HST HP101U Installation And Operation Manual

HP101U Conventional Fire Alarm Control Panel Installation And Operation Manual
NOTICE
All information, documentation, and specifications contained in this manual are subject to change without prior notice by the manufacturer.
Issue No. 8113 Ver1.0-2015
Fire Alarm System Limitations
While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of
smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control with
remote notification capability–can provide early warning
of a developing fire.
Such a system, however, does not assure protection
against property damage or loss of life resulting from a
fire.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise
following the recommendations of the current edition of
the National Fire Protection Association Standard 72
(NFPA 72), manufacturer's recommendations, State and
local codes, and the recommendations contained in the
Guide for Proper Use of System Smoke Detectors, which
is made available at no charge to all installing dealers. A
study by the Federal Emergency Management Agency
(an agency of the United States government) indicated
that smoke detectors may not go off in as many as 35%
of all fires. While fire alarm systems are designed to
provide early warning against fire, they do not guarantee
warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply
may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke
cannot reach the detectors such as in chimneys, in or
behind walls, on roofs, or on the other side of closed
doors. Smoke detectors also may not sense a fire on
another level or floor of a building. A second-floor
detector, for example, may not sense a first-floor or
basement fire.
Particles of combustion or "smoke" from a developing
fire may not reach the sensing chambers of smoke
detectors be- cause:
Barriers such as closed or partially closed doors,
walls, or chimneys may inhibit particle or smoke flow.
Smoke particles may become "cold," stratify, and not
reach the ceiling or upper walls where detectors are
located.
Smoke particles may be blown away from detectors
by air outlets.
Smoke particles may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to
alarm smoke detectors. Smoke detectors are designed
to alarm at various levels of smoke density. If such
density levels are not created by a developing fire at the
location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have
sensing limitations. Detectors that have photo electronic
sensing chambers tend to detect smoldering fires better
than flaming fires, which have little visible smoke.
Detectors that have ionizing-type sensing chambers tend
to detect fast-flaming fires better than smoldering fires.
Because fires develop in different ways and are often
unpredictable in their growth, neither type of detector is
necessarily best and a given type of detector may not
provide adequate warning of a fire.
Smoke detectors cannot be expected to provide
adequate warning of fires caused by arson, children
playing with matches (especially in bedrooms), smoking
in bed, and violent explosions (caused by escaping gas,
improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a
predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the
system for the connection of alarm transmission wiring,
communications, signaling, and/or power. If detectors are
not so located, a developing fire may damage the alarm
system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert
people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert
people with a disability or those who have recently
consumed drugs, alcohol or medication. Please note
that:
Strobes can, under certain circumstances, cause
seizures in people with conditions such as epilepsy.
Studies have shown that certain people, even when
they hear a fire alarm signal, do not respond or
comprehend the meaning of the signal. It is the
property owner's responsibility to conduct fire drills
and other training exercise to make people aware of
fire alarm signals and instruct them on the proper
reaction to alarm signals.
In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any
electrical power. If AC power fails, the system will
operate from standby batteries only for a specified time
and only if the batteries have been properly maintained
and replaced regularly.
Equipment used in the system may not be technically
compatible with the control. It is essential to use only
equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of
service or temporarily disabled. For added protection
against telephone line failure, backup radio transmission
systems are recommended.
The most common cause of fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations, and
UL and NFPA standards. At a minimum, the
requirements of Chapter 7 of NFPA 72 shall be followed.
Environments with large amounts of dust, dirt or high air
velocity require more frequent maintenance. A
maintenance agreement should be arranged through the
local manufacturer's representative. Maintenance should
be scheduled monthly or as required by National and/ or
local fire codes and should be performed by authorized
professional fire alarm installers only. Adequate written
records of all inspections should be kept.
Installation Precautions
Adherence to the following will aid in problem-
free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and
associated equipment may be damaged by removing
and/or inserting cards, modules, or interconnecting
cables while the unit is energized. Do not attempt to
install, service, or operate this unit until this manual is
read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this
product must be tested in accordance with NFPA 72
Chapter 7 after any programming operation or change in
site-specific soft- ware. Reacceptance testing is required
after any change, addition or deletion of system
components, or after any modification, repair or
adjustment to system hardware or wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be
100% tested. In addition, to ensure that other operations
are not inadvertently affected, at least 10% of initiating
devices that are not directly affected by the change, up to
a maximum of 50 de- vices, must also be tested and
proper system operation verified.
This system meets NFPA requirements for operation at
0-49° C/32-120° F and at a relative humidity of 85% RH
(non- condensing) at 30° C/86° F. However, the useful
life of the system's standby batteries and the electronic
components may be adversely affected by extreme
temperature ranges and humidity. Therefore, it is
recommended that this system and all peripherals be
installed in an environment with a nominal room
temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate
more than a 10% I.R. drop from the specified device
voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to
lightning-induced transients. Although no system is
completely immune from lightning transients and
interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended,
due to an increased susceptibility to nearby lightning
strikes. Consult with the Technical Services Department
if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing
or inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit
board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in
reduced terminal contact pressure and difficulty with
screw terminal removal.
Though designed to last many years, system
components can fail at any time. This system contains
static-sensitive components. Always ground yourself with
a proper wrist strap before handling any circuits so that
static charges are re- moved from the body. Use static-
suppressive packaging to protect electronic assemblies
removed from the unit.
Follow the instructions in the installation, operating,
and programming manuals. These instructions must be
followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability
depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment in
a residential area is likely to cause interference, in which
case the user will be required to correct the interference
at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
Notes
Table of Contents
CHAPTER 1: PRODUCT DESCRIPTION
.......................................................................................................................7
1.1
PRODUCT FEATURES
.............................................................................................................................................7
1.2
SPECIFICATIONS
.....................................................................................................................................................9
1.3 CONTROLS AND INDICATORS
............................................................................................................................9
1.4 CIRCUITS
..............................................................................................................................................................13
1.5 COMPONENTS
.....................................................................................................................................................14
CHAPTER 2: INSTALLATION
........................................................................................................................................15
2.1 MOUNTING OPTIONS
.........................................................................................................................................15
2.2 BACKBOX MOUNTING
.......................................................................................................................................15
2.3 OPERATING POWER
...........................................................................................................................................16
2.4 INPUT ZONES CIRCUITS
...................................................................................................................................18
2.5 INPUT SUPERVISORY APPLIANCE CIRCUITS
................................................................................................18
2.6 DC POWER OUTPUT CONNECTIONS
.............................................................................................................19
2.7 NOTIFICATION APPLIANCE CIRCUITS (SOUNDER OR BELL )
...................................................................19
2.8 COM-OUT CIRCUITS
.......................................................................................................................................19
2.9 RELAYS OUTPUT
.................................................................................................................................................20
2.10 POWER-LIMITED WIRING REQUIREMENTS
................................................................................................20
2.11 RS485 COMMUNICATION WITH REPEATER PANELS
...............................................................................20
CHAPTER 3 : PROGRAMMING INSTRUCTIONS
.................................................................................................21
3.1 KEY FUNCTIONS
......................................................................................................................................................21
3.2 ENTERING PROGRAM MODE
..................................................................................................................................21
3.3 PROGRAMMING FUNCTIONS
...................................................................................................................................21
3.4 ACTIVATE SOUND OUTPUT BY MANUAL
.................................................................................................................21
3.5 ZONE DISABLE
........................................................................................................................................................22
3.6 SOUND DISABLE
.....................................................................................................................................................22
3.7 MANUAL / AUTOMATIC RUNNING MODE SWITCH
...................................................................................................22
3.8 ZONE INPUT MODE SELECTION
...............................................................................................................................22
3.9 EARTH FAULT CHECK SELECTION
...........................................................................................................................22
3.10 EARTH FAULT CHECK SELECTION
........................................................................................................................22
CHAPTER 4: OPERATING INSTRUCTIONS
...........................................................................................................23
4.1 SWITCH FUNCTIONS IN NORMAL MODE
......................................................................................................23
4.2 STATUS LEDS
.....................................................................................................................................................24
4.3 OPERATION
..........................................................................................................................................................25
4.3.1 Fire Alarm Response
.................................................................................................................................26
4.3.2 Fire Alarm Restoral
.....................................................................................................................................26
4.3.3 System Supervisory Condition Response
...........................................................................................26
4.3.4 System Supervisory Restoral Response
..............................................................................................26
4.3.5 Fault Condition Response
........................................................................................................................26
4.3.6 Fault Condition Restoral
...........................................................................................................................26
APPENDIX A
BATTERY CALCULATIONS
............................................................................................................27
APPENDIX B
WIRE REQUIREMENTS
...................................................................................................................29
Main Circuit Board
PANEL Terminals and Connectors
Page 9 of 36
CHAPTER 1:
Product Description
The PANEL is a 4-zone to 16-zone FACP (Fire Alarm Control Panel), which uses conventional input devices. The
panel accepts water flow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other
normally-open contact devices. Outputs include four Notification Appliance Circuits (NAC, SOUND1-4), three
standard Form-A relays (alarm, trouble and supervisory) and an EIA-485 port to interface with remote
annunciators and optional remote relay modules. The FACP is field programmable via the panel keypad. It also
supervises all wiring, AC voltage and battery level.
This series of panels are basically the same in application and operation, their differences are shown in Table 1-1.
PANEL will be described as the example in the following sections.
Table 1-1
FACP Number of Detection Zones Number of Sounder Outputs Output Delay Settings
8113-4 4
1
N/A
8113-8 8
2
N/A
8113-16 16
4
N/A
1.1 Product Features
4,8,16 Class B Initiating Device Circuits (IDCs)
All zones accept conventional detectors and any normally open contact device
Four Class B Notification Appliance Circuits (NACs)
One Form-A Alarm Relay
One Form-A Trouble Relay
One Form-A Supervisory Relay
3.0 amps of system power
Max 30 conventional detectors in one zone.
Auto/Manual mode setting enable walk test.
Each Zone can be disabled,
Sound output can be disabled.
Manual active sound output enabled.
Able to report short and broken circuit of detection zones.
Designed with standby batteries and space provision for two sealed lead-acid batteries.
Testing and disable functions.
Can connect max 32 repeater panels by RS485 communication port
Dimensions : 14.57
" (37 cm) long X 17.32" (44 cm) high X 3.94"(10cm).
Weight: 6.6kg (without battery).
Page 10 of 36
Page 11 of 36
Loading...
+ 25 hidden pages