HT HT9022 User Manual

Page 1
© Copyright HT ITALIA 2011 Release EN 1.02 - 26/05/2011
ENGLISH
User manual
www. .com
Page 2
www. .com
Page 3
HT9022
EN - 1
Table of contents:
1. PRECAUTIONS AND SAFETY MEASURES ........................................................................... 3
1.1. Preliminary instructions .................................................................................................................... 4
1.2. During use ........................................................................................................................................ 4
1.3. After use ........................................................................................................................................... 4
1.4. Definition of measurement (overvoltage) category .......................................................................... 5
2. GENERAL DESCRIPTION ....................................................................................................... 6
2.1. Measuring average values and TRMS values ................................................................................. 7
2.2. Definition of true root mean square value and crest factor .............................................................. 7
2.3. Harmonics ........................................................................................................................................ 7
3. PREPARATION FOR USE ....................................................................................................... 8
3.1. Initial checks ..................................................................................................................................... 8
3.2. Instrument power supply .................................................................................................................. 8
3.3. Calibration ........................................................................................................................................ 8
3.4. Storage ............................................................................................................................................. 8
4. OPERATING INSTRUCTIONS ................................................................................................. 9
4.1. Instrument description ...................................................................................................................... 9
4.1.1. Description of the controls ................................................................................................................... 9
4.1.2. Alignment marks.................................................................................................................................. 9
4.1.3. Hand protection ................................................................................................................................. 10
4.1.4. Indication of the conventional direction of Current ............................................................................ 10
4.2. Description of the keys ................................................................................................................... 10
4.2.1. Keys F1 – F2 – F3 – F4 .................................................................................................................... 10
4.2.2. Key H................................................................................................................................................. 10
4.2.3. Key .............................................................................................................................................. 10
4.3. Initial screen ................................................................................................................................... 11
5. INSTRUMENT FUNCTIONS ................................................................................................... 12
5.1. Phase detection .............................................................................................................................. 12
5.2. “Settings” position: Instrument settings .......................................................................................... 12
5.2.1. General.............................................................................................................................................. 12
5.2.2. Date/Time .......................................................................................................................................... 12
5.2.3. Log .................................................................................................................................................... 13
5.2.4. InRush ............................................................................................................................................... 13
5.2.5. Continuity .......................................................................................................................................... 13
5.3. Position “V ”: DC, AC+DC voltage measurement and phase sequence verification ................... 14
5.3.1. DC voltage measurement.................................................................................................................. 14
5.3.1.1. Key F4 “Fnz” .................................................................................................................................... 15
5.3.1.2. Hold ................................................................................................................................................. 15
5.3.1.3. Backlight .......................................................................................................................................... 15
5.3.2. AC+DC voltage and Voltage Harmonics measurement .................................................................... 16
5.3.2.1. Key F2 “Par” .................................................................................................................................... 16
5.3.2.2. AC+DC voltage ................................................................................................................................ 16
5.3.2.2.1. Key F4 “Fnz” in AC+DC voltage measurement ........................................................................... 17
5.3.2.3. Voltage harmonics ........................................................................................................................... 17
5.3.2.3.1. Key F4 “Fnz” in Voltage Harmonics measurement...................................................................... 17
5.3.2.4. Hold ................................................................................................................................................. 18
5.3.2.5. Backlight .......................................................................................................................................... 18
5.3.3. Checking phase sequence and phase concordance with a lead ...................................................... 19
5.3.3.1. Verification of Phase Sequence. ...................................................................................................... 19
5.3.3.2. Verification of Phase Concordance .................................................................................................. 21
5.4. Position “A ”: DC, AC+DC current measurement ........................................................................ 23
5.4.1. DC current measurement .................................................................................................................. 23
5.4.1.1. Key F4 “Fnz” .................................................................................................................................... 24
5.4.1.2. Hold ................................................................................................................................................. 24
5.4.1.3. Backlight .......................................................................................................................................... 24
5.4.2. AC+DC current and Current Harmonics measurement ..................................................................... 25
5.4.2.1. Key F2 “Par” .................................................................................................................................... 25
5.4.2.2. AC+DC current ................................................................................................................................ 25
5.4.2.2.1. Key F4 “Fnz” in AC+DC current measurement ........................................................................... 26
5.4.2.3. Current harmonics ........................................................................................................................... 26
5.4.2.3.1. Key F4 “Fnz” in Current Harmonics measurement ...................................................................... 26
5.4.2.4. Hold ................................................................................................................................................. 27
5.4.2.5. Backlight .......................................................................................................................................... 27
www. .com
Page 4
HT9022
EN - 2
5.5. Position “W ”: DC, AC+DC power measurement ......................................................................... 28
5.5.1. DC power measurement ................................................................................................................... 29
5.5.1.1. Key F2 “Par” .................................................................................................................................... 29
5.5.1.2. DC power ......................................................................................................................................... 30
5.5.1.2.1. Key F4 “Fnz” in DC Power measurement ................................................................................... 30
5.5.1.3. DC voltage and current .................................................................................................................... 30
5.5.1.3.1. Key F4 “Fnz” in DC Voltage and Current measurement .............................................................. 31
5.5.1.4. DC Energy ....................................................................................................................................... 31
5.5.1.5. Hold ................................................................................................................................................. 31
5.5.1.6. Backlight .......................................................................................................................................... 31
5.5.2. Measurement of AC 1P or AC 3P Powers ........................................................................................ 32
5.5.2.1. Key F2 “Par” .................................................................................................................................... 32
5.5.2.2. AC+DC power .................................................................................................................................. 33
5.5.2.3. Pf and dPf ........................................................................................................................................ 33
5.5.2.3.1. Key F4 “Fnz” in Power or Pf-dPf measurement .......................................................................... 33
5.5.2.4. AC+DC Voltage and Current............................................................................................................ 34
5.5.2.4.1. Key F4 “Fnz” in AC Voltage and Current measurement .............................................................. 34
5.5.2.5. Voltage harmonics ........................................................................................................................... 35
5.5.2.6. Current harmonics ........................................................................................................................... 35
5.5.2.6.1. Key F4 “Fnz” in Voltage and Current Harmonics measurement .................................................. 35
5.5.2.7. AC Energy ....................................................................................................................................... 36
5.5.2.8. Hold ................................................................................................................................................. 36
5.5.2.9. Backlight .......................................................................................................................................... 36
5.6. Position “W ”: Log, On-Line Scope, SnapShot, MemorY, Download .......................................... 37
5.6.1. Key F3 “Sys”...................................................................................................................................... 37
5.6.1.1. “Start Log” recording ........................................................................................................................ 37
5.6.1.2. On-line ............................................................................................................................................. 38
5.6.1.3. Memory ............................................................................................................................................ 39
5.6.1.4. SnapShot ......................................................................................................................................... 39
5.6.1.5. Download ......................................................................................................................................... 40
5.7. Position “ ”: Resistance and continuity measurement .............................................................. 41
5.7.1. Key F4 “Fnz”...................................................................................................................................... 42
5.7.1.1. Hold ................................................................................................................................................. 42
5.7.1.2. Backlight .......................................................................................................................................... 42
5.8. Position “InRush A ”: inrush current measurement ..................................................................... 43
5.8.1. Virtual key “Zero” ............................................................................................................................... 44
5.8.2. Key F3 “Run” ..................................................................................................................................... 44
5.8.3. Key F4 “Mem”.................................................................................................................................... 44
6. MAINTENANCE ...................................................................................................................... 46
6.1. General information ........................................................................................................................ 46
6.2. Battery replacement ....................................................................................................................... 46
6.3. Cleaning the instrument ................................................................................................................. 46
6.4. End of life ....................................................................................................................................... 46
7. TECHNICAL SPECIFICATIONS ............................................................................................. 47
7.1. Technical characteristics ................................................................................................................ 47
7.1.1. Safety standards ............................................................................................................................... 49
7.1.2. General characteristics...................................................................................................................... 49
7.2. ENVIRONMENT ............................................................................................................................. 49
7.2.1. Environmental conditions for use ...................................................................................................... 49
7.3. Accessories provided ..................................................................................................................... 49
8. SERVICE ................................................................................................................................ 50
8.1. Warranty conditions ........................................................................................................................ 50
8.2. Service ........................................................................................................................................... 50
9. APPENDIX – THEORETICAL OUTLINE ................................................................................ 51
9.1. Calculation of powers in “AC 1P” mode ......................................................................................... 51
9.2. Calculation of powers in “AC 3P” mode ......................................................................................... 51
9.3. Calculation of powers in “DC” mode .............................................................................................. 51
9.4. voltage and current harmonics ....................................................................................................... 52
9.5. Limit values for harmonics ............................................................................................................. 53
9.6. Causes of the presence of harmonics ............................................................................................ 53
9.7. Consequence of the presence of harmonics ................................................................................. 54
www. .com
Page 5
HT9022
EN - 3
1. PRECAUTIONS AND SAFETY MEASURES
The instrument has been designed in compliance with directive IEC/EN61010-1 relevant to electronic measuring instruments. For your safety and in order to prevent damaging the instrument, please carefully follow the procedures described in this manual and read all
notes preceded by the symbol with the utmost attention.
Before and after carrying out the measurements, carefully observe the following instructions:
Do not carry out any voltage or current measurement in humid environments.
Do not carry out any measurements in case gas, explosive materials or flammables are
present, or in dusty environments.
Avoid contact with the circuit being measured if no measurements are being carried
out.
Avoid contact with exposed metal parts, with unused measuring probes, circuits, etc.
Do not carry out any measurement in case you find anomalies in the instrument such
as deformation, breaks, substance leaks, absence of display on the screen, etc.
Pay special attention when measuring voltages higher than 20V, since a risk of
electrical shock exists.
In this manual, and on the instrument, the following symbols are used:
Warning: observe the instructions given in this manual; an improper use could damage the instrument or its components.
High voltage danger: electrical shock hazard.
Double-insulated meter
AC voltage or current
DC voltage or current
Connection to earth
www. .com
Page 6
HT9022
EN - 4
1.1. PRELIMINARY INSTRUCTIONS
This clamp has been designed for use in environments of pollution degree 2.
It can be used for CURRENT and VOLTAGE measurements on installations with
measurement category CAT IV 600V and CAT III 1000V. For a definition of measurement categories, see § 1.4.
We recommend following the normal safety rules devised by the procedures for
carrying out operations on live systems and using the prescribed PPE to protect the user against dangerous currents and the instrument against incorrect use.
Only the leads supplied with the instrument guarantee compliance with the safety
standards. They must be in good conditions and replaced with identical models, when necessary.
In case the lack of warning against the presence of voltage may constitute a danger for
the operator:
1. always carry out a continuity measurement before carrying out the measurement of the live system to confirm the correct connection and condition of the leads;
2. before carrying out the critical measurement, carry out a measurement at a power socket where voltage is surely present. As an alternative, make this verification at your site before going to the unknown measuring point.
Do not test circuits exceeding the specified current and voltage limits.
Check that the battery is correctly inserted.
Before connecting the test leads to the circuit to be tested, make sure that the switch is
correctly set.
Make sure that the LCD display and the switch indicate the same function.
1.2. DURING USE
Please carefully read the following recommendations and instructions:
WARNING
Failure to comply with the Caution notes and/or Instructions may damage the instrument and/or its components or be a source of danger for the operator.
Before activating the switch, remove the conductor from the clamp jaw or disconnect
the test leads from the circuit under test.
When the instrument is connected to the circuit under test, do not touch any unused
terminal.
Keep your hands always under the hand protection. This protection is always located in
a suitable position to guarantee a correct safety distance from possible exposed or live parts (see Fig. 3: hand protection
Avoid measuring resistance if external voltages are present. Even if the instrument is
protected, excessive voltage could cause a malfunction of the clamp.
During current measurement, any other current near the clamp may affect
measurement precision.
When measuring current, always put the conductor as near as possible to the middle of
the clamp jaw, to obtain the most accurate reading.
While measuring, if the value or the sign of the quantity being measured remain
unchanged, check if the HOLD function is enabled.
1.3. AFTER USE
When measurement is complete, switch OFF the instrument.
If the instrument is not to be used for a long time, remove the batteries.
www. .com
Page 7
HT9022
EN - 5
1.4. DEFINITION OF MEASUREMENT (OVERVOLTAGE) CATEGORY
Standard CEI 61010: Safety requirements for electrical equipment for measurement, control and laboratory use, Part 1: General requirements” defines what measurement category, commonly called overvoltage category, is. In § 6.7.4: Measured circuits, circuits are divided into the following measurement categories:
(OMISSIS)
Measurement category IV is for measurements performed at the source of the
low-voltage installation.
Examples are electricity meters and measurements on primary overcurrent protection devices and ripple control units.
Measurement category III is for measurements performed on installations inside
buildings.
Examples are measurements on distribution boards, circuit breakers, wiring, including cables, bus-bars, junction boxes, switches, socket-outlets in the fixed installation, and equipment for industrial use and some other equipment, for example, stationary motors with permanent connection to fixed installation.
Measurement category II is for measurements performed on circuits directly
connected to the low-voltage installation.
Examples are measurements on household appliances, portable tools and similar equipment.
Measurement category I is for measurements performed on circuits not directly
connected to MAINS.
Examples are measurements on circuits not derived from MAINS, and specially protected (internal) MAINS-derived circuits. In the latter case, transient stresses are variable; for that reason, the standard requires that the transient withstand capability of the equipment is made known to the user.
www. .com
Page 8
HT9022
EN - 6
2. GENERAL DESCRIPTION
The clamp meter HT9022 carries out the following measurements:
DC voltage and AC+CD TRMS voltage
DC current and AC+CD TRMS current
Phase sequence
Active, reactive, apparent power and power factor on single-phase and/or balanced
three phase systems
Active, reactive, apparent energy on single-phase and/or balanced three-phase
systems
AC voltage harmonics (1st – 25th) and THD% up to 75Hz (1st – 8th above 75Hz)
AC current harmonics (1st – 25th) and THD% up to 75Hz (1st – 8th above 75Hz)
DC power
Frequency on voltage (leads) and current (clamp jaw)
Resistance and continuity test with buzzer
Electric motor starting currents (INRUSH)
Detection of presence of AC voltage with and without contact with in-built sensor in the
clamp jaw
Each of these functions can be selected using the 7-position selector switch, including an OFF position.
Keys F1, F2, F3, F4 e H / are also provided; for their use, please refer to § 4.2.
www. .com
Page 9
HT9022
EN - 7
2.1. MEASURING AVERAGE VALUES AND TRMS VALUES
Measuring instruments of alternating quantities are divided into two big families:
AVERAGE-VALUE meters: instruments measuring the value of the sole wave at fundamental frequency from 10 to 400Hz
TRMS (True Root Mean Square) VALUE meters: instruments measuring the TRMS value of the quantity being tested.
In the presence of a perfectly sinusoidal wave, the two families of instruments provide identical results. In the presence of distorted waves, instead, the readings shall differ. Average-value meters provide the RMS value of the sole fundamental wave, TRSM meters, instead, provide the RMS value of the whole wave, including harmonics (within the instrument’s bandwidth). Therefore, by measuring the same quantity with instruments from both families, the values obtained are identical only if the wave is perfectly sinusoidal. In case it is distorted, TRMS meters shall provide higher values than the values read by average-value meters.
2.2. DEFINITION OF TRUE ROOT MEAN SQUARE VALUE AND CREST FACTOR
The root mean square value of current is defined as follows: "In a time equal to a period, an alternating current with a root mean square value of the intensity of 1A, circulating on a resistor, dissipates the same energy that, during the same time, would have been dissipated by a direct current with the intensity of 1A". This definition results in the numeric
expression:
G=
+Tt
t
dttg
T
0
0
)(
1
2
The root mean square value is indicated with the acronym RMS.
The Crest Factor is defined as the relationship between the Peak Value of a signal and its
RMS value: CF (G)=
RMS
p
G
G
This value changes with the signal waveform, for a purely sinusoidal wave it is
2 =1.41.
In case of distortion, the Crest Factor takes higher values as wave distortion increases.
2.3. HARMONICS
See Appendix (Par.9.4)
www. .com
Page 10
HT9022
EN - 8
3. PREPARATION FOR USE
3.1. INITIAL CHECKS
Before shipping, the instrument has been checked from an electric as well as mechanical point of view. All possible precautions have been taken so that the instrument is delivered undamaged.
However, we recommend generally checking the instrument in order to detect possible damage suffered during transport. In case anomalies are found, immediately contact the forwarding agent.
We also recommend checking that the packaging contains all components indicated in paragraph 7.3. In case of discrepancy, please contact the Dealer.
In case the instrument should be replaced, please carefully follow the instructions given in chapter 8.2.
3.2. INSTRUMENT POWER SUPPLY
The instrument is supplied by two 1.5V LR03 AAA UM-4 batteries. Battery charge duration is approximately 54 hours of continuous use in Power mode (selector switch to “W ”).
Replace them following the instructions in paragraph 5.2.
3.3. CALIBRATION
The instrument has the technical specifications described in this manual. The instrument’s performance is guaranteed for one year.
3.4. STORAGE
In order to guarantee precise measurement, after a long storage time under extreme environmental conditions, wait for the instrument to come back to normal condition (see the environmental specifications contained in 6.2.1 before use).
www. .com
Page 11
HT9022
EN - 9
4. OPERATING INSTRUCTIONS
4.1. INSTRUMENT DESCRIPTION
4.1.1. Description of the controls
CAPTION:
1. Inductive clamp jaw
2. AC voltage indicator LED
3. Jaw trigger
4. Rotary selector switch
5. Key H / backlight
6. Function keys F1 – F2 – F3 – F4
7. LCD display
8. Input terminal V
9. Input terminal COM
Fig. 1: Instrument description
4.1.2. Alignment marks
Put the conductor as close as possible to the middle of the jaws on the intersection of the indicated marks (see Fig. 2) in order to meet the meter accuracy specifications.
CAPTION:
1. Alignment marks
2. Conductor
Fig. 2: alignment marks
www. .com
Page 12
HT9022
EN - 10
4.1.3. Hand protection
CAPTION:
1. Hand protection
2. Safe area
Fig. 3: hand protection
Always keep your hands under the hand protection. This protection is always located in a suitable position to guarantee a correct safety distance from possible exposed or live parts (see Fig. 3)
4.1.4. Indication of the conventional direction of Current
The photo in Fig. 4: current direction arrow shows an arrow which indicates the conventional direction of current.
Fig. 4: current direction arrow
4.2. DESCRIPTION OF THE KEYS
4.2.1. Keys F1 – F2 – F3 – F4
Keys F1 - F2 - F3 - F4 take different functions according to the measure set (for detailed
information, see the single functions).
4.2.2. Key H
Short pressing key “H” activates the function Data HOLD, i.e. the value of the measures quantity is frozen. The symbol "H" is displayed when this function is enabled. This operating mode is disabled when key “H” is pressed again or the switch is operated.
4.2.3. Key
To improve the readability of the values measured in dark places, the display has been provided with a backlighting function (backlight), which is turned on and off by long-
pressing key “H”. This function automatically deactivates after approximately 10 seconds
after being activated, in order not to discharge the battery.
www. .com
Page 13
HT9022
EN - 11
4.3. INITIAL SCREEN
When switching on the instrument, the initial screen appears for a few seconds. It shows:
the instrument model;
the serial number of the instrument;
the firmware version in the instrument’s memory.
HT9022
Sn 10120020
V. 2.00
WARNING
Please note down this information, especially the firmware version, in case it should be necessary to contact the Service Department.
After a few seconds, the instrument switches to the selected function.
www. .com
Page 14
HT9022
EN - 12
5. INSTRUMENT FUNCTIONS
5.1. PHASE DETECTION
With the selector switch set to “V ” (Voltage measurement) or “A ” (Current measurement), by taking the end of the clamp jaw near an AC source, the red LED at the base of the clamp jaw will turn on (see Fig. 1 – part 2), which indicates that current is present.
WARNING
Phase detection is not active when the clamp selector switch is set to “OFF”, “SETTINGS”, “W ”, “ ”,“InRush A ”.
5.2. “SETTINGS” POSITION: INSTRUMENT SETTINGS
By positioning the selector switch to “Settings”, the screen aside
will appear, containing the possible settings of the instrument.
Press keys F2, F3 (T, S) to move the cursor and key F4 (OK)
to confirm the selected item.
OK
General
Date/Time Log InRush Continuity
19/01-17:00:00
5.2.1. General
By selecting “General”, the screen to the side will appear. Press key F1 (Sel) to move the cursor and keys F2, F3 (T, S)
to change the selected item.
Press key F4 (OK) to save the changes made and go back to
the previous screen (see par.5.2).
Language: the language of the clamp may be chosen
among: Italian, English, Spanish. German, Swedish, Danish, Norwegian, French, Dutch, Portuguese, Finnish and Polish.
Sel
OK
Language: Italian Auto-Off: OFF
19/01-17:00:00
Auto-Off: the auto power off of the clamp may be set to ON or OFF. If set to ON, the
clamp will switch off after 5 minutes after it is last used.
5.2.2. Date/Time
By selecting “Date/Time”, the screen to the side will appear. Press key F1 (Sel) to move the cursor and keys F2, F3 (T, S)
to change the selected item. Item “Format” allows selecting the date and time format between EU (European) or USA (American).
Press key F4 (OK) to save the changes made and go back to
the previous screen (see par.5.2).
Sel
OK
Year: 11 Month: 01 Day: 19 Hour: 17 Minute: 00 Format: EU
19/01-17:00:00
www. .com
Page 15
HT9022
EN - 13
5.2.3. Log
By selecting “Log”, the screen to the side will appear. Press keys F2, F3 (T, S) to change the duration of the
integration period. It will take the following values: 1, 5, 10, 30, 60, 120, 300, 600 or 900 seconds.
Press key F4 (OK) to save the changes made and go back to
the previous screen (see par.5.2).
OK
Int.Period:
001 s
19/01-17:00:00
5.2.4. InRush
By selecting “InRush”, the screen to the side will appear. Press key F1 (Sel) to move the cursor and keys F2, F3 (T, S)
to change the selected item.
Press key F4 (OK) to save the changes made and go back to
the previous screen (see par.5.2).
Thresh: threshold value beyond which the inrush current
event is detected and recorded by the instrument. The current value may be set between 5A and 900A in steps of 1A.
Sel
OK
Thres: 080 Window: 1/1 Mode: Fix
19/01-17:00:00
Window: the value of the inrush current measuring window. The following values are
available:
¾ 1/1: sampling occurs every half-period; ¾ 1/2: sampling occurs one every two half-periods; ¾ 1/4: sampling occurs one every four half-periods;
Mode: the inrush current measuring mode. Following modes are available:
¾ Fix; ¾ Var.
For details about the measurement of Inrush Currents see par. 5.8.2.
5.2.5. Continuity
By selecting “Continuity”, the screen to the side will appear. Press keys F2, F3 (T, S) to change the setting of the resistance
limit value below which the buzzer will sound. It may be set between 1 and 150 in steps of 1Ω.
Press key F4 (OK) to save the changes made and go back to
the previous screen (see par.5.2).
Sel
OK
Res Lim:
010
19/01-17:00:00
www. .com
Page 16
HT9022
EN - 14
5.3. POSITION “V ”: DC, AC+DC VOLTAGE MEASUREMENT AND PHASE SEQUENCE VERIFICATION
WARNING
The maximum DC or AC+DC input voltage is 1000V. When the display shows “> 999.9V”, it means that the maximum value the clamp is able to measure has been exceeded. Exceeding these limits could result in electrical shocks to the user and damage to the instrument.
By positioning the selector switch to “V ”, the screen to the side
will appear.
Mod Par Fnz
AC <10.0 Hz
---- V
19/01-17:00:00
Press key F1 (Mod) to open the drop-down menu shown on the screen to the side. At each subsequent pressure of key F1, the
cursor will scroll through the available items, as follows:
AC: AC+DC voltage measurement;
DC: DC voltage measurement;
Ph Seq: verification of phase sequence;
Help: it displays the connection diagram of the instrument to
the system;
Mod Par OK
AC <10.0 Hz
---- V
19/01-17:00:00
Select the desired mode and press key F4 (OK) to confirm.
5.3.1. DC voltage measurement
Fig. 5: DC voltage measurement
AC
DC
Ph Seq Help Esc
www. .com
Page 17
HT9022
EN - 15
Insert the red cable into the input lead V and the black cable into the input lead COM
(Fig. 5), and position the leads to the desired points of the circuit being tested.
The screen shows an example of DC Voltage measurement.
Mod Par Fnz
DC
12.0 V
19/01-17:00:00
5.3.1.1. Key F4 “Fnz”
Press key F4 (Fnz) to open the drop-down menu shown on the screen to the side. At each subsequent pressure of key F4, the
cursor will scroll through the available items, as follows:
Max: it constantly displays the maximum value of the
measured DC Voltage;
Min: it constantly displays the minimum value of the
measured DC Voltage;
Mod Par OK Fnz
DC
12.0 V
19/01-17:00:00
Cr+: it constantly displays the maximum positive crest value;
Cr-: it constantly displays the minimum negative crest value;
Rst: it deletes all stored Max, Min, Cr+ and Cr- values;
Esc: it goes back to a normal measuring mode.
WARNING
Note: the measurement of the 4 Max, Min, Cr+ and Cr- values is simultaneous, regardless of the one displayed.
By pressing key F3 (OK), the selected item is confirmed.
To the side, an example of measurement with active Max function. The display shows the active function.
Mod Par Fnz
Max DC
12.0 V
19/01-17:00:00
5.3.1.2. Hold
Short pressing key “H” activates the function Data HOLD. The display shows the message
H” and the screen of the measurement in progress is “frozen”.
This operating mode is deactivated when key “H” is pressed again or the switch is
operated.
5.3.1.3. Backlight
Long pressing key “H” activates or deactivates the display backlight. This function
automatically deactivates after approximately 10 seconds after being activated, in order not to discharge the batteries.
Max
Min Cr+ Cr­Rst Esc
www. .com
Page 18
HT9022
EN - 16
5.3.2. AC+DC voltage and Voltage Harmonics measurement
Fig. 6: AC+DC voltage measurement
Insert the red cable into the input lead V and the black cable into the input lead COM,
and position the leads to the desired points of the circuit being tested (Fig. 6). The voltage and frequency value is shown on the display.
5.3.2.1. Key F2 “Par”
Press key F2 (Par) to open the drop-down menu shown on the screen to the side. At each subsequent pressure of key F2, the
cursor will scroll through the available items, as follows:
Voltage: it shows the measured Voltage value;
Voltage Har: it shows the measured Voltage harmonics;
Esc: it closes the drop-down menu.
Select the desired parameter and press key F4 (OK) to confirm.
Mod
Par OK
AC 50.0 Hz
220.5 V
19/01-17:00:00
5.3.2.2. AC+DC voltage
The screen shows an example of AC+DC Voltage measurement.
Mod Par Fnz
AC 50.0 Hz
220.5 V
19/01-17:00:00
Voltage
Voltage Har
Esc
www. .com
Page 19
HT9022
EN - 17
5.3.2.2.1. Key F4 “Fnz” in AC+DC voltage measurement
While measuring AC+DC voltage, press key F4 (Fnz) to open
the drop-down menu shown on the screen to the side. At each
subsequent pressure of key F4, the cursor will scroll through the
available items, as follows:
Max: it constantly displays the maximum RMS value of
Voltage;
Min: it constantly displays the minimum RMS value of
Voltage;
Mod Par OK Fnz
AC 50.0 Hz
220.5 V
19/01-17:00:00
Cr+: it constantly displays the maximum positive crest value;
Cr-: it constantly displays the minimum negative crest value;
Rst: it deletes all stored Max, Min, Cr+ and Cr- values;
Esc: it goes back to a normal measuring mode.
By pressing key F3 (OK), the selected item is confirmed.
To the side, an example of measurement with active Max function. The display shows the active function.
Mod Par Fnz
Max AC 50.0 Hz
220.5 V
19/01-17:00:00
5.3.2.3. Voltage harmonics
The screen shows an example of Voltage Harmonics measurement.
By pressing keys F1 (◄) or F3 (►), it is possible to move the
cursor over the graph and to select the harmonic to be measured. It is possible to measure up to the 25th harmonic, for fundamental frequencies between 10Hz and 75Hz, and up to the 8
th
harmonic for fundamental frequencies between 75Hz and
400Hz.
Par
Fnz
H01 215.0 V ThdV 10.0 %
19/01-17:00:00
5.3.2.3.1. Key F4 “Fnz” in Voltage Harmonics measurement
While measuring Voltage Harmonics, press key F4 (Fnz) to
open the drop-down menu shown on the screen to the side. At
each subsequent pressure of key F4, the cursor will scroll
through the available items, as follows:
Max: it constantly displays the maximum RMS value of the
selected current harmonic;
Min: it constantly displays the minimum RMS value of the
selected current harmonic;
Abs: it displays the absolute value of the harmonics in Volts;
Par OK Fnz
H01 215.0 V ThdV 10.0 %
19/01-17:00:00
Max
Min Abs % Rst Esc
Max
Min Cr+ Cr­Rst Esc
www. .com
Page 20
HT9022
EN - 18
%: it displays the value of the harmonics as percentage value with respect to the
fundamental;
Rst: it deletes all stored Max, Min values;
Esc: it goes back to a normal measuring mode.
Note: since the menu contains functions with a different meaning (Max-Min and Abs-%), it is necessary to enter the menu twice: once for displaying Abs or % values and another time to enable the Max or Min functions.
By pressing key F3 (OK), the selected item is confirmed.
To the side, an example of measurement with active Max function. The display shows the active function.
Par
Fnz
H01 215.0 V ThdV 10.0 %
Max
19/01-17:00:00
5.3.2.4. Hold
Short pressing key “H” activates the function Data HOLD. The display shows the message
H” and the screen of the measurement in progress is “frozen”.
This operating mode is deactivated when key “H” is pressed again or the switch is
operated.
5.3.2.5. Backlight
Long pressing key “H” activates or deactivates the display backlight. This function
automatically deactivates after approximately 10 seconds after being activated, in order not to discharge the batteries.
www. .com
Page 21
HT9022
EN - 19
5.3.3. Checking phase sequence and phase concordance with a lead
WARNING
While measuring, the instrument must be held in the operator’s hand.
Press key F1 (Mod) to open the drop-down menu shown on the screen to the side. At each subsequent pressure of key F1 (Mod), the cursor will scroll through the available items. Select “Ph Seq” and press key F4 (OK) to confirm the selected item.
Mod Par Ok
AC <10.0 Hz
---- V
19/01-17:00:00
5.3.3.1. Verification of Phase Sequence.
Fig. 7: verification of phase sequence
1. The instrument shows the screen here to the side, and waits
for the detection of phase L1.
2. Insert the red cable into input terminal V and connect the
red lead to phase L1 (Fig. 7).
Mod Go
Ph Seq
PH1
Wait
19/01-17:00:00
AC
DC Ph Seq Help Esc
www. .com
Page 22
HT9022
EN - 20
WARNING
If the frequency of the measured voltage is lower than 40Hz or higher than 70Hz, the display shows the message “F<40 Hz” or “F>70 Hz” and phase detection does not start.
3. When a voltage higher than or equal to 100V is detected, the
instrument gives an acoustic signal (buzzer) and the
message “Meas” is shown on the display. Do not press any
key and keep the test lead connected to L1 phase cable.
Mod Go
Ph Seq
PH1
Meas
19/01-17:00:00
4. Once phase L1 acquisition is complete, the displays shows
the screen here to the side. Disconnect the test lead from phase L1 cable.
Mod Go
Ph Seq
Discon.
Wait
19/01-17:00:00
5. The instrument shows the screen here to the side, and waits
for the detection of phase L2. Connect the test lead to phase L2 cable.
Mod Go
Ph Seq
PH2
Wait
19/01-17:00:00
WARNING
If more than 3 seconds elapse before detecting phase L2, the instrument
displays the message “Time Out”.
It is necessary to repeat the measuring cycle from the beginning, by
pressing key F4 (Go) and starting from step 1 again.
6. When a voltage higher than or equal to 100V is detected, the
instrument gives an acoustic signal (buzzer) and the
message “Meas” is shown on the display. Do not press any
key and keep the test lead connected to L2 phase cable.
Mod Go
Ph Seq
PH2
Meas
19/01-17:00:00
www. .com
Page 23
HT9022
EN - 21
7. If the two phases, to which the test lead has been connected,
are in the correct sequence, the instrument displays the screen here to the side. Should the phase sequence be
incorrect, the display shows “132”. To start a new measurement, press key F4 (Go).
Mod Go
Ph Seq
123
19/01-17:00:00
5.3.3.2. Verification of Phase Concordance
Fig. 8: verification of Phase Concordance
1. The instrument shows the screen here to the side, and waits
for the detection of phase L1.
2. Insert the red cable into input terminal V and connect the
red lead to phase L1 of the first sequence (Fig. 8).
Mod Go
Ph Seq
PH1
Wait
19/01-17:00:00
www. .com
Page 24
HT9022
EN - 22
3. When a voltage higher than or equal to 100V is detected, the
instrument gives an acoustic signal (buzzer) and the
message “Meas” is shown on the display. Do not press any
key and keep the test lead connected to L1 phase cable.
Mod Go
Ph Seq
PH1
Meas
19/01-17:00:00
4. Once phase L1 acquisition is complete, the displays shows
the screen here to the side. Disconnect the test lead from phase L1 cable.
Mod Go
Ph Seq
Discon.
Wait
19/01-17:00:00
5. The instrument shows the screen here to the side, and waits
for the detection of the second sequence of phase L1. Connect the test lead to phase L1 of the second sequence.
Mod Go
Ph Seq
PH2
Wait
19/01-17:00:00
WARNING
If more than 3 seconds elapse before detecting the phase L1 of the second
sequence, the instrument displays the message “Time Out”.
It is necessary to repeat the measuring cycle from the beginning, by
pressing key F4 (Go) and starting from step 1 again.
6. When a voltage higher than or equal to 100V is detected, the
instrument gives an acoustic signal (buzzer) and the
message “Meas” is shown on the display. Do not press any
key and keep the test lead connected to L1 phase cable of the second sequence.
Mod Go
Ph Seq
PH2
Meas
19/01-17:00:00
7. If there is concordance between the two phases, to which the
test lead has been connected, the instrument displays the
screen here to the side. Otherwise, it displays “123” or “132”. To start a new measurement, press key F4 (Go).
Mod Go
Ph Seq
11-
19/01-17:00:00
www. .com
Page 25
HT9022
EN - 23
5.4. POSITION “A ”: DC, AC+DC CURRENT MEASUREMENT
WARNING
The maximum measurable DC or AC+DC current is 1000A. When the display shows “> 999.9A”, it means that the maximum value the clamp is able to measure has been exceeded. Exceeding these limits could result in electrical shocks to the user and damage to the instrument. We recommend holding the clamp respecting the safety area created by the hand protection (see Fig. 3)
By positioning the selector switch to “A ”, the screen to the side
will appear.
Mod Par Fnz
AC <10.0 Hz
---- A
19/01-17:00:00
Press key F1 (Mod) to open the drop-down menu shown on the screen to the side. At each subsequent pressure of key F1, the
cursor will scroll through the available items, as follows:
AC: AC+DC voltage measurement;
DC: DC voltage measurement;
Help: it displays the connection between instrument and
system;
Esc: it closes the drop-down menu.
Mod Par OK
AC <10.0 Hz
---- A
19/01-17:00:00
Select the desired mode and press key F4 (OK) to confirm.
5.4.1. DC current measurement
Fig. 9: DC current measurement
WARNING
Insert the cable in the middle of the clamp jaws, in order to obtain accurate measures. Use the marks as a reference (see Fig. 2).
AC
DC
Help Esc
www. .com
Page 26
HT9022
EN - 24
The screen shows an example of DC current measurement.
Mod Par Fnz
DC
100.0 A
19/01-17:00:00
5.4.1.1. Key F4 “Fnz”
Press key F4 (Fnz) to open the drop-down menu shown on the screen to the side. At each subsequent pressure of key F4, the
cursor will scroll through the available items, as follows:
Max: it constantly displays the maximum value of DC current;
Min: it constantly displays the minimum selected value of DC
current;
Cr+: it constantly displays the maximum positive crest value;
Mod Par OK Fnz
DC
100.0 A
19/01-17:00:00
Cr-: it constantly displays the minimum negative crest value;
Zero: it zeroes the measured DC current;
Rst: it deletes all stored Max, Min, Cr+ and Cr- values;
Esc: it goes back to a normal measuring mode.
WARNING
Note:
carry out current zeroing before clamping the conductor;
the measurement of the 4 Max, Min, Cr+ and Cr- values is simultaneous,
regardless of the one displayed.
By pressing key F3 (OK), the selected item is confirmed.
To the side, an example of measurement with active Max function. The display shows the active function.
Mod Par Fnz
Max DC
100.0 A
19/01-17:00:00
5.4.1.2. Hold
Short pressing key “H” activates the function Data HOLD. The display shows the message
H” and the screen of the measurement in progress is “frozen”.
This operating mode is deactivated when key “H” is pressed again or the switch is
operated.
5.4.1.3. Backlight
Long pressing key “H” activates or deactivates the display backlight. This function
automatically deactivates after approximately 10 seconds after being activated, in order not to discharge the batteries.
Max
Min Cr+ Cr­Zero Rst Esc
www. .com
Page 27
HT9022
EN - 25
5.4.2. AC+DC current and Current Harmonics measurement
Fig. 10: AC+DC current measurement
WARNING
Insert the cable in the middle of the clamp jaws, in order to obtain accurate measures. Use the marks as a reference (see Fig. 2).
5.4.2.1. Key F2 “Par”
Press key F2 (Par) to open the drop-down menu shown on the screen to the side. At each subsequent pressure of key F2, the
cursor will scroll through the available items, as follows:
Current: it shows the measured current value;
Current Har: it shows the measured Current harmonics;
Esc: it closes the drop-down menu.
Select the desired parameter and press key F4 (OK) to confirm.
Mod Par OK
AC 50.0 Hz
100.0 A
19/01-17:00:00
5.4.2.2. AC+DC current
The screen shows an example of AC+DC current measurement.
Mod Par Fnz
AC 50.0 Hz
100.0 A
19/01-17:00:00
Current
Current Har
Esc
www. .com
Page 28
HT9022
EN - 26
5.4.2.2.1. Key F4 “Fnz” in AC+DC current measurement
While measuring Current, press key F4 (Fnz) to open the drop-
down menu shown on the screen to the side. At each
subsequent pressure of key F4, the cursor will scroll through the
available items, as follows:
Max: it constantly displays the maximum RMS value of
current;
Min: it constantly displays the minimum RMS value of
current;
Mod Par OK Fnz
AC 50.0 Hz
100.0 A
19/01-17:00:00
Cr+: it constantly displays the maximum positive crest value;
Cr-: it constantly displays the minimum negative crest value;
Zero: it zeroes the average value of the measured current;
Rst: it deletes all stored Max, Min, Cr+ and Cr- values;
Esc: it goes back to a normal measuring mode.
WARNING
Note: carry out current zeroing before clamping the conductor.
By pressing key F3 (OK), the selected item is confirmed.
To the side, an example of measurement with active Max function. The display shows the active function.
Mod Par Fnz
Max AC 50.0 Hz
100.0 A
19/01-17:00:00
5.4.2.3. Current harmonics
The screen shows an example of Current Harmonics measurement.
By pressing keys F1 (◄) or F3 (►), it is possible to move the
cursor over the graph and to select the harmonic to be measured. It is possible to measure up to the 25th harmonic, for fundamental frequencies between 10Hz and 75Hz, and up to the 8
th
harmonic for fundamental frequencies between 75Hz and
400Hz.
Par
Fnz
H01 100.0 A ThdI 10.0 %
19/01-17:00:00
5.4.2.3.1. Key F4 “Fnz” in Current Harmonics measurement
While measuring Current Harmonics, press key F4 (Fnz) to
open the drop-down menu shown on the screen to the side. At
each subsequent pressure of key F4, the cursor will scroll
through the available items, as follows:
Max: it constantly displays the maximum RMS value of the
selected current harmonic;
Min: it constantly displays the minimum RMS value of the
selected current harmonic;
Abs: it displays the value of the harmonics in Amperes;
Par OK Fnz
H01 100.0 A ThdI 10.0 %
19/01-17:00:00
Max
Min Abs % Rst Esc
Max
Min Cr+ Cr­Zero Rst Esc
www. .com
Page 29
HT9022
EN - 27
%: it displays the value of the harmonics as percentage value with respect to the
fundamental;
Rst: it deletes all stored Max and Min values;
Esc: it goes back to a normal measuring mode.
Note: since the menu contains functions with a different meaning (Max-Min and Abs-%), it is necessary to enter the menu twice: once for displaying Abs or % values and another time to enable the Max or Min functions.
By pressing key F3 (OK), the selected item is confirmed.
To the side, an example of measurement with active Max function. The display shows the active function.
Par
Fnz
H01 100.0 A ThdI 10.0 %
Max
19/01-17:00:00
5.4.2.4. Hold
Short pressing key “H” activates the function Data HOLD. The display shows the message
H” and the screen of the measurement in progress is “frozen”.
This operating mode is deactivated when key “H” is pressed again or the switch is
operated.
5.4.2.5. Backlight
Long pressing key “H” activates or deactivates the display backlight. This function
automatically deactivates after approximately 10 seconds after being activated, in order not to discharge the batteries.
www. .com
Page 30
HT9022
EN - 28
5.5. POSITION “W ”: DC, AC+DC POWER MEASUREMENT
WARNING
The maximum DC or AC+DC input voltage is 1000V and the maximum measurable DC or AC+DC current is 1000A. Do not measure voltages and currents exceeding the limits given in this manual. Exceeding these limits could result in electrical shocks to the user and damage to the instrument. We recommend holding the clamp respecting the safety area created by the hand protection (see Fig. 3)
By positioning the selector switch to “W ”, the screen to the
side will appear.
Mod Par Sys Fnz
AC <10.0 Hz
---- kW
---- kVari
---- kVA
1P
19/01-17:00:00
Press key F1 (Mod) to open the drop-down menu shown on the screen to the side. At each subsequent pressure of key F1, the
cursor will scroll through the available items, as follows:
AC 1P: measurement of AC Powers on single-phase system;
AC 3P: measurement of AC Powers on three-phase
balanced system;
DC: DC Power measurement;
Help: it displays the connection between instrument and
system;
Mod Par Sys OK
AC <10.0 Hz
---- kW
---- kVari
---- kVA
19/01-17:00:00
Esc: it closes the drop-down menu.
Select the desired measuring mode and press key F4 (OK) to confirm.
See par.9.1, 9.2 and 9.3 for details about calculation formulas.
AC 1P AC 3P
DC
Help Esc
www. .com
Page 31
HT9022
EN - 29
5.5.1. DC power measurement
Fig. 11: DC power measurement
Insert the red cable into input lead V and the black cable into input lead COM.
Position the red lead to “+” and the black lead to “-” and insert the “+” cable into the clamp jaws, respecting the direction of current indicated by the arrow (see Fig. 4)
ATTENZIONE
Insert the cable in the middle of the clamp jaws, in order to obtain accurate measures. Use the marks as a reference (see Fig. 2).
5.5.1.1. Key F2 “Par”
Press key F2 (Par) to open the drop-down menu shown on the screen to the side. At each subsequent pressure of key F2, the
cursor will scroll through the available items, as follows:
Power: it shows the measured Power value;
Volt-Curr: it displays the measured Voltage and Current
values;
Energy: it shows the measured energy value. This
measurement is only active when a recording is active (see par. 5.6.1.1).
Mod Par Sys OK
DC
0.40 kW
19/01-17:00:00
Esc: it closes the drop-down menu.
Select the desired parameter and press key F4 (OK) to confirm.
Power
Volt-Curr Energy Esc
www. .com
Page 32
HT9022
EN - 30
5.5.1.2. DC power
The screen to the side shows an example of DC power measurement.
Mod Par Sys Fnz
DC
0.40 kW
19/01-17:00:00
5.5.1.2.1. Key F4 “Fnz” in DC Power measurement
While measuring DC Power, press key F4 (Fnz) to open the
drop-down menu shown on the screen to the side. At each
subsequent pressure of key F4, the cursor will scroll through the
available items, as follows:
Max: it constantly displays the maximum value of the
measured parameter;
Min: it constantly displays the minimum value of the
measured parameter;
Rst: it deletes all stored Max and Min values;
Mod Par OK Fnz
DC
0.40 kW
19/01-17:00:00
Esc: it goes back to a normal measuring mode.
By pressing key F3 (OK), the selected item is confirmed.
To the side, an example of measurement with active Max function. The display shows the active function.
Mod Par Sys Fnz
Max DC
0.40 kW
19/01-17:00:00
5.5.1.3. DC voltage and current
The screen shows an example of DC Voltage and Current measurement.
Mod Par Sys Fnz
DC
80.0 V
20.0 A
19/01-17:00:00
Max
Min Rst Esc
www. .com
Page 33
HT9022
EN - 31
5.5.1.3.1. Key F4 “Fnz” in DC Voltage and Current measurement
While measuring Voltage and Current, press key F4 (Fnz) to
open the drop-down menu shown on the screen to the side. At
each subsequent pressure of key F4, the cursor will scroll
through the available items, as follows:
Max: it constantly displays the maximum value of the
measured parameter;
Min: it constantly displays the minimum value of the
measured parameter;
Cr+: it constantly displays the maximum positive crest value
Mod Par OK Fnz
DC
80.0 V
20.0 A
19/01-17:00:00
measured;
Cr-: it constantly displays the minimum negative crest value measured;
Zero: it zeroes the measured DC current;
Rst: it deletes all stored Max, Min, Cr+ and Cr- values;
Esc: it goes back to a normal measuring mode.
WARNING
Note: carry out current zeroing before clamping the conductor.
By pressing key F3 (OK), the selected item is confirmed.
To the side, an example of measurement with active Max function. The display shows the active function.
Mod Par Sys Fnz
Max DC
80.0 V
20.0 A
19/01-17:00:00
5.5.1.4. DC Energy
The screen shows an example of DC Energy measurement.
Mod Par Sys Fnz
DC
2.20 kWh
Log
19/01-17:00:00
5.5.1.5. Hold
Short pressing key “H” activates the function Data HOLD. The display shows the message
H” and the screen of the measurement in progress is “frozen”.
This operating mode is deactivated when key “H” is pressed again or the switch is
operated.
5.5.1.6. Backlight
Long pressing key “H” activates or deactivates the display backlight. This function
automatically deactivates after approximately 10 seconds after being activated, in order not to discharge the batteries.
Max
Min Cr+ Cr­Zero Rst Esc
www. .com
Page 34
HT9022
EN - 32
5.5.2. Measurement of AC 1P or AC 3P Powers
Fig. 12: measurement of AC 1P or AC 3P Powers
Insert the red cable into the input lead V and the black cable into the input lead COM,
and connect the instrument as described in Fig. 12.
WARNING
Insert the cable in the middle of the clamp jaws, in order to obtain accurate measures. Use the marks as a reference (see Fig. 2).
5.5.2.1. Key F2 “Par”
Press key F2 (Par) to open the drop-down menu shown on the screen to the side. At each subsequent pressure of key F2, the
cursor will scroll through the available items, as follows:
P-Q-S: it displays the measured values of Active, Reactive
and Apparent Power;
Pf-dPf: it displays the measured values of Power Factor and
Cosphi;
Voltage Harm: it shows the measured Voltage Harmonics;
Current Harm: it shows the measured Current Harmonics;
Mod Par Sys OK
AC <10.0 Hz
---- kW
---- kVari
---- kVA
19/01-17:00:00
Energy: it shows the measured energy value. This measurement is only active when a
recording is active (see par. 5.6.1.1).
Esc: it closes the drop-down menu.
Select the desired parameter and press key F4 (OK) to confirm.
P-Q-S
Pf-dPf Volt-Curr Voltage Har Current Har Energy Esc
www. .com
Page 35
HT9022
EN - 33
5.5.2.2. AC+DC power
The screen shows an example of AC+DC Power measurement.
Mod Par Sys Fnz
AC 50.0 Hz
21.47 kW
7.68 kVari
22.90 kVA
1P
19/01-17:00:00
5.5.2.3. Pf and dPf
The screen shows an example of Power Factor and Cosphi measurement.
Mod Par Sys Fnz
AC 50.0 Hz
Pf 0.94 i dPf 0.94 i
1P
19/01-17:00:00
5.5.2.3.1. Key F4 “Fnz” in Power or Pf-dPf measurement
While measuring Power or Pf-dPf, press key F4 (Fnz) to open
the drop-down menu shown on the screen to the side. At each
subsequent pressure of key F4, the cursor will scroll through the
available items, as follows:
Max: it constantly displays the maximum value of the
measured parameter;
Min: it constantly displays the minimum value of the
measured parameter;
Rst: it deletes all stored Max and Min values;
Mod Par OK Fnz
AC 50.0 Hz
21.47 kW
7.68 kVari
22.90 kVA
19/01-17:00:00
Esc: it goes back to a normal measuring mode.
By pressing key F3 (OK), the selected item is confirmed.
To the side, an example of measurement with active Max function. The display shows the active function.
Mod Par Sys Fnz
Max AC 50.0 Hz
21.47 kW
7.68 kVari
22.90 kVA
1P
19/01-17:00:00
Max
Min Rst Esc
www. .com
Page 36
HT9022
EN - 34
5.5.2.4. AC+DC Voltage and Current
The screen shows an example of AC+DC Voltage and Current measurement.
Mod Par Sys Fnz
AC 50.0 Hz
229.7 V
99.6 A
1P
19/01-17:00:00
5.5.2.4.1. Key F4 “Fnz” in AC Voltage and Current measurement
While measuring Voltage and Current, press key F4 (Fnz) to
open the drop-down menu shown on the screen to the side. At
each subsequent pressure of key F4, the cursor will scroll
through the available items, as follows:
Max: it constantly displays the maximum value of the
measured parameter;
Min: it constantly displays the minimum value of the
measured parameter;
Cr+: it constantly displays the maximum positive crest value
Mod Par OK Fnz
AC 50.0 Hz
229.7 V
99.6 A
19/01-17:00:00
measured;
Cr-: it constantly displays the minimum negative crest value measured;
Zero: it zeroes the average value of the measured current;
Rst: it deletes all stored Max, Min, Cr+ and Cr- values;
Esc: it goes back to a normal measuring mode.
WARNING
Note: carry out current zeroing before clamping the conductor.
By pressing key F3 (OK), the selected item is confirmed.
To the side, an example of measurement with active Max function. The display shows the active function.
Mod Par Sys Fnz
Max AC 50.0 Hz
229.7 V
99.6 A
1P
19/01-17:00:00
Max
Min Cr+ Cr­Zero Rst Esc
www. .com
Page 37
HT9022
EN - 35
5.5.2.5. Voltage harmonics
The screen shows an example of Voltage Harmonics measurement.
By pressing keys F1 (◄) or F3 (►), it is possible to move the
cursor over the graph and to select the harmonic to be measured. It is possible to measure up to the 25th harmonic, for fundamental frequencies between 10Hz and 75Hz, and up to the 8th harmonic for fundamental frequencies between 75Hz and 400Hz.
Par
Fnz
H05 2.3 V ThdV 2.4 %
19/01-17:00:00
5.5.2.6. Current harmonics
The screen shows an example of Current Harmonics measurement.
By pressing keys F1 (◄) or F3 (►), it is possible to move the
cursor over the graph and to select the harmonic to be measured. It is possible to measure up to the 25
th
harmonic, for fundamental frequencies between 10Hz and 75Hz, and up to the 8
th
harmonic for fundamental frequencies between 75Hz and
400Hz.
Par
Fnz
H05 2.9 A ThdI 10.7 %
19/01-17:00:00
5.5.2.6.1. Key F4 “Fnz” in Voltage and Current Harmonics measurement
While measuring Voltage or Current Harmonics, press key F4 (Fnz) to open the drop-down menu shown on the screen to the side. At each subsequent pressure of key F4, the cursor will
scroll through the available items, as follows:
Max: it constantly displays the maximum RMS value of the
selected current or voltage harmonic;
Min: it constantly displays the minimum RMS value of the
selected current or voltage harmonic;
Abs: it displays the value of the harmonics in Amperes or
Volts;
Par OK Fnz
H01 100.0 A ThdI 10.0 %
19/01-17:00:00
%: it displays the value of the harmonics as percentage value with respect to the
fundamental;
Rst: it deletes all stored Max and Min values;
Esc: it goes back to a normal measuring mode.
Note: since the menu contains functions with a different meaning (Max-Min and Abs-%), it is necessary to enter the menu twice: once for displaying Abs or % values and another time to enable the Max or Min functions.
By pressing key F3 (OK), the selected item is confirmed.
To the side, an example of measurement with active Max function. The display shows the active function.
Par
Fnz
H01 100.0 A ThdI 10.0 %
Max
19/01-17:00:00
Max
Min Abs % Rst Esc
www. .com
Page 38
HT9022
EN - 36
5.5.2.7. AC Energy
The screen shows an example of AC Energy measurement. The values of Active Energy, Reactive Energy, Inductive Energy and Capacitive Reactive Energy are shown.
Mod Par Sys Fnz
AC 50.0 Hz
2.24 kWh
0.84 kVarih
0.00 kVarch
Log 1P
19/01-17:00:00
5.5.2.8. Hold
Short pressing key “H” activates the function Data HOLD. The display shows the message
H” and the screen of the measurement in progress is “frozen”.
This operating mode is deactivated when key “H” is pressed again or the switch is
operated.
5.5.2.9. Backlight
Long pressing key “H” activates or deactivates the display backlight. This function
automatically deactivates after approximately 10 seconds after being activated, in order not to discharge the batteries.
www. .com
Page 39
HT9022
EN - 37
5.6. POSITION “W ”: LOG, ON-LINE SCOPE, SNAPSHOT, MEMORY, DOWNLOAD
WARNING
The maximum DC or AC+DC input voltage is 1000V and the maximum measurable DC or AC+DC current is 1000A. Do not measure voltages and currents exceeding the limits given in this manual. Exceeding these limits could result in electrical shocks to the user and damage to the instrument. We recommend holding the clamp respecting the safety area created by the hand protection (see Fig. 3).
Turn the rotary switch to “W ”. Insert the red cable into the input lead V and the black cable into the input lead COM, and connect the instrument as described in Fig. 12
WARNING
Insert the cable in the middle of the clamp jaws, in order to obtain accurate measures. Use the marks as a reference (see Fig. 2).
5.6.1. Key F3 “Sys”
While measuring DC, AC 1P or AC 3P Power, press key F3 (Sys) to open the drop-down menu shown on the screen to the side. At each subsequent pressure of key F3, the cursor will
scroll through the available items, as follows:
Start Log: it starts a recording of the electrical mains
parameters;
On-line: it starts a Bluetooth On-Line Scope;
Memory: it shows the list of the saved data;
SnapShot: it carries out an instant saving of the measured
Mod Par Sys OK
AC 50.0 Hz
21.47 kW
7.68 kVari
22.90 kVA
19/01-17:00:00
parameters;
Download: it sets to the mode for downloading the data saved in the memory;
Esc: it closes the drop-down menu.
By pressing key F4 (OK), the selected item is confirmed.
The electrical parameters recorded during a Recording, transmitted during an On-Line Scope or saved in a SnapShot, according to the mode set, are the following:
AC 1P:AC 1P: P, Q, S, pF, dPf, V, I, THDV, THDI, hV01..hVxx (xx=25 for fundamental
frequency 10..75Hz; xx=8 for fundamental frequency 75..400Hz);
AC 3P: P, Q, S, pF, dPf, V, I, THDV, THDI, hV01..hVxx (xx=25 for fundamental
frequency 10..75Hz; xx=8 for fundamental frequency 75..400Hz);
DC: P, V, I.
5.6.1.1. “Start Log” recording
Upon confirming the “Start Log” item, the instrument sets to
stand-by and waits for a recording to start. A recording shall be started when reaching the following minute as indicated by the instrument’s time.
The message “Wait” is displayed.
Mod Par Sys Fnz
AC 50.0 Hz
21.47 kW
7.68 kVari
22.90 kVA
Wait 1P
19/01-17:00:35
Start Log
Online Memory SnapShot Download Esc
www. .com
Page 40
HT9022
EN - 38
WARNING
When a recording is in progress, if the selector switch of the clamp is moved to any other position, the recording shall be interrupted. In the memory, you will find the values stored up to that moment.
While recording, the display shows the message “Log” and keys F2 (Par) and F4 (Fnz) are active, which give the possibility of
displaying the parameters or enabling the functions seen in the previous paragraphs.
Mod Par Sys Fnz
AC 50.0 Hz
21.47 kW
7.68 kVari
22.90 kVA
Log 1P
19/01-17:01:00
While recording, press key F3 (Sys) to open the drop-down
menu shown in the screen to the side. At each subsequent
pressure of key F3, the cursor will scroll through the available
items, as follows:
Stop Log: it stops the recording in progress;
Info: it shows some information about the recording in
progress;
Esc: it closes the drop-down menu. By pressing key F4 (OK), the selected item is confirmed.
Mod Par Sys OK
AC 50.0 Hz
21.47 kW
7.68 kVari
22.90 kVA
Log
19/01-17:01:00
On the right, an example of the screen which is displayed when
the item Info is selected. It shows:
Start: starting date and time of recording;
Int. Period: the integration period set (see par. 5.2.3);
N. Periods: number of periods recorded;
Auton.: memory autonomy expressed in days/hours.
Pressing key F4 (Esc) goes back to the parameter measuring
screen.
Esc
Start: 19/01-17:01:00 Int.Period: 1 N.Periods:00025 Auton: 00d/02h
19/01-17:01:25
5.6.1.2. On-line
Upon confirming the “On-line” item, the instrument sets to
Bluetooth transmission mode; the display shows the message
Onl.”. Keys F2 (Par) and F4 (Fnz) are active, which give the possibility
of displaying the parameters or enabling the functions seen in the previous paragraphs.
Mod Par Sys Fnz
AC 50.0 Hz
21.47 kW
7.68 kVari
22.90 kVA
Onl.. 1P
19/01-17:00:35
WARNING
When an on-line transmission is in progress, if the selector switch of the clamp is moved to any other position, the transmission shall be interrupted.
Stop Log
Info Esc
www. .com
Page 41
HT9022
EN - 39
During a Bluetooh transmission, press key F3 (Sys) to open the
drop-down menu shown in the screen to the side. At each
subsequent pressure of key F3, the cursor will scroll through the
available items, as follows:
Stop: it stops the transmission in progress;
Esc: it closes the drop-down menu.
By pressing key F4 (OK), the selected item is confirmed.
Mod Par Sys OK
AC 50.0 Hz
21.47 kW
7.68 kVari
22.90 kVA
Onl.
19/01-17:01:00
5.6.1.3. Memory
Upon confirming the “Memory” item, the instrument shows the
screen here to the side.
The screen lists the recordings (L) with starting date and time and SnapShots (S) with saving date and time.
The residual memory autonomy is shown, expressed in days(d) / hours(h), according to the integration period set (see par. 5.2.3).
Del OK Esc
S01:01/01-10:41:28 S02:01/01-10:41:35 L03:01/01-10:45:00 S04:02/01-12:05:11 L05:02/01-14:00:00 Auton: 00d/02h
19/01-17:00:35
Each page lists 5 memory locations; by pressing key F1 (), it is possible to scroll through
the following pages.
Press key F2 (Can) to open the drop-down menu shown on the screen to the side. At each subsequent pressure of key F2, the
cursor will scroll through the available items, as follows:
Del. Tot.: it deletes all Recordings (L) and Snapshots (S)
saved in the memory;
Del. Last: it deletes the last information saved in the
memory.
When pressing key F3 (OK) once, the display shows the message “Delete?”; pressing key F3 again confirms the selected
item.
Del OK Esc
S01:01/01-10:41:28 S02:01/01-10:41:35 L03:01/01-10:45:00 S04:02/01-12:05:11 L05:02/01-14:00:00 Auton: 00d/02h
Delete?
19/01-17:00:35
By pressing key F4 (Esc) once, the selected item is not confirmed. Pressing key F4 again
goes back to the parameter measuring screen.
5.6.1.4. SnapShot
Upon confirming the “SnapShot” item, the instrument instantly saves the measured parameters and shows the message “Mem Ok” on the display for 1 second, to confirm that saving has been
carried out.
Mod Par Sys Fnz
AC 50.0 Hz
21.47 kW
7.68 kVari
22.90 kVA
Mem Ok 1P 19/01-17:00:35
Stop
Esc
Del.Tot.
Del.Last
www. .com
Page 42
HT9022
EN - 40
5.6.1.5. Download
Upon confirming the “Download” item, the instrument sets to the
mode for downloading the data saved in the memory and shows the screen to the side.
Pressing key F4 (Esc) goes back to the parameter measuring
screen.
Esc
Download
19/01-17:00:35
www. .com
Page 43
HT9022
EN - 41
5.7. POSITION ”: RESISTANCE AND CONTINUITY MEASUREMENT
WARNING
Before attempting any resistance measurement, remove power from the circuit under test and discharge all capacitors, if present.
By positioning the selector switch to “ ”, the screen to the side will appear.
Mod OK Fnz
> 60.0 k
19/01-17:00:00
Fig. 13: resistance measurement
Insert the red cable into the input lead V and the black cable into the input lead COM,
and connect the instrument as described in Fig. 13.
Press key F1 (Mod) to open the drop-down menu shown on the screen to the side. At each subsequent pressure of key F1, the
cursor will scroll through the available items, as follows:
Resistance: resistance measurement;
Continuity: continuity measurement;
Help: it displays the connection between instrument and
system;
Esc: it closes the drop-down menu.
Mod OK Fnz
> 60.0 k
19/01-17:00:00
Select the desired mode and press key F3 (OK) to confirm.
Resistance
Continuity Help Esc
www. .com
Page 44
HT9022
EN - 42
The screen shows an example of Resistance measurement.
Mod OK Fnz
50.0 k
19/01-17:00:00
The screen shows an example of Continuity measurement. If the measured resistance is lower than the limit resistance value set (see par. 5.2.5) shown below (Lim Res: 1), the Buzzer sounds continuously.
Mod OK Fnz
0.3
Res Lim: 1
19/01-17:00:00
5.7.1. Key F4 “Fnz”
While measuring Resistance or Continuity, press key F4 (Fnz) to
open the drop-down menu shown on the screen to the side. At
each subsequent pressure of key F4, the cursor will scroll
through the available items, as follows:
Max: it constantly displays the maximum resistance value
measured;
Min: it constantly displays the minimum resistance value
measured;
Mod OK Fnz
50.0 k
19/01-17:00:00
Rst: it deletes all stored Max and Min values;
Esc: it goes back to a normal measuring mode.
By pressing key F3 (OK), the selected item is confirmed.
To the side, an example of measurement with active Max function. The display shows the active function.
Mod OK Fnz
Max
50.0 k
19/01-17:00:00
5.7.1.1. Hold
Short pressing key “H” activates the function Data HOLD. The display shows the message
H” and the screen of the measurement in progress is “frozen”.
This operating mode is deactivated when key “H” is pressed again or the switch is
operated.
5.7.1.2. Backlight
Long pressing key “H” activates or deactivates the display backlight. This function
automatically deactivates after approximately 10 seconds after being activated, in order not to discharge the batteries.
Max
Min Rst Esc
www. .com
Page 45
HT9022
EN - 43
5.8. POSITION “INRUSH A ”: INRUSH CURRENT MEASUREMENT
WARNING
The maximum measurable DC or AC+DC current is 1000A. Do not
measure currents exceeding the limits given in this manual. Exceeding these limits could result in electrical shocks to the user and damage to the instrument.
We recommend holding the clamp respecting the safety area created by
the hand protection (see Fig. 3).
Currents <3A are zeroed.
By positioning the selector switch to “InRush A ”, the screen to
the side will appear. The display shows the current settings for recording inrush currents (see par. 5.2.4).
Mod Zero Run Mem
50Hz 01/10
10 A
Fix 15A 1/1
19/01-17:00:00
Fig. 14: inrush current measurement
Press key F1 (Mod) to open the drop-down menu shown on the screen to the side. At each subsequent pressure of key F1, the
cursor will scroll through the available items, as follows:
50Hz: 50Hz inrush current measurement;
60Hz: 60Hz inrush current measurement;
400Hz: 400Hz inrush current measurement;
DC: DC inrush current measurement;
Mod Zero Run OK
50Hz 01/10
10 A
Fix 15A 1/1
19/01-17:00:00
Help: it displays the connection between instrument and
system;
Esc: it closes the drop-down menu.
Select the desired mode and press key F4 (OK) to confirm.
50Hz
60Hz 400Hz DC Help Esc
www. .com
Page 46
HT9022
EN - 44
5.8.1. Virtual key “Zero” By pressing key F2 (Zero), the average value of measured current is zeroed.
WARNING
Note: carry out current zeroing before clamping the conductor.
5.8.2. Key F3 “Run”
WARNING
For any frequency of 50Hz, 60Hz and DC, 32 samples are taken in each half­period for 100 half-periods, while for a frequency of 400Hz 8 samples are taken every half-period for 100 half-periods. In Fix mode, the event is detected when the RMS value of the current exceeds the set current threshold value. In Var mode, the event is detected when the difference between the RMS value of a half-period and that of the previous one exceeds the set current threshold value. The maximum number of events which can be saved in a single campaign is 10 and the maximum number of storable recordings is 20.
Pressing key F3 (Run) starts an inrush current recording and the indication relevant to key F3 turns into Stp. On the right, a
sample screen, which contains:
the message “Log”, to indicate that recording is in progress;
indication “03/10”, relevant to the last detected event;
indication of date/time and current value reached by the last
detected event.
By pressing key F3 (Stp) again, recording is stopped and the
data are stored in the memory.
Mod Zero Stp Mem
50Hz 03/10
24/01-16:30:49
19 A
Fix 15A 1/1
Log
24/01-16:30:50
If 10 events are detected while recording, recording is automatically stopped.
5.8.3. Key F4 “Mem”
By pressing key F4 (Mem), the screen to the side appears,
which lists the Inrush Currents saved in the memory. Each displayed page lists 5 memory locations and, by pressing
key F1 (), it is possible to scroll through each single location.
Del OK Esc
I01:24/01-16:23:13
I02:24/01-16:26:23 I03:24/01-16:30:47 I04:24/01-16:53:38 I05:24/01-17:06:45
25/01-17:05:00
Press key F2 (Can) to open the drop-down menu shown on the screen to the side. At each subsequent pressure of key F2, the
cursor will scroll through the available items, as follows:
Del. Tot.: it deletes all InRush current data saved in the
memory;
Del. Last: it deletes the last information saved in the
memory.
When pressing key F3 (OK) once, the display shows the message “Delete?”; pressing key F3 again confirms the
selected item.
Del OK Esc
I01:24/01-16:23:13
I02:24/01-16:26:23 I03:24/01-16:30:47 I04:24/01-16:53:38 I05:24/01-17:06:45
25/01-17:05:00
Del.Tot.
Del.Last
www. .com
Page 47
HT9022
EN - 45
By pressing key F4 (Esc) once, the selected item is not confirmed. Pressing key F4 again
takes you back to the Inrush Current measuring screen.
Pressing key F3 (OK) shows the trend of inrush current relevant
to the selected memory location. It shows:
starting date/time of the recorded event;
maximum current value reached during the event;
number of the event relevant to the measuring campaign;
measuring modes set relevant to the measuring campaign;
the number of the selected location.
Can OK Esc
24/01-16:30:47 19A 1/10
Fix 15A 1/1
Irc03
25/01-17:05:00
By pressing key F1 (▼), it is possible to display the other events relevant to the selected
campaign.
Pressing key F4 (Esc) goes back to the list of the Inrush Currents saved in the memory
(see par. 5.8.3).
www. .com
Page 48
HT9022
EN - 46
6. MAINTENANCE
6.1. GENERAL INFORMATION
1. The instrument you purchased is a precision instrument. While using and storing the
instrument, carefully observe the recommendations listed in this manual in order to prevent possible damage or danger during use.
2. Do not use the instrument in environments with high humidity levels or high
temperatures. Do not expose to direct sunlight.
3. Always switch off the instrument after use. In case the instrument is not to be used for
a long time, remove the batteries to avoid liquid leaks that could damage the instrument’s internal circuits.
6.2. BATTERY REPLACEMENT
WARNING
Only expert and trained technicians should perform this operation. Before carrying out this operation, make sure you have removed all cabled from the input leads or the cable being tested from inside the clamp jaw.
1. Turn the rotary switch to the OFF position.
2. Disconnect the cabled from the input leads and the cable being tested from the clamp
jaw.
3. Loosen the battery cover fastening screw and remove the cover.
4. Remove the flat batteries from the battery compartment.
5. Insert two new batteries of the same type (1.5V LR 03 AAA). Pay attention to the
correct polarity.
6. Position the battery cover back over the compartment and fasten it with the relevant
screw.
7. Do not scatter old batteries into the environment. Use the relevant containers for
disposal.
6.3. CLEANING THE INSTRUMENT
Use a soft and dry cloth to clean the instrument. Never use wet cloths, solvents, water, etc.
6.4. END OF LIFE
WARNING: the symbol on the instrument indicates that the appliance and its
accessories must be collected separately and correctly disposed of.
www. .com
Page 49
HT9022
EN - 47
7. TECHNICAL SPECIFICATIONS
7.1. TECHNICAL CHARACTERISTICS
Uncertainty is indicated as [% of reading + digit number]. It is referred to the following reference conditions: temperature 23°C ± 5°C with relative humidity < 80%.
DC voltage
Range Resolution Uncertainty
Protection against
overcharge
0.5 ÷ 999.9V
0.1V
±
(1.0%rdg+4dgt)
1000VDC/ACrms
Input impedance: 2.6M
AC Voltage (AC+DC TRMS)
Range Resolution
Uncertainty
Protection against
overcharge
43 ÷ 63Hz 10 ÷ 47Hz, 63 ÷ 400Hz
1000VDC/ACrms
0.5 ÷ 999.9V
0.1V
±(1.0%rdg+3dgt)
±
(3.5%rdg+3dgt)
Input impedance: 2.6MΩ; Max. Crest Factor: 1.41
AC/DC voltage: MAX / MIN / CREST
Function Range Resolution Uncertainty Response time
MAX,MIN,CREST
0.5 ÷ 999.9V
0.1V
±
(3.5%rdg+5dgt)
1sec
Input impedance: 2.6MΩ; Max. Crest Factor: 1.41
DC current
Range Resolution Uncertainty
Protection against
overcharge
0.5 ÷ 999.9A
0.1A
±
(2.0%rdg+5dgt)
2000ADC/ACrms
AC current (AC+DC TRMS)
Range Resolution
Uncertainty
Protection against
overcharge
43 ÷ 63Hz 10 ÷ 47Hz, 63 ÷ 400Hz
2000ADC/ACrms
0.5 ÷ 999.9A
0.1A
±(2.0%rdg+4dgt)
±
(3.5%rdg+5dgt)
Max. Crest Factor: 3
Corrente AC/DC:AC/DC current: MAX / MIN / CREST
Function Range Resolution Uncertainty Response time
MAX,MIN,CREST
0.5 ÷ 999.9A
0.1A
±
(3.5%rdg+5dgt)
1sec
Max. Crest Factor: 3
Resistance and Continuity test
Range Best resolution Uncertainty
Protection against
overcharge
0.0÷ 59.9k 0.1Ω
±
(1.0%rdg+5dgt)
1000VDC/ACrms x 60s
Frequency (with test leads/ with jaws)
Range Resolution Uncertainty
Protection against
overcharge
10.0 ÷ 99.9Hz
0.1Hz
±(1.0%rdg+5dgt)
1000VDC/ACrms 2000ADC/ACrms
100 ÷ 400Hz
1Hz
Voltage range for frequency measure: 0.5 ÷ 1000V / Current range for frequency measure with jaws: 0.5 ÷ 1000A
DC power
Ra n g e [kW] Resolution [kW] Uncertainty
0.00 ÷ 99.99
0.01
±(3.0%rdg+3dgt)
100.0 ÷ 999.9
0.1
Uncertainty defined for: Voltage > 10V, Current ≥ 2A
Active Power, Apparent power:
Range [kW], [kVA] Resolution [kW], [kVA] Uncertainty
0.00 ÷ 99.99
0.01
±(2.0%rdg+3dgt)
100.0 ÷ 999.9
0.1
Uncertainty defined for: sine waveform 10..65Hz, Voltage > 10V, Current 2A, Pf 0.5
www. .com
Page 50
HT9022
EN - 48
Range [kW], [kVA] Resolution [kW], [kVA] Uncertainty
0.00 ÷ 99.99
0.01
±(3.0%rdg+3dgt)
100.0 ÷ 999.9
0.1
Uncertainty defined for: sine waveform > 65Hz, Voltage > 10V, Current 5A, Pf 0.5
Active Energy
Ra n g e [kWh] Resolution [kWh] Uncertainty
0.00 ÷ 99.99
0.01
±(2.0%rdg+3dgt)
100.0 ÷ 999.9
0.1
Uncertainty defined for: sine wave 10..65Hz, Voltage > 10V, Current 2A, Pf 0.5
Ra n g e [kWh] Resolution [kWh] Uncertainty
0.00 ÷ 99.99
0.01
±(3.0%rdg+3dgt)
100.0 ÷ 999.9
0.1
Uncertainty defined for: sine waveform > 65Hz, Voltage > 10V, Current 5A, Pf 0.5
Reactive Power
Ra n g e [kVAR] Resolution [kVAR] Uncertainty
0.00 ÷ 99.99
0.01
±(2.0%rdg+3dgt)
100.0 ÷ 999.9
0.1
Uncertainty defined for: sine wave 10..65Hz, Voltage > 10V, Current 2A, 0.992 Pf 0.5
Ra n g e [kVAR] Resolution [kVAR] Uncertainty
0.00 ÷ 99.99
0.01
±(3.0%rdg+3dgt)
100.0 ÷ 999.9
0.1
Uncertainty defined for: sine waveform > 65Hz, Voltage > 10V, Current 5A, 0.992 Pf 0.5
Reactive Energy
Ra n g e [kVARh] Resolution [kVARh] Uncertainty
0.00 ÷ 99.99
0.01
±(2.0%rdg+3dgt)
100.0 ÷ 999.9
0.1
Uncertainty defined for: sine wave 10..65Hz, Voltage > 10V, Current 2A, 0.992 Pf 0.5
Ra n g e [kVARh] Resolution [kVARh] Uncertainty
0.00 ÷ 99.99
0.01
±(3.0%rdg+3dgt)
100.0 ÷ 999.9
0.1
Uncertainty defined for: sine waveform > 65Hz, Voltage > 10V, Current 5A, 0.992 Pf 0.5
Power factor
Range Resolution Uncertainty
0.20 ÷ 1.00
0.01
±
Uncertainty defined for: sine waveform 10..65Hz, Voltage > 10V, Current 2A Uncertainty defined for: sine waveform > 65Hz, Voltage > 10V, Current 5A
Voltage and Current harmonics
Harmonic order Frequency [Hz] Resolution [V], [A] Uncertainty
1 ÷ 25 10 ÷ 75
0.1
±(5.0%rdg+5dgt)
1 ÷ 8 75 ÷ 400
Phase sequence and 1-lead phase coincidence
Range Input impedance
100 ÷ 1000V 1.3MΩ
Frequency range: 40..70Hz. (*) Measurement carried out under the following standard conditions: instrument firmly held in the hand, standard shoes, standard floor,
etc.
www. .com
Page 51
HT9022
EN - 49
7.1.1. Safety standards
Compliant with Standards: IEC / EN61010-1, IEC / EN61010-2 – 032 Technical documentation: IEC/EN61187 Safety of measuring accessories: IEC/EN61010-31 Insulation: Class 2, double insulation Pollution level: 2 Max height: 2000m, indoor use Overvoltage category: CAT IV 600V / CAT III 1000V to earth, max 1000V between
inputs
7.1.2. General characteristics Characteristics of radio module
Radio: Bluetooth V2.0 Frequency: 2.4 GHz (2400-2483.5MHz) Power: Class 2 Data rate: 57600 baud
Memory
Internal memory: 2Mbytes
Recordings
N°. max Log + Snapshot stores: 99 N°. max InRush stores: 20 (each with max 10 events)
Mechanical characteristics
Size: 252 (L) x 88 (W) x 44 (H) mm; 9.92 x 3.46 x 1.73 in Weight (batteries included): approx 420g; 14.8 ounces Jaw opening / Max cable size: 45mm; 1.77 in
Power supply
Battery type: 2 batteries x 1.5V LR 03 AAA Battery life: approx. 53 hours of use in “W ” position Auto power OFF: 5 min. with enabled function The display shows the following
symbol “
Display
Characteristics: graphic display 128x128 pixels Sampling rate: 128 samples per period (base sampling) Updating frequency: 1/s
7.2. ENVIRONMENT
7.2.1. Environmental conditions for use
Reference calibration temperature: 23° ± 5 °C Operating temperature: 0 ÷ 40 °C Allowable relative humidity: < 80% Storage temperature: -10 ÷ 60 °C Storage humidity: < 70%
This instrument satisfies the requirements of Low Voltage Directive 2006/95/EEC
(LVD) and of EMC Directive 2004/108/EEC
7.3. ACCESSORIES PROVIDED
Instrument
Pair of test leads
Pair of alligator clips
ISO9000 calibration certificate
User manual
Bag
Batteries
www. .com
Page 52
HT9022
EN - 50
8. SERVICE
8.1. WARRANTY CONDITIONS
This instrument is warranted against any material or manufacturing defect, in compliance with the general sales conditions. During the warranty period, defective parts may be replaced. However, the manufacturer reserves the right to repair or replace the product.
The warranty shall not apply in the following cases:
Repair and/or replacement of accessories and batteries (not covered by warranty).
Repairs that may become necessary as a consequence of an incorrect use of the
instrument or due to its use together with non-compatible appliances.
Repairs that may become necessary as a consequence of improper packaging.
Repairs which may become necessary as a consequence of interventions performed
by unauthorized personnel.
Modifications to the instrument performed without the manufacturer’s explicit
authorization.
Use not provided for in the instrument’s specifications or in the instruction manual.
The content of this manual cannot be reproduced in any form without the manufacturer’s authorization.
Our products are patented and our trademarks are registered. The manufacturer
reserves the right to make changes in the specifications and prices if this is due to improvements in technology.
8.2. SERVICE
If the instrument does not operate properly, before contacting the After-sales Service, please check the conditions of batteries and cables and replace them, if necessary. Should the instrument still operate improperly, check that the product is operated according to the instructions given in this manual.
Should the instrument be returned to the After-sales Service or to a Dealer, transport will be at the Customer’s charge. However, shipment will be agreed in advance. A report will always be enclosed to a shipment, stating the reasons for the product’s return. Only use original packaging for shipment; any damage due to the use of non-original packaging material will be charged to the Customer.
www. .com
Page 53
HT9022
EN - 51
9. APPENDIX – THEORETICAL OUTLINE
9.1. CALCULATION OF POWERS IN “AC 1P” MODE
The instrument measures the values of Rms Voltage and Rms Current and calculates the average Power values for each period. The formulas for power calculation are:
=
××=
N
i
ii
iv
N
P
1
1
==
×××=
N
i
i
N
i
i
i
N
v
N
S
1
2
1
2
11
22
PSQ =
S
P
Pf =
where: N = number of samples in the period
9.2. CALCULATION OF POWERS IN “AC 3P” MODE
The instrument measures the values of Rms Voltage and Rms Current and calculates the average Power values for each period. The formulas for power calculation are:
=
×××=
N
i
ii
iv
N
Q
1
1
3
==
××××=
N
i
i
N
i
i
i
N
v
N
S
1
2
1
2
11
3
22
QSP =
S
P
Pf =
where: N = number of samples in the period
9.3. CALCULATION OF POWERS IN “DC” MODE
The instrument measures the values of Avg Voltage and Avg Current and calculates the average Power value for each period. The formula for power calculation is:
⎟ ⎠
××
⎟ ⎠
⎜ ⎝
×=
==
N
i
i
N
i
i
i
N
v
N
P
11
11
www. .com
Page 54
HT9022
EN - 52
9.4. VOLTAGE AND CURRENT HARMONICS
Any periodic non-sinusoidal wave may be represented by a sum of sinusoidal waves, each with a frequency which is a whole multiple of the fundamental, according to the relationship:
)tsin(VVv(t)
kk
1k
k0
ϕω
++=
=
(1)
where: V0 = Average value of v(t) V1 = Amplitude of the fundamental of v(t) Vk = Amplitude of the k-nth harmonic of v(t)
CAPTION:
1. Fundamental
2. Third Harmonic
3. Distorted waveform sum of two previous components.
Effect of the sum of 2 multiple frequencies.
For network voltage, the fundamental has a frequency of 50 Hz, the second harmonic has
a frequency of 100 Hz, the third harmonic has a frequency of 150 Hz and so on. Harmonic
distortion is a continuous problem and must not be confused with short-duration phenomena such as peaks, drops or fluctuations. It can be seen from (1) that each signal consists of the summation of infinite harmonics. However, an order number exists beyond which the value of the harmonics may be considered as negligible. Standard EN 50160 suggests cutting the summation in the
expression (1) at the 40th harmonic.
A fundamental index to detect the presence of harmonics is the THD defined as:
1
40
2
2
V
V
THDv
h
h
=
=
This index takes into consideration the presence of all harmonics, and the more distorted is the waveform, the higher is the index.
www. .com
Page 55
HT9022
EN - 53
9.5. LIMIT VALUES FOR HARMONICS
Standard EN-50160 prescribes the limits for the Voltage Harmonics the Energy Provider may introduce into the network. In normal operating conditions, at any time in a week, 95% of the efficient values of each harmonic voltage, averaged to 10 minutes, must be lower than or equal to the values indicated in the following Table. The total harmonic distortion (THD%) of supply voltage (including all harmonics up to the 40th order) must be lower than or equal to 8%.
Odd Harmonics Even Harmonics
Not multiple of 3 Multiple of 3
Order h
Relative
Voltage %Max
Order h Relative Voltage %Max Order h Relative Voltage %Max
5 6 3 5 2 2
7 5 9 1,5 4 1 11 3,5 15 0,5 6..24 0,5 13 3 21 0,5 17 2 19 1,5 23 1,5 25 1,5
These limits, which theoretically apply only to Electric Power Suppliers, anyway provide a series of reference values within which also the harmonics put into network by users should be kept.
9.6. CAUSES OF THE PRESENCE OF HARMONICS
Any appliance altering the sinusoidal wave or simply using a part of such wave causes distortions to the sinusoid, and hence harmonics. All current signals are therefore someway virtually distorted. The most common distortion is the harmonic distortion caused by non-linear loads such as household appliances, personal computers or motor speed adjusters. Harmonic distortion generates significant currents at frequencies which are whole multiples of network voltage. Harmonic currents have a remarkable effect on neutral conductors of electrical systems. In most countries, the network voltage used is three-phase 50/60Hz, supplied by a transformer with triangle-connected primary circuit and star-connected secondary circuit. The secondary circuit generally generates 230V AC between phase and neutral and 400V AC between phase and phase. Balancing loads for each phase has always been a problem electrical system designers. Until approximately ten years ago, in a well balanced system, the vector sum of the currents in the neutral was zero or anyway quite low (given the difficulty of obtaining a perfect balance). Connected devices were incandescent lights, small motors and other devices that presented linear loads. The result was an essentially sinusoidal current in each phase and a low current on the neutral at a frequency of 50/60Hz. “Modern” devices such as TV sets, fluorescent lights, video machines and microwave ovens normally draw current for only a fraction of each cycle, thus causing non-linear loads and, consequently, non-linear currents. All this generates odd harmonics of the 50/60Hz line frequency. For this reason, nowadays the current in the transformers of the distribution boxes contains not only a 50Hz (or 60Hz) component, but also a 150Hz (or 180Hz) component, a 250Hz (or 300Hz) component and other significant harmonic components up to 750Hz (or 900Hz) and above. The vector sum of the currents in a well balanced system that feeds non-linear loads may still be quite low. However, the sum does not eliminate all harmonic currents. The odd multiples of the third harmonic (called “TRIPLENS”) are added together in the neutral conductor and can cause overheating even with balanced loads.
www. .com
Page 56
HT9022
EN - 54
9.7. CONSEQUENCE OF THE PRESENCE OF HARMONICS
Generally, harmonics of even, 2nd, 4th etc. order do not create problems. Designers must consider the following points when designing a power distribution system containing harmonic currents:
Installation parts Effects attributed to Harmonics
Fuses
Non-uniform heating of internal fuse element and consequent overheating which can also lead to an explosion of the fuse casing.
Cables
Increase in “body” effect; this means that, for cables with many wires, the internal wires have higher impedance than the external wires. As a consequence, current, which normally distributes along the external surface of the wire, produces: – over-heating of the conductor; – a premature degrading of the cable’s insulation; – an increase in line voltage drop.
Neutral conductor
Triple harmonics, odd multiple of three, sum on neutral (instead of nullifying themselves), thus generating a potentially dangerous overheating of the conductor.
Transformers
Increase in copper loss due to a higher TRMS value of the current that circulates on internal circuits, and also due to the “body” effect on protected wires. Increase of iron loss due to hysteresis cycle distortion and due to the generation of leakage currents on the magnetic core. Heating of insulation material due to a possible DC component that can generate saturation of the magnetic core column.
Motors
Increase of loss due to overheating of internal circuits and possible damage of insulation material. The 5
th
and 11th harmonic components generate some abnormal electromagnetic coupling that
can increase motor speed.
Re-phasing capacitors
Increase in “parallel resonance” present inside a circuit, due to inductive loads and re-phasing capacitors, when at least one of the harmonics has the same frequency as the resonance phenomenon. Effects of this event can be very dangerous, with explosion of used re-phasing capacitors.
RCD devices
Possible saturation of current sensing toroidal transducers resulting in malfunction, both in terms of untimely intervention and increase of the intervention threshold.
Energy disk counters
Increased rotation speed of a disk resulting in measurement errors (especially in case of low power factor loads).
Power controls switch
Reduction of electric duration of contact surfaces.
UPS
Reduced power generation from UPS.
Electronics devices
Internal damage of electronic components not protected by suitable devices.