006.6
10008.1
150012.9
200016.25
Table 4 - Heat Exchanger Volume
2. The expansion tank must be located as shown in Applications, this
manual, or following recognized design methods. See expansion tank
manufacturer’s instructions for details.
3. Connect the expansion tank to the air separator only if the separator
is on the suction side of the circulator. Always install the system ll
connection at the same point as the expansion tank connection to the
system.
4. Most chilled water systems are piped using a closed type expansion
tank.
E. Circulators
Never use dielectric unions or galvanized steel ttings when
connecting to a stainless steel storage tank or boiler. Failure to
follow this instruction can lead to premature failure of the boiler
system. Such failures ARE NOT covered by warranty.
The boiler should not be operated as a potable hot water heater.
The boiler should not be used as a direct hot water heating
device.
DO NOT use the boiler circulator in any location other than the
ones shown in this manual. The boiler circulator location is selected
to ensure adequate ow through the boiler. Failure to comply with
this caution could result in unreliable performance and nuisance
shutdowns from insucient ow.
SIZING SPACE HEAT SYSTEM PIPING
Size the piping and components in the space heating system using
recognized design methods.
F. Hydronic Piping with Circulators, Zone Valves, and
Multiple Boilers
The boiler is designed to function in a closed loop hydronic system.
The included temperature and pressure gauge allows the user to
monitor system pressure and outlet temperature from the boiler. It is
important to note that the boiler has a minimal amount of pressure
drop that must be calculated when sizing the circulators. Each boiler
installation must have an air elimination device that will remove air
from the system.
Install the boiler so the gas ignition system components are protected
from water (dripping, spraying, etc.). Allow clearance for basic service of
the boiler circulator, valves, and other components. Observe minimum
1” clearance around all uninsulated hot water pipes when openings
around pipes are not protected by non-combustible materials.
On a boiler installed above radiation level, some states and local codes
require a low water cut o device. This is provided standard on the
boiler. Check with local codes for additional requirements. If the boiler
supplies hot water to heating coils in air handler units, ow control
valves or other devices must be installed to prevent gravity circulation
of boiler water in the coils during the cooling cycle. Chilled water
medium must be piped in parallel with the boiler.
Freeze protection for new or existing systems must use glycol
specically formulated for this purpose. This glycol must include
inhibitors that will prevent it from attacking metallic system
components. Make certain that the system uid is checked for the
correct glycol concentration and inhibitor level. The system should be
tested at least once a year and as recommended by the producer of the
glycol solution. Allowance should be made for the expansion of the
glycol solution in the system piping. Example: 50% by volume glycol
solution expands 4.8% in volume for the temperature increase from
32oF to 180oF, while water expands 3% over the same temperature rise.
In addition, the boiler heat exchanger has a minimum total water ow rate that must be taken into account when sizing the circulator.
Pressure drops are listed in the table below.
Model
4003912.0267.2194.0
5004811.4325.4243.2
6506311.5426.2314.0
8007712526393
10009614.0647484.7
150014616977.6734.7
20001942112911.5976.7
Table 5 - Pressure Drop at Various Temperature Rises
GPMFt / HdGPMFt / HdGPMFt / Hd
The boiler heat exchanger does have a pressure drop which must be considered in system design.
The chart below represents the combined ow rates and pipe sizes when using multiple boilers to design the manifold system for the primary
circuit. To size, simply add up the number of boilers and the required ow rates for the system design temperature.
Example: (5) 1000 boilers with a design of 30oF temperature rise with each boiler having an individual ow rate of 64 GPM. To correctly size
the manifold feeding these boilers, you would need a pipe size of 6”.
Model
4003344555
5003445556
6504455666
8004556688
10004566888
1500568881010
20006688101012
Table 6 - Multiple Boiler Manifold Piping - NOTE: Table based on water velocity less than Five (5) feet per second.
2345678
Number of Units and Recommended Common Header Pipe Sizes in Inches
lp-666 Rev. 003 Rel. 004 Date 9.3.20
20
CAUTION
CAUTION
CAUTION
H. Check / Control Water Chemistry
NOTE: Boiler failure due to improper water chemistry is not
covered by warranty.
• Water pH between 6.5 and 8.5
• Hardness between 5 and 12 grains (71.3 and 205 mg/L)
• Chloride concentration less than 150 ppm (mg/L)
• Total Dissolved Solids (TDS) between 100 and 450 ppm
(mg/L)
*NOTE: It is recommended to clean the heat exchanger at least once a
year to prevent lime scale buildup. To clean the heat exchanger, follow
the maintenance procedure in this manual.
Clean system to remove sediment*
1. You must thoroughly ush the system (without boiler connected)
to remove sediment. The high-eciency heat exchanger can be
damaged by buildup or corrosion due to sediment.
2. For zoned systems, ush each zone separately through a purge
valve. (If purge valves and isolation valves are not already installed,
install them to properly clean the system.)
3. Flush system until water runs clean and you are sure piping is free
of sediment.
*NOTE: It is recommended you clean heat exchanger at least once a
year to prevent lime scale buildup. Follow the maintenance procedure
to clean the heat exchanger in the Maintenance Section of this manual.
Test/replace freeze protection uid
1. For systems using freeze protection uids, follow uid manufacturer’s
instructions to verify inhibitor level and that other uid characteristics
are satisfactory.
2. Freeze protection uid must be replaced periodically due to
degradation of inhibitors over time. Follow all uid manufacturer
instructions.
I. Plumbing
Piping Components
Heating System Piping
System piping MUST meet the technical pipe requirements listed in
Table 7. Reducing pipe size can restrict ow rate through the boiler,
causing inadvertent short cycling and poor system performance.
Check Valves
Field supplied. Check valves are recommended for installation as
shown in Applications.
Isolation Valves
Field supplied. Full port ball valves are required. Failure to use full port
ball valves could result in a restricted ow rate through the boiler.
Anti-Scald Mixing Valve
Field supplied. An anti-scald mixing valve is recommended when
storing domestic hot water above 115°F.
Steel Flanges
Field supplied. Recommended for unit serviceability.
Pressure Relief Valve
Factory supplied on boiler. The pressure relief valve is sized to ASME
specications. Storage tank may require additional relief valves
depending on local codes.
This boiler should not be operated as a potable hot water heater. It
should not be used as a direct hot water heating device.
Basic steps are listed below that will guide the installation of the boiler.
1. Connect the system return marked “Inlet”.
2. Connect the system supply marked “Outlet”.
3. Install purge and balance valve or shut o valve and drain on system
return to purge air out of each zone.
4. Install a back ow preventer on the cold feed make-up water line.
5. Install a pressure reducing valve on the cold feed make-up water
line (15 PSI nominal on the system return). Check temperature and
pressure gauge when operating. It should read a minimum pressure
of 12 PSI.
6. Install a circulator as shown in piping details (this section). Make
sure the circulator is properly sized for the system and friction loss.
7. Install an expansion tank on the system supply. Consult the tank
manufacturer’s instructions for specic information relating to
expansion tank installation. Size the expansion tank for the required
system volume and capacity.
8. Install an air elimination device on the system supply.
9. The relief valve is installed at the factory. A pipe discharge line
should be installed to discharge 6” above the drain in the event of
pressure relief. The pipe size must be the same size as the relief valve
outlet. NEVER BLOCK THE OUTLET OF THE SAFETY RELIEF VALVE.
Minimum Water Pipe Size
ModelSize
400 - 10002” NPT
1500 - 20002 1/2” Flange
Table 7 - Minimum Pipe Size
J. Fill and Purge Heating System
• Attach the hose to balance and purge hose connector or
drain valve and run hose to nearest drain.
• Close the other side of the balance and purge valve or the
shut o valve after the drain.
• Open rst zone balance and purge or drain valve to let
water ow out the hose. If zone valves are used, open the
valves one at a time manually. (NOTE: You should check the
valve manufacturer’s instructions prior to opening valves
manually, so as not to damage the valves.)
• Manually operate ll valve regulator. When water runs out
of the hose, you will see a steady stream of water (without
bubbles). Close balance and purge valve or drain to stop the
water from owing. Disconnect the hose and connect it to
next zone to be purged.
• Repeat this procedure for additional zones (one at a time).
For installation that incorporates standing iron radiation and
systems with manual vents at the high points, follow previous
section and, starting with the nearest manual air vent, open until
water ows out. Then close vent. Repeat procedure, working your
way toward the furthest air vent. It may be necessary to install
a basket or magnetic strainer in an older system where larger
amounts of sediment may be present. Annual cleaning of the
strainer may be necessary.
Upon completion, make sure that the ll valve is in the automatic
position and each zone balance and purge or shut o is in an open
position and zone valves are positioned for automatic operation.
K. Freeze Protection Fluids
Use only inhibited glycol solutions which are specially formulated
for hydronic systems. Ethylene glycol is toxic and can attack
gaskets and seals used in hydronic systems. Glycol mixtures
should not exceed 50%.
1. Glycol in hydronic applications is specially formulated for this
purpose, and includes inhibitors that prevent the glycol from
attacking metallic system components. Make certain that the
system uid is checked for the correct glycol concentration and
inhibitor level.
2. The glycol solution should be tested at least once a year and as
recommended by the glycol manufacturer.
3. Anti-freeze solutions expand more than water. For example: A
50% by volume solution expands 4.8% in volume for a temperature
lp-666 Rev. 003 Rel. 004 Date 9.3.20
CAUTION
increase from 32oF to 180oF, while water increases 3% over the same
temperature rise. Allowances must be made for this expansion in
the system design.
4. A 30% mixture of glycol will result in a BTU output loss of 15% with
a 5% increase in head against the system circulator.
5. A 50% mixture of glycol will result in a BTU output loss of 30% with
a 50% increase in head against the system circulator.
It is highly recommended that you carefully follow the glycol
manufacturer’s recommended concentrations, expansion
requirements, and maintenance recommendations (pH additive
breakdown, inhibitor reduction, etc.). Carefully gure the
additional friction loss in the system as well as the reduction in
heat transfer coecients.
L. Zoning with Zone Valves
1. When zoning with zone valves, connect the boiler to the system
as shown in Applications. The primary/secondary piping shown
ensures the boiler loop will have sucient ow. It also avoids
applying the high head of the boiler circulator to the zone valves.
2. Connect DHW (domestic hot water) piping to indirect storage
water heater as shown in Applications.
M. Zoning with Circulators
1. When using circulator zoning, connect the boiler to the system as
shown in Applications. NOTE: The boiler circulator cannot be used
for a zone. It must only supply the boiler loop.
2. Install a separate circulator for each zone.
3. Connect DHW (domestic hot water) piping to indirect storage
water heater as shown in Applications.
N. Multiple Boilers
1. Connect multiple boilers as shown in Applications.
2. All piping shown is reverse return to assure balanced ow
throughout the connected boilers.
3. Each connected boiler must have its own circulator pump to
assure adequate ow.
4. Connect DHW (domestic hot water) piping to indirect storage
water heater as shown in Applications.
5. The system ow (secondary loop) must be greater than the
boiler’s primary loop ow.
21
lp-666 Rev. 003 Rel. 004 Date 9.3.20
22
WARNING
!
O. Applications*
*NOTE: Systems shown are
primary/secondary piping
systems. These recommended
systems have a primary (boiler)
loop, and secondary circuits
for heating. The primary loop
and secondary circuits have
separate circulators. The use
of other near boiler piping
congurations could result in
improper ow rates, leading
to inadvertent boiler high limit
shutdowns and poor system
performance.
NOTE: In piping applications
utilizing a single zone, it
is recommended that the
installer use ow / check valves
with weighted seats at or
near the appliance to prevent
gravity circulation.
FIGURE NOTES:
1. This drawing is meant to
demonstrate system piping
concept only.
2. A mixing valve is
recommended if the DHW
temperature is set above the
factory setting of 119oF.
3. Install a minimum of 12
diameters of straight pipe
upstream of all circulators.
4. Install a minimum of 6
diameters of straight pipe up
and downstream of all closely
spaced tees.
5. Piping shown is Primary/
Secondary.
6. The minimum pipe size for
connecting an HTP indirect
red water heater is 1”.
7. DO NOT down size the boiler
heating loop connections.
8. System ow (Secondary
Loop) must be greater than the
boiler’s Primary Loop ow.
9. Installations must comply
with all local codes.
10. In Massachusetts, a vacuum
relief valve must be installed
on the cold water line per 248
CMR.
11. See Multiple Boiler Manifold
Piping chart, this manual, when
sizing and installing a multiple
boiler system.
BOILER CIRCULATOR
BOILER CIRCULATOR
INDIRECT
INDIRECT
TANK
TANK
PURGE VALVE(TYP)
MAY SUBSTITUTE FOR
LOW LOSS HEADER
4 PIPE DIA. SPACING
FROM SYSTEM
CHECK VALVE
DHW CIRCULATOR
MAXIMUM
CHECK
VALVE
Y-STRAINER
(RECOMMENDED)
Figure 12 - Single Boiler Space Heating with Indirect Priority
MAY SUBSTITUTE FOR
LOW LOSS HEADER
FROM SYSTEM
DHW CIRCULATOR
4 PIPE DIA. SPACING MAX
BOILER CIRCULATOR
CHECK VALVE
PURGE VALVE
BALL
VALVE
BALL VALVE
TYPICAL
Figure 13 - Cascaded Boilers with Indirect Priority on One
BALL VALVE
TYPICAL
AIR SEPARATOR
CHECK VALVE
AIR SEPARATOR
Y-STRAINER
RECOMMENDED
SYSTEM
CIRCULATOR
SYSTEM SENSOR
PRESSURE GAUGE
PRESSURE GAUGE
CHECK VALVE
TO SYSTEM
MAKE-UP
WATER
BACK FLOW
PREVENTER
PRESSURE
REDUCING
VALVE
EXPANSION
TANK
LP-666-C
12/20/18
SYSTEM CIRCULATOR
TO SYSTEM
MAKE-UP
WATER
BACKFLOW
PREVENTOR
PRESSURE
REDUCING VALVE
EXPANSION
TANK
LP-666-D
12/20/18
An ASSE 1017 thermostatic mixing valve is recommended on all indirect water heaters if the hot water temperature leaving the heater is
above 119oF. Failure to do so could result in substantial property damage, serious injury, or death.
The piping will not support the weight of the circulators. Refer to the circulator manufacturer’s instructions to properly support the circulator.
Failure to comply with these instructions could result in property damage, severe personal injury, or death.
lp-666 Rev. 003 Rel. 004 Date 9.3.20
Part 5 - Venting
DANGER
!
DANGER
!
DANGER
!
WARNING
!
DANGER
!
WARNING
!
Exhaust
LP-179-JJ
11/30/17
Length
Greater than
Six (6) Inches
Enclosed
Space
Within First Three (3) Linear Feet of
Appliance Exhaust Vent Adapter
The boiler must be vented as detailed in this section. Ensure
exhaust vent and intake piping complies with these instructions
regarding vent system. Inspect nished exhaust vent and intake
piping thoroughly to ensure all joints are well secured, airtight,
and comply with all applicable code requirements, as well as the
instructions provided in this manual. Failure to properly install the
vent system will result in severe personal injury or death.
A. General
This boiler is certied as a “Category IV” appliance and requires
a special venting system. The vent system will operate with a
positive pressure in the pipe. Exhaust gases must be piped directly
outdoors using the vent materials and rules outlined in these
instructions. Do not connect vent connectors serving appliances
vented by natural draft into any portion of mechanical draft
systems operating under positive pressure. Follow the venting
instructions carefully. Failure to do so will result in substantial
property damage, severe personal injury, or death.
1. Installation should be made in accordance with the regulations of
the Authority Having Jurisdiction, local code authorities, and utility
companies which pertain to this type of water heating equipment.
2. Install the venting system in accordance with these instructions
and with the National Fuel Gas Code, ANSI Z223.1/NFPA 54, CAN/
CGA B149, and / or applicable provisions of local building codes.
3. This boiler must be vented with materials, components, and
systems listed and approved for Category IV appliances.
Exhaust and intake are to be piped separately. This boiler cannot
share a common exhaust or intake with multiple appliances.
Failure to follow these instructions will result in substantial
property damage, severe personal injury, or death.
NOTE: To avoid contamination often contained in indoor air, it is
best to pipe all intake combustion air directly to the outdoors.
NOTE: Care must be taken to prevent condensate freezing in the
exhaust vent pipe system. See local, state, provincial, and national
codes for best practices to prevent condensate freezing in the
exhaust vent pipe system.
Improper seating of vent pipe gaskets can cause eventual gasket
failure and exhaust gas leakage. Ensure the exhaust vent pipe is
properly beveled and seated before insertion into the ue adapter.
Failure to do so could result in property damage, severe personal
injury, or death.
Exhaust vent adaptors are not designed as load-bearing devices,
and must not be used to support exhaust vent piping. All vent
pipes must be properly connected, supported, and the exhaust
vent must be pitched a minimum of 1/4” per foot back to the boiler
to allow drainage of condensate. Failure to properly support vent
piping and follow the information in this statement could result in
product damage, severe personal injury, or death.
Vents must be properly supported. Boiler exhaust and intake
connections are not designed to carry heavy weight. Vent support
brackets must be within 1’ of the boiler and the balance at 4’
intervals. Boiler must be readily accessible for visual inspection
for rst 3’ from the boiler. Failure to properly support vents could
result in property damage, severe personal injury, or death.
23
Due to the extreme ammability of most glues, cements, solvents,
and primers used to join plastic exhaust vent and intake pipes,
explosive solvent vapors must be cleared from all vent piping before
start-up. Avoid using excess cement or primer, as this may pool in the
vent pipes. Vent assemblies should be allowed to cure for a period of
at least 8 hours before powering a connected appliance. Failure to
follow these instructions will result in substantial property damage,
severe personal injury, or death. It is the installers’ responsibility to
understand the hazards associated with explosive solvents and take
the necessary precautions to avoid these risks.
• DO NOT insulate the rst three (3) linear feet of the exhaust vent
run.
• CPVC, Polypropylene, or Stainless
Steel pipe material MUST be used if
the rst three (3) linear feet of the
exhaust vent run passes through an
enclosed space greater than 6” in
length, such as a wall. NOTE: Only
Stainless Steel pipe material may be
insulated.
• If CPVC is used to meet these
requirements, the balance may be
installed with approved PVC pipe.
• If Polypropylene or Stainless Steel
is used to meet these requirements, the balance of the vent run
must be installed with the same material.
• Failure to comply with this warning could result in property
damage, severe personal injury, or death.
It is required to insert exhaust and intake screens into the vent
terminations to prevent blockage caused by debris or birds. Failure
to keep terminations clear could result in property damage, severe
personal injury, or death.
lp-666 Rev. 003 Rel. 004 Date 9.3.20
24
CAUTION
WARNING
!
DANGER
!
B. Approved Materials for Exhaust Vent and Intake Pipe
ItemMaterial
Pipe and Fittings Approved for Intake ONLYABS*ANSI/ASTM D2661ANSI/ASTM D2661
PVC Schedule 40/80UL-1738 or ANSI/ASTM D1785
Pipe Approved for
Intake OR Exhaust Vent
PVC-DWV Schedule 40/80UL-1738 or ANSI/ASTM D2665
CPVC Schedule 40/80UL-1738 or ANSI/ASTM F441
PolypropyleneUL-1738 or ULC-S636
Stainless Steel AL29-4CCertied for Category IV and Direct Vent Appliance Venting
Standards for Installation In:
United StatesCanada
UL-1738 or ULC-S636
PVC Schedule 40
Pipe Fittings
Pipe Cement
Pipe PrimerPVC / CPVCASTM F656
• The exhaust and intake components installed with this appliance must be used for near appliance piping BEFORE transitioning to the
approved materials listed above. DO NOT REMOVE these installed components. Doing so WILL VOID appliance warranty.
• PVC / CPVC pipe and ttings of the same diameter are considered interchangeable.
• The use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel® (polyphenolsulfone) in exhaust venting systems is prohibited.
• Covering non-metallic vent pipe and ttings with thermal insulation is prohibited.
• DO NOT connect PVC/CPVC to Polypropylene without an approved vent connector.
• Any transition to Polypropylene MUST be done in the vertical within ve (5) feet of the appliance.
• When installing AL29-4C vent piping, install a PVC-to-stainless adapter at the appliance vent connection, and at the termination
when using a PVC termination kit. DO NOT mix AL29-4C piping from dierent manufacturers unless using adapters specically
designed for the purpose by the manufacturer.
• A double wall vent or insulated material may be used when using stainless steel vent material in a freezing climate.
• *ABS may be used for air intake applications ONLY.
• Contact the venting material manufacturer if there is any question about the applicability of the proposed venting material.
Failure to follow these directions will result in substantial property damage, severe personal injury, or death.
Table 8 - Approved Materials for Exhaust Vent and Intake Pipe
PVC Schedule 80
CPVC Schedule 40UL-1738 or ANSI/ASTM F438
CPVC Schedule 80UL-1738 or ANSI/ASTM F439
ABS*ANSI/ASTM D2235ANSI/ASTM D2235
PVCANSI/ASTM D2564
CPVCANSI/ASTM F493
UL-1738, ANSI/ASTM D2466
or D2665
UL-1738, ANSI/ASTM D2467
or D2665
UL-1738 or ULC-S636
IPEX System 636 Cements and
Primers
DO NOT mix components from dierent venting systems without
proper adapters. The vent system could fail, causing leakage of
ue products into the living space. Use only the approved pipe and
tting materials, and primer and cement specically designed for
the material used, as listed in the above table. Failure to do so could
result in property damage, serious injury, or death.
High heat sources (generating heat 100oF / 37oC or greater, such
as boiler ue pipes, space heaters, etc.) may damage plastic
components of the boiler as well as plastic vent pipe materials. Such
damages ARE NOT covered by warranty. It is recommended to keep
a minimum clearance of 8” from high heat sources. Observe heat
source manufacturer instructions, as well as local, state, provincial,
and national codes, laws, regulations, and ordinances when installing
this boiler and related components near high heat sources.
lp-666 Rev. 003 Rel. 004 Date 9.3.20
You must not use “B” vent in an exhaust application. “B” vent is for
intake applications ONLY. Using “B” vent in an exhaust application
will result in serious injury or death.
C. Additional Requirements for Installation in Canada
1. Installations must be made with a vent pipe system certied to
ULC-S636. Additionally, you may use AL29-4C stainless steel venting
to comply with Canadian requirements.
2. The rst three (3) feet of vent pipe from the boiler ue outlet must
be readily accessible for visual inspection.
3. The components of the certied vent system must not be
interchanged with other vent systems or unlisted pipe / ttings.
D. Exhaust Vent and Intake Pipe Location
B
H
B
BM
G
E
LP-179-CC
A
FIXED
CLOSED
OPERABLE
I
E
E
E
CLOSED
OPERABLE
FIXED
03/28/17
E
E
D
I
E
E
I
DETAIL
I
INSIDECORNER
A
B
B
J
L
K
F
C
K
E
E
E
Exhaust Vent Terminal
I
Intake Pipe Terminal
Area Where Intake Terminal Is Not Permitted
WARNING
!
WARNING
!
Figure 14 - Exit Terminals for Direct Vent Systems - ANSI Z223.1 / NFPA 54 for US and CAN/CSA B149.1 for Canada
Vertical clearance to ventilated sot located above the terminal within
D
a horizontal distance 2 feet (61 cm) from the center line of the terminal
*
EClearance to unventilated sot*
FClearance to outside corner*
GClearance to inside corner*
Clearance to each side of center line extended above meter / regulator
H
assembly
*
IClearance to service regulator vent outlet*
Clearance to nonmechanical air supply inlet to building or
J
the combustion air inlet to any other appliance
KClearance to mechanical air supply inlet
Clearance above paved sidewalk or paved driveway located
L
MClearance under veranda, porch deck, or balcony*1 foot (30 cm)
Table 9 - Vent Termination Clearances - *NOTE: For clearances not specied in ANSI Z223.1 / NFPA 54 for US and CAN/CSA B149.1 for Canada, please
use clearances in accordance with local installation codes and the requirements of the gas supplier.
on public property
Direct Vent1 foot
Power Vent
4 ft below or to side of
opening; 1 ft above opening
3 feet above if within 10 feet
horizontally
Direct Vent*
Power Vent7 feet (2.13 m)
3 feet (91 cm)
Above a regulator
within 3 feet (91 cm)
horizontally of the
vertical center line of
the regulator vent outlet
to a maximum vertical
distance of 15 ft (4.5 m)
3 feet (91 cm)
6 feet (1.83 m)
7 feet (2.13 m)
25
The building owner is responsible for keeping the exhaust and intake
terminations free of snow, ice, or other potential blockages, as well
as scheduling routing maintenance. Failure to keep the vent piping
terminations clear and properly maintain the heater could result in
property damage, severe personal injury, or death.
For each oor containing bedroom(s), a carbon monoxide
detector and alarm shall be placed in the living area outside the
bedrooms, as well as in the room that houses the heater. Detectors
and alarms shall comply with NFPA 720 (latest edition). Failure to
comply with these requirements could result in product damage,
severe personal injury, or death.
lp-666 Rev. 003 Rel. 004 Date 9.3.20
26
CAUTION
WARNING
!
DANGER
!
E. Exhaust Vent and Intake Pipe Sizing
1. The exhaust vent and intake pipe size is 4”, 6”, or 8”, depending on
model.
2. The maximum total equivalent length of exhaust vent and intake
pipe should not exceed 125 feet for 400 to 1000 models, and 150 feet for 1500 and 2000 models.
a. The equivalent length of elbows, tees, and other ttings are
listed in the Friction Loss Table.
Friction Loss Equivalent in Piping and Fittings
Fittings or Piping
90 Degree Elbow5’
45 Degree Elbow3’
Coupling0’
Air Inlet Tee0’
One Foot of Straight Pipe1’
V Series Vent Kit1’
AL29 4c Vent Terminal1’
Table 10 - NOTE: Consult Polypropylene venting instructions for friction
loss and pressure drop equivalents.
b. For example: If the exhaust vent is 6” in diameter, has two 90o
elbows, and 10 feet of PVC pipe we will calculate:
Exhaust Vent Equivalent Length = (2x5) + 10 = 20 feet.
Further, if the 6” intake pipe has two 90o elbows, one 45o elbow,
and 10 feet of PVC pipe, the following calculation applies:
Intake Pipe Equivalent Length = (2x5) + 3 + 10 = 23 feet.
The total equivalent length is 43 feet, well below the maximum
of 125 feet.
c. Eort should be made to keep a minimum dierence in
equivalent length between the exhaust vent and intake pipe.
3. The minimum total equivalent length is 10 feet for 400 to 1000
models, and 15 feet for 1500 and 2000 models.
Do not exceed the maximum lengths for vent pipes. Excessive
length could result in boiler shutdown and property damage.
Failure to provide the minimum total vent length could result in
property damage and improper product operation.
Equivalent Feet
4”6”8”
4. When using PVC or CPVC pipe, all joints must be properly cleaned,
primed, and cemented. Use only cement and primer approved for use
with the pipe material. Cement must conform to ASTM D2564 for PVC
and ASTM F493 for CPVC pipe.
NOTE: The use of colored primer is recommended.
NOTE: DO NOT CEMENT POLYPROPYLENE PIPE. Follow
manufacturer’s instructions for proper installation.
NOTE: Clean and dry the boiler adapters.
DO NOT use primer or cement on the boiler adapters.
a. Clean all pipe ends and ttings using a clean dry rag. (Moisture will
retard curing and dirt or grease will prevent adhesion.)
b. Dry t piping to ensure proper t up before assembling any joint.
The pipe should go a third to two-thirds into the tting to ensure
proper sealing after cement is applied.
c. Priming and Cementing:
i. Handle ttings and pipes carefully to prevent contamination of
surfaces.
ii. Apply a liberal even coat of primer to the tting socket and to the
pipe end to approximately 1/2” beyond the socket depth.
iii. Apply a second primer coat to the tting socket.
iv. While primer is still wet, apply an even coat of approved cement
to the pipe equal to the depth of the tting socket along with an
even coat of approved cement to the tting socket.
v. Apply a second coat of cement to the pipe.
vi. While the cement is still wet, insert the pipe into the tting, if
possible twist the pipe a 1/4 turn as you insert it. NOTE: If voids
are present, sucient cement was not applied and joint could be
defective.
vii. Wipe excess cement from the joint removing ring or beads as it
will needlessly soften the pipe.
8" PVC PIPE
(FIELD SUPPLIED)
8" PVC COUPLING
(FIELD SUPPLIED)
8" CPVC PIPE
STARTER PIECE
MINIMUM 12" LONG
(FIELD SUPPLIED)
8" PVC TO STAINLESS STEEL (FNS)
ADAPTER
(AVAILABLE FROM FACTORY)
7550P-064
Total maximum equivalent length of exhaust vent and intake
pipe must not exceed the lengths dened in this manual. Failure
to keep the total equivalent length below the maximum lengths
determined in this manual will result in faulty boiler operation,
substantial property damage, serious personal injury, or death.
F. Exhaust Vent and Intake Pipe Installation
All joints of positive pressure vent systems must be sealed
completely to prevent leakage of ue products into the living
space. Failure to do so could result in property damage, serious
injury, or death.
1. Use only solid PVC, CPVC, or stainless steel pipe or a Polypropylene
vent system approved for use with Category IV appliances.
ABS pipe material may be used on air intake piping only.
2. Work from the boiler to exhaust vent or intake air termination.
Do not exceed the lengths given in this manual for the vent or air
piping.
3. Cut pipe to the required lengths and deburr the inside and outside
of the pipe ends. Chamfer the outside of each pipe end to ensure
even cement distribution when joining.
lp-666 Rev. 003 Rel. 004 Date 9.3.20
STAINLESS STEEL (FNS) ELBOW
(AVAILABLE FROM FACTORY)
7550P-067
LP-666-AA
04/01/20
Figure 15 - 1500 and 2000 Models - Near Boiler PVC/CPVC Venting (Flue
Connections from the Factory are sized for Stainless Steel Venting)
5. Ensure the vent is located where it will not be exposed to prevailing
winds.
6. In all roof venting applications, exhaust discharge must point away
from the pitch of the roof.
7. If the exhaust vent is to be terminated in a walled o area (such
as a roof with a parapet wall), ensure the exhaust vent terminates a
minimum of 10’ from nearest wall and extends level with or above
the top of the wall. This will ensure ue gas does not get trapped and
possibly recirculated into the intake air pipe, which could contaminate
the combustion air.
8. To prevent water leakage, install adequate roof ashing where the
pipe enters the roof.
9. Do not locate vent over public walkways, driveways, or parking lots.
Condensate could drip and freeze, resulting in a slip hazard or damage
GREATER (TYP)
MAINTAIN12" MINIMUM
CLEARANCEABOVEHIGHEST
ORGRADE, WHICHEVERIS
VENT KIT
EXHAUST
ANTICIPATED SNOWLEVEL
EXTERIOR WALL
06/23/15
LP-505-A
Sidewall Ventingwith Kit
WARNING
!
to vehicles and machinery.
10. Due to potential moisture build-up, sidewall venting may not be
the preferred venting option. To save time and cost, carefully consider
venting installation and location.
11. Horizontal lengths of exhaust vent must slope back towards the
boiler not less than ¼” per foot to allow condensate to drain from the
vent pipe.
12. The exhaust vent must terminate where vapors cannot make
accidental contact with people or pets, or damage shrubs or plants.
13. In vacant chimney applications, install and seal a rain cap over
existing chimney openings.
14. All piping must be fully supported. Use pipe hangers at a minimum
of 4 foot intervals to prevent sagging of the pipe where condensate
may form.
15. Do not use the boiler to support any piping.
16. Ensure the outdoor exhaust vent and intake pipe terminations are
screened to prevent blockage caused by debris or birds.
17. Maximum Snow Level Determination: These installation
instructions reference snow levels in establishing a minimum height
for the installation of exhaust vent or air intake terminations. Snow
levels shall be determined as follows:
a. The installation location may, by ordinance, designate how snow
levels are calculated in that location; or
b. In the absence of specic ordinances, snow levels shall be calculated
from the average monthly maximum depth of snow accumulation as
indicated by the National Weather Service’s 10 year statistics for the
installation location/geographical area.
In addition:
• Total length of vent piping shall not exceed the limits specied
in this manual.
• The vent piping for this direct vented appliance is approved for
zero clearance to combustible construction.
• The ue products coming from the exhaust vent will create a
large plume when the heater is in operation. Avoid venting in
areas that will aect neighboring buildings or be considered
objectionable.
• DO NOT locate exhaust vent or intake pipe in a parking area
where machinery may damage the pipe.
• DO NOT vent near sot vents, crawl space vents, or other areas
where condensate or vapor could create a nuisance or hazard or
cause property damage.
• DO NOT vent where condensate vapor could cause damage or
could be detrimental to the operation of regulators, relief valve,
or other equipment.
In the Commonwealth of Massachusetts and as Required by State
and Local Codes:
• The vented gas fueled appliance shall not be installed so its
combustion, ventilation, or dilution air is obtained from a
bedroom or bathroom.
• Signage: Whenever any through-the-wall (horizontal or sidewall)
vent is installed less than seven feet above the nished grade,
a metal or plastic identication plate shall be permanently
mounted to the exterior of the building at a minimum height
of eight feet above grade directly in line with the exhaust vent
terminal. The sign shall read, in print no less than 0.5 inches
in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS”.
• Marking of Exhaust Vent and Intake Pipe: Piping used for
ventilation, make-up, or combustion air intake shall be labeled
as follows:
a. Throughout the entire developed length:
i. Labels must be placed every ten feet for exposed/visible
piping; or
ii. Labels must be placed every three feet for concealed piping.
b. At all changes of direction;
27
c. On each side of a penetration through a partition, wall or
ceiling; and
d. The labels shall be black lettering that:
i. Indicates that the piping is used for ventilation, make-up,
or combustion air intake, and
ii. The letters shall be sized equal to a minimum of the pipe
diameter. However, for piping with a diameter exceeding
two inches, said lettering does not need to be larger than
two inches.
G. Applications
1. Direct Vent Installation of Exhaust and Intake
If installing a direct vent option, combustion air must be drawn
from the outdoors directly into the boiler intake, and exhaust
must terminate outside. There are three basic direct vent options
detailed in this manual: 1. Side Wall Venting, 2. Roof Venting, and 3.
Unbalanced Venting.
Be sure to locate the boiler such that the exhaust vent and intake
pipe can be routed through the building and properly terminated.
Dierent vent terminals can be used to simplify and eliminate
multiple penetrations in the building structure (see Optional
Equipment in Venting Section). The exhaust vent and intake pipe
lengths, routing and termination methods must all comply with the
methods and limits given in the Venting section of this manual.
When installing a combustion air intake from outdoors, care must be
taken to utilize uncontaminated combustion air. NOTE: To prevent
combustion air contamination, see Table 1.
Figure 16 - Sidewall Venting with Tee and Coupling and Optional Kit
NOTE: These drawings are meant to demonstrate system venting
only. The installer is responsible for all equipment and detailing
required by local codes.
Ensure the terminations are screened to prevent blockage caused
by debris or birds.
All vent pipes must be glued, properly supported, and the exhaust
pitched a minimum of 1/4” per foot back to the boiler to allow
drainage of condensate. When placing support brackets on vent
piping, the rst bracket must be within 1 foot of the boiler and
the balance of 4 foot intervals on the vent pipe. Venting must be
readily accessible for visual inspection from the rst three feet
from the boiler.
Take extra precaution to adequately support the weight of vent
pipes terminating through the roof. Failure to properly support
roof terminated vent piping could result in property damage,
serious personal injury, or death due to ue gas leakage.
An unbalanced vent system can be installed ONLY when the
exhaust is in the vertical position. Failure to do so could result in
serious personal injury or death.
lp-666 Rev. 003 Rel. 004 Date 9.3.20
Loading...
+ 63 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.