HPE BW974A Getting Started Guide

have older product names and model numbers that differ from current models.
QuickSpecs
HP Modular Cooling System G2
HP Modular Cooling System G2
HP Modular Cooling System G2HP Modular Cooling System G2
Overview
DA - 12919 Worldwide — Version 7 — June 20, 2011
Page 1
have older product names and model numbers that differ from current models.
QuickSpecs
HP Modular Cooling System G2
HP Modular Cooling System G2
HP Modular Cooling System G2HP Modular Cooling System G2
Overview
At a Glance
At a Glance
At a GlanceAt a Glance
Supports cooling two HP 42U racks at a time at 17.5kW per side or 35kW in a single rack 35kW of cooling capacity, up from 30kW Six hot swappable high airflow fans High air flow heat exchanger with bi-directional air distribution CTO capability of up to 2000 Lbs dynamic load for both the standard MCS G2 rack as well as the MCS G2 Expansion rack Expand MCS G2 to support a second rack with MCS G2 Expansion rack Automatic door opening system for both racks ships standard with every MCS G2. The automatic door opening mechanism is not CTO capable and therefore ships in the accessories box and is to be installed onsite 42U rack height (2 meters) and 1.5 racks wide to maintain datacenter tiling configuration. Environmental Monitor with SNMP integration to Systems Insight Manager (SIM) Power Input Redundancy for dual power source Condensate Evacuation system to prevent condensation from entering air stream Site Preparation Guide available at:
http://h20000.www2.hp.com/bizsupport/TechSupport/DocumentIndex.jsp?contentType=SupportManual&lang=en &cc=us&docIndexId=64179&taskId=101&prodTypeId=3447589&prodSeriesId=3657806
DA - 12919 Worldwide — Version 7 — June 20, 2011
Page 2
have older product names and model numbers that differ from current models.
QuickSpecs
HP Modular Cooling System G2
HP Modular Cooling System G2
HP Modular Cooling System G2HP Modular Cooling System G2
Models
Site Preparation
Site Preparation
Site PreparationSite Preparation HP Modular Cooling System G2 Hook up Kit HP MCS G2 Site Preparation Service
NOTE:
NOTE:
NOTE: NOTE:
http://h20219.www2.hp.com/services/cache/11077-0-0-225-121.aspx.
NOTE:
NOTE:
NOTE:NOTE: preparation purposes. The kit contains set of 1.0 inch diameter, Couplings and Parallel-to-Tapered adapter included to address regional differences.
Modular Cooling System G2 (MCS G2)
Modular Cooling System G2 (MCS G2)
Modular Cooling System G2 (MCS G2)Modular Cooling System G2 (MCS G2) HP Modular Cooling System G2 Rack HP 10642 G2 Rack Rear Extension Kit
NOTE:
NOTE:
NOTE: NOTE: Monitored PDU
HP Modular Cooling System G2 10642 G2 Expansion Rack HP Install Modular Cooling System Service
NOTE:
NOTE:
NOTE:NOTE: CTO.
NOTE:
NOTE:
NOTE: NOTE: CTO.
NOTE:
NOTE:
NOTE: NOTE: unit attached.
NOTE:
NOTE:
NOTE: NOTE:
Use Per Event Support and Consulting Service
The Modular Cooling System Water Hook-up kit can be ordered ahead of the MCS G2 for site
The Rack Rear Extension kit is required when racking the HP c7000 Enclosure in conjunction with an HP
Install MCS G2 per the product user installation manual. All MCS G2 units ship with shock pallet for
Install MCS G2 per the product user installation manual. All MCS G2 units ship with shock pallet for
The purchase of HP Modular Cooling System G2 (P/N AF025A) includes 10642 G2 rack and cooling
A loaded MCS G2 rack should only be moved by professional movers.
AF089A
N/A
AF025A AF036A
AF026A UE005E
DA - 12919 Worldwide — Version 7 — June 20, 2011
Page 3
have older product names and model numbers that differ from current models.
QuickSpecs
Standard Features
Product Description
Product Description
Product DescriptionProduct Description
HP Modular Cooling System G2 rack is designed for high density server and blade deployments. It re­circulates and cools the hot server exhaust air through the heat exchanger residing in the MCS G2 unit. The air is then expelled in front of the enclosed rack at a much lower temperature providing sufficient cool air for a load of 35kW of servers or blades, or two racks at 17.5kW each.
The MCS G2 unit contains six fans and a heat exchanger deployed along the full height of the rack to ensure that all the equipment installed receives sufficient chilled air. All fans are swappable while the unit is online, providing great servicing flexibility. Redundant power is ensured through a failover power switch that can be connected to two power sources. The environmental monitor controls the air temperature to the servers and adjusts automatically to meet the pre-established air temperature goal. The environmental monitor interacts with HP SIM (Systems Insight Manager) via SNMP traps.
The Water Hookup kit is made available as a separate kit to prepare the water hookup ahead of the arrival of the MCS G2.
A Site Preparation Guide is available for download at:
http://h20000.www2.hp.com/bizsupport/TechSupport/DocumentIndex.jsp?contentType= SupportManual&lang=en&cc=us&docIndexId=64179&taskId=101&prodTypeId=3447589&prod SeriesId=3657806
HP Modular Cooling System G2
HP Modular Cooling System G2
HP Modular Cooling System G2HP Modular Cooling System G2
.
This guide provides details on how to prepare the datacenter for the successful deployment of the MCS G2. It may be advisable to contact HP Professional Services for a Site Datacenter Thermal Quick Assessment Service, reference HB691A1 and HB691AE. Visit additional information. The MCS G2 unit mounted next to a HP 10000 G2 Series rack is designed to occupy 1.5 tiles in the datacenter maintaining tile count for cable routing and access to the plenum.
The MCS G2 and the MCS G2 Expansion Rack are CTO capable with a dynamic load capacity of 2000 Lbs each. For HP CTO services go to:
http://h18004.www1.hp.com/products/servers/platforms/rackandpower.html
NOTE:
NOTE: A loaded MCS G2 unit should only be moved by professional movers.
NOTE:NOTE:
NOTE:
NOTE:
We support 3000lbs of static IT Equipment on leveling feet.
NOTE:NOTE: Caution: Static loading limits cannot be achieved if the rack is
1.
Not on its leveling feet and
2.
Rolled or pushed from its position.
Not responsible for floor damages where the rack resides. Your floor weight capacity may not support the full static load capacity. Check with your floor provider before loading.