HPE Basic PDUs are designed to provide reliable and cost effective power distribution for your Hewlett Packard Enterprise and
non
form factors allowing you to configure access to power in your rack where you need it the most.
HPE
D
hey can be installed on either side of the rack
with outlets facing the back of the rack for easy access and improved clearance.
also
With effective power
distribution supporting from 12 to 42 outlet receptacles and power levels ranging from
can provide
HPE
a unique modular architecture designed specifically for data center customers who want
to maximize power distribution and
(core) and
mounted in any 1U space or in the
with some models, optional on other models)
allowing you to configure
access to power where you need it
Extension Bars installed) and power levels ranging from 2.8 kVA to 22k
configurations.
0U/1U Models (H5M54A shown)
Half Height Models (H5M55A shown)
Mid Height Models (H5M62A shown)
Full Height Models (H5M67A/H5M73A shown)
-Hewlett Packard Enterprise IT racks. Offering simple 0U and 1U installation options, HPE Basic PDUs are available in multiple
Vertical Basic PDUs provide a low-profile single-piece design allowing for easy access to rear devices for maintenance.
esigned for HPE racks, but also compatible with a large variety of third party racks, t
For higher power density configurations, they can
be installed side by side on both sides of the rack with the outlets facing in towards the center of the rack.
2.8 kVA to 19.9kVA, HPE Vertical PDUs
single or three-phase power for most IT configurations.
Horizontal/Modular Basic PDUs offer
space efficiencies in the rack. These PDUs consist of two building blocks - the Control Unit
the Extension Bar(s) (sticks). The Control Unit is a core PDU module that offers up to six C-19 outlets which can be
true 0U space on the side of HPE racks between the RETMA rails. Extension Bars (included
mount directly to the frame of the rack in multiple locations
the most. HPE Horizontal/Modular PDU models support up to 42 outlet receptacles (with all
VA, with options for single or three-phase power
QuickSpecs
HPE Basic Power Distribution Units (PDU)
Overview
Page 2
Why do you need a Power Distribution Unit (PDU) for your rack?
power in your racks – for more information on these features, please visit the Hewlett Packard Enterprise PDU website.
Why buy HPE Power Distribution Units (PDU)?
HPE
r
HPE
servers
While you have many choices for rack and power infrastructure products,
and KVM products to meet your needs.
and maintenance for your organization by providing a single point of contact for all your needs.
• PDUs distribute the power supplied to your rack to multiple rack U locations to power devices such as servers, storage,
and networking equipment.
• With rack densities ever-increasing as more and more equipment is added to your racks, PDUs allow you to conveniently
place access to power wherever you need most in your IT racks
• PDUs can also offer additional features such as power monitoring and outlet switching to help you better manage the
Foundation Care services purchased for servers and storage extend to our rack and power infrastructure products such as
acks, power distribution units, uninterruptible power systems, and KVM console and switches.
•What is the HPE advantage for you? You don’t have to spend additional budget to cover extended warranties and
services for your rack and power infrastructure as you would with non-Hewlett Packard Enterprise products.
rack and power infrastructure products are designed and developed to be used specifically with Hewlett Packard Enterprise
and storage.
•What is the HPE advantage for you? You can use HPE rack and power products with non-Hewlett Packard Enterprise
IT equipment; however, when used with Hewlett Packard Enterprise servers, you are able to take advantage of various
server and IP-based tools used for maintaining and managing all the equipment in the rack.
Hewlett Packard Enterprise offers a range of rack, power,
•What is the HPE advantage for you? Hewlett Packard Enterprise can help to simplify IT purchasing, installation, usage,
• Vertical and Horizontal models with power output options ranging from 1.9kVA to 22kVA
•
•
•
Horizontal/Modular
PDU Models
All HPE Horizontal PDUs can be installed in any U position in your rack.HPE Horizontal/Modular PDUs
have a unique modular architecture designed specifically for data center customers who want to
maximize power distribution and space efficiencies in the rack. Horizontal/Modular PD
building blocks
stick)
the 0U space between the RETM
(see diagram below)
allowing you the flexibility of placing access to power where it is needed.
Horizonta
Horizontal/Modular, 0U/1U, Single
Horizontal/Modular, 0U/1U, Three
Single and three-phase models to meet all your facility power needs Multiple mounting options allowing for easy access to outlets and flexible integration into your rack Low-profile, single-piece design does not interfere with rear maintenance area of your racks
- the Control Unit (or core) offering up to six C-19 outlets and the Extension Bar (or
providing seven C-13 outlets per bar. The Control Unit can be installed in either a 1U space or in
A rails on HPE racks, providing greater space efficiencies in the rack
. Extension Bars mount directly to the frame of the rack in multiple locations
l, 1U, Single-Phase models
• Low-voltage (100-120V) input voltage PDU with 12x NEMA 5-20R outlets
• High-voltage (200-240V) input voltage PDU with 12x C-13 outlets
• Both models can be installed in any 1U space within your rack
-Phase models
• Both low-voltage (100-120V) and high-line (200-240V) input voltage models
• Each model includes a single-phase Control Unit (core) that branches out to 4 single-phase
branch circuits
• Extension Bars (sticks) can be plugged into the Control Unit, and can be mounted directly to
the rack frame, spanning the entire length of the rack and providing 7x C-13 outlets per bar
• Multiple models include either 2 or 4 Extension Bars (see “Models” section for details) -
Extension Bars can also be purchased separately in pairs (see “Related Options” section for
details)
• Each model includes a three-phase Control Unit (core) that branches out to 6 single-phase
branch circuits
• Optional Extension Bars (sticks) can be plugged into the Control Unit, and can be mounted
directly to the rack frame, spanning the entire length of the rack and providing 7x C-13 outlets
per bar
Us consist of two
QuickSpecs
HPE Basic Power Distribution Units (PDU)
St
andard Features
Page 5
Horizontal/Modular PDU 0U Installation in HPE Rack
Vertical PDU Models
All HPE Basic Vertical PDU models use industry standard button and keyhole mounting for simple drop
in installation in
profile single piece design provides multiple mounting options. For high power density requirements you
can install two (2) full
outlets facing in towards the center of th
Half
• Up to 2 Half-Height Basic PDUs can be mounted per side in the optional rear facing
HPE Advanced and Enterprise Series racks, as well as many third party racks. The low
• A wide range of single and three-phase options providing up to 19.9kVA of output power
• Multiple form factors to meet the space requirements of most racks
• Mounts vertically on either side in the rear of the rack using industry standard button and
keyhole mounting
• Standard mounting faces the outlet towards the rear of the rack preventing interference in the
-height/mid-height PDU’s or (4) half-height PDU’s on each side of the rack with
e rack.
maintenance zone between rear RETMA rails.
• Using the optional configuration of facing the outlets into the rack, multiple PDUs can be
mounted on one side of the rack for higher power density
-Height Vertical PDUs
• Designed to fit in 22U and taller racks
• Support low-voltage (100-120V) and high-line (200-240V) input voltages
• Single and three-phase models with up to 20 outlets
QuickSpecs
HPE Basic Power Distribution Units (PDU)
St
andard Features
Page 6
configuration in a 42U or taller rack.
Up to 4 PDUs can be mounted on one side of a 42U or 47/48U rack using the standard inward
Mid
Full Height Vertical PDUs
NOTE: Facing the outlets into the rack will interfere with the lower few rack U spaces of the rear
maintenance zone due to breakers on the PDUs.
Easy Installation and
compatibility
Whether you choose to mount the Modular PDU in zero-U or 1U space, all required mounting brackets,
accessories, and installation instructions are shipped with the product.
mounting provides simple drop in installation
Rack and many third party racks.
Warranty Upgrade
Options
HPE Basic PDUs are backed by a limited 3-year warranty.
HPE
server in the same rack.
•
facing configuration
-Height Vertical PDUs
• Designed to fit in 36U and taller racks
• Support high input voltage (200-240V)
• Single and three-phase models with up to 36 outlets
• Three-phase Dual Voltage models provide three NEMA 5-20 convenience outlets for low
voltage equipment in a high voltage rack
• When mounted in the standard rear facing configuration only 1 Mid-Height Basic PDU can be
mounted per side of the rack
• Up to 2 Mid-Height PDUs can be mounted on one side of a 42U or 47/48U rack using the
optional inward facing configuration
• Designed for 42U and taller racks
• Three-phase, high voltage models with 42 outlets
• When mounted in the standard rear facing configuration only 1 Full-Height Basic PDU can be
mounted per side of the rack
• Up to 2 Full-Height PDUs can be mounted on one side of a 42U or 47/48U rack using the
optional inward facing configuration
Standard button and keyhole
for Vertical PDUs in HPE Advanced and Enterprise Series
Basic PDUs automatically assume the Support Services coverage level of any covered ProLiant
QuickSpecs
HPE Basic Power Distribution Units (PDU)
Service and Support
Page 7
HPE Support Services
Hewlett Packard Enterprise support services provide a range of life cycle support options that let you
choose the service levels that meet your business requirements, from basic to mission
A
hardware and software services are available
including:
NOTE:
worldwide
http://www.hp.com/hps/carepack
NOTE:
and
NOTE:
available at: http://h18004.www1.hp.com/products/servers/platforms/warranty/index.html
-critical.
full range of Hewlett Packard Enterprise support services
• Installation and start up
• Education courses
• Extended onsite hardware coverage hours from same business day 13 hours, 5 day to 24
hours, 7 days call window with options including 4-hour response or 6-hour Call To Repair
• Comprehensive range of software technical support for Microsoft, Linux, ProLiant Essentials
and VMWare-based IT solutions helping to deliver high level of application availability.
Response times range from 30 minutes for critical problems to 2 hours.
• System Management, Performance Services and Mission Critical Support Solution
For more information on Hewlett Packard Enterprise support services, contact any of our
sales offices or resellers or visit our worldwide Web site on the internet at:
For more complete information on Hewlett Packard Enterprise Services offerings, customers
resellers, please visit us at: http://www.hp.com/hps
Additional information regarding worldwide limited warranty and technical support is
QuickSpecs
HPE Basic Power Distribution Units (PDU)
Related Options
Page 8
Related Options
HPE Two C-13 PDU
Extension Bars
HP Two C13 PDU Extension Bar
AF500A
NOTE: Kit includes two extension bars, each with a single C-19 input and seven C-13
outlets.
HPE Two Fixed Cord
Extension Bars
HP Fixed Cord Extension Bars
351655-B21
NOTE: Kit includes two extension bars, each with a single C-19 input and seven C-13
receptacles on fixed (hardwired) 13
option is ideal for powering 1U servers and components.
HPE Support Services
HPE Install Rack and Rack Options Service
U2871E
HPE Power Cables
HP C13 - Nema 5-15P US/CA 110V 10Amp 1.83m Power Cord
AF556A
HP C19 - Nema L6-20P NA/JP 250V 20Amp High Voltage 3.6m Power Cord
AF593A
HP C19 - NBR-14136 BR 250V 16Amp 2.5m Power Cord
AF592A
HP C19 - GB-1002 CN 250V 16Amp 2.5m Power Cord
AF584A
HP C19 - IS-1293 IN/PK/BD 250V 16Amp 2.5m Power Cord
AF582A
HP C19 - ISI-32 IL 250V 16Amp 2.5m Power Cord
AF583A
HP C19 - AS3112-3 AU/NZ 250V 15Amp 3.6m Power Cord
AF577A
HP C19 - IEC-309 DK/SE/AR 250V 16Amp 3.6m Power Cord
AF581A
HP C19 - CEE-VII EU 250V 16Amp 3.6m Power Cord
AF576A
HP C19 - CEI-23-50 IT/CL 250V 16Amp 3.6m Power Cord
AF580A
HP C19 - SABS-164 ZA 250V 16Amp 3.6m Power Cord
AF579A
HP C19 - BS-1363/A UK/HK/SG 250V 13Amp 3.6m Power Cord
359615-031
HP 240 VAC 4.5M Unterminated End NA Power Cord
E7806A
HP C19 - C20 WW 250V 16Amp 2.5m Jumper Cord
295633-B22
NOTE: HPE Basic PDU models H5M56A and H5M57A require an IEC 320-C19 to
country specific plug inlet cord which is sold separately.
NOTE: Please refer to the HPE ProLiant Power Cables website for more information
on power cords and cables.
NOTE: Please refer to the HPE ProLiant Power Cables website for more information
on power cords and cables.
HPE Mounting Brackets
HP Vertical PDU 10K G2 Mounting Kit
H6L32A
-inch cords attached to the extension bars. The
QuickSpecs
HPE Basic Power Distribution Units (PDU)
Related Options
Page 9
NOTE: This kit allows for HPE Basic PDU vertical models to be mounted in HPE
10000 G2 series racks and in the
for mounting in the HPE Advanced or Enterprise Series racks.
HPE 277 Volt options
for H3X07A and
H3X08A
HP LS-26 to LS-25 277 Volt 15Amp AC 0.76m Jumper Cord
TK801A
HP LS-26 to LS-25 277 Volt 15Amp AC 1.37M Jumper Cord
TK802A
HP 800VA - 277V Input / 230V Output NA Rack Mount Transformer
H3X09A
NOTE: 720 watt, 2U transformer converts 277V to 230V for up to 4 devices.
NOTE:
on power cords and cables.
HPE Value Series rack. This bracket is not needed
Please refer to the HPE ProLiant Power Cables website for more information
QuickSpecs
HPE Basic Power Distribution Units (PDU)
Model Selection Matrix
Page 10
PDU
Output
Part Number
Input
Voltage
Current
Maximum
Load
C
Input Connection
Output
C
Breakers
Outlet
Connections
Half-Height Vertical Models
2.8kVA
H5M55A
100-120V
24A 2880VA @ 120V
8ft(2.4m) attached
cord
2 x 20A
18 x NEMA 520R
3.6kVA
H5M57A
200-240V
16A 3680VA @ 230V
IEC 60320-C20 inlet*
2 x 16A
20 x IEC C13
4.9kVA
H5M58A
200-208V
24A 4992VA @ 208V
8ft(2.4m) attached
cord NEMA L6-30P
2 x 20A
20 x IEC C13
7.3kVA
H5M68A
200-240V
32A 7360VA @ 230V
8ft(2.4m) attached
cord
3W
2 x 16A
20 x IEC C13
8.6kVA
H5M61A
200-208V
3-Phase Delta
24A 8646VA @ 208V
8ft(2.4m) attached
cord NEMA L15-30
3 x 20A
18 x IEC C13
Mid-Height Vertical Models
4.9kVA
H5M59A
200-240V
24A 4992VA @ 208V
8ft(2.4m) attached
cord NEMA L6-30P
2 x 20A
24 x IEC C13
6 x IEC C19
5.7kVA
(Dual
Voltage)
H5M63A
100-120V/
200
3-Phase WYE
16A per
phase
5764VA @ 208V
8ft(2.4m) cord with
attached NEMA L21
20P
3 x 20A
24 x IEC C13
3 x NEMA 5
20R
7.3kVA
H5M70A
200-240V
32A
7360VA @ 230V
8ft(2.4m) attached
cord IEC 60309 32A
3W
2 x 16A
24 x IEC C13
6 x IEC C19
8.3kVA
H5M60A
200-208V
40A 8320VA @ 208V
8ft(2.4m) attached
cord CS8265C
3 x 20A
30 x IEC C13
6 x IEC C19
8.6kVA
(Dual
Voltage)
H5M64A
100-120V/
200
30A
3-Phase WYE
24A
per phase
8646VA @ 208V
8ft(2.4m) attached
cord NEMA L21
3 x 20A
24 x IEC C13
3 x IEC C19
3 x NEMA 5
20R
8.6kVA
H5M62A
200-208V
3-Phase Delta
24A 8646VA @ 208V
8ft(2.4m) attached
cord NEMA 15-30P
3 x 20A
24 x IEC C13
6 x IEC C19
9.2kVA
H5M75A
200-240V
40A 9200VA @ 230V
Terminal block for
hardwired installation
3 x 16A
30 x IEC C13
6 x IEC C19
11kVA
H5M71A
200-240V
48A
11040VA @ 230V
8ft(2.4m) attached
cord IEC 60309 63A
3W
3 x 16A
30 x IEC C13
6 x IEC C19
11kVA
H5M72A
200-240V/
380
3
16A
per phase
11040VA @ 400V
8ft(2.4m) attached
cord IEC 60309 16A
5W
3 x 16A
24 x IEC C13
6 x
Full-Height Vertical Models
11kVA PDU
H5M73A
200-240V/
380
3-Phase WYE
16A
per phase
11040VA @ 400V
8ft(2.4m) attached
cord IEC 60309 16A
5W
3 x 16A
36 x IEC C13
6 x IEC C19
11kVA PDU
H5M67A
200-240V/
380
3-Phase WYE
16A
per phase
11040VA @400V
8ft(2.4m) attached
cord IEC 530P6
3 x 20A
36 x IEC C13
6 x IEC C19
13.2kVA PDU
H3X07A
277/480V
3
16A
per phase
13302VA @480V
9.8ft(3m) attached
cord IEC 60309 30A
5W
3 x 20A
15 x LS-26
19.9kVA PDU
H3X08A
277/480V
30A 3
WYE
24A
per phase
19953VA @480V
9.8ft(3m) attached
cord IEC 60309 30A
5W
6 x 20A
30 x LS-26
apacity
ircuit
NEMA L5-30P
IEC 60309 32A
-208V
-208V
-
-30P
-
-
-415V
-Phase WYE
-415V
-415V
-Phase WYE
-Phase
IEC C19
QuickSpecs
HPE Basic Power Distribution Units (PDU)
Model Selection Matrix
Page 11
PDU
Output
Part Number
Input
Voltage
Current
Maximum
Load
Capacity
Input Connection
Output
Circuit
Breakers
Outlet
Connections
Horizontal Models
1.9kVA
H5M54A
100-120V
16A 1920VA @120V
8ft(2.4m) attached
cord NEMA L5
1 x 20A
12 x NEMA 520R
3.6kVA
H5M56A
200-240V
16A 3680VA @ 230V
IEC 60320-C20 inlet*
1 x 16A
12 x IEC C13
Horizontal/Modular Models
2.8kVA
252663-D71
100-125V
24A 2880VA @ 120V
11.8ft (3.6m) attached
cord NEMA L5
n/a 4 x IEC C-19
3.6kVA
252663-B24
200-240V
16A 3680VA @ 230V
IEC 60320 C20 inlet
2 x 16A
2 x IEC C-19
4.9kVA
252663-D74
200-240V
24A 4992VA @ 208V
11.8ft (3.6m) attached
cord NEMA L6
4 x 15A
4 x IEC C-19
4.9kVA
252663-D72
200-240V
24A 4992VA @208V
11.8ft (3.6m) attached
cord NEMA L6-30P
4 x 20A
4 x IEC C-19
7.3kVA
252663-B33
200-240V
32A 7360VA @ 230V
11.8ft (3.6m) attached
cord IEC 60309
3W
4 x 16A
4 x IEC C-19
7.3kVA
252663-B31
200-240V
32A 7360VA @ 230V
11.8ft (3.6m) attached
cord IEC 60309 32A
3W
4 x 16A
4 x IEC C-19
8.3kVA
252663-D75
200-240V
40A 8320VA @ 208V
11.8ft (3.6m) attached
cord, CS8265C
4 x 15A
4 x IEC C-19
8.3kVA
252663-D73
200-240
40A 8320VA @ 208V
11.8ft (3.6m) attached
cord CS8265C
4 x 20A
4 x IEC C-19
8.6kVA
AF512A
200-208V
3-Phase Delta
24A 8646VA @ 208V
11.8ft (3.6m) attached
cord, NEMA L15-30P
6 x 20A
6 x IEC C-19
9.2kVA
252663-B34
200-240V
40A 9200VA @ 230V
11.8ft (3.6m) attached
cord, IEC 60309 63A
3W
4 x 15A
4 x IEC C-19
9.2kVA
252663-B21
200-240V
40A 9200VA @ 230V
Terminal block for
hardwired installation
4 x 16A
4 x IEC C-19
9.2kVA
252663-B32
200-240V
40A 9200VA @ 230V
11.8ft (3.6m) attached
cord IEC 60309 63A
3W
4 x 16A
4 x IEC C-19
11kVA
AF513A
200-240V/
380
3-Phase Wye
16A
per phase
11040 @ 230V
11.8ft (3.6m) attached
cord, IEC 60309 16A
5W
6 x 16A
6 x IEC C-19
14.4kVA
AF519A
200-208V
3-Phase Delta
40A 14410VA @ 208V
11.8ft (3.6m) attached
cord, CS8365C
6 x 20A
6 x IEC C-19
17.3kVA
AF511A
200-208v
3-Phase Delta
48A 17292VA @ 208V
11.8ft (3.6m) attached
cord IEC 60309 60A
6 x 20A
6 x IEC C-19
22kVA
AF518A
200-240V/
346
3-Phase Wye
32A
per phase
22080VA @ 230V
11.8ft (3.6m) attached
cord, IEC 60309 32A
5W
6 x 16A
6 x IEC C-19
*NOTE: HPE Basic PDU models H5M56A and H5M57A require an IEC 320-C19 to country specific plug inlet cord which is sold
separately.
Disclaimer: Hewlett Packard Enterprise makes no recommendations regarding power connector manufactures. Please consult a
licensed professional to determine the best connector or receptacle for your specific needs.
UL, CUL, CE, NOM, D - 40A models
UL, CUL, NOM
CE, D - 32A model
Mechanical Dimensions (WxHxD)
0U/1U models
17.5 x 1.66 x 6 in (44.45 x 4.2x 15.3 cm)
Half-Height models
1.9 x 29.02 x 3.75.0 in (4.83 x 73.7x 9.5 cm)
Mid-Height models
1.9 x 55.12 x 9.5in (4.83 x 140 x 9.5 cm)
Full-Height models
1.9 x 65.59 x 3.75 in (4.83 x 166.6 x 9.5 cm)
Single Phase 4.9kVA to 9.2kVA
Unit Weight
18 lb (8.16 kg)
Shipping Dimensions (WxHxD)
21.5 x 12.25 x 13.0 in (54.61 x 31.12 x 33.02 cm)
Three Phase 8.6 kVA to 22 kVA
Unit Weight
20 lb (9.07 kg)
Shipping Dimensions (WxHxD)
21.5 x 12.25 x 15.0 in (54.61 x 31.12 x 38.1 cm)
Kit Contents
All Basic PDU models ship with:
•Read me first card
Environment-friendly
End-of-life Management
and Recycling
Hewlett Packard Enterprise offers end-of-life product return, trade-in, and
recycling programs, in many geographic areas, for our products. Products
returned to Hewlett Packard Enterprise will
disposed of in a responsible manner.
The EU WEEE directive (2002/95/EC) requires manufacturers to provide
treatment information for each product type for use by treatment facilities.
This information (product disassembly instruction
Hewlett Packard Enterprise web site. These instructions may be used by
- INTL models
- WW models
- 24A models
• Mounting brackets/hardware
• Cord Retention bracket
• Tie wraps
• Shipping bracket (varies by model)
Products and Approach
be recycled, recovered or
-
/environmentalprogress/product-
-lPA_krKiM
s) is posted on the
QuickSpecs
HPE Basic Power Distribution Units (PDU)
Technical Specifications
Page 14
recyclers and other WEEE treatment facilities as well as Hewlett Packard
Enterprise OEM customers who integrate and re
Enterprise equipment.
The only warranties for Hewlett Packard Enterprise products and services are set forth in the express
warranty statements
constituting an additional warranty. Hewlett Packard Enterprise shall not be liable for technical or editorial
errors or omissions contained herein
c04111392
Selection Matrix, PDU Plugs, and Technical Specifications were
PDU Family Information, PDU Plugs, and Technical
Overview
Standard Features
Related Options
accompanying such products and services. Nothing herein should be construed as
.
- 14557 - Worldwide – V14 - 13-February-2017