1.2 About Motor and Load ..................................................................................................................... 1
1.3 About HD31 ....................................................................................................................................... 2
Chapter 2 Product Information ............................................................................................................................... 5
2.1 Model .................................................................................................................................................. 5
2.3 Rated Value ........................................................................................................................................ 6
2.4 Technical Data ................................................................................................................................... 6
2.5 Parts of Inverter ................................................................................................................................. 8
4.2.1 Wiring specifications of input and output......................................................................................... 15
4.2.2 Power terminal lug .................................................................................................................................... 16
4.3 Main Circuit Terminals and Wiring ............................................................................................... 16
4.3.1 Supply and Motor Terminal .................................................................................................................... 17
4.3.2 Supply and Motor Connection .............................................................................................................. 18
4.4 Control Board and I/O Board ......................................................................................................... 19
4.4.1 Control Board Terminal ............................................................................................................................ 20
9.3 Braking Resistor and Braking Unit ............................................................................................... 72
Appendix A Parameters ......................................................................................................................................... 73
Safety Information and Precautions
Product Information
Machenical Installation
Electrical Installation
Keypad
Function Introduction
Application Reference
Troubleshooting
Accessories
Parameters
1
2
3
4
5
6
7
8
9
A
Shenzhen Hpmont Technology Co., Ltd. Chapter 1 Safety Information and Precautions
W
Chapter 1 Safety Information and Precautions
1.1 Safety Definition
Danger
arning
Note
A Danger contains information which is critical for avoiding safety hazard.
Danger:
A Warning contains information which is essential for avoiding a risk of damage to products or other
Warn ing:
equipements.
A Note contains information which helps to ensure correct operation of the product.
Note:
1.2 About Motor and Load
Compared to the industrial frequency running
The HD31 series inverters are voltage-type frequency inverters and their output is PWM wave with
certain harmonic wave. Therefore, the temperature, noise and vibration of the motor will be a little
higher than that at industrial frequency running.
Constant torque at low-speed running
When HD31 drives a standard motor at low-speed running for a long time, the output torque ratings
will become worse due to the motor cooling is less effective. In that case, we suggest that you should
choose variable frequency motor.
Thermal protection of motor
When choose the adaptive motor, HD31 can effectively implement thermal protection of motor.
Otherwise it must adjust the motor protection parameters or other protection measures to ensure that
the motor is at a safe and reliable running.
Running above the rated frequency of motor
If the motor runs exceeding its rated frequency, the noise will increase. Pay attention to the motor
vibration as well as ensure the motor bearings and mechanical devices to meet the requirement of
running speed range.
Lubrication of mechanical devices
At long time low-speed running, provide periodical lubrication maintenance for the mechanical
devices such as gear box and geared motor etc. to make sure the drive results meet the site need.
1
HD31 Series User Manual V1.1 ―1―
Chapter 1 Safety Information and Precautions Shenzhen Hpmont Technology Co., Ltd.
Mechanical resonance point of load
Set the skip frequency (F05.17 - F05.19) to avoid the load device or the motor mechanical resonance
point.
Start and stop HD31
User should use the control terminal to start and stop HD31.
It is strictly forbidden to use contactor or other switches on the input side of HD31 to start and stop
directly, or it will damage the device.
Check the insulation of the motor
For the first time using of the motor or after long time storage, it needs checking the insulation of the
motor. Worse insulation can cause damage to HD31.
Note:
Use a 500V Mega-Ohm-Meter to test and the insulation resistance must be higher than 5Mohm.
Load and negative torque
For the occasion to boost load and the like, negative torque often occurs. Consider setting proper
parameters of the braking unit if HD31 is prone to overcurrent or overvoltage fault trip.
Requirement for leakage current protector RCD
Since the device generates high leakage current which goes through the protective grounding
conductor, please install B type leakage current protector RCD on one side of the power supply.
For the selection of RCD, users need to consider the possible problems of ground leakage current in
both transient status and steady status at start and during running. It is recommended to choose
either special RCD that can suppress the higher harmonics, or general RCD that has more aftercurrent.
Warning for ground mass leakage current
The device generates mass leakage current, so users need to confirm the reliable grounding before
connect to the power supply. The grounding should comply with the local relative IEC standard.
1.3 About HD31
No capacitor or varistor on the output side
Since HD31 output is PWM wave, it is strictly forbidden to connect capacitor for improving the power
factor or varistor for lightning protection to the output terminals so as to avoid HD31 fault trip or
component damage.
Contactors and circuit breakers connected to the output of HD31
If circuit breaker or contactor needs to be connected between HD31 and the motor, be sure to operate
these circuit breakers or contactor when HD31 has no output, so as to avoid any damage to HD31.
Running voltage
HD31 is prohibited to be used beyond the specified range of running voltage. If needed, please use
suitable voltage regulation device to change the voltage.
―2―HD31 Series User Manual V1.1
Shenzhen Hpmont Technology Co., Ltd. Chapter 1 Safety Information and Precautions
Capacitor energy storage
When the AC power supply is cut off, capacitor of HD31 sustains deadly power for a while. So to
disassemble HD31 that is powered, please cut off the AC power supply for more than 10 minutes,
confirm the internal charge indicator is off and the voltage between (+) and (-) of the main circuit
terminals is below 36V.
Generally, the internal circuit enables the capacitor to discharge. However, the discharging may fail in
some exceptions. In these cases, users need to consult Hpmont or our regional distributor.
Lightning surge protection
HD31 internal design has lightning surge overcurrent protection circuit, and has certain self-protection
capacity against the lightning.
Altitude and derating
In area where altitude exceeds 1000 meters, HD31 should be derating since the heatsink efficiency will
be reduced because of the tenuous air.
The rated value of output current derates by 1% for each 100m increase of the altitude. I.e. for the
altitude of 4000m, derated rate is 30% for rated current of HD31. Figure 1–1 is the derating curve of
rated current and the altitude.
Rated current of HD31
100%
70%
Altitude
1000m4000m
Figure 1–1 Derating curve of rated current and altitude
1
HD31 Series User Manual V1.1 ―3―
Shenzhen Hpmont Technology Co., Ltd. Chapter 2 Product Information
Chapter 2 Product Information
2.1 Model
HD31-4T7P5-P
Product Series
Power Supply Voltage
380 - 460VAC = 4
Input Phase
Three-phase input = T
Power
Product Type
2.2 Nameplate
Fan and pump = P
FWD
REV
ALM
LOCK
LO/RE
HZ
A
V
RPM %
2
Product model
Motor power
Input specification
Output specification
Software version
MODEL:
POWER:
INPUT:
OUTPUT:
HD31-4T7P5P
7.5kW
3PH 380-460V 19A 50/60Hz
11kVA 0-460V 17A 0-400Hz
1.00Version:
Serial number
HD31 Series User Manual V1.1 ―5―
Chapter 2 Product Information Shenzhen Hpmont Technology Co., Ltd.
2.3 Rated Value
Refer to section 3.4 Dimensions and Weight (on page 11) for size information.
Model
HD31-4T2P2P 2.2 3.4 7.3 5.1 F2
HD31-4T3P7P 3.7 5.9 11.9 9.0 F2
HD31-4T5P5P 5.5 8.5 15 13 F2
HD31-4T7P5P 7.5 11 19 17 F2
HD31-4T011P 11 16 28 25 F3
HD31-4T015P 15 21 35 32 F3
HD31-4T018P 18.5 24 39 37 F4
HD31-4T022P 22 30 47 45 F4
HD31-4T030P 30 39 62 60 F5
HD31-4T037P 37 49 77 75 F5
HD31-4T045P 45 59 92 90 F6
HD31-4T055P 55 72 113 110 F6
HD31-4T075P 75 100 156 152 F6
HD31-4T090P 90 116 180 176 F7
HD31-4T110P 110 138 214 210 F7
HD31-4T132P 132 167 256 253 F7
Motor
(kW)
Rated Capacity
(kVA)
Rated Input
Current (A)
Rated Output
Current (A)
Size
2.4 Technical Data
Electrical
Input voltage
Input frequency 50/60Hz ± 5%
Output voltage 0 - input voltage
Output frequency 0 - 400.00Hz
Perf orman ce
Control mode V/f, SVC
Max. current
Running command Keypad; Terminals; Communication
Speed setting Digital; Analogue; Communication
Speed resulotion
SVC
Torque control accuracy ±5%
Three-phase: 380 - 460V, 50/60Hz
Fluctuating within ± 10%, imbalance rate < 3%
120% rated output current for 5 minutes;
135% rated output current for 35 seconds
Digital setting: 0.01Hz
Analogue setting: 0.1% × max-frequency
Speed cont rol accuracy: ± 0 .5%
Speed control range: 1:100
Torque control response: < 200ms
Start torq ue: 180% rated torque / 0.5Hz
―6―HD31 Series User Manual V1.1
Shenzhen Hpmont Technology Co., Ltd. Chapter 2 Product Information
Protection Functions
Stall overvoltage Bus voltage can auto-control against overvoltage fault
Auto-limit current protection Output current can auto-limit against overcurrent fault
Overload pre-alarm and
alarm
Load loss protection Load loss alarm function
Input / Output voltage
phase loss protection
Braking fault protection Braking detection and alarming function
Five LEDs display, 5 unit indicators, 5 status indicators
Setting frequency, output frequency, output voltage, output current, motor speed,
output torque, switching value terminal, status parameter, programm menu
parameter and fault code etc.
2
HD31 Series User Manual V1.1 ―7―
Chapter 2 Product Information Shenzhen Hpmont Technology Co., Ltd.
e
C
C
Environment
Running temperature
Storage temperature -40 - +70℃
Location for use
Altitude Less than 1000 meters, otherwise should be derating use
Humidity Less than 95%RH, non-condensing
Vibration Resistance It is 3.5m/s2 in 2 - 9Hz, it is 10m/s2 (IEC60721-3-3) in 9 - 200Hz
Protection class IP20
Pollution level Level 2 (Dry, non conducting dust pollution)
Accessorie s
Bus communication
About keypad
Power units Dynamic braking unit [HDBU]
-10 - +40℃, max. 50℃, air temperature fluctuation is less than 0.5℃/min
The derating value of the output current of HD31 shall be 2% for each degree
centigrade above 40℃. Max. allowed temperature is 50℃
Indoor, preventing from direct sunlight, no dust, corrosive, flammable gases, oil mist,
water vaper, dripping or salt etc.
PROFIBUS option [HDFB-PROFIBUS-DP]
DeviceNet option [HDFB-DeviceNet]
CAN option [HDFB-CAN]
LCD k eypad ( HD-LCD)
Mounting base to keypad (HD-KMB)
1m/2m/3m/6m extension cable to keypad (HD -CAB-1M/2M/3M/6M)
• Do not install if HD31 is incomplete or impaired.
• When conveying HD31, please employ suitable tools according to its weight. Avoid scratch to the product. Be
careful: rollover and drop may cause hurt.
• Make sure that HD31 is far from explosive and flammable things.
• Do not do wiring operation until power supply is cut off for more than 10 minutes, the internal charge indicator of
HD31 is off and the voltage between (+) and (-) of the main circuit terminals is below 36V.
• It is required not only carry the keypad and the cover but also bottom enclosure of HD31.
• Do not let wires, screws or residues fall into HD31 when installing.
3.2 Installation Site Requirement
Ensure the installation site meets the following requirements:
• Do not install at direct sunlight, moisture, water droplet location;
• Do not install at flammable, explosive, corrosive gas and liquid location;
• Do not install at oily dust, fiber and metal powder location;
• Be vertical installed on fire-retardant material with a strong support;
• Make sure adequate cooling space for HD31 so as to keep ambient temperature between
- 10 - + 40℃;
• Install at where the vibration is 3.5m/s2 in 2 - 9Hz, 10m/s2 in 9 - 200Hz (IEC60721-3-3);
• Install at where the humidity is less than 95%RH and non-condensing location;
• Protection level of HD31 is IP20 and pollution level is 2 (Dry, non-conducting dust pollution).
Note:
1. It needs derating use if running temperature exceeds 40℃. The derating value of the output current of
HD31 shall be 2% for each degree centigrade. Max. allowed temperature is 50℃.
2. Keep ambient temperature between -10 - +40℃. It can improve the running performance if install at
location with good ventilation or cooling devices.
Shenzhen Hpmont Technology Co., Ltd. Chapter 6 Function Introduction
6.2 Group F: General Parameters
6.2.1 F00: Basic Parameters
Ref. Code Fun ction De scripti on Setting Range [Default]
F00.01 Motor control mode 0 - 2 [0]
0: V/f control. Constant voltage/frequency ratio control.
• It is specially applicable for occasions when one inverter drives more than one motors to achieve
proper efficiency.
• When select V/f control, please properly set the V/f control Group F09 to achieve proper efficiency.
1: Unused.
2: SVC control. Sensorless vector control.
• It is applicable for application with high requirement on inverter performance and torque.
• At first, it must perform motor parameter auto-tuning. And then adjust the settings of F08.00 - F08.04
according to the nameplate of the motor. Start the motor parameter auto-tuning function and
properly set Group F10 parameters, so as to achieve excellent vector control efficiency.
F00.02 Inverter type setting 0,1 [1]
0: G type, to drive heavy and general motor.
F00.04 Extension card selection 0,2 [2]
0: Invalid.
F00.05 HD31 extended function 0,1 [0]
0: No extended.
F00.06 Max. output frequency of HD31 50.00 - 400.00 [50.00Hz]
Defines the max. frequency that HD31 is allowed to output.
F00.07 Upper limit of running frequency setting source 0 - 2 [0]
Defines the highest frequency that user can set, and select setting sources to set the upper limit frequency
F00.08 Upper limit of running frequency 0 - F00.06 [50.00Hz]
F00.07 = 0, the upper limit frequency is set by F00.08.
F00.09 Lower limit of running frequency 0 - F00.08 [0.00Hz]
Use F00.09 to limit the actual output frequency. When the setting frequency value < F00.09, it will operate
1: P type, to drive pump and fan.
2: HD30-WIO extension valid.
1: Constant pressure water supply.
• Be careful to set reasonable parameters accordin g to the nameplate of the motor and the actual running
condition s.
via F00.07.
0: Digital setting. Set the upper limit frequency by F00.08.
1: Analogue input setting. Refer to Group F16.
2: DI6 pulse setting. Set by F16.17, and its max. pulse input frequency corresponds to F00.06 (max. output
frequency of HD31).
at lower limit frequency.
• Properly set the parameters according to the nameplate of the motor and actual running conditions.
• No limitation on the motor parameter auto-tuning function.
• Besides the lower /upper limit frequency, the running frequency of inverter is also limited by the
parameter settings of skip frequency (F05.17 - F05.19).
6
HD31 Series User Manual V1.1 ―29―
Chapter 6 Function Introduction Shenzhen Hpmont Technology Co., Ltd.
Ref. Code Fun ction De scripti on Setting Range [Default]
F00.10 Frequency setting sources 0 - 4 [0]
0: Keypad setting. Change the value by pressing the or key of the keypad.
F00.11 Command setting source 0 - 2 [0]
0: Keypad setting. Start and stop the inveter by pressing , and.
F00.12 M key function 0 - 2 [2]
0: Switch running direction. Switch the keypad running direction by key.
F00.13 Starting frequency digital setting 0 - upper limit [50.00Hz]
F00.10 = 0 or 1, F00.13 sets the initial frequency value.
F00.14 UP / DOWN digital setting 000 - 111 [000]
Only valid when F00.11 = 0 or 1.
Initial value is set by F00.13.
1: Terminal digital setting. Change the value by using the terminals UP / DN, F00.13 sets initial value.
2: SCI communication setting. Change the setting frequency by SCI communication frequency command.
• The initial value of the SCI communication frequency is 0.
3: Analogue setting. Set by the analogue input voltage.
• Refer to Group F16.
• Refer to Group F5 for the corresponding relationship between the analogue value and the running
frequency of HD31.
4: DI6 pulse setting.
• The specification of input pulse signal: voltage range 15 - 30V; frequency range 0 - 50.0kHz.
• Refer to Group F05 for the corresponding relationship between the pulse terminal frequency and the
running frequency of HD31.
1: Terminal setting. Start and stop by using the corresponding external terminals.
• DI terminal is set as FWD (No. 2 function), REV (No. 3 function), refer to Group F15.
2: SCI communication setting. Start and stop by SCI communication port according to communication
protocol.
• F00.11 = 0, it is valid. Do not save when power is off.
1: Switch local and remote control. Switch the local and remote control by key.
• F00.11 = 0 or 1, it is valid.
2: Invalid.
• The current setting frequency value will be replaced by a new one when the value of the F00.13 has been
changed by setting the parameter.
Units: Save selection of frequency setting at power outage
• 0: Do not save at power outage.
• 1: Save to F00.13 at power outage.
Tens: Control selection of frequency setting at stop
• 0: Do not restore to F00.13 at stop.
• 1: Restore to F00.13 at stop.
Hundreds: Save selection of communication setting frequency
• 0: Do not save when power is off.
• 1: Save to F00.13 when power is off.
―30―HD31 Series User Manual V1.1
Shenzhen Hpmont Technology Co., Ltd. Chapter 6 Function Introduction
J
Ref. Code Fun ction De scripti on Setting Range [Default]
F00.15 Jog running frequency digital setting 1 0 - upper limit frequency
F00.16 Interval of jog running 0.0 - 100.0 [0.0s]
After cancel the jog command, HD31 will not
respond to the jog command at the interval of jog
running set by F00.16.
• After the interval of jog is completed, it
immediately executes the arrived jog
command. As show in figure.
F00.17 Running direction 0,1 [0]
0: The same as running command.
1: Opposite to running command.
F00.18 Reverse 0,1 [0]
This function is valid when F00.11 = 0,1,2.
0: Permitted.
1: Prohibitted. It can respond to the FWD / REV commands. When the analogue value is set to positive /
negative voltage and the negative voltage corresponds to the reverse frequency, HD31 will run in
accordance with the zero -frequency run.
F00.19 Dead time of direction switch 0.0 - 3600.0 [0.0s]
Defines the dead time of direction switch, namely, the time of
zero-frequ ency output in th e process of direction switch sho wn as
the right figure.
F00.20 Key enable of optional keypad 0,1 [0]
0: Enabled. When HD31 connects to two keypads, the keys of optional display using the communication
port can be operated.
1: Invalid. When HD31 connects to two keypads, the keys of optional display using the communication port
can not be operated.
F00.21 Dormant function 0,1 [0]
0: Disabled. This function is invalid.
1: Enabled. At running status, when the setting frequency ≤ lower limit of running frequency (F00.09), HD31
coasts to stop and enters dormant status.
F00.22 Dormancy wake up time 0.0 - 360.0 [0.0s]
When HD31 is at dormanc y status, and the setting frequency > lower limit of running frequency (F00.09),
and the duration achieves the setting time of F00.22, then HD31 wakes up from dormancy status, and starts
at the mode of F02.00.
og running
frequency
Jog command
Frequ ency
AccDec
Frequ ency
FWD
0
F00.16
F00.19
[5.00Hz]
Time
Time
Time
REV
6
HD31 Series User Manual V1.1 ―31―
Chapter 6 Function Introduction Shenzhen Hpmont Technology Co., Ltd.
H
6.2.2 F01: Protection of Parameters
Ref. Code Fun ction De scripti on Setting Range [Default]
F01.00 User’s password 00000 - 65535 [00000]
XXXXX: To enable the password protection function, set any non-zero numbe r as the password.
• Once the password is set, to change any parameter, input correct password. Otherwise, all the
parameters cannot be changed but only read.
• When input correct password, by pressing key to exit to stop / run display status or by detecting
no press on the keypad within 5 minutes, the user’s password will be valid. To change parameters, input
correct password. It will restart when there is no press on the keypad within 5 minutes.
00000 : The factory setting of F01.00 is 00000, namely the password protection function is disabled.
• If user unlocks the password, it means clearing the user’s password.
F01.01 Menu mode 0,1 [0]
0: Full menu mode. All function parameters can be displayed.
F01.02 Function code parameter initialization (download) 0 - 6 [0]
0: No operation. HD31 is in regular parameter read / write status.
• Steps: If set F01.02 = 1, press to ensure and the parameters are
restored to factory settings. The keypad dispalys “rESEt”. Then the
keypad will display parameters in stop status after finish restoring to
factory setting.
2: Download the keypad EEPROM parameter 1 to the current function code settings.
3: Download the keypad EEPROM parameter 2 to the current function code settings.
4: Clear fault information. The fault history of F20.21 - F20.37 will be clear.
5: Download the keypad EEPROM parameter 1 to the current function code settings (including the motor
parameters).
6: Download the keypad EEPROM parameter 2 to the current function code settings (including the motor
parameters).
1: Upload the current function code settings to the keypad EEPROM
parameter 1.
2: Upload the current function code settings to the keypad EEPROM
parameter 2.
Note: F01.00, F01.02, F01.03, F20.21 - F20.37 and Group y do not upload or
download
Download
Keypad store d
functionparameter
F01.02 = 2 / 3 / 5 / 6
Upload
D31 pr esent s etti ng
function parameter
F01.0 3 = 1 /2
Keypad
HD31
Keypad
HD31
―32―HD31 Series User Manual V1.1
Shenzhen Hpmont Technology Co., Ltd. Chapter 6 Function Introduction
e
6.2.3 F03: Acc / Dec Parameters
Ref. Code Funct ion Des cription Setting Range [Default]
F03.01 Acc time 0.1 - 6000.0
[18.5kW and below: 10.0s]
F03.02 Dec time
Acc time is the time that output frequency accelerates from
0 Hz to F00.06 (the max-output frequency) in linear form.
Dec time is the time that output frequency decelerates from
F00.06 (the max-output frequency) to 0 Hz in linear form.
F03.15 Acc time of jog running 0.1 - 6000.0 [6.0s]
F03.16 Dec time of jog running 0.1 - 6000.0 [6.0s]
F03.15 and F03.16 define the Acc / Dec time of jog running.
F03.17 Dec time of emergency stop 0.1 - 6000.0 [10.0s]
Defines the Dec time of emergency stop.
Frequ ency
F00.06
0
F03.01F03.02
[22 - 75kW: 30.0s]
[90kW and above: 60.0s]
Tim
6.2.4 F05: External Setting Curve Parameters
Ref. Code Func tion Des criptio n Setting Range [Default]
Note: Except F08.03, F08.04 and F08.06, the other factory settings are depended on motor.
Ref. Code Func tion Des cription Setting Range [Default]
F08.00 Rated power of motor 0.2 - 500.0kW
F08.01 Rated voltage of motor 0 - 999V
F08.02 Rated current of motor 7.5kW above motor0.1 - 999.9A
7.5kW and below motor0.01 - 99.99A
F08.03 Rated frequency of motor 1.0 - 400.0 [50.0Hz]
F08.04 Rated RPM of motor 1 - 24000 [1500rpm]
F08.03 and F08.04 should be set in accordance with the parameters of motor nameplate.
F08.05 Power factor of motor 0.001 - 1.000
F08.06 Parameter auto-tuning of motor 0 - 2 [0]
0: Auto-tuning is disabled.
1: Stationary auto-tuning.
• In the process of stationary auto-tuning, the motor is at rest. The stator resistance, rotor resistance and
leakage inductance will be measured and written into F08.07, F08.08 and F08.09 automatically.
2: Rotary auto-tuning.
• In process of rotary auto-tuning, the motor is at rest at the beginning, and the stator resistance, rotor
resistance and leakage inductance will be measured. Hinterher the motor will start rotating,
accordingly mutual inductance and idling excitation inductance will be measured automatically. All the
measured values above will be saved respectively in F08.07, F08.08, F08.09, F08.10 and F08.11
• When the motor is in rotating status, oscillation, even overcurrent, might occur. In this case, press the
key to stop auto-tuning and then adjust the F09.15 (oscillation-suppression mode) and F09.16
(oscillation-suppression coefficient) suitably to mitigate the possible oscillation.
Note: The auto-tuning is enabled only in keypad control mode (F00.11 = 0).
F08.01
2√3πF08.03F08.11
F08.09
6
HD31 Series User Manual V1.1 ―35―
Chapter 6 Function Introduction Shenzhen Hpmont Technology Co., Ltd.
V
y
V
Ref. Code Func tion De scripti on Setting Range [Default]
F08.07 Stator resistance of motor 7.5kW above motor0.000 - 9.999Ω
7.5kW and below motor0.00 - 99.99Ω
F08.08 Rotor resistance of motor 7.5kW above motor0.000 - 9.999Ω
7.5kW and below motor0.00 - 99.99Ω
F08.09 Leakage inductance of motor 7.5kW above motor0.00 - 500.00mH
7.5kW and below motor0.0 - 5000.0mH
F08.10 Mutual inductance of motor 7.5kW above motor0.00 - 500.00mH
7.5kW and below motor0.0 - 5000.0mH
F08.11 Idling excitation current of motor 7.5kW above0.0 - 999.9A
7.5kW and below0.00 - 99.99A
Auto-tuning steps:
• 1. Input correct motor parameters as per its nameplate (F08.00 - F08.04).
• 2. When F08.06 is set as 2, set proper Acc time (F03.01) and Dec time (F03.02) and make sure the motor is
disconnected with the load for security.
• 3. Set F08.06 as 1 or 2 firstly, then press the key, and therewith press key to star t auto-tuning.
The LED will display “tunE”.
• 4. When the RUN indicator is flashing, it indicates that auto-tuning has been completed.Now the keypad
displays the parameters of stop status and F08.06 resets to 0.
6.2.6 F09: V/f Control Parameters
Ref. Code Name Description Setting Range [Default]
F09.00 V/f curve of motor 0 - 4 [0]
Defines flexible V/f setting modes so as to meet requirements of different load characteristics.
F09.01 V/f frequency of motor (F3) F09.03 - F08.03 [0.00Hz]
F09.02 V/f voltage of motor (V3) F09.04 - F08.01 [0V]
F09.03 V/f frequency of motor (F2) F09.05 - F09.01 [0.00Hz]
F09.04 V/f voltage of motor (V2) F09.06 - F09.02 [0V]
F09.05 V/f frequency of motor (F1) 0.00 - F09.03 [0.00Hz]
F09.06 V/f voltage of motor (V1) 0 - F09.04 [0V]
F09.01 - F09.06 is user- definable V/f curve.
• Four curves and one user-defined curve can be selected
according to the setting of F09.00.
0: Line. Shown as curve 0 in figure.
1: Square curve. Shown as curve 1 in the figu re.
2: 1.2 exponential curve. Shown as curve 2 in the Figure.
3: 1.7 exponential curve. Shown as curve 3 in the Figure.
4: User-defined curve.
• If F09.00 = 4 (user-definable curve), F09.06 is
enabled.
• The V/f curve can be defined by connecting 3
points of (V1, F1), (V2, F2) and (V3, F3), to
adapt to special load.
• According to the actual condition, set proper
curve to meet the requirements of load
characteristics.
F09.02×F08.01
F09.04×F08.01
F09.06×F08.01
F08.01
0
1/3
×F08. 01
F08.01
oltage
F09.05×
F08.03
0
V2,F2
V1,F1
oltage
1/3
×F08.03
F09.03×
F08.03
V3,F3
F09.01×
F08.03
F08.03
F08.03
0
2
3
1
Frequ enc
Frequ ency
―36―HD31 Series User Manual V1.1
Shenzhen Hpmont Technology Co., Ltd. Chapter 6 Function Introduction
V
V
o
Ref. Code Name Description Setting Range [Default]
F09.07 Torque boost of motor 0.0 - 30.0
F09.08 Cut-off point used for manual torque boost of motor 0.0 - 50.0 (F08.03) [10.0%]
In order to compensate the torque drop at low frequency, HD31 can boost the voltage so as to boost the
F09.09 Slip compensation gain of motor 0.0 - 300.0 [100.0%]
F09.10 Slip compensation filter time of motor 0.01 - 10.00 [0.10s]
F09.11 Slip compensation limit of motor 0.0 - 250.0 [200.0%]
F09.12 Compensation time constant of motor 0.1 - 25.0 [2.0s]
The motor slip changes with the load torque, which results in the variance of motor speed. Reduce the
F09.14 AVR (automatic voltage regulation) function of motor 0 - 2 [1]
0: Disabled.
F09.15 Oscillation-suppression mode of motor 0,1 [0]
0: Depend on excitation current component.
F09.16 Oscillation-suppression coefficient of motor 0 - 200 [50]
This function is used to damp oscillation when output current is continually unstable.
torque.
• No matter what kind of V/f curve is set by
F09.00, the torque boost is enabled.
F09.07 is manually torque boost.
• If F09.07=0, it is manually torque boost. User
needs to set rated frequency (F08.03) and rated
rotary speed (F08.04) of the motor correctly
according to its nameplate.
F09.08 is relative to percentage of rated frequency
(F08.03).
influence through slip compensation (HD31 will automatically adjust its output frequency according to the
load torque).
• In driving status (the actual speed < the setting speed) and in
• The auto slip compensation depends on the rated slip of motor,
• Range of slip compensation = F09.11 × Rated slip.
• Rated slip = F08.03 - F08.04 × Np / 60.
1: Enabled all the time.
2: Disabled in Dec process.
• The output voltage can be regulated to maintain constant via AVR. Thus, normally the AVR function
• In Dec process, if F09.14 = 0 or 2, the running current will be a little higher; while if F09.14 =1, the moto r
1: Depend on torque current component.
• This function helps to keep the motor running smoothly through correctly adjusting the setting of
generating status (the actual speed > the setting speed), the slip
compensation gain (F09.09) should be increased gradually.
consequently make sure the rated frequency (F08.03) and rated
speed (F08.04) are set correctly.
• Np is the number of the motor pole pairs.
should be enabled, especially when the input voltage is higher than the rated voltage.
will decelerate steadily and the current will be smaller.
F09.16.
F08.01
oltage of manual
torque boost
0
[55kW and below: 2.0%]
oltage
Boosted
value
F09.08max
Posit ive sli p
compensation
-100 %
[75 - 132kW: 1.0%]
Frequ ency
F08.03
Slip
Load
100%
Negative slip
c
mpens ation
6
HD31 Series User Manual V1.1 ―37―
Chapter 6 Function Introduction Shenzhen Hpmont Technology Co., Ltd.
6.2.7 F15: Digital I/O Terminal Parameters
Ref. Code Fun ction De scripti on Setting Range [Default]
F15.00 DI1 function 0 – 54 [2]
F15.01 DI2 function 0 - 54 [3]
F15.02 DI3 function 0 - 54 [0]
F15.03 DI4 function 0 - 54 [0]
F15.04 DI5 function 0 - 54 [0]
F15.05 DI6 function 0 - 54 [0]
F15.06 DI7 function 0 - 54 [0]
F15.07 DI8 function 0 - 54 [0]
F15.08 DI9 function 0 - 54 [0]
0: Unused. It disables the terminal function. HD31 ignores the signal input via this terminal.
• The unused terminal is recommended to be set as 0 to avoid wrong connection or action.
1: Inverter enabled.
• When enabled, HD31 is enabled to run;
• When disabled, HD31 is disabled to run and will be in auto stop status.
• If no terminal selects this function, it defaults that HD31 is enabled.
2,3: FWD / REV.
• Set any DI terminal for the FWD / REV to control run / stop of HD31.
• FWD / REV is valid only in terminal control mode (F00.11 = 1).
• Refer to parameter F15.16.
4: Three- wire running mode.
• Refer to parameter 15.16.
12: External stop command input.
• F00.05=1, the pump stops in sequence, otherwise stops according to stop mode. It is valid for all
running command sources.
41,42: Coast to stop normally open / normally closed input.
• HD31 will stop outputting immediately and the load will coast to stop in accordance with the
mechanical inertia when a DI terminal is set as 41 or 42.
44,45: External fault normally open / normally closed input.
• When HD31 receives the EXT signal, E0024 fault (fault of external equipment) will be displayed.
• The fault signal has two input modes: normally open and normally closed input.
46: External reset (RST) input. When HD31 alarms fault, reset it by this terminal.
• The function of RST terminal is the same as the key.
53: Pulse frequency input (DI6).
• This terminal is used to input pulse signal as frequency setting.
• Refer to Group F05 for the relationship between input pulse frequency and frequency setting.
54: Clear fault records. In valid, clear P04.04 at stop.
3: Motor RPM (0 - max. output frequency corresponding to RPM).
4: Output current (0 - twice rated current of motor).
Analogue
input filtering
Analogue inputgain
Analogue input bias
Analogue value
after calcu lating
6
HD31 Series User Manual V1.1 ―41―
Chapter 6 Function Introduction Shenzhen Hpmont Technology Co., Ltd.
Ref. Code Func tion De scripti on Setting Range [Default]
5: Output current (0 - twice rated current of motor)
6 - 9: Unused.
10: Output torque (0 - 3 times rated torque of motor).
11: Output voltage (0 - 1.2 times rated voltage of HD31).
12: Bus voltage (0 - 2.2 times rated voltage of HD31).
13: Output power (0 - twice rated power of motor).
14: AI1 input (after calculating).
15: AI2 input (after calculating).
16: AI3 input (after calculating).
17: AI4 input (after calculating).
18,19: Output frequency / setting frequency (- 1 times - 1 times max. output frequency).
F16.22 AO1 bias -100.0 - 100.0 [0.0%]
F16.23 AO1 gain 0.0 - 200.0 [100.0%]
The proportiona l relation of output can be adjusted by output ga in, as shown in the figure below.
• The formula is: AO1 actual output = F16.23 × Value before calculating + F16.22
Valu e af ter
calculating (V)
100%
F16.22=50%
F16.23=50%
50%
010
F16.24 AO2 bias -100.0 - 100.0 [0.0%]
F16.25 AO2 gain 0.0 - 200.0 [100.0%]
Refer to F16.22 and F16.23.
F16.26 DO2 max. output pulse frequency 0.1 - 50.0 [10.0kHz]
Defines the DO2 terminal allowable max. output frequency.
F16.2 2=0
F16.23=100%
Value befor e
calculating (V)
100%
F16.22=0
F16.23=200%
Value aft er
calculating (V)
F16.22 =0
F16.23=100%
Value be fore
calculating (V)
0510
―42―HD31 Series User Manual V1.1
Shenzhen Hpmont Technology Co., Ltd. Chapter 6 Function Introduction
6.2.9 F17: SCI Communication Parameters
Ref. Code Fun ction D escript ion Setting Range [Default]
F17.00 Data format 0 - 5 [0]
0: 1-8-2 fo rmat, no parity, RTU.
1: 1-8-1 format, even parity, RTU.
2: 1-8-1 format, odd parity, RTU.
3: 1-7-2 format, no parity, ASCII.
4: 1-7-1 format, even parity, ASCII.
5: 1-7-1 format, odd parity, ASCII.
F17.01 Baud rate 0 - 5 [3]
0: 1200bps.
1: 2400bps.
2: 4800bps.
3: 9600bps.
4: 19200bps
5: 38400bps.
F17.02 Local address 0 - 247 [2]
F17.02 = 0, it means broadcast address.
F17.03 Host PC response time 0 - 1000 [0ms]
F17.04 Detection time at communication timeout 0.0 - 1000.0 [0.0s]
Time at no communication data > setting time of F17.04, it will be considered as E0028 fault (SCI timeout
fault).
• F17.04 = 0, it will not detect communication timeout.
F17.05 Detection time at communication error 0.0 - 1000.0 [0.0s]
Time at communication error > setting time of F17.05, it will be considered as E0029 fault (SCI error).
• When F17.05 = 0, it will not detect the communication error.
F17.06 Action selection at communication timeout 0 - 3 [3]
F17.07 Action selection at communication error 0 - 3 [3]
F17.08 Action selection at communication peripheral device fault 0 - 3 [1]
F17.06 defines the action selection at commmunication timeout.
F17.07 defines the action selection at communication error.
In the communication command setting mode, F17.08 will define the action selection when
communication peripheral device fault is alarmed.
0: Coast to stop.
1: Emergency stop.
2: Decelerate to stop.
3: Continue to run.
6
HD31 Series User Manual V1.1 ―43―
Chapter 6 Function Introduction Shenzhen Hpmont Technology Co., Ltd.
6.2.10 F18: Display Control Parameters
Ref. Code Func tion Des criptio n Setting Range [Default]
F18.00 Language selection 0,1 [0]
Defines the displaying language on the LCD keypad.
0: Chinese.
1: English.
F18.01 Display contrast of the LCD keypad 1 - 10 [5]
To select LCD display contrast.
F18.02 Set parameter 1 of run status 0 - 49 [8]
F18.03 Set parameter 2 of run status 0 - 49 [7]
F18.04 Set parameter 3 of run status 0 - 49 [36]
F18.05 Set parameter 4 of run status 0 - 49 [13]
F18.06 Set parameter 5 of run status 0 - 49 [14]
F18.07 Set parameter 6 of run status 0 - 49 [18]
F18.08 Set parameter 1 of stop status 0 - 49 [7]
F18.09 Set parameter 2 of stop status 0 - 49 [18]
F18.10 Set parameter 3 of stop status 0 - 49 [20]
F18.11 Set parameter 4 of stop status 0 - 49 [22]
F18.12 Set parameter 5 of stop status 0 - 49 [35]
F18.13 Set parameter 6 of stop status 0 - 49 [36]
The keypad displays parameters which is the run status (F18.02 - F18.07) and stop status (F18.08 - F18.13).
• It can be cycling displayed by key on the keypad.
• Each content of display parameter can be set corresponding to 49 statuses.
• For instance: when set F18.08 as 7, the stop parameter is setting frequency at initial power on.
1: Rated current of HD31.
7: Setting frequency.
8: Setting frequency (after Acc / Dec).
9: Output frequency. At running status,
indicator is flashing.
10: Setting RPM.
11: Running RPM. At running status, indicator
is flashing.
12: Three-phase power supply input phase
sequence.
• 0: Positive sequence, L1(R) preceding L2(S)
preceding L3(T ).
• 1: Negative sequence, L1(R) preceding L3(T)
preceding L2(S)
13: Output voltage.
14: Output current.
16: Output torque.
17: Output power.
18: DC bus voltage.
19: Potentiometer input voltage.
20: AI1 voltage.
21: AI1 voltage (after calculating).
22: AI2 voltage.
23: AI2 voltage (after calculating).
24: AI3 voltage.
25: AI3 voltage (after calculating).
26: AI4 voltage.
27: AI4 voltage (after calculating).
28: DI6 pulse input frequency.
29, 30: AO1 / AO2 output.
31: High-speed output pulse frequency.
32: Heatsink temperature.
35: Content water supply pressure setting.
36: Actula feedback pressure.
37: PID setting.
38: PID feedback.
39: PID error.
40: PID integral value.
41: PID output.
43: Input terminal status.
• Bit0 - Bit8 are corresponding to DI1 - DI9.
44: Output terminal status
• Bit0 - Bit11 are corresponding to DO1, DO2,
RLY1 - RLY10
48: Total time at power on (hour).
49: Total time at running (hour).
―44―HD31 Series User Manual V1.1
Shenzhen Hpmont Technology Co., Ltd. Chapter 6 Function Introduction
6.2.11 F19: Function-boost Parameters
Cooling fan (F19.07 - F19.08)
Ref. Code Name Description Setting Range [Default]
F19.07 Fan control 0 - 2 [0]
F19.08 Fan control delay time 0.0 - 600.0 [30.0s]
Defines the control mode of cooling fan. With overheat protection, the fan runs all the time.
0: Auto stop.
• The fan runs all the time when HD31 is in running status. After HD31stops for the time set by F19.08, the
fan continues running if overheat protection is activated.
1: Immediate stop.
• The fan runs all the time when HD31 is in running status and stops when HD31stops.
2: Runs all the time when power on.
Restart after power failure (F19.16 - F19.17)
Ref. Code Name Description Setting Range [Default]
F19.16 Restart af ter power failure 0,1 [0]
0: Disabled.
F19.17 Delay time for restart after power failure 0.00 - 10.00 [2.00s]
Protection of stall overvoltage (F19.18 - F19.19)
Ref. Code Name Description Setting Range [Default]
F19.18 Stall overvoltage 0,1 [1]
0: Disabled. Braking unit and braking resistor are recommended to be installed if F19.18 is set as 0.
F19.19 Stall overvoltage point 0 - 1200 [740V]
If the stall overvoltage point is set a little lower, Dec time should be comparatively longer.
• The fan runs all the time when HD31 is powered on.
When terminal sets running command, this function decides whether HD31 starts automatically or
not and the delay time for restart when HD31 restarts after power failure.
1: Enabled. In the terminal two-wire control mode and suddenly power failure during running process, when
HD31 is powered on again and the terminal is still enabled, it will wait certain time defined by F19.17 and
then restart with speed tracking mode.
During Dec, the actual decrease rate of motor may < output frequency due to the load inertia. At this
time, the motor will feed the energy back to HD31, resulting in voltage rise on the DC bus. If no
measure is taken, HD31 will trip due to overvoltage.
1: Enabled. During the Dec, HD31 detects the bus voltage and compares it with F19.19.
• If the detected bus voltage > F19.19, HD31 will stop reducing its output frequency. When detect again, if
Chapter 6 Function Introduction Shenzhen Hpmont Technology Co., Ltd.
Auto current limit (F19.20 - F19.22)
Auto current limit is used to limit the load current in real time < F19.21. Therefore HD31 will not trip
due to surge current. It is especially suitable for applications with big load inertia or big change of load.
In auto current limit process, output frequency of HD31 may change; therefore, it is recommended not
to enable when stable output frequency is required.
Ref. Code Name Description Setting Range [Default]
F19.20 Auto current limit 0 - 2 [1]
0: Disabled.
1: Enabled in Acc / Dec running process, but disabled in constant speed running process.
2: Enabled both in Acc / Dec and constant speed running process.
• When the auto current limit is enabled, the output overload capacity will be impaired if auto current limit
threshold is set too low.
F19.21 Auto current limit threshold 20.0 - 200.0 [110%]
Defines the current threshold of auto current limit. The current = F19.21 × rated current of HD31.
F19.22 Dec time at auto current limit 0.0 - 6000.0
Defines the speed rate for the output frequency adjustment at auto current limit action.
• If the setting is too big, it will not be easy to get over the auto current limit status and finally result in
overload fault. If the setting is too small, the frequency will change too sharply and therefore, HD31 may be
in generating status for a long time, which may result in overvoltage protection.
• F19.22=0 , it will not decelerate at current limit.
F19.23 Enabled terminal at power on 0,1 [0]
0: Rise edge.
• For many applications, HD31 is not allowed to auto run to avoid device damage and ensure safety due to
no person interference at power on. In these applications, when the inverter has power initialized and
ready to run, it can not start to run until the terminal run command is given.
1: Level.
• For certain applications, when ensured personal safety and device safety, HD31 needs immediately run at
power on in order to provide automation and efficiency. In these applications, HD31 will immediately run
as soon as the terminal running command is given whether before or after power on.
[18.5kW and below: 10.0s]
[22 - 75kW: 30.0s]
[90kW and above 60.0s]
Braking unit (F19.24)
Ref. Code Name Description Setting Range [Default]
F19.24 Action voltage of braking unit 630 - 750 [720V]
Note: Only in inverter running status is the braking enabled.
―46―HD31 Series User Manual V1.1
Shenzhen Hpmont Technology Co., Ltd. Chapter 6 Function Introduction
6.2.12 F20: Fault Protection Parameters
Overload fault (F20.00 - F20.02)
Ref. Code Name Description Setting Range [Default]
Defines the current threshold of load-loss. The current = F20.01 × rated current of HD31.
F20.05 Output load-loss detection time of HD31 0.00 - 20.00 [1.00s]
If the output current of HD31 < F20.04 and exceeds the time defined by load-loss detection time (F20.05),
1: It detect all the time in running process, and then continues running after detecting (alarm).
2: It detects only at constant speed, and then continues running after detecting (alarm) .
3: It detects all the time in running process, and then cuts off the output after detecting (fault).
4: It detects only at constant speed, and then cuts off the output after detecting (fault).
HD31 will alarm E0018 fault (inverter output load-loss).
• F20.04 or F20.05 = 0, HD31 will not detect load-loss fault.
HD31 Series User Manual V1.1 ―47―
6
Chapter 6 Function Introduction Shenzhen Hpmont Technology Co., Ltd.
Motor overheat fault (F20.06 - F20.07)
It can connect the electronic thermistor embedded motor stator coils to the AI terminal of HD31 in
order to protect motor overheat.
Ref. Code Name Description Setting Range [Default]
F20.06 Motor overheat signal input type 0 - 2 [0]
0: Does not detect the motor overheat.
1: Positive charateristic (PTC).
2: Negative charateristic (NTC).
F20.07 Thermistor value at motor overheat 0 - 10.0 [5.0kΩ]
Input and output voltage phase loss fault (F20.08 - F20.11)
Ref. Code Name Description Setting Range [Default]
F20.08 Input voltage phase loss detection setting 0 - 50 [30%]
F20.09 Input voltage phase loss detection time 1.00 - 5.00 [1.00s]
The detection voltage = F20.08 × rated voltage of HD31.
When HD31 detects certain input voltage < the detection setting (F20.08) and exceeds the detection time
(F20.09), HD31 will alarm E0015 fault (input voltage phase loss).
• F20.08 = 0, HD31 will not detect input voltage phase loss fault.
F20.10 Output voltage phase loss detection setting 0 - 50 [20%]
F20.11 Output voltage phase loss detection time 0.00 - 20.00 [3.00s]
The detection current = F20.10 × rated current of HD31.
When HD31 detects certain output current < the detection setting (F20.10) and exceeds the detection time
(F20.11), HD31will alarm E0016 fault (output voltage phase loss).
• F20.10 or F20.11 = 0, HD31 will not detect output voltage phase loss fault.
PID setting and feedback loss fault (F20.12 - F20.17)
Ref. Code Name Description Setting Range [Default]
F20.12 PID setting lose detection value 0 - 100 [0%]
F20.13 PID setting loss detection time 0.0 - 10.0 [0.20s]
F20.12 value is a percentage of the max. setting source.
F20.14 PID feedback loss detection value 0 - 100 [0%]
F20.15 PID feedback loss detection time 0.0 - 10.0 [0.20s]
F20.14 value is a percentage of the max. feedback s ource.
If the PID setting < F20.12 in the detection time (F20.13), HD31 will alarm E0025 fault (PID setting loss).
• F20.12 or F20.13 =0, HD31 will not detect PI D setting loss fault.
If the PID feedback value < F20.14 in the detection time (F20.15), HD31 will alarm E0026 fault (PID feedback
loss).
• F20.14 or F20.15 = 0, HD31 will not detect PID feedback loss fault.
―48―HD31 Series User Manual V1.1
Shenzhen Hpmont Technology Co., Ltd. Chapter 6 Function Introduction
Fault at PID feedback value out of the limit (F20.16 - F20.17)
Ref. Code Name Description Setting Range [Default]
F20.16 Detection value at PID feedback out of the limit 0 - 100 [100%]
F20.17 Detection time at PID feedback out of the limit 0.00 - 10.00 [0.20s]
F20.16 value is a percentage of the max. feedback s ource.
If the PID feedback value > F20.16 in the detection time (F20.17), HD31 will alarm E0027 fault (PID feedback
out of limit).
• F20.16=100 or F20.17=0, HD31 will not detect PID feedback out of limit fault.
Fault auto reset function and faulted relay action (F20.18 - F20.20)
Auto reset function enables HD31 to reset the fault as per the reset times and interval.
During the reset interval, HD31 stops output and it will automatically restarts with speed tracking
mode.
The following faults do not have the auto reset function:
E0008: Power module fault E0021: Read / Write fault of control board EEPROM
E0010: Braking unit fault E0023: Parameter setting fault
• Adding variable frequency pump: when the system meets the conditions of adding pump and if next
pump is an inverter drive one.
• The currently running variable frequency pump needs switching to run with power frequency. A
disconnected inverter must comply with P00.13. HD31 needs to accelerate to P00.08, thus to reduce
the network pipe pressure drop and then stops output.
• Disconnect inverter drive contactor, apply P00.13, and connect the normal drive contactor to complete
the frequency change. At the same time, HD31 controls the next pump to proceed to PI
commissioning.
• Adding power frequency pump: when the system meets the conditions of adding pump and if next
pump is a normal drive one.
• The system automatically starts the next power frequency pump.
• To avoid a sudden increase in the pipe pressure, the current variable frequency pump decreases its
output frequency to F00.09 according to P00.09, and proceeds to PI conmissioning.
Note:
1. Priority of adding pumps: variable frequency pump > power frequency pump.
2. If there are multiple normal / inverter frequency pumps, the system adds pumps in a circle way according to
"first stop, first resume".
Conditions for reducing pump:
1 When the current variable frequency pump operates at the lower limit
P00.15 Switch circle of power frequency pump 0 - 9999 [0h]
P00.16 Switch circle of variable frequency pump 0 - 9999 [0h]
Switch between power frequency pumps: When there are one power frequency pump in running status
P00.17 Dormancy enable 0 - 4 [0]
0: No dormancy.
P00.18 Pressure tolerance of dormancy awakening 0.0 - 100.0 [10.0%]
P00.19 Delay time of dormancy awakening 0.0 - 3600.0 [5.0s]
Used during the pump switch process. It is used for the mechanical delay close and open of the contactor.
And more importantly, it's used to avoid the remanence effect. This effect occurs during the process of
variable frequency switching to power frequency. Remanence effect may cause the switch fail.
• P00.13 is the duration of HD31 from sending a command of free stop (send an instruction to disconnect
HD31 drive contactor simultaneously) to close the normal drive contactor.
• For pumps over 45kW which require to switch from variable frequency to power frequency, P00.13 can
effectively reduce the switching current and improve successful switching.
• P00.14 is the duration from sending a close command of inverter drive contactor to the output moment
of HD31. It allows for the mechenical delay of the contactor before starting the next variable frequency
pump.
and one that is waiting, the switch will occur only when the running pump meets P00.15.
Switch between variable frequency pumps: When there are one variable frequency pump in running status
and one that is waiting, the switch will occur only when the running pump meets P00.16.
• P00.15 and P00.16 = 0, the switch function is valid.
1: Constant pressure dormancy.
2: Specified pressure dormancy.
3: No flow dormancy1.
4: No flow dormancy 2.
Note: F00.21 and F00.22 support specified pressure dormancy (it's dormant when the setting frequency meets
lower limit frequency).
P00.17 = 0: dormant function is invalid.
• P00.17 = 1: when the system meets the condition of reducing pump, provided that there is no power
frequency pump or variable frequency pump that runs with power frequency, the system enters dormant
status. Mmeanwhile, is will start a dormant pump if there is one in the system.
• P00.17 = 2: when feedback pressure > setting pressure + setting pressure × P00.20, and surpass setting
time of P00.22, the system stops all running pumps and enters dormant status.
• P00.17 = 3: when only one inverter existed in the system, feedback pressure > setting prsssure + setting
pressure × P00.20 and output frequency is smaller than P00.23 for certain time, (if it is starting procedure,
the time will be P00.24, others will be P00.22. if no special requirements, can set P00.22 = P00.24), system
will sleep.
• P00.17 = 4: when only one inverter existed in the system, feedback pressure > setting prsssure + setting
pressure × P00.20 and output frequency is smaller than no-flow power or output frequency is smaller
than P00.23 for a certain time (P00.22), system will sleep.
In dormant status, when feedback pressure < setting pressure - setting pressure × P00.18, and exceeds
setting time of P00.19, the dormancy is awakened. While if P00.17 = 1 , the dormant pump is disconnected.
When dormant is awakened, HD31 drive pump is preferably added if there is any waited in the system. If
there is power frequency pump waiting, it is added directly.
6
HD31 Series User Manual V1.1 ―53―
Chapter 6 Function Introduction Shenzhen Hpmont Technology Co., Ltd.
Ref. Code Name Description Setting Range [Default]
P00.21 Interval of shutdown the pump and water supply 0.0 - 60.0 [10.0s]
When the system receives stop command, it will shut off the pumps in accordance with P00.21. The shutoff
sequence is: dormant pump > sewage pump > power frequency pump > variable frequency pump running
with power frequency > variable frequency pump running with variable frequency.
P00.22 Detection time of shutdown detection 0.0 - 3600.0 [6.0s]
P00.23 No-flow detecting frequency 0.0 - 50.00[25.00Hz]
P00.24 Detecting time for no-flow detecting start delay 0.0 - 3600.0[60.0s]
P00.25 No flow correction factor 1 - 400[100%]
P00.26 No-flow low speed 0.00 - 99.99 [0.00Hz]
P00.27 No-flow low speed power 0.00 - 10.00 [0.00kW ]
P00.28 No-flow high speed 0.00 - 99.99 [0.00Hz]
P00.29 No-flow high speed power 0.00 - 10.00 [0.00kW]
P00.30 No-flow detection curve 0 - 3 [0]
P00.31 Phase sequence detection enable from variable frequency to power
Before correcting no-flow frequency, pls refer to d00.41.
No-flow power measuring steps:
•
Set F00.05 = 0, F00.10 = 0 and ensure the system reach normal temporature before no-flow power
testing.
•
Close main valve and stop flow
•
When the setted frequency is about 50% of motor rated frequency, recording setted frequency in
P00.26 and recording current value of D00.40 in P00.27
•
When the setted frequency is about 85% of motor rated frequency, recording setted frequency in
P00.28 and recording current value of D00.40 in P00.29.
0: Square curve.
1: Straight line.
2: Cubic curve 1.
3: Cubic curve 2.
Note: By P00.26 - P00.29, corresponding no-flow power will be work out by setted curve and will be recorded in
d00.41, pleasure select reasonbale curve.
0,1 [0]
frequency
0: Disable.
•
No phase sequency detecting before switch variable frequency into power frequency.
1: Enable.
•
Before switch cariable frequency into power frequency, detect phase sequency. And difference of
power frequency phase angle will be changed within range of P00.32 - P00.38.
Note: Detailed steps refer to 7.2 Debugging for Switching between VF and PF, on page 66.
―54―HD31 Series User Manual V1.1
Shenzhen Hpmont Technology Co., Ltd. Chapter 6 Function Introduction
Ref. Code Name Description Setting Range [Default]
P00.32 Switching angle of variable and power frequecny of pump 1 -50.0 - 50.0 [0.0°]
P00.33 Switching angle of variable and power frequecny of pump 2 -50.0 - 50.0 0.0°]
P00.34 Switching angle of variable and power frequecny of pump 3 -50.0 - 50.0 [0.0°]
P00.35 Switching angle of variable and power frequecny of pump 4 -50.0 - 50.0 [0.0°]
P00.36 Switching angle of variable and power frequecny of pump 5 -50.0 - 50.0 [0.0°]
P00.37 Switching angle of variable and power frequecny of pump 6 -50.0 - 50.0 [0.0°]
P00.38 Switching angle of variable and power frequecny of pump 7 -50.0 - 50.0 [0.0°]
When seting as positive angle, variabe frequency phase exceeds power frequency and the difference
reaches setted angle, switching action from variable frequency to power frequcny will be started.
When setting as negative angle, variable frequency is slower than power frequency and the difference
reaches setted angle, switching action from variable frequency to power frequcny will be started.
For details, pleasure see P00.13, P00.14.
6
HD31 Series User Manual V1.1 ―55―
Chapter 6 Function Introduction Shenzhen Hpmont Technology Co., Ltd.
6.3.2 P01: Water Supply Pump Parameter
Ref. Code Name Description Setting Range [Default]
P01.00 Pump 1 type 0 - 4 [0]
P01.01 Pump 2 type 0 - 4 [0]
P01.02 Pump 3 type 0 - 4 [0]
P01.03 Pump 4 type 0 - 4 [0]
P01.04 Pump 5 type 0 - 4 [0]
P01.05 Pump 6 type 0 - 4 [0]
P01.06 Pump 7 type 0 - 4 [0]
0:Invalid. It is not installed or does not work in the system.
1: Variable frequency pump. It starts with variable frequency.
• If it is unqualified to switch, it works as an inverter drive adjustable pump for the whole system. It is
controlled by HD31, which adjust the rotating speed of pump according to the actual pressure so as to
maintain constant system pressure.
• If it is qualified to switch, the pump switches to power frequency running or exit running, depending
on the switch mode.
2: Power frequency pump. It only runs with power frequency.
• Adopt full-pressure direct start method when the power grid is sufficient and the pump power is
under 15kW.
• It is recommended to adopt reduced-voltage method such as reduced-voltage of Y-△mode, self
coupling voltage start, soft start, etc. for pumps with power of no less than 18.5kW. That can reduce
the impact on the power grid and pipe network.
3: Dormant pump. It serves as dormant pump for the system.
• The system enters dormant run when it meets the dormant condition. It will enter dormant running or
awaken dormancy according to the dormant pressure and tolerant limit.
4: Sewage pump. It serves as dormant pump for the system.
• Condition for setting a sewage pump: water level sensor of sewage pool must be installed in the
system and correctly connect to HD31. HD31 automatically controls the start and stop of the sewage
pump according to WL of sewage water pool.
Note:
1. For a pump which is set as variable frequency pump, the corresponding inverter / normal drive relay must be
set again, otherwise it's not recognized as effective pump. After starting the system, HD31 will not output if there
is only one variable frequency pump in the system and no setting for inverter / normal drive relay.
2. For a pump which is set as variable frequency pump, dormant pump and sewage pump, the corresponding
inverter drive relay must be set again, otherwise the is not recognized as effective pump.
P01.07 Rated current of pump 1 7.5kW above motor0.1 - 999.9A [Depend on motor]
7.5kW and below motor0.01 - 99.99A [Depend on motor]
P01.08 Rated current of pump2 7.5kW above motor0.1 - 999.9A [Depend on motor]
7.5kW and below motor0.01 - 99.99A [Depend on motor]
P01.09 Rated current of pump3 7.5kW above motor0.1 - 999.9A [Depend on motor]
7.5kW and below motor0.01 - 99.99A [Depend on motor]
P01.10 Rated current of pump4 7.5kW above motor0.1 - 999.9A [Depend on motor]
7.5kW and below motor0.01 - 99.99A [Depend on motor]
P01.11 Rated current of pump5 7.5kW above motor0.1 - 999.9A [Depend on motor]
7.5kW and below motor0.01 - 99.99A [Depend on motor]
P01.12 Rated current of pump6 7.5kW above motor0.1 - 999.9A [Depend on motor]
7.5kW and below motor0.01 - 99.99A [Depend on motor]
―56―HD31 Series User Manual V1.1
Shenzhen Hpmont Technology Co., Ltd. Chapter 6 Function Introduction
Ref. Code Name Description Setting Range [Default]
P01.13 Rated current of pump7 7.5kW above motor0.1 - 999.9A [Depend on motor]
7.5kW and below motor0.01 - 99.99A [Depend on motor]
Please set the above rated current according to the nameplate on the motor. These parameters will affect
the overload protection of HD31 for the motor.
6.3.3 P02: Water Supply PID Parameter
Ref. Code Name Description Setting Range [Default]
P02.00 Pressure setting source 0 - 2 [0]
0: Digital setting. P02.01 sets the setting pressure.
1: Pressure setting of timing water supply. P02.02 - P02.26 set the setting pressure.
2: Pressure setting of analogue water supply. The selected analogue of P03.00 - P03.03 set the setting
pressure.
P02.01 Pressure digital setting 0.0 - P05.03×10 [0.0 kg/cm2]
Used for digital pressure setting. 100.0% of digital setting is corresponding to 10V or 20mA.
Note:
1. 100.0% of the feedback signal is corresponding to 10V or 20mA.
2. 100% of P00.05
P02.26, P04.00 and P04.02 is corresponding to 10V or 20mA.
3. 100% of P00.06, P00.10, P00.18 and P00.20 is corresponding to the setting pressure of P02.00.
P02.02 Pressure time 1 - 12 [1]
P02.00 = 1, multi-time pressure is valid.
P02.03 T1 start time 00.00 - 23.59 [00.00]
P02.05 T2 start time 00.00 - 23.59 [00.00]
P02.07 T3 start time 00.00 - 23.59 [00.00]
P02.09 T4 start time 00.00 - 23.59 [00.00]
P02.11 T5 start time 00.00 - 23.59 [00.00]
P02.13 T6 start time 00.00 - 23.59 [00.00]
P02.15 T7 start time 00.00 - 23.59 [00.00]
P02.17 T8 start time 00.00 - 23.59 [00.00]
P02.19 T9 start time 00.00 - 23.59 [00.00]
P02.21 T10 start time 00.00 - 23.59 [00.00]
P02.23 T11 start time 00.00 - 23.59 [00.00]
P02.25 T12 start time 00.00 - 23.59 [00.00]
P02.04 T1 time pressure 0.0 - P05.03×10 [0.0 kg/cm2]
P02.06 T2 time pressure 0.0 - P05.03×10 [0.0 kg/cm2]
P02.08 T3 time pressure 0.0 - P05.03×10 [0.0 kg/cm2]
P02.10 T4 time pressure 0.0 - P05.03×10 [0.0 kg/cm2]
P02.12 T5 time pressure 0.0 - P05.03×10 [0.0 kg/cm2]
P02.14 T6 time pressure 0.0 - P05.03×10 [0.0 kg/cm2]
P02.16 T7 time pressure 0.0 - P05.03×10 [0.0 kg/cm2]
P02.18 T8 time pressure 0.0 - P05.03×10 [0.0 kg/cm2]
P02.20 T9 time pressure 0.0 - P05.03×10 [0.0 kg/cm2]
P02.22 T10 time pressure 0.0 - P05.03×10 [0.0 kg/cm2]
P02.24 T11 time pressure 0.0 - P05.03×10 [0.0 kg/cm2]
Make wave filter to the output frequency signal of the regulator, and avoid the jumping interfering signal to
P02.34 Regulating characteristic of pressure closed-loop 0,1 [0]
0: Positive characteristic. When the setting is added, pressure increases.
P02.35 Digital setting for saving selection when power failure 0,1 [1]
0: Not saving.
time.
• Principle of time s etting: T1 ≤ T2 ≤ T3 ≤ T4 ≤ T5 ≤ T6 ≤ T7 ≤ T8 ≤ T9 ≤ T10 ≤ T11 ≤ T12.
• T1 refers to the beginning of T1 till beginning of T2; T2 refers to the beginning of T2 till the beginning of
T3, and so forth. T12 refer to the beginning of T12 till the beginning of T1.
• The beginning time of a certain period may be the same as its' previous one. In this case, the previous
one joins to this period.
• There is only one period per day if T1 = T2 = T3 = T4 = T5 = T6 = T7 = T8 = T9 = T10 = T11 = T12.
higher intensity will be.
adjustment for the tolerance of feedback / setting pressure.
• When the tolerance of feedback / setting pressure is 100%, the integral regulator, with the continuous
adjustment of P02.29, reaches the max. pressure (overlook the effect of P02.28 and P02.30).
• The shorter integration time is, the faster adjustment speed will be.
tolerance change of the feedback / setting pressure.
• The adjustment of the derivative adjustment is max. pressure if the feedback pressure changes 100%
within P02.30 (overlook the effect of P02.28 and P02.29).
• The longer integration time is, the higher adjustment intensity will be.
• The longer sampling time is, the slower response will be.
range, the re gulator stops regulating.
influence on the system.
• Adjustment sensitivity is affected by overlong time of wave filtering.
1: Negative characteristic. When the setting is added, pressure decreases.
1: Saving.
When P02.00 = 0 and inverter is in stop/running, setted pressure is displaying. We can adjust the setted
pressure through button or . After power failure, adjusted pressure value can be saved by P02.35.
―58―HD31 Series User Manual V1.1
Shenzhen Hpmont Technology Co., Ltd. Chapter 6 Function Introduction
6.3.4 P03: Water Supply AIO Function Parameter
Ref. Code Name Description Range setting [Default]
P03.00 AI1 function 0 - 3 [0]
P03.01 AI2 function 0 - 3 [0]
P03.02 AI3 function 0 - 3 [0]
P03.03 AI4 function 0 - 3 [0]
0: Unused.
1: Analogue pressure setting.
• When P02.00 = 2 (pressure setting of analogue water supply), this function is selected by analogue
source, which corresponds to input voltage. The input voltage sets the setting pressure.
2: Analogue feedback setting.
• This function is selected by analogue source, which corresponds to input voltage. The input voltage
sets the feedback pressure.
3: Anologue WL feedback
• When P00.01 = 2 (WL signal is set by analogue source), this function is selected by analogue source,
which corresponds to input volta ge. The input voltage decides the WL signal.
Note:
1. Once set P03.00 - P03.01, the corresponding F16.01 - F16.02 are invalid.
2. 0 - 10V of AI1 - AI4 are corresponding to feedback signal 0 - 100.0%.
P03.04 DI1 function 0 - 19 [0]
P03.05 DI2 function 0 - 19 [0]
P03.06 DI3 function 0 - 19 [0]
P03.07 DI4 function 0 - 19 [0]
P03.08 DI5 function 0 - 19 [0]
P03.09 DI6 function 0 - 19 [0]
P03.10 DI7 function 0 - 19 [0]
P03.11 DI8 function 0 - 19 [0]
P03.12 DI9 function 0 - 19 [0]
0: Unused.
1 - 7: pump 1 - 7 commissioning running.
• Respectively specify inverter drive motor that needs commissioning start. When the commission
terminal of the specified variable frequen cy pump is valid, the pump will start with variable frequenc y,
and switch to power frequency after meeting P00.08. If there are multiple valid commission terminals,
HD31 starts and switches them according to their consequence of switch off.
8 - 14: pump 1 - 7 invalid.
• Respectively specify motors that needs to quit the system. When the command is effective, the
corresponding motor will not participate in switch logic of the system. This function enables force quit
if the motor needs inspecting or fault occurs to the motor. That can enhance the switch efficiency.
15: Upper limit water level( WL) of intake pool.
16: Lower limit WL of intake pool.
17: Water shortage WL.
• When P00.01 =1 , No. 15- 17 decide the upper limit WL, lower limit WL and water shortage WL.
18: Upper limit WL of sewage pool.
19: Lower limit WL of sewage pool.
• The sewage pump is triggered into use when WL of sewage pool exceeds upper limit WL; otherwise it
deactivates and stops output.
Note: After setting the P03.04 - P03.09 functions, the corresponding F15.00 - F15.05 function are invalid.
6
HD31 Series User Manual V1.1 ―59―
Chapter 6 Function Introduction Shenzhen Hpmont Technology Co., Ltd.
Ref. Code Name Description Setting Range [Default]
P03.13 DO1 function 0 - 23 [0]
P03.14 DO2 function 0 - 23 [0]
P03.15 RLY1 function 0 - 23 [0]
P03.16 RLY2 function 0 - 23 [0]
P03.17 RLY3 function 0 - 23 [0]
P03.18 RLY4 function 0 - 23 [0]
P03.19 RLY5 function 0 - 23 [0]
P03.20 RLY6 function 0 - 23 [0]
P03.21 RLY7 function 0 - 23 [0]
P03.22 RLY8 function 0 - 23 [0]
P03.23 RLY9 function 0 - 23 [0]
P03.24 RLY10 function 0 - 23 [0]
0: Unused. No output function.
1,3,5,7,9,11,13: pump 1 - 7 variable frequency running.
2,4,6,8,10,12,14: pump 1 - 7 power frequency running.
• Define the control signal of every pump. HD31 drive pump needs both control signals of variable
frequency and industrial signal.
• Please do wiring correctly during commissioning.
• Only power frequency signal is effective for power frequency pump, sewage pump and dormant
pump.
15: Dormant running.
• This signal is valid when the system is in dormant running mode.
16: Over-pressure.
• This signal is valid when the pressure of pipe network is pressure of P04.00 or above, and sustains the
setting time of P04.01.
17: Under- pressure.
• This signal is valid when pipe network pressure is pressure of P04.02 or below, and sustains the setting
time of P04.03.
18: Backup pressure running.
• This signal is valid when the system meets the running condition of backup pressure and runs
according to it.
• Refer to P00.01 - P00.05.
19: Pool water shortage.
• This signal is valid when WL of the intake pool < shortage WL.
20: WL of the sewage pool reaches the upper limit.
• This signal is valid when WL of the sewage pool exceeds the upper limit WL.
21: Faulty pump occurs.
• This signal is valid when P04.04 is not 0.
22: Unused.
23: The supply system is in running status.
• This signal is valid when the water supply system is in running status.
Note: After setting the P03.13 - P03.15 functions, the corresponding functions of F15.18 - F15.20 are invalid.
―60―HD31 Series User Manual V1.1
Shenzhen Hpmont Technology Co., Ltd. Chapter 6 Function Introduction
6.3.5 P04: Water Supply Fault Protection Parameter
Ref. Code Name Description Setting Range [Default]
P04.00 Setting value of over-pressure protection 0.0 - P05.03×10 [0.0 kg/cm2]
P04.01 Detection time of over-pressure protection 0.0 - 3600.0 [300.0s]
The system alarms for over-pressure when the pipe network pressure reaches the max. setting of P04.00
P04.02 Setting value of under-pressure protection 0.0 - P05.03×10 [0.0 kg/cm2]
P04.03 Detection time of under-pressure protection 0.0 - 3600.0 [300.0s]
Alarm on and off for under-pressure protection is similar with over-pressure protection (refer to P04.00 and
P04.04 Record of faulty pump 0 - 0x7F [0]
P04.05 Troubleshooting for the inverter 0,1 [0]
0: The whole system stops.
and sustains the setting time of P04.01.
The alarm will stop only after value of the pipe network pressure is no more than the over-pressure
protection value and sustains the setting time of P04.01.
P04.01).
• When an variable frequency pump occurs fault which can be reset, the system automatically reset the
pump according to F20.18 and F20.19. If the fault can not be reset, the system automatically stops the
pump.
• Reset times for fault > setting value of F20.18 and fault still exits, HD31 records this pump (its bit set as 1)
and marks it as invalid. Meanwhile, the faulty pump quits the system and does not participate in the
switch logic.
• The following figure shows corresponding relationship between the pump and the position.
Bit8 Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1
Unuse d Pum p 7 Pum p 6 Pum p 5 Pum p 4 Pum p 3 Pump 2 Pump 1
• The faulty pump which had troubleshot can participate the switch logic only after clear fault information
(F01.02 = 4).
Example: P04.04 = 0x18= 00011000B indicates that the pump 4 and pump 5 occurs fault.
• Record the current faulty pump and stop the whole water supply system.
• If the the system had set auto-reset function, it will reset for the corresponding times and carry out the
above operation. Otherwise it will carry out the above operation directly without reset.
1: HD31 automatically switches to the next variable frequency pump; while if there is no such pump, HD31
controls in power frequency mode.
• Record the current faulty pump and quit the water supply system. The system preferentially starts an
inverter drive one if there are variable frequency pump or power frequency pump ready to run.
• If the the system had set auto-reset function, it will reset for the corresponding times and carry out the
above operation. Otherwise it will carry out the above operation directly without reset.
6.3.6 P05: Water Supply Time Parameter
Ref. Code Name Description Setting Range [Default]
P05.00 Set current time ( Year) 11 – 99 [Actual value]
Set time of the system: Year.
P05.01 Set current time (Month & Date) 0101 – 1231 [Actual value]
Set time of the system: Month & Date.
P05.02 Set current time (Hour & Minute) 0000 – 2359 [Actual value]
Set time of the system: Hour & Minute.
6
HD31 Series User Manual V1.1 ―61―
Chapter 6 Function Introduction Shenzhen Hpmont Technology Co., Ltd.
Ref. Code Name Description Setting Range [Default]
P05.03 Pressure sensor range setting 0.0 - 10.0 [1.6MPa]
1MPa=10kg/cm2.
P05.04 Pressure sensor signal type selection 0 - 2 [0]
0: 0 - 10V.
1: 0 - 20mA.
2: 4 - 20mA.
Note:
1. Only the AI2, AI3, AI4 terminals can be input the current signal and need to change the CN6 of the control
board or the CN2 or CN3 jumper on water supply card. Please refer to the jumper description in the user manual
for details.
2. When P05.04 = 2, set the F05.00 teb bit to 1 and set F05.05 = 20.0%. When P05.04 = 0 or 1, set F05.00 ten bit to
0 and set to F05. 05 = 0.0%.
P05.05 Water supply method selection 0x00 - 0x75 [0x00]
Modify P05.05 and system will automatically set P01.00 - P01.06, P03.15 - P03.24. Set the principle:
Follow P01.00 - P01.06 to set the frequency conversion / power frequency pump, set P03.16 - P03.24,
P03.15 power and variable frequency control in turns.
For ex ample
Ref. Code Funct ion Va lue Defination
P01.00 Pum p 1 type 1 Pump 1 is
P01.01 Pum p 2 type 1 Pump 2 is
P01.02 Pum p 3 type 1 Pump 3 is
P01.03 Pum p 4 type 1 Pump 4 is
P01.04 Pum p 5 type 2 Pump 5 is power fre quency pu mp
P01.05 Pum p 6 type 2 Pump 6 is power fre quency pu mp
P01.06 Pum p 7 type 0 Invalid
P03.15 RLY1 function 12 Pump 6 power frequency running
P03.16 RLY2 function 1 Pump 1 variable frequency running
P03.17 RLY3 function 2 Pump 1 power frequency running
P03.18 RLY4 function 3 Pump 2 variable frequency running
P03.19 RLY5 function 4 Pump 2 power frequency running
P03.20 RLY6 function 5 Pump 3 variable frequency running
P03.21 RLY7 function 6 Pump 3 power frequency running
P03.22 RLY8 function 7 Pump 4 variable frequency running
P03.23 RLY9 function 8 Pump 4 power frequency running
P03.24 RLY10 function 10 Pump 5 power frequency running
Note:
1. A bit indicates the number of variable frequency pumps in the system; ten indicates the number of frequency
pumps in the system.
2. The number of frequency pump plus frequency pump can not exceed 7, the total number of relays can not be
more than 10.
: Set P05.05 = 0x24, the parameters automatically set, as follows:
For the braking unit HDBU-4T150, the max. braking current is 150A. Refer to the “HDBU Series Dynamic
Braking Unit User Manual” for more details.
The braking resistor selection is shown as Table 9-2. If needed, please order goods.
The connection of braking resistor and the braking unit is shown as section 4.3.2 Supply and Motor
Connection (on page 18).
Table 9-2 Recommendation for the braking unit and braking resistor
Model Motor Braking unit Braking resistor Value Braking resistor power
HD31-4T2P2P 2.2 kW Built-in 200 - 300 Ω 0.2 kw
HD31-4T3P7P 3.7 kW Built-in 150 - 250 Ω 0.25 kw
HD31-4T5P5P 5.5 kW Built-in 100 - 150 Ω 0.3 kW
HD31-4T7P5P 7.5 kW Built-in 80 - 100 Ω 0.5 kW
HD31-4T011P 11 kW Built-in 60 - 80 Ω 0.7 kW
HD31-4T015P 15 kW Built-in 40 - 50 Ω 1 kW
HD31-4T018P 18.5 kW Built-in 30 - 40 Ω 1.5 kW
HD31-4T022P 22 kW Built-in 25 - 30 Ω 2 kW
HD31-4T030P 30 kW Built-in 20 - 25 Ω 2.5 kW
HD31-4T037P 37 kW Built-in 15 - 20 Ω 3 kW
HD31-4T045P 45 kW Built-in 15 - 20 Ω 3.5 kW
HD31-4T055P 55 kW Built-in 10 - 15 Ω 4.5 kW
HD31-4T075P 75 kW Built-in 10 - 15 Ω 5.5 kW
HD31-4T090P 90 kW HDBU-4T150 8 - 10 Ω 7.5 kW
HD31-4T110P 110 kW HDBU-4T150 8 - 10 Ω 9 kW
HD31-4T132P 132 kW HDBU-4T150 6 - 8 Ω 11 kW
Note:
1. Please select braking resistor based on the above table.
Bigger resistor can protect the braking system in faulty condition, but oversized resistor may bring a
capacity decrease, leading to over voltage protection.
2. The braking resistor should be mounted in a ventilated metal housing to prevent inadvertent contact
during it works, for the temperature is high.
―72―HD31 Series User Manual V1.1
Shenzhen Hpmont Technology Co., Ltd. Appendix A Parameters
Appendix A Parameters
Attributes are changed:
“X”: It denotes that the setting of this parameter cannot be modified when HD31 is in run status.
“O”: It denotes that the setting of this parameter can be modified when HD31 is in run status.
“*”: It denotes that the value of this parameter is the actual value which cannot be modified.