HPE G2 Metered and Switched Power Distribution Units

Overview

Page 1
New G2 features allow for greater management of power and environment in IT racks
HPE Enterprise Series G2 Metered and Switched PDUs are designed to work precisely with HPE Infrastructure and Compute solutions for your stan warranty operational reliability for power distribution in your IT rac
A major concern for IT administrators and facility managers is their ability to quickly diagnose and service power related pr in their IT racks
r simple and
quick access to IT equipment and power cables in the rear of the rack
HPE G2 Metered & Switched PDU features alleviates the need to maintain older switch soluti density outlet configurations that provide up to 48 power outlets power in the rack while minimizing physical cabl and exhaustive
in both the front and rear
of the rack.
All G2 Metered & Switched PDU most HPE G2 PDUs against vibration during shipping Cords provide a safe and secure solution against the common issues that lead to power
Why
HPE offers multiple Metered PDU form factors that promote efficient use of space in the rack and provide flexibility in how
, providing a highly accurate (billing grade accuracy) power distribution solution with outlet-level metering and switching
IT racks. Designed for use with HPE Standard, Advanced, and Enterprise racks (and compatible with other industry-
dard server racks), HPE G2 Metered and Switched PDUs guaranty a compatible fit and reliable operation backed by a 3 year
. HPE G2 Metered & Switched PDUs are also rated for operating temperatures up to 60°C, adding an increased level of
ks.
. G2 Metered & Switched PDU features such as color-coded outlets and low-profile form factors allow fo
.
are also directly focused on other pain points in the data center. 1Gb Ethernet
ons that have been traditionally required for PDU network connectivity. High-
in a full-height vertical form factor allow for simple access to
e requirements. Support for up to eight sensors per PDU provides a cost-effective
solution for monitoring the environmental elements (temperature, humidity, and leakage)
models feature support for HPE’s IEC Locking Power Cords, a new supported option available for
. The IEC Locking Power Cords provide secure cable retention to both the PDU and target device, protecting
and ensuring that cables are not dislodged during a service event. HPE’s IEC Locking Power
HPE Metered and Switched PDUs?
HPE Foundation Care services purchased for server and storage products, such as extended warranties and premium
support services, extend to our PDU products free of charge when purchased together.
HPE guarantees 100% compatibility between its Rack and Power Infrastructure products and its industry-standard
compute, storage, and networking solutions, backed with a 3-year warranty for all G2 Metered PDU models.
each PDU can be mounted and configured with cables.
-related downtime.
oblems
QuickSpecs
HPE G2 Metered and Switched Power Distribution Units

Models

Page 2
200-208V Input, Single Phase, North America/Japan
HPE G2 Metered/Switched 4.9kVA/L6-30P 24A/208V Outlets (20) C13, (4) C19/Vertical NA/JP PDU
P9S15A
220-240V Input, Single Phase, International
HPE G2 Metered/Switched 7.3kVA/60309 3-Wire 32A/230V Outlets (20) C13, (4) C19/Vertical INTL PDU
P9S18A
200-208V Input, Three Phase, North America/Japan
HPE G2 Metered/Switched 3Ph 8.6kVA/L15-30P 24A/208V Outlets (18) C13, (6) C19/Vertical NA/JP PDU
P9S19A
HPE G2 Metered/Switched 3Ph 14.4kVA/CS8365C 40A/208V Outlets (12) C13, (12) C19/Vertical NA/JP PDU
P9S21A
HPE G2 Metered/Switched 3Ph 17.3kVA/60309 4-wire 48A/208V Out (12) C13, (12) C19/Vertical NA/JP PDU
P9S22A
HPE G2 Metered/Switched 3Ph 17.3kVA/60309 4-wire 48A/208V Out (36) C13, (12) C19/Vertical NA/JP PDU
P9S23A
220-240V Input, Three Phase, International
HPE G2 Metered/Switched 3Ph 11kVA/60309 5-Wire 16A/230V Out (18) C13, (6) C19/Vertical INTL PDU
P9S20A
HPE G2 Metered/Switched 3Ph 22kVA/60309 5-Wire 32A/230V Out (12) C13, (12) C19/Vertical INTL PDU
P9S24A
HPE G2 Metered/Switched 3Ph 22kVA/60309 5-Wire 32A/230V Out (36) C13, (12) C19/Vertical INTL PDU
P9S25A
QuickSpecs
HPE G2 Metered and Switched Power Distribution Units
Models
Page 3
Single-Phase Full-Height Model (P9S15A, P9S18A)
Three-Phase Full-Height Model (P9S21A, P9S24A)
Three-Phase High-Density Outlet Model (P9S23A, P9S25A)
QuickSpecs
HPE G2 Metered and Switched Power Distribution Units

Key Features

Page 4
Power Metering and Management
All G2 HPE Metered & Switched PDUs meet IEC 62053-21, Class 1 standards for ±1% or better accuracy in
o Kilowatts per hour
OLED display provides local monitoring and alert indications
CLI, and third-party software applications supporting SNMP
Compatibility
Designed specifically for use with HPE rack enclosures, but compatible with most 3rd party IT racks
Integrated web-based user interface compatible with IPv4/IPv6 and SNMPv1/SNMPv3
Usability
Multiple full-height vertical models with a range of outlet configurations
Local and remote firmware updates
Security
Outlet-level on/off power switching that can be accessed locally and remotely
Configurable alarm thresholds for both power and environmental monitoring
HPE G2 Metered & Switched PDUs support multiple features that are unique to HPE and help to provide the best user experience. Inf User’s Guide.
Rated for High Operating Temperatures
Increasing IT densities and escalating operating costs have created a need for rack infrastructure that can operate reliably at higher operating temperatures rated premium components and construction that support increased reliability levels at elevated temperatures HPE G2 PDUs are rated for operation in temperatures up to 60°C (or 140°F) in the rear of the rack.
IEC Locking Power Cords
HPE G2 PDU models support optional IEC Locking Power Cords with an integrated locking technology on both ends of the cable multiple cable length options, and can be purchased in single or six been included with each PDU model that supports either a C13 and/or C19 outlet.
High-Density Vertical PDU Models
High-density Vertical PDU models provide 48 outlets in a full-height (42U) form factor. This density is achieved by placing the power receptacles on one side of the PDU and access to the circuit breakers on the opposite side without significantly impacting the height (profile) of the PDU information on high-density PDU models.
Color-Coded Outlets
All HPE G2 PDU models now include color-coded outlets which are highly visible from the rear of the rack. The color configuring your IT equipment.
1Gb Ethernet Support
HPE is the first IT solutions company to standardize on 1Gb Ethernet for PDU network connectivity. This eliminates the need to maintain older switching solutions needed for the 10/100 connectivity provided by most other PDU manufacturers.
outlet-level power metering of:
o Amperage o Voltage o Wattage
Remote PDU management and power monitoring supported through integrated web-based user interface,
Low-profile form factors ensure integrity of rear-rack keep-out zone for IT maintenance Color-coded receptacles to easily distinguish between the different load segments/phases Integrated cord retention for all IEC C19 and C13 receptacles Optional dual-locking power cords securing both power connections
Local and LDAP security with multiple access levels Support for HTTP, HTTPS, and SSH protocols
ormation on these features is summarized below with additional information found online in HPE G2 Metered & Switched PDU
. HPE G2 PDUs have been designed with high temperature-
. HPE Locking Power Cord are available for both C13/14 and C19/20 power receptacles in
-pack kits. One IEC Locking Power Cord has
. See the Model Matrix section for more
.
-coding helps to easily and clearly identify outlets to simplify cabling and power phase balancing when
QuickSpecs
HPE G2 Metered and Switched Power Distribution Units
Key Features
Page 5
Environmental Sensors
HPE G2 Metered & Switched PDU models include two environmental sensor ports (can be upgraded to six ports with the addition of up to two measurements
midity, water
leakage, and intrusion for each rack. Please review the Related Options section for a list of the options available.
Flexible Mounting
Most vertical HPE G2 PDU models support mounting on the back and both sides of the PDU using an industry­standard button and keyhole mounting capability that allows power cables to be configured rack.
HPE PDU Extension Ba Options
HPE PDU extension bar options help expand the availability of power in the rear of the rack. Each extension bar includes a locking input power cord that connects to the PDU and supports HPE’s new IEC Locking Power Cords for C13/C14 and C19/C20 o models the rack when needed the flexibility of placing access to power where it is options are available to help you customize the outlet configurations you require compatible with previous generation PDU models that offer C20 outlets (locking feature only supported on new G2 PDU models). See the Related Options section for more information on G2 Extension Bar models.
3-Year Warranty
HPE G2 Metered PDU models are supported with a 3-year warranty. Additionally, the HPE Foundation Care Extension program provides additional support and services for your PDU models when purchased with HPE servers, storage, and networking solutions at no additional charge Additional
http://h17007.www1.hpe.com/us/en/enterprise/servers/warranty/index.aspx#.V-10xE3rvbq
G2 PDU Sensor Port Hubs) that can monitor and record up to eight sensor
. Multiple senor options are available providing the ability to monitor temperature, hu
system for easy drop-in installation. This provides a flexible mounting
with outlets facing toward the center, back, or front of the
r
utlets. HPE PDU extension bars can be added to Horizontal and Vertical PDU
, with available C19 outlets, to add additional power outlets and expand access to power in the back of
. Extension Bars mount directly to the frame of the rack in multiple locations allowing you
needed most (see figure above). Multiple extension bar
extension bars are also
.
information regarding worldwide limited warranty and technical support is available at:
QuickSpecs
HPE G2 Metered and Switched Power Distribution Units

Related Options

Page 6
Related Options
Extension Bars
HPE G2 IEC C20 Input/(8) C13 Expansion Outlets/PDU Extension Bar Kit
P9Q66A
HPE G2 IEC C20 Input/(4) C13 (2) C19 Expansion Outlets/PDU Extension Bar Kit
P9Q67A
HPE G2 IEC C20 Input/(7) 5-20R Expansion Outlets/PDU Extension Bar Kit
P9Q68A
NOTE: All kits include 2 extension bars with a locking C19 input power cord (1.8m).
IEC Locking Power Cords
HPE C13 - C14 WW 250V 10Amp 0.7m Black Locking Power Cord
Q0P67A
HPE C13 - C14 WW 250V 10Amp 0.7m Black 6-pack Locking Power Cord
Q0Q02A
HPE C13 - C14 WW 250V 10Amp 1.4m Black Locking Power Cord
Q0P68A
HPE C13 - C14 WW 250V 10Amp 1.4m Black 6-pack Locking Power Cord
Q0Q03A
HPE C13 - C14 WW 250V 10Amp 2m Black Locking Power Cord
Q0P69A
HPE C13 - C14 WW 250V 10Amp 2m Black 6-pack Locking Power Cord
Q0Q04A
HPE C13 - C14 WW 250V 10Amp 3m Black Locking Power Cord
Q0P70A
HPE C13 - C14 WW 250V 10Amp 3m Black 6-pack Locking Power Cord
Q0Q05A
HPE C19 - C20 WW 250V 16Amp 0.7m Black Locking Power Cord
Q0R19A
HPE C19 - C20 WW 250V 16Amp 0.7m 6-pack Black Locking Power Cord
Q0R15A
HPE C19 - C20 WW 250V 16Amp 1.2m Black Locking Power Cord
Q0P71A
HPE C19 - C20 WW 250V 16Amp 1.2m 6-pack Black Locking Power Cord
Q0R16A
HPE C19 - C20 WW 250V 16Amp 2m Black Locking Power Cord
Q0P72A
HPE C19 - C20 WW 250V 16Amp 2m 6-pack Black Locking Power Cord
Q0R17A
HPE C19 - C20 WW 250V 16Amp 2.5m Black Locking Power Cord
Q0P73A
HPE C19 - C20 WW 250V 16Amp 2.5m 6-pack Black Locking Power Cord
Q0R18A
NOTE: HPE Locking Power Cords are only supported on either C13/14 or C19/20
outlets using HPE G2 PDUs.
IEC Standard Power Cords
HP C13 - C14 WW 250V 10A Gray 0.7m Jumper Cord
A0K03A
HP C13 - C14 WW 250V 10Amp 0.7m Jumper Cord
142257-B28
HP C13 - C14 WW 250V 10Amp 1.4m Jumper Cord
142257-006
HP C13 - C14 WW 250V 10A Gray 1.37m Jumper Cord
A0K04A
HP C13 - C14 WW 250V 10Amp 1.4m 15 pc Jumper Cord
142257-007
HP C13 - C14 WW 250V 10Amp 2.0m Jumper Cord
A0K02A
HP C13 - C14 WW 250V 10Amp Flint Gray 2.0m Jumper Cord
AF573A
HP C13 - C14 WW 250V 10Amp 2.5m Jumper Cord
142257-002
HP C13 - C14 WW 250V 10Amp 3.0m Jumper Cord
142257-003
HP C13 - C14 WW 250V 10A Gray 3.0m Jumper Cord
A0K06A
HP C20 - C13 WW 250V 15Amp 2.0m Jumper Cord
AF590A
HP C19 - C20 WW 250V 16Amp Flint Gray 1.20m Jumper Cord
AF575A
HP C19 - C20 WW 250V 16Amp Flint Gray 2.0m Jumper Cord
AF574A
HP C19 - C20 WW 250V 16Amp 2.5m Jumper Cord
295633-B22
HP 200-250V 10A C15 to C14 .76m Jumper Cable
E7807A
Country-Specific Power
HP C13 - NEMA 5-15P US/CA 110V 10Amp 1.83m Power Cord
AF556A
HP C13 - NEMA 5-15P TH/PH 250V 10Amp 1.83m Power Cord
AF559A
HP C19 - CEE-VII EU 250V 16Amp 3.6m Power Cord
AF576A
HP C19 - AS3112-3 AU/NZ 250V 15Amp 3.6m Power Cord
AF577A
HP C19 - SABS-164 ZA 250V 16Amp 3.6m Power Cord
AF579A
HP C19 - CEI-23-50 IT/CL 250V 16Amp 3.6m Power Cord
AF580A
HP C19 - IEC-309 DK/SE/AR 250V 16Amp 3.6m Power Cord
AF581A
Cords
QuickSpecs
HPE G2 Metered and Switched Power Distribution Units
Related Options
Page 7
HP C19 - IS-1293 IN/PK/BD 250V 16Amp 2.5m Power Cord
AF582A
HP C19 - ISI-32 IL 250V 16Amp 2.5m Power Cord
AF583A
HP C19 - GB-1002 CN 250V 16Amp 2.5m Power Cord
AF584A
HP C19 - NEMA 5-15P TH-PH 125V 15Amp 3.6m Power Cord
AF586A
HP C19 - NBR-14136 BR 250V 16Amp 2.5m Power Cord
AF592A
HP C19 - NEMA 5-15 US/CA 125V 15Amp 3.6m Power Cord
235603-001
HP C19 - NEMA L6-20P NA/JP 250V 20Amp High Voltage 3.6m Power Cord
AF593A
HP C19 - BS-1363/A UK/HK/SG 250V 13Amp 3.6m Power Cord
359615-031
HP C19 - NEMA 5-20P US/CA 125V 20Amp 4.5m Power Cord
E7802A
HP 240 VAC 4.5M Unterminated End NA Power Cord
E7806A
HPE Mounting Brackets
HPE Vertical PDU 10K G2 Mounting Kit
H6L32A
NOTE: This kit allows for vertical HPE G2 PDU models to be mounted in HPE 10000 G2 series racks and in the HPE Standard Series rack.
Environmental Sensors
HPE G2 Metered PDUs include 2 physical sensor ports and can monitor and record up to eight sensor measurements user interface (GUI), or by third supported API software applications.
HPE G2 PDU Environmental Temperature Sensor
NOTE: Requires one input port and monitor/records one sensor measurement.
P9T00A
HPE G2 PDU Environmental Temperature and Humidity Sensor
NOTE: Requires one input port and monitors/records two sensor measurements.
P9T01A
HPE G2 PDU Environmental 3-Temperature and 1-Humidty Sensor
NOTE: Requires one input port and monitors/records four sensor measurements.
P9T02A
HPE G2 PDU Open/Close Door Sensor
NOTE:
P9T03A
HPE G2 PDU Leak Detection Sensor
NOTE:
covers up to six linear meters and can be expanded to cover up to thirty linear meters with the addition of up to four HPE G2 PDU Leak Detection Sensor Extension Kits (P9T08A).
P9T04A
HPE G2 PDU Sensor Port Hub
NOTE:
sensor ports.
P9T07A
HPE G2 PDU Leak Detection Sensor Extension Kit
NOTE:
con Detection Sensor to cover up to a maximum of thirty linear meters.
P9T08A
. Data collected by each sensor can be viewed and managed through the integrated graphical
-party applications that communicate through SNMP or through a Redfish
. Consult the HPE G2 Metered PDU User Guide for more information on use with third-party
Requires two input ports and monitors/records two sensor measurements.
Requires one input port and monitors/records one sensor measurement. Kit
This is an adapter that expands a single physical sensor port into three physical
Leak Detection Sensor (P9T04A) must be purchased separately to use in
junction with this kit. Up to four Extension Kits can be added to a single Leak
QuickSpecs
HPE G2 Metered and Switched Power Distribution Units
Model
Matrix – Input Power
Page 8
Mounting options for Vertical PDU models in HPE Advanced and Enterprise racks (1075mm depth)
W x H x D
(inches)
Unit Weight
(lbs.)
Maximum PDUs per Side of Rack
22U
36U
42U
48U
P9S15A
2.047 x 68.898 x 2.087
17.6
Full-Height
- - 2
2
P9S18A
2.047 x 68.898 x 2.087
15.0
Full-Height
- - 2
2
P9S19A
2.047 x 68.898 x 2.087
16.2
Full-Height
- - 2
2
P9S20A
2.047 x 68.898 x 2.087
12.5
Full-Height
- - 2
2
P9S21A
2.047 x 68.898 x 2.953
25.2
Full-Height
- - 1
1
P9S22A
2.047 x 68.898 x 2.953
25.6
Full-Height
- - 2
2
P9S23A*
2.047 x 71.654 x 4.409
32.0
Full-Height
- - 2
2
P9S24A
2.047 x 68.898 x 2.953
20.2
Full-Height
- - 2
2
P9S25A*
2.047 x 71.654 x 4.409
24.2
Full-Height
- - 1
1
* HPE high density model mounts on its side with outlets facing the back of the rack
NOTE: HPE G2 Advanced and Enterprise 1200mm deep racks include an extra set (2) of PDU trays in the rear of the rack
enabling support of up to 2x the number of PDUs listed above for 1075mm deep racks.

Model Matrix – Input Power

Phase & Nominal
Voltage
Input Cord
Length
P9S15A
NA/JP
1-ph, 208V
24A
(2) 2-pole 20A
L6-30P
10’
P9S18A
INTL
1-ph, 230V
32A
(2) 1-pole 16A
IEC 32A, 1ph
10’
P9S19A
NA/JP
3-ph, 208V
24A
(3) 2-pole 20A
L15-30P
10’
3-ph, 200-240V
P9S21A
NA/JP
3-ph, 208V
40A
(6) 2-pole 20A
CS8365C
10’
P9S22A
NA/JP
3-ph, 208V
48A
(6) 2-pole 20A
IEC 60A, 3ph
10’
P9S23A
NA/JP
3-ph, 208V
48A
(6) 2-pole 20A
IEC 60A, 3ph
10’
3-ph, 200-240V 3-ph, 346-415V
3-ph, 200-240V 3-ph, 346-415V
NOTE: All Input Circuit Ratings for NA/JP models have been de-rated according to NEC requirements.
Nominal Input Voltage Ratings used for calculating output power are as follows:
200 – 240V/346 – 415V: 230V
Model
Model Region
P9S20A INTL
3-ph, 346-415V
Vertical Height
Input Amps Circuit Breaker Input Plug Type
16A none IEC 16A, 3ph 10’
P9S24A INTL
P9S25A INTL
200 – 208V: 208V
220 – 240V: 230V
32A (6) 1-pole 16A IEC 32A, 3ph 10’
32A (6) 1-pole 16A IEC 32A, 3ph 10’
QuickSpecs
HPE G2 Metered and Switched Power Distribution Units
Model Matrix
– Output Power
Page 9
Model Matrix – Output Power
Support Extension Bar
P9S15A
NA/JP
4.9
200-208V
(20)C13, (4)C19
P9S18A
INTL
7.3
220-240V
(20)C13, (4)C19
P9S19A
NA/JP
8.6
200-208V
(18)C13, (6)C19
P9S20A
INTL
11
220-240V
(18)C13, (6)C19
P9S21A
NA/JP
14.4
200-208V
(12)C13, (12)C19
P9S22A
NA/JP
17.3
200-208V
(12)C13, (12)C19
P9S23A
NA/JP
17.3
200-208V
(36)C13, (12)C19
P9S24A
INTL
22
220-240V
(12)C13, (12)C19
P9S25A
INTL
22
220-240V
(36)C13, (12)C19
Model Region kVA
Output Voltage
Range
Output Receptacles
Options
Support Locking
Power Cord Options
QuickSpecs
HPE G2 Metered and Switched Power Distribution Units

PDU Plugs

Page 10
Sample Plug Image
(color may vary by manufacturer)
Receptacle (R)
Plug (P)
3
Voltage Amps # Wires Plug Name
100-125 V
Single Phase
200-240 V
Single Phase
15 A 3 NEMA 5-15
20 A 3 NEMA 5-20
30 A 3 NEMA L5-30
20 A 3 IEC C20
30 A 3 NEMA L6-30
32 A 3 IEC 309 32A
50 A
CS8265C
63 A 3 IEC 309 63A
200 - 208 V
Three Phase
200 – 240 V 400 – 415 V
Three Phase
NA/JPN
INTL
30 A 5 NEMA L15-30
30 A 5 NEMA L21-30
50 A 4 CS8365C
60 A 4 IEC 309 60A
16 A 5 IEC 309 16 A
32 A 5 IEC 309 32 A