HPE H5M71A, H5M72A Getting Started Guide

QuickSpecs
HPE Basic Power Distribution Units (PDU)

Overview

Page 1
HPE Basic Power Distribution Units (PDU)
HPE Basic PDUs are designed to provide reliable and cost effective power distribution for your Hewlett Packard Enterprise and non form factors allowing you to configure access to power in your rack where you need it the most.
HPE D
hey can be installed on either side of the rack with outlets facing the back of the rack for easy access and improved clearance. also
With effective power distribution supporting from 12 to 42 outlet receptacles and power levels ranging from can provide
HPE
a unique modular architecture designed specifically for data center customers who want to maximize power distribution and (core) and mounted in any 1U space or in the with some models, optional on other models)
allowing you to configure access to power where you need it Extension Bars installed) and power levels ranging from 2.8 kVA to 22k configurations.
0U/1U Models (H5M54A shown)
Half Height Models (H5M55A shown)
Mid Height Models (H5M62A shown)
Full Height Models (H5M67A/H5M73A shown)
-Hewlett Packard Enterprise IT racks. Offering simple 0U and 1U installation options, HPE Basic PDUs are available in multiple
Vertical Basic PDUs provide a low-profile single-piece design allowing for easy access to rear devices for maintenance.
esigned for HPE racks, but also compatible with a large variety of third party racks, t
For higher power density configurations, they can
be installed side by side on both sides of the rack with the outlets facing in towards the center of the rack.
2.8 kVA to 19.9kVA, HPE Vertical PDUs
single or three-phase power for most IT configurations.
Horizontal/Modular Basic PDUs offer
space efficiencies in the rack. These PDUs consist of two building blocks - the Control Unit
the Extension Bar(s) (sticks). The Control Unit is a core PDU module that offers up to six C-19 outlets which can be
true 0U space on the side of HPE racks between the RETMA rails. Extension Bars (included
mount directly to the frame of the rack in multiple locations
the most. HPE Horizontal/Modular PDU models support up to 42 outlet receptacles (with all
VA, with options for single or three-phase power
QuickSpecs
HPE Basic Power Distribution Units (PDU)
Overview
Page 2
Why do you need a Power Distribution Unit (PDU) for your rack?
power in your racks – for more information on these features, please visit the Hewlett Packard Enterprise PDU website.
Why buy HPE Power Distribution Units (PDU)?
HPE r
HPE servers
While you have many choices for rack and power infrastructure products, and KVM products to meet your needs.
and maintenance for your organization by providing a single point of contact for all your needs.
PDUs distribute the power supplied to your rack to multiple rack U locations to power devices such as servers, storage,
and networking equipment.
With rack densities ever-increasing as more and more equipment is added to your racks, PDUs allow you to conveniently
place access to power wherever you need most in your IT racks
PDUs can also offer additional features such as power monitoring and outlet switching to help you better manage the
Foundation Care services purchased for servers and storage extend to our rack and power infrastructure products such as
acks, power distribution units, uninterruptible power systems, and KVM console and switches.
What is the HPE advantage for you? You don’t have to spend additional budget to cover extended warranties and
services for your rack and power infrastructure as you would with non-Hewlett Packard Enterprise products.
rack and power infrastructure products are designed and developed to be used specifically with Hewlett Packard Enterprise
and storage.
What is the HPE advantage for you? You can use HPE rack and power products with non- Hewlett Packard Enterprise
IT equipment; however, when used with Hewlett Packard Enterprise servers, you are able to take advantage of various server and IP-based tools used for maintaining and managing all the equipment in the rack.
Hewlett Packard Enterprise offers a range of rack, power,
What is the HPE advantage for you? Hewlett Packard Enterprise can help to simplify IT purchasing, installation, usage,
QuickSpecs
HPE Basic Power Distribution Units (PDU)

Models

Page 3
Vertical, Single Phase, Half-Height (22U)
HPE Basic 2.8kVA/L5-30P 24A/120V Outlets (18) 5-20R/Vertical NA/JP PDU
H5M55A
HPE Basic 4.9kVA/60320 C20 Detachable 16A/230V Outlets (20) C13/Vertical WW PDU
H5M57A
HPE Basic 4.9kVA/L6-30P 24A/208V Outlets (20) C13/Vertical NA/JP PDU
H5M58A
HPE Basic 7.3kVA/60309 5-wire 32A/230V Outlets (20) C13/Vertical INTL PDU
H5M68A
Vertical, Three Phase, Half-Height (22U)
HPE Basic 3Ph 8.6kVA/L15-30P 24A/208V Outlets (18) C13/Vertical NA/JP PDU
H5M61A
Vertical , Single Phase, Mid-Height (36U)
HPE Basic 4.9kVA/L6-30P 24A/208V Outlets (24) C13 (6) C19/Vertical NA/JP PDU
H5M59A
HPE Basic 8.3kVA/CS8265C 40A/208V Outlets (30) C13 (6) C19/Vertical NA PDU
H5M60A
HPE Basic 7.3kVA/60309 3-wire 32A/230V Outlets (24) C13 (6) C19/Vertical INTL PDU
H5M70A
HPE Basic 9.2kVA/50A Terminal Block 40A/230V Outlets (30) C13 (6) C19/Vertical WW PDU
H5M75A
HPE Basic 11kVA/60309 63A 3-wire 48A/230V Outlets (30) C13 (6) C19/Vertical INTL PDU
H5M71A
Vertical, Three Phase, Mid-Height (36U)
HPE Basic 3Ph 5.7kVA/ L21-20P 16A/120-208V Outlets (24) C13 (3) 5-20R/Vertical NA/JP PDU
H5M63A
HPE Basic 3Ph 8.6kVA/L15-30P 24A/208V Outlets (24) C13 (6) C19/Vertical NA/JP PDU
H5M62A
HPE Basic 3Ph 8.6kVA/L21-30P 24A/120-208V Outlets (24) C13 (3) C19 (3) 5-20R/Vertical NA/JP PDU
H5M64A
HPE Basic 3Ph 11kVA/60309 5-wire 16A/230V Outlets (24) C13 (6) C19/Vertical INTL PDU
H5M72A
Vertical, Three Phase, Full-Height (42U)
HPE Basic 3Ph 11kVA/60309 5-wire 16A/230V Outlets (36) C13 (6) C19/Vertical INTL PDU
H5M73A
HPE Basic 3Ph 11kVA/60309 16A/240V Outlets (36) C13 (6) C19/Vertical NA PDU
H5M67A
Horizontal, Single Phase, 1U
HPE Basic 1.9kVA/L5-20P 16A/120V Outlets (12) 5-20R/Horizontal NA/JP PDU
H5M54A
HPE Basic 3.6kVA/60320 C20 Detachable 16A/230V Outlets (12) C13/Horizontal WW PDU
H5M56A
Horizontal/Modular, Single Phase, 0U/1U
HPE Basic Modular 2.8kVA/L5-30P 24A/120V Outlets (4) C19/Horizontal NA/JP PDU
252663-D71
NOTE: PDU kit ships with four (4) 7-outlet C-13 extension bars.
HPE Basic Modular 4.9kVA/L6-30P 24A/208V Outlets (4) C19/Horizontal NA/JP Core Only PDU
252663-D74
HPE Basic Modular 7.3kVA/60309 3-wire 32A/230V Outlets (4) C19/Horizontal INTL Core Only PDU
252663-B33
HPE Basic Modular 8.3kVA/CS8265C 40A/208V Outlets (4) C19/Horizontal NA/JP Core Only PDU
252663-D75
HPE Basic 9.2kVA/Terminal Block 40A/230V Outlets (4) C19/Horizontal WW PDU
252663-B21
NOTE: PDU kit ships with four (4) 7-outlet C-13 extension bars.
HPE Basic Modular 9.2kVA/60309 63A 3-wire 40A/230V Outlets (4) C19/Horizontal INTL PDU
252663-B32
NOTE: PDU kit ships with four (4) 7-outlet C-13 extension bars.
HPE Basic Modular 9.2kVA/60309 63A 3-wire 40A/230V Outlets (4) C19/Horizontal INTL Core Only PDU
252663-B34
Horizontal/Modular, Three Phase, 0U/1U
HPE Basic Modular 3Ph 8.6kVA/L15-30P 24A/208V Outlets (6) C19/Horizontal NA/JP PDU
AF512A
HPE Basic Modular 3Ph 11kVA/60309 5-wire 16A/230V Outlets (6) C19/Horizontal INTL PDU
AF513A
HPE Basic Modular 3Ph 14.4kVA/CS8365C 40A/208V Outlets (6) C19/Horizontal NA/JP PDU
AF519A
HPE Basic Modular 3Ph 17.3kVA/60309 60A 4-wire 48A/208V Outlets (6) C19/Horizontal NA/JP PDU
AF511A
HPE Basic Modular 3Ph 22kVA/60309 5-wire 32A/230V Outlets (6) C19/Horizontal INTL PDU
AF518A
QuickSpecs
HPE Basic Power Distribution Units (PDU)

Standard Features

Page 4
Features
Vertical and Horizontal models with power output options ranging from 1.9kVA to 22kVA
Horizontal/Modular PDU Models
All HPE Horizontal PDUs can be installed in any U position in your rack. HPE Horizontal/Modular PDUs have a unique modular architecture designed specifically for data center customers who want to maximize power distribution and space efficiencies in the rack. Horizontal/Modular PD building blocks stick) the 0U space between the RETM (see diagram below) allowing you the flexibility of placing access to power where it is needed.
Horizonta
Horizontal/Modular, 0U/1U, Single
Horizontal/Modular, 0U/1U, Three
Single and three-phase models to meet all your facility power needs Multiple mounting options allowing for easy access to outlets and flexible integration into your rack Low-profile, single-piece design does not interfere with rear maintenance area of your racks
- the Control Unit (or core) offering up to six C-19 outlets and the Extension Bar (or
providing seven C-13 outlets per bar. The Control Unit can be installed in either a 1U space or in
A rails on HPE racks, providing greater space efficiencies in the rack
. Extension Bars mount directly to the frame of the rack in multiple locations
l, 1U, Single-Phase models
Low-voltage (100-120V) input voltage PDU with 12x NEMA 5-20R outlets
High-voltage (200-240V) input voltage PDU with 12x C-13 outlets
Both models can be installed in any 1U space within your rack
-Phase models
Both low-voltage (100-120V) and high-line (200-240V) input voltage models
Each model includes a single-phase Control Unit (core) that branches out to 4 single-phase
branch circuits
Extension Bars (sticks) can be plugged into the Control Unit, and can be mounted directly to
the rack frame, spanning the entire length of the rack and providing 7x C-13 outlets per bar
Multiple models include either 2 or 4 Extension Bars (see “Models” section for details) -
Extension Bars can also be purchased separately in pairs (see “Related Options” section for details)
-Phase models
High-voltage (200-240V), three-phase input voltages
Each model includes a three-phase Control Unit (core) that branches out to 6 single-phase
branch circuits
Optional Extension Bars (sticks) can be plugged into the Control Unit, and can be mounted
directly to the rack frame, spanning the entire length of the rack and providing 7x C-13 outlets per bar
Us consist of two
QuickSpecs
HPE Basic Power Distribution Units (PDU)
St
andard Features
Page 5
Horizontal/Modular PDU 0U Installation in HPE Rack
Vertical PDU Models
All HPE Basic Vertical PDU models use industry standard button and keyhole mounting for simple drop in installation in profile single piece design provides multiple mounting options. For high power density requirements you can install two (2) full outlets facing in towards the center of th
Half
Up to 2 Half-Height Basic PDUs can be mounted per side in the optional rear facing
HPE Advanced and Enterprise Series racks, as well as many third party racks. The low
A wide range of single and three-phase options providing up to 19.9kVA of output power
Multiple form factors to meet the space requirements of most racks
Mounts vertically on either side in the rear of the rack using industry standard button and
keyhole mounting
Standard mounting faces the outlet towards the rear of the rack preventing interference in the
-height/mid-height PDU’s or (4) half-height PDU’s on each side of the rack with e rack.
maintenance zone between rear RETMA rails.
Using the optional configuration of facing the outlets into the rack, multiple PDUs can be
mounted on one side of the rack for higher power density
-Height Vertical PDUs
Designed to fit in 22U and taller racks
Support low-voltage (100-120V) and high-line (200-240V) input voltages
Single and three-phase models with up to 20 outlets