Chapter 7 Troubleshooting Shenzhen Hpmont Technology Co., Ltd.
-22- HD09 Series User Manual V1.1
Fault Fault reasons Counter-measures
E0007 Stall overvoltage
• Bus voltage is too high
• The setting of stall overvoltage is
too low
• Please check power input or the
function of brake
• Set the value of stall overvoltage
properly (F19.19)
E0008
Fault of power
module
• Short circuit between phases
output
• Short circuit to the ground
• Output current is too high
• Power module is damaged
• Please check the connection and
connect the wire properly
• Please check the connection and
connect the wire properly
• Please check the connection and
mechanism
• Please contact the supplier for
repairing
E0009 Heatsink overheat
• Ambient temperature is too high
• Inverter external ventilation is
not good
• Fan fault
• Fault occurs to temperature
detection circuit
• Please use inverter with higher
power capacity
• Improve the ventilation around the
inverter
• Replace the cooling fan
• Please seek technical support
E0011 CPU fault • CPU abnormal
• Please detect at power on after
completely power outage
• Please seek technical support
E0012
Parameters
auto-tuning fault
• Parameter auto-tuning is time
out
• Please check the motor’s connection
• Input the correct motor parameters
(F08.01 - F08.03)
• Please seek technical support
E0013
Contactor is not
actuated
• Contactor fault
• Fault of control circuit
• Replace the contactor
• Please seek technical support
E0014
Fault of current
detection circuit
• Current detection circuit is
damaged
• Please contact the supplier for
repairing
E0016 Fault of output phase
• Output phase disconnection or
loss
• Heavy imbalance of inverter’s
three-phase load
• Please check the connection
between inverter and motor
• Please check the quality of motor
E0017 Inverter overload
• Acceleration time is too short
• Improper setting of V/f curve or
torque boost leads to over
current
• Mains supply voltage is too low
• Motor load is too high
• Adjust acceleration time (F03.01)
• Adjust V/f curve (F09.01 - F09.06) or
torque boost (F09.07, F09.08)
• Please check mains supply voltage
• Please use inverter with proper
power rating