NOTE TO CONSUMER: PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE.
This manual must only be used by a qualified heating installer/service technician. Read all instructions in this manual before installing.
Perform steps in the order given. Failure to comply could result in substantial property damage, severe personal injury, or death.
INSTALLATION
START-UP
MAINTENANCE
PARTS
Models*
EFT-55 / 80 / 110 / 155 / 199 / 285 / 399
*A suffix of “LP” denotes propane gas
*A suffix of “N” denotes natural gas
NOTICE: HTP reserves the right to make product changes or updates without notice and will not be held liable for typographical errors
in literature.
120 Braley Rd. P.O. Box 429 East Freetown, MA 02717-0429 www.htproducts.com
LP-387 REV. 6.10.14
2
IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT, CAUSING
PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE. DO NOT STORE GASOLINE OR OTHER FLAMMABLE VAPORS
AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER BOILER.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any boiler.
Do not touch any electrical switch.
Do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department. Installation and service must be provided by a qualified installer,
service agency, or the gas supplier.
LP-387 REV. 6.10.14
3
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk
levels, or to important product information.
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property
damage.
NOTICE
NOTICE is used to address practices not related to personal injury.
This manual must only be used by a qualified heating installer/service technician. Read all instructions in this manual before installing.
Perform steps in the order given. Failure to comply could result in substantial property damage, severe personal injury, or death.
FOREWORD
This manual is intended to be used in conjunction with other literature provided with the boiler. This includes all related control
information. It is important that this manual, all other documents included with this system, and additional publications including the
National Fuel Gas Code, ANSI Z223.1-2002, be reviewed in their entirety before beginning any work.
Installation should be made in accordance with the regulations of the Authority Having Jurisdiction, local code authorities, and utility
companies which pertain to this type of water heating equipment.
Authority Having Jurisdiction (AHJ) – The Authority Having Jurisdiction may be a federal, state, local government, or individual such
as a fire chief, fire marshal, chief of a fire prevention bureau, labor department or health department, building official or electrical
inspector, or others having statutory authority. In some circumstances, the property owner or his/her agent assumes the role, and at
government installations, the commanding officer or departmental official may be the AHJ.
NOTE: HTP, Inc. reserves the right to modify product technical specifications and components without prior notice.
FOR THE INSTALLER
This boiler must be installed by qualified and licensed personnel. The installer should be guided by the instructions furnished with the
boiler, and with local codes and utility company requirements. In the absence of local codes, preference should be given to the National
Fuel Gas Code, ANSI Z223.1-2002.
INSTALLATIONS MUST COMPLY WITH:
Authority Having Jurisdiction, local, state, provincial, and national codes, laws, regulations and ordinances.
The latest version of the National Fuel Gas Code, ANSI Z223.1, from American Gas Association Laboratories, 8501 East Pleasant
Valley Road, Cleveland, OH 44131.
In Canada – CGA No. B149 (latest version), from Canadian Gas Association Laboratories, 55 Scarsdale Road, Don Mills, Ontario,
Canada M3B 2R3. Also, Canadian Electrical Code C 22.1, from Canadian Standards Association, 5060 Spectrum Way, Suite 100,
Mississauga, Ontario, Canada L4W 5N6.
LP-387 REV. 6.10.14
4
The hydronic supply and return connections of these products are for installation in closed loop systems ONLY! Use of this
product in any manner other than described in this manual may result in premature product failure, substantial property damage, severe
personal injury, or death. Damage or failure of this product (or the system in which it is installed) due to unauthorized use IS NOT COVERED BY WARRANTY.
NOTICE
In accordance with Section 325 (f) (3) of the Energy Policy and Conservation Act, HTP, Inc. has provided this boiler with
multiple features designed to save energy by reducing the boiler water temperature as heating load decreases.
These features include:
A modulating combustion system that adjusts firing rate based on heat demand.
Adjustment of boiler set point based on inferred heat load as determined by an outdoor sensor. The outdoor sensor
is supplied by HTP, Inc. with this boiler.
This boiler does not include a standing pilot.
This boiler is designed and shipped to assure the highest efficiency operation possible. Such high efficiency is
achieved by limiting heating circuit water temperature to 140°F when there is no anticipated heat load, based upon
the outdoor sensor and the Outdoor Reset Curve (sensor response curve) in the boiler software.
This feature may be over-ridden as described below in specific installations:
The boiler control is equipped with an outdoor sensor override for use with building management systems or in
cascaded systems (for systems with total input of 300,000 BTU/hr or greater).
See statement below for an important notice on the use of the override.
In accordance with Section 325 (f) (3) of the Energy Policy and Conservation Act, this boiler is equipped with a feature that
saves energy by reducing the boiler water temperature as the heating load decreases. This feature is equipped with an
override which is provided primarily to permit the use of an external energy management system that serves the same
function. THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE:
An external energy management system is installed that reduces the boiler water temperature as the heating load
decreases.
This boiler is not used for space heating.
This boiler is part of a modular or multiple boiler system having a total input of 300,000 BTU/hr or greater.
This boiler is equipped with a tankless coil.
NOTICE
The CSD-1 ASME Code, Section CW-400 requires that hot water heating and supply boilers have a) a UL 353 temperature control
device, b) at least one (1) temperature-actuated control to shut off the fuel supply when system water reaches a preset operating
temperature, c) a high temperature limit control that prevents the water temperature from exceeding the maximum allowable
temperature by causing a safety shutdown and lockout, and d) its own sensing element and operating switch.
Certain AHJs, locales, and states will require that commercial boiler installations meet the CSD-1 ASME Code, Section CW-400. To
meet this code, HTP, Inc. has integrated a temperature control system into the 926 control provided with this heating appliance. This
control system complies with the requirements of CSD-1 Section CW-400 as a temperature operation control. The control monitors the
temperature difference between the inlet and the outlet sensor, which is affected by boiler water flow. If this temperature difference
exceeds 55°F (typically because of low water flow or very low heat load), the control will reduce the maximum fan speed. If the
temperature difference exceeds 60°F, the control will effectively sense there is little or no water flow or heat load and shut the boiler
down. The controller will restart automatically once the temperature difference has dropped below 55°F and the minimum off time (anticycle time) has expired. In addition, if the control senses that the outlet water temperature has reached 210°F, the boiler is put into a
hard lockout and requires manual reset to restart.
Installers should review the regulations of the AHJ, local and state code authorities, and utility companies which pertain to this type of
boiler BEFORE performing installation.
Code for the installation of Heat Producing Boilers (latest version), from American Insurance Association, 85 John Street, New York, NY
11038.
The latest version of the National Electrical Code, NFPA No. 70.
NOTE: The gas manifold and controls met safe lighting and other performance criteria when the boiler underwent tests specified in
ANSI Z21.13 – latest edition.
LP-387 REV. 6.10.14
TABLE OF CONTENTS
PART 1 – GENERAL SAFETY INFORMATION .......................................................................................................................... 8
A. PRECAUTIONS .......................................................................................................................................................................... 8
B. IMPROPER COMBUSTION ....................................................................................................................................................... 8
C. GAS ............................................................................................................................................................................................ 8
D. WHEN SERVICING THE BOILER.............................................................................................................................................. 8
E. BOILER SYSTEM ....................................................................................................................................................................... 8
F. BOILER WATER CHEMISTRY ................................................................................................................................................... 9
G. FREEZE PROTECTION FLUIDS ............................................................................................................................................... 9
PART 2 – BEFORE YOU START ................................................................................................................................................ 9
A. WHAT’S IN THE BOX ................................................................................................................................................................. 9
B. HOW BOILER OPERATES ...................................................................................................................................................... 10
C. OPTIONAL EQUIPMENT ......................................................................................................................................................... 11
PART 3 – PREPARE BOILER LOCATION ............................................................................................................................... 11
A. BEFORE LOCATING THE BOILER ......................................................................................................................................... 11
B. LEVELING ................................................................................................................................................................................ 12
C. CLEARANCES FOR SERVICE ACCESS ................................................................................................................................ 12
D. RESIDENTIAL GARAGE, CLOSET, AND ALCOVE INSTALLATIONS.................................................................................... 15
E. EXHAUST VENT AND INTAKE PIPE....................................................................................................................................... 15
F. PREVENT COMBUSTION AIR CONTAMINATION .................................................................................................................. 15
G. REMOVING AN BOILER FROM A COMMON VENT SYSTEM ............................................................................................... 16
PART 4 – PREPARE BOILER ................................................................................................................................................... 16
5
A. REMOVE THE BOILER FROM PACKAGING .......................................................................................................................... 16
B. WALL MOUNTING CONSIDERATIONS .................................................................................................................................. 17
C. WALL MOUNTING INSTRUCTIONS ....................................................................................................................................... 17
1. MOUNTING TO A WOOD STUDDED WALL .................................................................................................................................................... 17
2. MOUNTING TO A METAL FRAME ................................................................................................................................................................... 18
PART 5 – BOILER PIPING ........................................................................................................................................................ 18
A. GENERAL PIPING INFORMATION ......................................................................................................................................... 19
B. RELIEF VALVE ........................................................................................................................................................................ 19
C. BACKFLOW PREVENTER ...................................................................................................................................................... 20
D. SYSTEM WATER PIPING METHODS ..................................................................................................................................... 20
E. CIRCULATORS ........................................................................................................................................................................ 20
F. HYDRONIC PIPING WITH CIRCULATORS, ZONE VALVES, AND MULTIPLE BOILERS ...................................................... 21
G. PIPING DETAILS ..................................................................................................................................................................... 21
H. PIPING INSTALLATION ........................................................................................................................................................... 29
I. CIRCULATOR SIZING ............................................................................................................................................................... 29
J. CHECK/CONTROL WATER CHEMISTRY ............................................................................................................................... 30
K. FILL AND PURGE HEATING SYSTEM .................................................................................................................................... 31
L. GLYCOL ANTIFREEZE SOLUTIONS ....................................................................................................................................... 32
M. ZONING WITH ZONE VALVES ............................................................................................................................................... 32
LP-387 REV. 6.10.14
N. ZONING WITH CIRCULATORS ............................................................................................................................................... 32
O. MULTIPLE BOILERS ................................................................................................ ................................ ............................... 32
PART 6 – VENTING, COMBUSTION AIR, AND CONDENSATE REMOVAL ........................................................................... 33
A. GENERAL ................................................................................................................................................................................ 33
B. APPROVED MATERIALS FOR EXHAUST VENT AND INTAKE PIPE .................................................................................... 34
C. REQUIREMENTS FOR INSTALLATION IN CANADA ................................ ................................................................ ............. 34
D. EXHAUST VENT AND INTAKE PIPE LOCATION ................................................................................................................... 35
E. EXHAUST VENT AND INTAKE PIPE SIZING .......................................................................................................................... 39
F. EXHAUST VENT AND INTAKE PIPE INSTALLATION ............................................................................................................ 40
G. DIAGRAMS FOR SIDEWALL VENTING .................................................................................................................................. 41
H. DIAGRAM FOR HORIZONTAL VENTING ............................................................................................................................... 43
I. DIAGRAM FOR UNBALANCED FLUE / VERTICAL VENT ....................................................................................................... 44
J. DIAGRAM FOR VERTICAL VENTING ...................................................................................................................................... 45
K. VENTING THROUGH AN EXISTING SYSTEM ....................................................................................................................... 46
2. VENTING AS A CHASE .................................................................................................................................................................................... 47
L. INDOOR COMBUSTION AIR INSTALLATION IN CONFINED OR UNCONFINED SPACE ..................................................... 48
PART 7 – GAS PIPING .............................................................................................................................................................. 50
6
A. GAS CONNECTION ................................................................................................................................................................. 50
B. GAS PIPING ............................................................................................................................................................................. 50
C. CHECK INLET GAS PRESSURE............................................................................................................................................. 51
D. BOILER GAS VALVE ............................................................................................................................................................... 52
PART 8 – FIELD WIRING .......................................................................................................................................................... 53
A. INSTALLATION MUST COMPLY WITH: .................................................................................................................................. 53
B. FIELD WIRING TERMINATIONS ............................................................................................................................................. 53
C. FIELD WIRING ......................................................................................................................................................................... 53
D. LINE VOLTAGE WIRING FOR STANDARD BOILER .............................................................................................................. 54
E. ALARM CONNECTIONS ................................................................................................................................ .......................... 54
F. LOW VOLTAGE CONNECTIONS FOR STANDARD BOILER ................................................................................................. 54
G. THERMOSTAT ........................................................................................................................................................................ 54
H. OUTDOOR SENSOR ............................................................................................................................................................... 55
I. INDIRECT SENSOR .................................................................................................................................................................. 55
J. OPTIONAL 0-10 VOLT BUILDING CONTROL SIGNAL ................................ ........................................................................... 55
K. OPTIONAL UL353 LOW WATER CUT-OFF INTERFACE KIT ................................................................................................ 56
L. WIRING OF CASCADE SYSTEM COMMUNICATION BUS .................................................................................................... 56
M. CASCADE MASTER PUMP AND SENSOR WIRING.............................................................................................................. 57
N. CASCADE FOLLOWER PUMP AND SENSOR WIRING ......................................................................................................... 57
PART 9 – START-UP PREPARATION...................................................................................................................................... 60
A. CHECK / CONTROL WATER CHEMISTRY ............................................................................................................................. 60
B. CHECK FOR GAS LEAKS ....................................................................................................................................................... 61
C. FREEZE PROTECTION (WHEN USED) .................................................................................................................................. 61
LP-387 REV. 6.10.14
D. FILL AND TEST WATER SYSTEM .......................................................................................................................................... 61
E. PURGE AIR FROM WATER SYSTEM ..................................................................................................................................... 62
F. CHECK THERMOSTAT CIRCUIT(S) ....................................................................................................................................... 62
G. CONDENSATE REMOVAL ...................................................................................................................................................... 62
H. FINAL CHECKS BEFORE STARTING BOILER ...................................................................................................................... 63
I. CASCADE SYSTEM .................................................................................................................................................................. 63
J. LOCKOUT CONDITION ............................................................................................................................................................ 64
PART 10 – START-UP PROCEDURE ....................................................................................................................................... 64
A. CONTROL OVERVIEW ............................................................................................................................................................ 64
B. NAVIGATION OF THE DISPLAY ............................................................................................................................................. 64
C. OPERATING INSTRUCTIONS ................................................................................................................................................ 65
D. PROGRAMMING BOILER SETTINGS ..................................................................................................................................... 65
E. PROGRAMMING THE SYSTEM SETTING ............................................................................................................................. 66
F. SYSTEM SETTING PROGRAM NAVIGATION ........................................................................................................................ 66
G. RESETTING THE MAINTENANCE SCHEDULE ..................................................................................................................... 68
PART 11 – START-UP PROCEDURES FOR INSTALLER ....................................................................................................... 69
7
A. BOILER CONTROL STATUS MENU ....................................................................................................................................... 69
B. CASCADE MENU ..................................................................................................................................................................... 71
C. BOILER TEST MODE .............................................................................................................................................................. 71
PART 12 – SHUTDOWN ............................................................................................................................................................ 72
A. SHUTDOWN PROCEDURE ..................................................................................................................................................... 72
B. VACATION PROCEDURE ....................................................................................................................................................... 72
C. FAILURE TO OPERATE .......................................................................................................................................................... 72
PART 13 – TROUBLESHOOTING ............................................................................................................................................ 73
A. BOILER ERROR CODE ........................................................................................................................................................... 73
B. BOILER ERROR ...................................................................................................................................................................... 73
C. BOILER FAULT ........................................................................................................................................................................ 73
D. USER INTERFACE DISPLAY .................................................................................................................................................. 74
PART 14 – MAINTENANCE ...................................................................................................................................................... 78
A. MAINTENANCE PROCEDURES ............................................................................................................................................. 78
B. COMBUSTION CHAMBER COIL CLEANING INSTRUCTIONS FOR BOILER ....................................................................... 79
C. CLEANING WATER SIDE OF HEAT EXCHANGER ................................................................................................................ 79
D. MAINTAINING THE CONDENSATE SYSTEM ........................................................................................................................ 80
HTP CUSTOMER INSTALLATION RECORD FORM ............................................................................................................................................ 91
LP-387 REV. 6.10.14
INSTALLER – Read all instructions in this manual before installing. Perform steps in the order given.
USER – This manual is for use only by a qualified heating installer/service technician. Have this boiler serviced/inspected by a qualified service technician annually.
FAILURE TO ADHERE TO THE GUIDELINES ON THIS PAGE AND HAVE THIS BOILER SERVICED/INSPECTED ANNUALLY
CAN RESULT IN SUBSTANTIAL PROPERTY DAMAGE, SEVERE PERSONAL INJURY, OR DEATH.
DO NOT USE THIS BOILER IF ANY PART HAS BEEN SUBMERGED IN WATER. Immediately call a qualified service technician. The
boiler MUST BE replaced if it has been submerged. Attempting to operate a boiler that has been submerged could create numerous
harmful conditions, such as a potential gas leakage causing a fire and/or explosion, or the release of mold, bacteria, or other harmful
particulates into the air. Operating a previously submerged boiler could result in property damage, severe personal injury, or death.
NOTE: Boiler damage due to flood or submersion is considered an Act of God, and IS NOT covered under product warranty.
Be sure to disconnect electrical power before opening boiler cabinet or performing service. Failure to do so could result in an electrical
shock that could result in property damage, serious personal injury, or death.
NOTE: If the boiler is exposed to the following, do not operate until all corrective steps have been made by a qualified serviceman:
1. FIRE
2. DAMAGE
3. WATER
Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
Due to the low water content of the boiler, improper sizing of the boiler with regard to heating system load will result in excessive cycling
and accelerated component failure. HTP DOES NOT warrant failures caused by improperly sized boiler applications. DO NOT oversize
the boiler to the system. Modular boiler installations greatly reduce the likelihood of boiler oversizing.
Do not obstruct the flow of combustion and ventilating air. Adequate air must be provided for safe operation. Failure to keep the vent
and combustion air intake clear of ice, snow, or other debris could result in property damage, serious personal injury, or death.
PART 1 – GENERAL SAFETY INFORMATION
A. PRECAUTIONS
This boiler is for indoor installations only. Clearance to combustible materials: 6” top, bottom, and sides, 0” back. Left side has all boiler
mechanical connections. Front must have room for service, 24” recommended. (A combustible door or removable panel is acceptable
front clearance.) This boiler has been approved for closet installation. Do not install this boiler directly on carpeting. For installation on
combustible flooring. Category IV vent systems only.
NOTE: When inquiring about service or troubleshooting, reference the model and serial numbers from the boiler rating label.
8
B. IMPROPER COMBUSTION
C. GAS
Should overheating or gas supply fail to shut off, do not turn off or disconnect electrical supply to the circulator. Instead, shut off the gas
supply at a location external to the boiler.
D. WHEN SERVICING THE BOILER
To avoid electric shock, disconnect electrical supply before performing maintenance.
To avoid severe burns, allow boiler to cool.
E. BOILER SYSTEM
Thoroughly flush the system (without boiler connected) to remove sediment. The high-efficiency heat exchanger can be
LP-387 REV. 6.10.14
damaged by build-up or corrosion due to sediment. HTP recommends a suction strainer in all systems.
ACIDITY
6 to 8 pH
CONDUCTIVITY
Less than 400 uS/cm at 25oC
CHLORIDE
Less than 100 ppm
IRON
Less than 0.5 mg/L
COPPER
Less than 0.1 mg/L
SODIUM
Less than 20 mg/L
HARDNESS
Less than 7 Grains
NEVER use automotive or standard glycol antifreeze, or ethylene glycol made for hydronic systems, with this boiler. Use only inhibited
propylene glycol solutions, which are specifically formulated for hydronic systems. Ethylene glycol is toxic and can attack gaskets and
seals used in hydronic systems.
Consider boiler piping and installation when determining boiler location.
Do not use petroleum-based cleaning or sealing compounds in boiler system. Gaskets and seals in the system may be
damaged, possibly resulting in substantial property damage.
Do not use “homemade cures” or “boiler patent medicines”. Substantial
property damage, damage to boiler, and/or serious personal injury may
result.
Continual fresh make-up water will reduce boiler life. Mineral buildup in
the heat exchanger reduces heat transfer, overheats the stainless steel
heat exchanger, and causes failure. Addition of oxygen from make-up
water can cause internal corrosion in system components. Leaks in the
boiler or piping must be repaired at once.
F. BOILER WATER CHEMISTRY
Sodium less than 20mGL.
Water pH between 6 and 8
oMaintain water pH between 6 and 8. Check with litmus paper or
have it chemically analyzed by water treatment company.
oIf the pH differs from above, consult local water treatment
company for treatment needed.
Hardness less than 7 grains
oConsult local water treatment companies for unusually hard
water areas (above 7 grains hardness).
Chlorine concentration less than 100 ppm
o Using chlorinated fresh water should be acceptable as levels are typically less than 5 ppm.
o Do not connect the boiler to directly heat swimming pool or spa water.
o Do not fill boiler or operate with water containing chlorine in excess of 100 ppm.
NOTE: It is recommended to clean heat exchanger at least once a year to prevent lime scale buildup. To clean the heat exchanger,
follow the maintenance procedure in Part 13, Section B of this manual.
9
Table 1 – Water Quality Requirements
G. FREEZE PROTECTION FLUIDS
NOTE: Damages resulting from incorrect installation or from use of products not approved by HTP, Inc. ARE NOT covered by warranty.
PART 2 – BEFORE YOU START
A. WHAT’S IN THE BOX
Also included with the boiler:
Temperature and Pressure Gauge (Part #7500P-098)
Pressure Relief Valve (Part #7250P-080 for EFT-55/80/110/155/199, #7350P-066 for EFT-285/399)
Wall Mount Bracket (Part # 7600P-021 for EFT-55/80/110, #7600P-121 for EFT-155/199/285, #7600P-221 for EFT-399)
Indirect Sensor (Part # 7250P-325)
Outdoor Sensor (Part # 7250P-319)
Intake PVC Tee with Screens
Exhaust PVC Coupling with Screens
LP-387 REV. 6.10.14
10
Installation Manual
Warranty
CSD-1 Form
H-2 Data Sheet
NAT to LP Conversion Kit (Included with NAT models)
B. HOW BOILER OPERATES
ELITE FT® condensing technology intelligently delivers hydronic heating while maximizing efficiency. Outlined below are the features of
the system and how they operate:
Stainless Steel Heat Exchanger - The highly efficient stainless steel heat exchanger is designed to extract all available heat from the
supply line before it is exhausted.
Modulating Combustion System - The combustion system will modulate the output of the burner during operation to match the
system demand and achieve the control set point while in operation. The set point can change by internal or external signals which
enhance the overall performance of the system.
Control – The integrated control system monitors the system and regulates fan speed to control boiler output. This allows the boiler to
deliver only the amount of heat energy required and nothing more.
The control can be set up to monitor outdoor temperature through an outdoor sensor to regulate boiler set point. The system can be
further enhanced by installing an indirect water heater to provide domestic hot water.
The control can regulate the output of multiple boilers through its cascade system function. The cascade system is capable of
connecting up to eight boilers together in such a way that they function as one boiler system. This allows for greater turn down ratios
and provides systematic control of the multiple boilers in an installation to minimize downtime and maximize efficiency.
The cascade system works by establishing one boiler as the master and the other connected boilers as followers. The master boiler
requires a sensor to provide feedback on set point temperature in order to adjust heating input from the connected boilers. Each
cascaded boiler will have its own pump to provide maximum flow and control heat exchanger flow rate.
Text Display and Operational LED Light Indicators – The display allows the user to change system parameters and monitor system
outputs.
Gas Valve – Senses suction from the blower, allowing gas to flow only if powered and combustion air is flowing.
All Metal Integrated Venturi – Controls air and gas flow into the burner.
Burner – Constructed of high grade stainless steel, the burner uses premixed air and gas fuel and provides a wide range of firing rates.
Spark Ignition – The burner is ignited by applying high voltage through the system spark electrode. This causes the spark from the
electrode to ignite mixed gas off of the burner.
Supply Water Temperature Sensor – This sensor monitors boiler outlet water temperature (System Supply). The control adjusts boiler
firing rate so the supply temperature will match boiler set point.
Return Water Temperature Sensor – This sensor monitors the boiler return water temperature (System Return).
Flue Sensor – Monitors flue temperature and adjusts firing rate.
Temperature and Pressure Gauge – Allows the user to monitor system temperature and pressure.
Electrical field connections with terminal strips – The electrical cover allows easy access to the line voltage and low voltage
terminals strips which are clearly marked to facilitate wiring of the boiler.
Condensation Collection System – This boiler is a high efficiency boiler, and will produce condensate. The collection system has a
float switch which monitors the condensation level and prevents condensation from backing up into the combustion system. Inside the
collection system there is a built in trap which seals the combustion system from the connected drain. This condensate should be
neutralized to avoid damage to the drainage system or piping.
Outdoor Sensor – The outdoor sensor monitors outdoor temperature and adjusts boiler set point to provide greater efficiency.
0-10 Volt Input – Allows Installer to connect a BMS (Building Management System) to control the boiler.
Condensate Flue Check System – The check system prevents exhaust from the heat exchanger from backing up into cabinet.
LP-387 REV. 6.10.14
11
Carefully consider installation when determining boiler location. Please read the entire manual before attempting installation. Failure to
properly take factors such as boiler venting, piping, condensate removal, and wiring into account before installation could result in
wasted time, money, and possible property damage and personal injury.
Incorrect ambient conditions can lead to damage to the heating system and put safe operation at risk. Ensure that the boiler installation
location adheres to the information included in this manual. Failure to do so could result in property damage, serious personal injury, or
death.
Failure of boiler or components due to incorrect operating conditions IS NOT covered by product warranty.
The service life of the boiler’s exposed metallic surfaces, such as the casing, as well as internal surfaces, such as the heat exchanger,
are directly influenced by proximity to damp and salty marine environments. In such areas, higher concentration levels of chlorides from
sea spray coupled with relative humidity can lead to degradation of the heat exchanger and other boiler components. In these
environments, boilers must not be installed using direct vent systems which draw outdoor air for combustion. Such boilers must be
installed using room air for combustion. Indoor air will have a much lower relative humidity and, hence, potential corrosion will be
minimized.
Pump Service Mode – Allows manual operation of pumps to commission system and check pump operation.
The Vision II System (Optional) – Allows the user to supply mixed temperatures in up to eight zones. The Vision II system controls the
temperature to each zone by employing three way mixing valves. The Vision II also controls the output temperature of the boiler to
assure accurate temperature delivery to all connected zones.
C. OPTIONAL EQUIPMENT
Below is a list of optional equipment available from HTP. These additional options may be purchased through your HTP distributor:
NOTE: When using an optional system sensor, pipe insulation must be wrapped around it to improve temperature measurement
accuracy and increase overall system efficiency.
PART 3 – PREPARE BOILER LOCATION
A. BEFORE LOCATING THE BOILER
1. Installation Area (Mechanical Room) Operating Conditions
Ensure ambient temperatures are higher than 32oF/0oC and lower than 104oF/40oC.
Prevent the air from becoming contaminated by the products, places, and conditions listed in this manual, Part 3, Section F.
Avoid continuously high levels of humidity
Never close existing ventilation openings
LP-387 REV. 6.10.14
12
This boiler is certified for indoor installations only. Do not install the boiler outdoors. Failure to install this boiler indoors could result in
substantial property damage, severe personal injury, or death.
Failure to keep boiler area clear and free of combustible materials, liquids, and vapors can result in substantial property damage,
severe personal injury, or death.
Gas conversion should be performed BEFORE the boiler is installed. Carefully follow the gas conversion instructions when performing
the conversion. Failure to do so could result in property damage, severe personal injury, or death.
Consider boiler piping and installation when determining boiler location.
In order for the condensate to properly flow out of the collection system, the boiler must be installed level. The location must also
support the boiler when it is full of water.
2. Check for nearby connections to:
System water piping
Venting connections
Gas supply piping
Electrical power
Condensate drain
3. Check area around boiler. Remove any combustible materials, gasoline, and other flammable liquids.
4. Gas control system components must be protected from dripping water during operation and service.
5. If the boiler is to replace an existing boiler, check for and correct any existing system problems, such as:
System leaks
Location that could cause the system and boiler to freeze and leak.
Incorrectly-sized expansion tank
6. Clean and flush system when reinstalling a boiler.
NOTE: When installing in a zero clearance location, it may not be possible to read or view some product labeling. It is recommended to
make note of the boiler model and serial number.
B. LEVELING
C. CLEARANCES FOR SERVICE ACCESS
See Figure 1 for recommended service clearances. If you do not provide the minimum clearances shown, it may not be possible to
service the boiler without removing it from the space.
LP-387 REV. 6.10.14
13
Space must be provided with combustion/ventilation air openings correctly sized for all other boilers located in the same space as the
boiler. The boiler cover must be securely fastened to prevent it from drawing air from the mechanical room. This is particularly important
if the boiler is in a room with other boilers. Failure to comply with the above warnings could result in substantial property damage,
severe personal injury, or death.
Always take future maintenance into consideration when locating the boiler. If the boiler is located in an installation location with limited
clearances, it may be necessary to remove the boiler from the space to perform maintenance. Failure to consider maintenance when
determining installation location could result in property damage.
Figure 1 – Required Clearances
MINIMUM CLEARANCES FROM COMBUSTIBLE MATERIALS
Hot water pipes – at least 1” from combustible materials.
Exhaust vent pipe – at least 1” from combustible materials.
LP-387 REV. 6.10.14
SPECIFICATIONS AND DIMENSIONS
14
Figure 2 – LP-387-K
LP-387 REV. 6.10.14
Check with your local Authority Having Jurisdiction for requirements when installing boiler in a garage, closet, or alcove. Please read
the entire manual before attempting installation. Failure to properly take factors such as boiler venting, piping, condensate removal, and
wiring into account before installation could result in wasted time, money, and possible property damage and personal injury.
For closet or alcove installations, a two pipe venting system must be used. Failure to follow this warning could result in substantial
property damage, severe personal injury, or death.
The space must be provided with correctly sized combustion/ventilation air openings for all other boilers located in the space with the
boiler. Do not install the boiler in an attic. Failure to comply with these warnings could result in substantial property damage, severe
personal injury, or death.
Vent pipes must be properly supported. The boiler exhaust and intake connections are not designed to carry heavy weight. Vent
support brackets must be within 1’ of the boiler and the balance at 4’ intervals. Venting must be readily accessible for visual inspection
for the first 3’ from the boiler.
PRODUCTS TO AVOID
AREAS LIKELY TO HAVE CONTAMINANTS
Spray cans containing fluorocarbons
Dry cleaning/laundry areas and establishments
Permanent wave solutions
Swimming pools
Chlorinated waxes/cleaners
Metal fabrication plants
Chlorine-based swimming pool chemicals
Beauty shops
Calcium chloride used for thawing
Refrigeration repair shops
Sodium chloride used for water softening
Photo processing plants
Refrigerant leaks
Auto body shops
Paint or varnish removers
Plastic manufacturing plants
Hydrochloric or Muriatic acid
Furniture refinishing areas and establishments
Cements and glues
New building construction
Antistatic fabric softeners used in clothes dryers
Remodeling areas
Chlorine-type bleaches, laundry detergents, and cleaning solvents
Garages and workshops
Adhesives used to fasten building products
D. RESIDENTIAL GARAGE, CLOSET, AND ALCOVE INSTALLATIONS
PRECAUTIONS
If the boiler is located in a residential garage, it should be installed per the latest edition of the National Fuel Gas Code, ANSI Z223.1,
and CGA-B149 Installation Code in Canada.
Mount the bottom of the boiler a minimum of 18” above the floor of the garage, to ensure the burner and ignition devices are
well off the floor.
Locate or protect the boiler so it cannot be damaged by a moving vehicle.
NOTE: For installations using room air for combustion, refer to the boiler venting section, Part 6 in this manual.
15
E. EXHAUST VENT AND INTAKE PIPE
The boiler is rated ANSI Z21.13 Category IV (pressurized vent, likely to form condensate in the vent), and requires a special vent
system designed for pressurized venting.
You must also install air intake piping from outdoors to the boiler flue adaptor. NOTE: To prevent combustion air contamination, see
Table 2 in this section when considering exhaust vent and intake pipe termination.
Exhaust vent and intake pipe must terminate near each other and vented vertically through the roof. Venting methods are detailed in
the Venting Section. Do not attempt installation using any other means. Be sure to locate the boiler so exhaust vent and intake pipe can
be routed through the building and properly terminated. The exhaust vent and intake piping lengths, routing and termination method
must all comply with methods and limits given in the venting section.
F. PREVENT COMBUSTION AIR CONTAMINATION
Install intake piping for the boiler as described in the Venting section. Do not terminate exhaust in locations that can allow
contamination of intake air.
Table 2
LP-387 REV. 6.10.14
You must ensure that intake air will not contain any of the contaminants listed in Table 2. For example, do not pipe intake vent near a
swimming pool. Avoid areas subject to exhaust fumes from laundry facilities. These areas always contain contaminants. Contaminated
air will damage the boiler, resulting in possible substantial property damage, severe personal injury, or death.
Do not install the boiler into a common vent with any other boiler. This will
cause flue gas spillage or boiler malfunction, resulting in possible
substantial property damage, severe personal injury, or death.
Failure to follow all instructions can result in flue gas spillage and carbon
monoxide emissions, causing severe personal injury or death.
UNCRATING BOILER – Any claims for damage or shortage in shipment must be filed immediately against the transportation company
by the consignee.
Cold weather handling – If boiler has been stored in a very cold location (below 0oF) before installation, handle with care until the plastic
components come to room temperature.
Figure 3 – CO Warning Label
NOTE: DAMAGE TO THE BOILER CAUSED BY EXPOSURE TO
CORROSIVE VAPORS IS NOT COVERED BY WARRANTY. (Refer to the
limited warranty for complete terms and conditions).
G. REMOVING AN BOILER FROM A COMMON VENT SYSTEM
When removing an existing boiler, the following steps must be followed.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch to
determine if there is blockage, leakage, corrosion or other deficiencies that
could cause an unsafe condition.
3. If practical, close all building doors, windows and all doors between the common venting system and other spaces in the building.
Turn on clothes dryers and any boilers not connected to the common venting system. Turn on any exhaust fans, such as range hoods
and bathroom exhausts, at maximum speed. Do not operate a summer exhaust fan. Close all fireplace dampers.
4. Place in operation the boiler being inspected. Follow the lighting instructions. Adjust the thermostat so the boiler will operate
continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle or
smoke from a cigarette.
6. After it has been determined that each boiler remaining connected to common venting system properly vents when tested as
outlined, return doors, windows, exhaust fans, fireplace dampers and any other gas burning boiler to their previous condition of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms to the National Fuel Gas
Code, ANSI Z223.1. When resizing any portion of the common venting system, the common venting system should be resized to
approach the minimum size as determined using the appropriate tables in Appendix G in the National Fuel Gas Code, ANSI Z 223.1.
16
PART 4 – PREPARE BOILER
A. REMOVE THE BOILER FROM PACKAGING
Remove all sides of the shipping crate, and the wooden block that holds the boiler in place during shipping. Slide the boiler from the
mounting bracket, which is affixed to the skid (Figure 4 and 5). Remove the mounting bracket from the crate (Figure 5). Take care to
place the boiler in a safe location prior to installation to prevent damage to the mechanical connections.
LP-387 REV. 6.10.14
17
The mounting location must be capable of carrying the weight of the boiler and its related components. If the mounting location cannot
support a minimum of 250 lbs. (115 kg), it is recommended to locate the boiler in a mounting location that can support the minimum
weight. Failure to comply with the above and properly mount the boiler could result in substantial property damage, severe personal
injury, or death.
This boiler is too heavy for one person to lift. It is highly recommended to install the boiler with two people. Use caution as to not drop
the boiler, which could damage the boiler and cause property damage and/or severe personal injury. Verify that the boiler is properly
and securely mounted before leaving unsupervised. Failure to comply with the above and properly mount the boiler could result in
substantial property damage, severe personal injury, or death.
This wall mounting system is not seismic rated and should not be applied as such. Failure to comply with the above and properly mount
the boiler could result in substantial property damage, severe personal injury, or death.
DO NOT use the bolts included in shipping for wall mounting the boiler. Doing so may result in property damage, serious injury, or
death.
Figure 4 – Pallet with Mounting Bracket Affixed Figure 5 –Boiler Mounted to Bracket
B. WALL MOUNTING CONSIDERATIONS
These boilers are wall mounted. Use only the wall mounting instructions included in this manual.
Ensure the wall that the boiler is intended to be mounted on is comprised of cement, brick, block, or wooden studs spaced 16” apart
from center. Ensure the wall is capable of supporting at least 250 lbs (115 kg) for EFT-55 – 110 models, 300 lbs (136 kg) for EFT-155 –
285 models, and 500 lbs (227 kg) for EFT-399.
If flooding is possible, elevate the boiler to prevent floodwater from reaching the boiler.
Ensure the boiler is installed in a location that minimizes the risk of water damage due to leaking valves, pumps, unions, etc.
C. WALL MOUNTING INSTRUCTIONS
Figure 6 – Wall Mounting Bracket – NOTE: Drawing for Demonstration Purposes ONLY
1. MOUNTING TO A WOOD STUDDED WALL
a. The building frame (studs) must be 2 X 4 minimum and 16” on center (24” on the EFT-399). If not, you must use ½” minimum
plywood 24” x 48” with at least fourteen (14) #12 x 3” (3/16” x 3”) round head tapping screws to the frame of the building to provide
proper support for the boiler. No alternate methods of mounting or fastening (ex. Toggle bolts, hollow wall anchors, or any other
fastener) may be used.
LP-387 REV. 6.10.14
18
REQUIRED AMOUNT OF BOLTS FOR WALL MOUNTING THE EFT BOILER
MODEL
AMOUNT OF BOLTS
EFT-55 – EFT-110
2
EFT-155 – EFT-285
4
EFT-399
6
PILOT HOLE SIZE BY WOOD TYPE
TYPE
DRILL BIT SIZE
SOFT
3/32”
HARD
3/16”
If the boiler is not installed vertically plumb, improper and unsatisfactory operation may occur, causing excessive condensation build-up,
nuisance fault codes, and unnecessary maintenance.
If the boiler is not installed upright and level, improper and unsatisfactory operation may occur, causing excessive condensation buildup, nuisance fault codes, and unnecessary maintenance.
Failure to follow the instructions in this section WILL VOID the warranty and may result in property damage, serious injury, or death.
b. The provided mounting bracket must be mounted directly to the center of at least 2 studs using standard steel or stainless steel ¼” x
2 ½” lag bolts for all models. Be sure the bracket is level and mark the hole location of the bracket height and horizontal stud location.
Ensure the marked holes are located in the center of the building frame (studs).
c. For all EFT models, 2 ½” is the minimum lag bolt length if the bracket is directly on stud. Increase lag bolt length for any materials
covering the studs.
d. Predrill pilot holes on the marked stud locations. The pilot holes for bare studs should be 2” deep for all EFT models. See table below
for pilot hole diameter by wood type. Increase length for any material covering the stud. Ensure that the predrilled holes are straight and
square to the wall. Failure to do so could lead to insufficient support or out of level boiler. See Figure 6.
NOTE: Bolt must embed into the wood structure a minimum of 2”.
d. Using the predrilled holes, mount the hanger bracket to the building frame (studs) using the appropriately sized standard steel (or
stainless) lag bolt. Hang boiler on the wall mounted bracket. Be sure that the bracket is engaged before letting the boiler hang free.
Slowly release the weight of the boiler while ensuring that the bracket is properly secured. Verify that the boiler is securely mounted
before leaving the boiler unsupervised.
2. MOUNTING TO A METAL FRAME
a. The provided mounting bracket must be mounted to the center of at least 2 studs using standard steel or stainless steel toggle bolts
3/16” diameter or larger, and at least 2” long for direct mounting on stud for EFT-55 – 110 models, and 3/8” diameter or larger, and at
least 2” long for EFT-155 – 399 models for direct mounting on at least 18 gauge studs. Be sure the bracket is level and mark the hole
location of the top bracket height and horizontal stud location. Ensure the marked holes are located in the center of the building frame
(studs).
b. 2” is the minimum toggle bolt length if the bracket is directly on stud. Increase length for any materials covering the studs.
c. Predrill holes on the marked stud locations. The predrilled holes should be ½” in diameter for 3/16” bolts, and ¾” in diameter for 3/8”
bolts, to allow for the collapsed wings of the toggle to slide through. Ensure that the predrilled holes are straight and square to the wall.
Failure to do so could lead to insufficient support of out of level boiler. See Figure 6.
d. Using the predrilled holes, mount the hanger bracket to the building frame (studs) with the toggle bolts. Ensure that the bolt toggles
are through the stud and expanded catching the inside of the stud. Tighten the toggle bolt until the mounting bracket is secure. Hang
boiler on the now wall mounted bracket. Be certain that the bracket is engaged before letting the boiler hang free. Slowly release the
weight of the boiler while ensuring the bracket is properly secure. Verify that the boiler is securely mounted before leaving it
unsupervised.
PART 5 – BOILER PIPING
LP-387 REV. 6.10.14
The building piping system must meet or exceed the piping requirements in this manual.
Use two wrenches when tightening water piping at the boiler. Use one wrench to prevent the boiler return or supply line from turning.
Failure to prevent piping connections from turning could cause damage to boiler components.
The control module uses temperature sensors to provide both high limit protection and modulating temperature control. The control
module may also provide low water protection (through the addition of an optional kit) by sensing the water level in the heat exchanger.
An optional flow switch may be installed on the supply of the system to activate the boiler when there is enough flow. Some
codes/jurisdictions may require additional external controls.
To avoid water damage or scalding due to relief valve operation:
Discharge line must be connected to relief valve outlet and run to a safe place of disposal. Terminate the discharge line in a
manner that will prevent possibility of severe burns or property damage should the relief valve discharge.
Discharge line must be as short as possible and the same size as the valve discharge connection throughout its entire length.
Discharge line must pitch downward from the valve and terminate at least 6” above the floor drain, making discharge clearly
visible.
Discharge line shall terminate plain, not threaded, with a material serviceable for temperatures of 375oF or greater.
Do not pipe discharge to any location where freezing could occur.
No shutoff valve may be installed between the relief valve and boiler or in the discharge line. Do not plug or place any
obstruction in the discharge line.
Test the operation of the relief valve after filling and pressurizing the system by lifting the lever. Make sure the valve
discharges freely. If the valve fails to operate correctly, replace it with a new relief valve.
Test relief valve at least once annually to ensure the waterway is clear. If valve does not operate, turn the boiler “off” and call
a plumber immediately.
Take care whenever operating relief valve to avoid scalding injury or property damage.
For boilers installed with only a pressure relief valve, the separate storage vessel must have a temperature and pressure relief
valve installed. This relief valve shall comply with Relief Valves for Hot Water Supply Systems, ANSI Z21.22 CSA4.4.
FAILURE TO COMPLY WITH THE ABOVE GUIDELINES COULD RESULT IN FAILURE OF RELIEF VALVE OPERATION,
RESULTING IN POSSIBILITY OF SUBSTANTIAL PROPERTY DAMAGE, SEVERE PERSONAL INJURY, OR DEATH.
Never use dielectric unions or galvanized steel fittings when connecting to a stainless steel storage tank or boiler. Failure to follow this
instruction can lead to premature failure of the boiler system. Such failures ARE NOT covered by warranty.
The National Standard Plumbing Code, the National Plumbing Code of Canada, and the Uniform Plumbing Code limit the pressure of
the heat transfer fluid to less than the minimum working pressure of the potable water system up to 30 psi maximum. The heat transfer
fluid must be water or other non-toxic fluid having a toxicity of Class 1, as listed in Clinical Toxicology of Commercial Products, 5th
Edition.
Plumbing of this product should only be done by a qualified, licensed plumber in accordance with all local plumbing codes. The boiler
may be connected to a storage tank to supply domestic hot water. HTP offers 60/80/119/175 gallon size storage tanks in either
stainless steel or glass-lined construction. These storage tanks can be directly connected to the boiler supply and return connection.
A. GENERAL PIPING INFORMATION
19
NOTE: The addition of a high temperature limiting device is important if the boiler is to be connected to a domestic hot water system.
B. RELIEF VALVE
LP-387 REV. 6.10.14
Expansion tanks must be sized according to total system volume. This includes all length of pipe, all fixtures, boilers, etc. Failure to
properly size system expansion could result in wasted time, money, and possible property damage, personal injury, or death.
ADDED VOLUME TO SYSTEM BY ELITE FT BOILER
MODEL
GALLONS
EFT-55 / EFT-80
2.2
EFT-110
2.6
EFT-155
6.2
EFT-199
6.1
EFT-285
6.1
EFT-399
7.9
Undersized expansion tanks cause system water to be lost from the relief valve, causing make-up water to be added. Eventual boiler
failure can result due to excessive make-up water addition. SUCH FAILURE IS NOT COVERED BY WARRANTY.
DO NOT install automatic air vents on closed type expansion tank systems. Air must remain in the system and return to the tank to
provide an air cushion. An automatic air vent would cause air to leave the system, resulting in improper operation of the expansion tank.
DO NOT use the boiler circulator in any location other than the ones shown in this manual. The boiler circulator location is selected to
ensure adequate flow through the boiler. Failure to comply with this caution could result in unreliable performance and nuisance
shutdowns from insufficient flow.
C. BACKFLOW PREVENTER
Use a backflow preventer specifically designed for hydronic installations. This valve should be installed on the cold water fill supply line
per local codes (see Piping Details, Part 5, Section G).
D. SYSTEM WATER PIPING METHODS
EXPANSION TANK AND MAKE-UP WATER
1. Ensure that the expansion tank is designed and sized to correctly handle system water volume and temperature. For sizing
information, refer to expansion tank manufacturer’s sizing guidelines or the latest ASHRAE expansion tank sizing standards.
20
Table 3
2. The expansion tank must be located as shown in Part 5, Boiler Piping, or following recognized design methods. See expansion tank
manufacturer’s instructions for details.
3. Connect the expansion tank to the air separator only if the air separator is on the side of the circulator. Always install the system fill
connection at the same point as the expansion tank connection to the system.
DIAPHRAGM (OR BLADDER) EXPANSION TANK
Always install an automatic air vent on top of the air separator to remove residual air from the system.
E. CIRCULATORS
Sizing Space Heat System Piping
1. See Piping Details, Part 5, Section G. In most diagrams, the space heating system is isolated from the boiler loop by the
primary/secondary connection.
2. Size the piping and components in the space heating system using recognized design methods.
LP-387 REV. 6.10.14
21
Mixing valves are required for the protection of low temperature loops.
F. HYDRONIC PIPING WITH CIRCULATORS, ZONE VALVES, AND MULTIPLE BOILERS
This boiler is designed to function in a closed loop hydronic system. It is recommended to install a temperature and pressure gauge (not
included with the boiler) to allow the user to monitor system pressure and outlet temperature from the boiler. It is important to note that
the boiler has a minimal amount of pressure drop that must be calculated when sizing the circulators. Unless the system has a closed
type expansion tank, each boiler installation must have an air elimination device that will remove air from the system.
Install the boiler so the gas ignition system components are protected from water (dripping, spraying, etc.) Allow clearance for basic
service of boiler circulator, valves and other components.
Observe the minimum 1” clearance around all uninsulated hot water pipes when openings around pipes are not protected by noncombustible materials.
On a boiler installed above radiation level, some states and local codes require a low water cut off device, which is an optional part
available through HTP (Part # 7600P-104 for EFT-55 – 110 models, 7600P-990 for EFT-155 – 399 models). Check with local codes for
additional requirements. If the boiler supplies hot water to heating coils in air handler units, flow control valves or other devices must be
installed to prevent gravity circulation of boiler water in the coils during the cooling cycle.
Chilled water medium must be piped in parallel with, and isolated from, the boiler. Freeze protection for new or existing systems must
use glycol that is specifically formulated for this purpose. Antifreeze must include inhibitors that will prevent the glycol from attacking the
metallic system components. Make certain that the system fluid is checked for the correct glycol concentration and inhibitor level. The
system should be tested at least once a year and as recommended by the producer of the glycol solution. Allowance should be made
for the expansion of the glycol solution in the system piping. Example: 50% by volume glycol solution expands 4.8% in volume for a
temperature increase from 32oF to 180oF, while water expands 3% with the same temperature rise.
G. PIPING DETAILS
LP-387 REV. 6.10.14
22
Figure 7 – Near Boiler Piping* – NOTE: This drawing is meant to show system piping concept only. Installer is responsible for all
equipment and detailing required by local codes. *Top / Bottom Supply / Return Connections available on EFT-155, EFT-199, EFT-285, and
EFT-399 Models ONLY
NOTE: In piping applications utilizing a single zone, it is recommended that the installer use flow / check valves with weighted seats at
or near the boiler to prevent gravity circulation.
LP-387 REV. 6.10.14
23
Figure 8 – Piping Symbol Legend
LP-387 REV. 6.10.14
24
Figure 9 – Standard Piping with Zone Valves and DHW Priority - NOTES:
1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes.
2. All closely spaced tees shall be within 4 pipe diameters center to center spacing.
3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees.
4. The minimumpipe size for connecting a SuperStor indirect water heater is 1”
5. The minimum pipe size for connecting an EFT-55 or 80 - 1”.
6. Circulators are shown with isolation flanges. The alternative is standard flanges with full port ball valves. Purge valves can be used with circulator
flanges as an alternative.
7. A mixing valve is recommended if the DHW temperature is set above the factory setting of 119oF.
8. Piping shown is Standard. VERY IMPORTANT: Minimum flow rates outlined in the manual must be maintained to minimize short cycling.
9. Install a minimum of 12 diameters of straight pipe upstream of all circulators.
LP-387 REV. 6.10.14
25
Figure 10 - Standard Piping with Pumps and DHW Priority - NOTES:
1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes.
2. All closely spaced tees shall be within 4 pipe diameters center to center spacing.
3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees.
4. The minimumpipe size for connecting a SuperStor indirect water heater is 1”
5. The minimum pipe size for connecting an EFT-55 or 80 - 1”.
6. Circulators are shown with isolation flanges. The alternative is standard flanges with full port ball valves. Purge valves can be used with circulator
flanges as an alternative.
7. A mixing valve is recommended if the DHW temperature is set above the factory setting of 119oF.
8. Piping shown is Standard.
9. Install a minimum of 12 diameters of straight pipe upstream of all circulators.
10. VERY IMPORTANT – Minimum flow rates outlined in this manual must be maintained through the heat exchanger to minimize short cycling.
LP-387 REV. 6.10.14
26
Figure 11 – Primary/Secondary Boiler Piping – Zone Valves and DHW Priority – Outdoor Reset - NOTES:
1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes.
2. All closely spaced tees shall be within 4 pipe diameters center to center spacing.
3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees.
4. The minimumpipe size for connecting a SuperStor indirect water heater is 1”
5. The minimum pipe size for connecting an EFT-55/80/110 - 1”, EFT-155/199/285 – 1.25”, EFT-399 – 1.5”.
6. Circulators are shown with isolation flanges. The alternative is standard flanges with full port ball valves. Purge valves can be used with circulator
flanges as an alternative.
7. A mixing valve is recommended if the DHW temperature is set above the factory setting of 119oF.
8. Piping shown is Primary/Secondary. System flow (secondary loop) must be greater than the boiler’s primary loop flow.
9. Install a minimum of 12 diameters of straight pipe upstream of all circulators.
10. VERY IMPORTANT – Minimum flow rates outlined in this manual must be maintained through the heat exchanger to minimize short cycling.
1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes.
2. All closely spaced tees shall be within 4 pipe diameters center to center spacing.
3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees.
4. The minimumpipe size for connecting a SuperStor indirect water heater is 1”
5. The minimum pipe size for connecting an EFT-55/80/110 - 1”, EFT-155/199/285 – 1.25”, EFT-399 – 1.5”.
6. Circulators are shown with isolation flanges. The alternative is standard flanges with full port ball valves. Purge valves can be used with circulator
flanges as an alternative.
7. A mixing valve is recommended if the DHW temperature is set above the factory setting of 119oF.
8. Piping shown is Primary/Secondary. System flow (secondary loop) must be greater than the boiler’s primary loop flow.
9. Install a minimum of 12 diameters of straight pipe upstream of all circulators.
10. VERY IMPORTANT – Minimum flow rates outlined in this manual must be maintained through the heat exchanger to minimize short cycling.
1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes.
2. All closely spaced tees shall be within 4 pipe diameters center to center spacing.
3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees.
4. The minimumpipe size for connecting a SuperStor indirect water heater is 1”
5. The minimum pipe size for connecting an EFT-55/80/110 - 1”, EFT-155/199/285 – 1.25”, EFT-399 – 1.5”.
6. Circulators are shown with isolation flanges. The alternative is standard flanges with full port ball valves. Purge valves can be used with circulator
flanges as an alternative.
7. A mixing valve is recommended if the DHW temperature is set above the factory setting of 119oF.
8. Piping shown is Primary/Secondary. System flow (secondary loop) must be greater than the boiler’s primary loop flow.
9. Install a minimum of 12 diameters of straight pipe upstream of all circulators.
10. VERY IMPORTANT – Minimum flow rates outlined in this manual must be maintained through the heat exchanger to minimize short cycling.
LP-387 REV. 6.10.14