such a way that their force, due to internal pressure,
may act on the pump flange.
Maximum forces and moments allowed on the pump
flanges vary with the pump size and type. These
external strains may cause misalignment, hot
bearings, worn couplings, vibrations and the
possible failure of the pump casing.
Page 15 of 35
Ensure piping and fittings are flushed
before use.
Ensure piping for hazardous liquids is
arranged to allow pump flushing before removal of
the pump.
Page 16
FP USER INSTRUCTIONS ENGLISH 71576286 - 07/06
4.5.2 Suction piping
4.5.2.1 Design of a flooded suction line
The suction line must be as short and direct as
possible, never mount an elbow directly on the inlet
flange of the pump.
Valve
Non-return valve
Continous flow
valve
Flooded suction configuration
a) Avoid sharp elbows or sudden narrowing. Use
convergent 20° (total angle).
b) Arrange thepipework so that there are no air
pockets (no bulges).
c) If high points cannot be avoided in suction line,
provide them with air relief cocks.
d) If a strainer is necessary, its net area should be
three or four times the area of the suction pipe.
e) If an inlet valve is necessary, choose a model
with direct crossing.
c) If a foot valve is necessary, do not oversize it
because it would generate pulsations (valve
beating).
Do not tighten flanges before the final
check (see § 4.5.4).
4.5.3 Discharge piping
4.5.3.1 Design of a discharge line
a) If discharge line is provided with a divergent, its
total angle will be between 7° and 12°.
b) Install the discharge valve after the non-return
valve downstream.
c) The non-return valve will be set in the discharge
pipe to protect the pump from any excessive
pressure surge and from reverse rotation.
If necessary, a control manometer can be connected
on the pipework.
Control manometer
Do not tighten flanges before the final
check (see § 4.5.4).
4.5.2.2 Design of a suction lift line
The inlet pipe must be as short and as direct as
possible, never place an elbow directly on the pump
inlet nozzle.
Valve
Non-returnvalve
SUFFICIENTIMMERSION
I:
I 3xD
Valvestrainer
Sump suction configuration
a) Avoid sharp elbows or sudden narrowing. Use
convergent 20° (total angle) with upright
generating.
b) Arrange that the suction pipework is inclined
upwards towards the pump ensuring that there
are no peaks.
Setting of the control manometer
Do not tighten flanges before the final
check (see § 4.5.4).
4.5.4 Final checks
a) Check the tightening of anchor bolts. Tighten
them if necessary.
b) Check that protective covers on suction and
discharge flanges are removed.
c) Check that holes of pipework flanges are parallel
and correspond to those of the pump.
d) Tighten suction and discharge flanges.
4.6 Electrical connections
Electrical connections must be made
by a qualified Electrician in accordance with relevant
local national and international regulations. This
includes any grounding.
It is important to be aware of the EUROPEAN
DIRECTIVE on potentially explosive areas where
compliance with IEC60079-14 is an additional
requirement for making electrical connections.
Page 16 of 35
Page 17
FP USER INSTRUCTIONS ENGLISH 71576286 - 07/06
Avoid mechanical, hydraulic or electrical
overload by using motor overload trips or a power
monitor and make routine vibration monitoring.
It is important to be aware of the EUROPEAN
DIRECTIVEon electromagneticcompatibilitywhen
wiring up andinstallingequipmentonsite.Attention
mustbepaidtoensurethat the techniques usedduring
wiring/installationdonot increaseelectromagnetic
emissions or decreasetheelectromagnetic immunityof
theequipment,wiringoranyconnecteddevices. If in
anydoubt,contact Flowserve for advice.
The motor must be wired up in
accordance with the motor manufacturer's
instructions (normally supplied within the terminal
box) including any temperature, earth leakage,
current and other protective devices as appropriate.
If there are any circumstances in which the system
can allow the pump to run dry, or start up empty, a
power monitor should be fitted to stop the pump or
prevent it from being started. This is particularly
relevant if the pump is handling a flammable liquid.
If leakage of product from the pump or its associated
sealing system can cause a hazard it is
recommended that an appropriate leakage detection
system is installed.
To prevent excessive surface temperatures at
bearings it is recommended that temperature or
vibration monitoring are carried out. See sections
5.5.4 and 5.5.5.
If a defect of cooling can lead to temperature higher
than those acceptable a system of cooling
surveillance must be installed.
The identification nameplate should be checked to
ensure the power supply is appropriate.
A device to provide emergency stopping shall be
fitted.
Carry out the ground connections according to the
current local regulations.
To avoid any risk of jamming, the direction of
rotation will be checked after priming of the pump (§
5.3.1, 5.3.2) and before the first start (§ 5.4.2).
4.7 Final shaft alignment check
a) Check the alignment pump-motor according to
the procedure § 4.4.2. Rectify if necessary by
adjusting the motor only.
b) Check by hand that the pump turns freely. A
binding indicates a distortion of the pump, which
is due to excessive pipes strains. If necessary
the pipework design must be re-examined.
c) If it provided, connect auxiliary pipe systems
(hydraulic, pneumatic, sealing system).
d) Control tightness and functionality of auxiliary
piping.
4.8 Protection systems
The following protection systems are
recommended particularly if the pump is installed in
a potentially explosive area or is handling a
hazardous liquid. If in doubt consult Flowserve.
If there is any possibility of the system allowing the
pump to run against a closed valve or below
minimum continuous safe flow a protection device
should be installed to ensure the temperature of the
liquid does not rise to an unsafe level.
Except when explicitly required by the customer in
the specifications, when a possibility of reverse
rotation exists the customer must install a reverse
rotation protection device.
The customer must install all equipment required to
avoid water hammer.
5 COMMISSIONING, START-UP,
OPERATION AND SHUTDOWN
These operations must be carried out by
fully qualified personnel.
5.1 Direction of rotation
Starting or operating pumps with the
wrong direction of rotation can be harmful to the
pumps. Ensure that the pump rotation is the same
as the arrow on the pump casing. It is preferable to
check the direction of rotation before installing the
coupling. If not, the pump must be filled in with the
liquid before start-up.
If maintenance work has been carried
out to the site's electricity supply, the direction of
rotation should be re-checked as above in case the
supply phasing has been altered.
5.2 Guarding
Guarding is supplied fitted to the pump set.
If this has been removed or disturbed ensure that all
the protective guards around the pump coupling and
exposed parts of the shaft are securely fixed.
Page 17 of 35
Page 18
FP USER INSTRUCTIONS ENGLISH 71576286 - 07/06
5.3 Priming and auxiliary supplies
Where there is any risk of the pump being run
against a closed valve generating high liquid and
casing external surface temperatures it is
recommended that users fit an external surface
temperature protection device.
Ensure all electrical, hydraulic,
pneumatic, sealant and lubrication systems (as
applicable) are connected and operational.
Ensure the inlet pipe and pump
casing are completely full of liquid before starting
continuous duty operation.
These operations must be carried out by personnel
with approved qualifications.
5.3.1 Priming of a flooded pump
a) As discharge valve is closed, fill the pump by
opening the valve at suction.
b) Let air escape by removing the plugs situated on
the flange of the discharge casing and suction
casing (for the 122, 152 to 202 FP pumps). For
the 50 to 125 FP pumps, plugs are located on
pipework.
c) The discharge pipe is headed and there is a by-
pass valve on the check valve, open slightly the
discharge valve and the by-pass of the check
valve.
d) When the pump is totally free of air bubbles,
replace the plugs.
c) When the pump is totally free of air bubbles,
replace the plugs.
Air escape
Air escape
Priming of sump suction pump with foot valve
*Without foot valve:
Priming may be accomplished by means of venting
system.
Foot valves are not recommended when
the pumped liquid has suspended solid particles.
They may lodge between foot valve seat and
shutter.
5.4 Starting the pump
5.4.1 Bring controls and preparation before the
first starting and after each service call
Airescape
Airescape
Priming of a flooded pump
5.3.2 Priming of a sump suction pump
* With foot valve:
a) Fill suction pipe and casing with liquid from an
independent source (pressure 1 to 2 bars).
b) Let air escape by removing the plugs situated on
the flange of the discharge casing and suction
casing (for the 122, 152 to 202 FP pumps). For
the 50 to 125 FP pumps, plugs are located on
pipes.
Necessarily:
a) Check the tightening of the different plugs.
b) Check that the gland lightly tightens the packing
rings.
c)Risk of seal ring overheating.
d) Check the direction of rotation of the motor.
Refer to the rotation arrow of the pump.
e)Install all protection systems and more
particularly the coupling guard and the shield
grid (reference [9331]) of the bearing.
f)Open all suction valves (if existing).
g) Close the outlet valve and the bypass valve.
h) Ensure inlet pipe and pump casing are
completely full of liquid.
5.4.2 First pump start-up
Suction valves must be fully open
when pump is running. Never run the pump dry, it
will cause damage.
Page 18 of 35
Page 19
a) Start motor and check outlet pressure.
2445
2110
4200
4610
4240
4213
b) If pressure is satisfactory, slowly OPEN outlet
valve.
c) Do not run the pump with the outlet valve closed
for a period longer than 30 seconds.
d) If NO pressure, or LOW pressure, STOP the
pump. Refer to faultfinding chart for fault
diagnosis.
The pump should run smoothly and without
vibration.
The pump must never run at a capacity of less than
10% of that at the best efficiency.
Never remove a plug when the pump is
running.
5.5 Running the pump
5.5.1 Venting the pump
Vent the pump to enable all trapped air to
escape taking due care with hot or hazardous
liquids.Under normal operating conditions, after the
pump has been fully primed and vented, it should be
unnecessary to re-vent the pump.
5.5.2Pump fitted with a stuffing box
If the pump has a packed gland there must be some
leakage from the gland. Gland nuts should initially
be finger tight only. Leakage should take place soon
after the stuffing box is pressurized. If no leakage
takes place the packing will begin to overheat. If
overheating takes place the pump should be
stopped and allowed to cool before being restarted.
When the pump is restarted it should be checked to
ensure leakage is taking place at the packed gland.
FP USER INSTRUCTIONS ENGLISH 71576286 - 07/06
Shield grids being removed during installation
of the gland packing, it must be ensured that they
are replaced as soon as this operation is completed.
5.5.3 Pump fitted with mechanical seal
A mechanical seal ensures a seal without leakage
and does not need any adjustment. Nevertheless if a
light leakage occurs during start-up, it should
disappear after the initial running in of the friction
faces.
When adjusting an operating stuffing box
(shield grids removed for this operation) the operator
must be very careful. Safety gloves are compulsory
and loose clothes are not allowed (above all to the
arms) to avoid being caught by the pump shaft.
The pump should be run for ten minutes with steady
leakage and the gland nuts tightened by 10 degrees
at a time until leakage is reduced to an acceptable
level. The temperature of the gland should be
checked after each round of tightening. If the
temperature starts to climb rapidly then back off the
gland nuts until the temperature drops down. Wait
for the temperature to stabilize before tightening
again.The leakage must not be reduced below a
rate of 20 drops per minute. Bedding in of the
packing may take several hours.
Page 19 of 35
NEVER RUN A MECHANICAL SEAL
DRY, EVEN FOR A SHORT WHILE.
SAFETY INSTRUCTIONS WHEN THE PUMP IS
RUNNING:
If hot or freezing components of the machine
can present a danger to operators, they must be
shielded to avoid accidental contact. If a 100 %
protection is not possible, the machine access must
be confined to the maintenance staff only.
If the temperature is greater than 80 °C, a
warning plate must be clearly placed on the pump.
Page 20
FP USER INSTRUCTIONS ENGLISH 71576286 - 07/06
It is strictly forbidden to open switch
cupboards, switch boxes, or all other live electric
equipment. If it is necessary to open them in order to
take readings, to carry out tests or adjustments for
example, only a skilled technician may do them with
adapted tools. Make sure that physical protections
against electrical risks are used.
5.5.4 Bearings
If the pumps are working in a potentially
explosive atmosphere, temperature or vibration
monitoring at the bearings is recommended.
If bearing temperatures are to be monitored it is
essential that a benchmark temperature is recorded
at the commissioning stage and after the bearing
temperature has stabilized.
Record the bearing temperature (t) and the
ambient temperature (ta)
Estimate the likely maximum ambient
temperature (tb)
Set the alarm at (t+tb-ta+5) C [(t+tb-ta+10) F]
and the trip at 100 C (212 F) for oil lubrication
and 105 C (220 F) for grease lubrication
It is important, particularly with grease lubrication, to
keep a check on bearing temperatures. After start up
the temperature rise should be gradual, reaching a
maximum after approximately 1.5 to 2 hours. This
temperature rise should then remain constant or
marginally reduce with time.
5.5.5 Normal vibration levels, alarm and trip
For guidance, pumps generally fall under a
classification for rigid support machines within the
International rotating machinerystandards and the
recommended maximum levels below are based on
those standards.
Alarm and trip values for installed
pumps should be based on the actual
measurements (N) taken on site on the bearing
housings of the pump in the fully commissioned as
new condition.
Vibration Velocity - unfiltered
NormalN5.6 (0.22)
AlarmN x 1.257.1 (0.28)
Shutdown Trip N x 2.011.2 (0.44)
Horizontal Configuration
mm/s (in./s) r.m.s.
5.5.6 Stop/start frequency
Pump sets are normally suitable for the number of
equally spaced stop/starts per hour shown in the
table below. Check actual capability of the driver and
control/starting system before commissioning.
Motor rating kW (hp)
Up to 15 (20)15
Between 15 (20) and 90 (120)10
90 (120) to 150 (200)6
Above 150 (200)Refer
Maximumstop/starts
per hour
Where duty and standby pumps are installed it is
recommended that they are run alternately every
week.
5.6 Stopping and shutdown
5.6.1 Stopping and restarting in continuous
running
According to hydraulic conditions of the installation
and its automation degree, stop and restart
procedures can have different forms. Nevertheless
all of them must respect imperatively the following
rules:
Stopping:
a) Avoid that the unit turns in the opposite direction
to the normal running.
b) Make sure that the discharge line pressure does
not reach the foot valve.
c) Avoid a continuous running below the authorized
flow rate (see § 5.4.2).
The example (N) value is given for the preferred
operating flow region (typically this may extend to 70
to 120 % of the pump best efficiency point); outside
the preferred flow region the actual vibration
experienced may be multiplied by up to 2.
These standard values can vary with the rotational
speed and the power absorbed by the pump. For
any special case, do not hesitate to consult us.
Measuring vibration at regular intervals will then
show any deterioration in pump or system operating
conditions.
Page 20 of 35
Restart:
a) Ensure that the pump is completely full of liquid.
b) Ensure a continuous supply with a sufficient
available NPSH.
c) Ensure a backpressure so that the motor power
is not in excess.
d)Respect the starting frequency
imposed by the motor manufacturer.
e)Protect the pump against water hammer
when stopping or starting.
Page 21
FP USER INSTRUCTIONS ENGLISH 71576286 - 07/06
Shutdown:
Close the outlet valve and stop the
motor. Eventually close the inlet valve.
For prolonged shutdowns and
especially when ambient temperatures are likely to
drop below freezing point, the pump and any cooling
and flushing arrangements must be drained or
otherwise protected.
5.7 Hydraulic, mechanical and electrical
duty
This product has been supplied to meet the
performance specifications of your purchase order,
however it is understood that during the life of the
product these may change. The following notes may
help the user decide how to evaluate the
implications of any change. If in doubt contact your
nearest Flowserve office.
5.7.1 Specific gravity (SG)
Pumpcapacity and total head in meters (feet) do not
change with SG, however pressure displayed on a
pressure gauge is directly proportional to SG. Power
absorbed is also directly proportional to SG. It is
therefore important to check that any change in SG
will not overload the pump driver or over-pressurize
the pump.
NPSHrequired(NPSHR) is the minimum head required
at theimpeller inlet, above the vapour pressureofthe
If the pump has an internal coating, this coating
must be inspected periodically. Any wear or cracks
of the coating found must be immediately repaired.
Failure to do this may lead to accelerated wear of
the coating during operation and corrosion of the
exposed base metal, depending on the material and
pumped liquid. Special attention must be paid to the
coating edges. Any loss of coating material is
considered to be normal wear and tear on the pump
and is not considered as warranty. Flowserve has
applied the coatings according to the supplier's
instructions but will not be held responsible for
coating wear or cracks that may develop over time.
6.3 Spare parts
6.3.1 Ordering of spares
Flowserve keeps records of all pumps that have
been supplied. When ordering spares the following
information should be quoted:
The pump size and serial number are shown on the
pump nameplate.
To ensure continued satisfactory operation,
replacement parts to the original design specification
should be obtained from Flowserve. Any change to
the original design specification (modification or use
of a non-standard part) will invalidate the pump’s
safety certification.
Page 24 of 35
1) Pump serial number.
2) Pump size.
3) Part name
4) Part number
5) Number of parts required.
Page 25
FP USER INSTRUCTIONS ENGLISH 71576286 - 07/06
6.3.2 Storage of spares
Spares should be stored in a clean dry area away
from vibration. Inspection and re-treatment of
metallic surfaces (if necessary) with preservative is
recommended at 6 monthly intervals.
a) Destroy all the gaskets after dismantling, replace
them when reassembling.
b)IT IS RECOMMENDED THAT
BEARINGS ARE NOT REUSED AFTER ANY
REMOVAL FROM THE SHAFT.
c) After serving during two years, replace the gland
packing.
c) Wait for the moment when the pump casing is
cooled and at ambient temperature.
d)DRAIN PUMP.
e) Dismantle inlet and outlet pipeworks as well as
all pipeworks.
f)REMOVE PUMP TAKING INTO
ACCOUNT SAFETY (§ 1) AND HANDLING
(§ 2.2) PROCEDURES.
ANY DISASSEMBLY, REPAIR OR
REASSEMBLY WILL BE CARRIED OUT UNDER
FLOWSERVE' RESPONSABILITY, EITHER
DIRECTLY BY THE AFTER-SALES SERVICE OR
BY OTHER FLOWSERVE-AGENTS WHO WILL
GET THE REQUIRED INSTRUCTIONS AND
APPROVALS. THIS IS THE CASE OF
AUTHORIZED REPAIRERS WHOSE ADDRESSES
AND TELEPHONE NUMBERS WILL BE GIVEN
ON REQUEST.
6.5 Disassembly
Refer to section 1.6, Safety, and section 6
Maintenance, before dismantling the pump.
Before dismantling the pump for
overhaul, ensure genuine Flowserve replacement
parts are available. Refer to sectional drawings for
part numbers and identification.
REPAIR OF THE PUMP
If the pump presents abnormalities or a
persistent malfunction, contact immediately:
FLOWSERVE
After-sales Service
Tel.: 02 43 40 57 57
(33) 2 43 40 57 57
Fax.: 02 43 40 58 17
(33) 2 43 40 58 17
According to the After-sales Service instructions,
disassembly will be limited to the dismantling of the
pump:
a)DISCONNECT THE UNIT FROM
POWER.
b) Close the inlet valve (if fitted) and outlet valve.
Page 25 of 35
Page 26
7 FAULTS; CAUSES AND REMEDIES
POSSIBLE CAUSESSOLUTIONS
Pump or suction pipe not completelyfilled- Check and complete filling
Air bubbles in pipes- Check and desecrate the pipes
Suction level too low- Check: the available NPSH > the requiredNPSH
Wrong rotation- Reverse 2 phases on motor terminalboxes
The motor is running on 2 phasesonly- Check and control the motor electrical powersupply
Motor running too low- Checktheconnection inthe terminal box according to the
Total manometric head system higher than
pump differential head
Total manometric head system lower than
pump differential head
Pipes (valves, filter...)- Control, dismantle and clean
Insufficient flow rate- Check the suction and discharge pipes (valves, back
Worn wear-ring surfaces- Foresee pump mending. CONSULT FLOWSERVE
Seizure, jamming- CONSULT FLOWSERVE
Excessive strains on flanges- Check the flange connections and eliminate strains (pipe
Defective gland packing on the shaft- Check and replace all the gland packingparts
Defective motor bearings- CONSULT FLOWSERVE
Specific gravity or viscosity of liquid too high- Consult our local agent to analyze the problem
Misalignment- Check the alignment of the pump and ofitsdriver
Foundations not sufficiently rigid
FP USER INSTRUCTIONS ENGLISH 71576286 - 07/06
Insufficient flow rate
Irregular pump running
Driver overloaded
Mechanical seal leak
Equipment vibration
Excessive pump casing temperature
- Reduce geometrical suction lift
- Reduce head losses in pipes and infittings(diameter
increase and appropriate fittingpositions)
- Check valves and strainers
- Check the immersion head of the suctionvalve
voltage
- Check the discharge head
- Check the head losses in discharge pipes (partly closed valve,
foreign particles, back pressuretoohigh)
- Modify the installation or changethe pump set
-Throttle at discharge valve or trim the impeller (contact our
local agent) CONSULT FLOWSERVE
pressure)
positioning or elastic sleevesmounting)
- Mechanical seal: CONSULT FLOWSERVE
- Check the setting of base plates: tightening,bad adjustment,
seal
Insufficient pressure
Pump looses prime after starting
POSSIBLE CAUSESSOLUTIONS
Rotation speed too low (check thedriver)- Check the connection in the terminal boxaccording to the
Presence of air- Check and de-aerate
Suction pressure insufficient- Check: the available NPSH > the requiredNPSH
Mechanical defects- CONSULT FLOWSERVE
Air leak in the suction pipe- Check suction pipe is airtight
Restriction in suction pipe- Check diameter of suction pipe
Suction level too low- Check the NPSH >NPSH
Obstruction of suction pipe- Check condition of pipe
Defective gland packing on the shaft- Check and replace all the gland packing.
Defective gasket- CONSULT FLOWSERVE
voltage
- Reduce geometrical suction lift
- Reduce head losses in pipes and infittings(diameter increase
and appropriate fitting positions)
- Check valves and strainers
- Check the immersion head ofthesuction valve
- Mechanical seal: CONSULT FLOWSERVE
Page 26 of 35
Page 27
8 PARTS LIST AND DRAWINGS
8.1 Sectional drawings
8.1.1 122 FP Pumps
FP USER INSTRUCTIONS ENGLISH 71576286 - 07/06
Page 27 of 35
Page 28
8.1.2 152 FP Pumps
FP USER INSTRUCTIONS ENGLISH 71576286 - 07/06
Page 28 of 35
Page 29
8.1.3202 FP Pumps
FP USER INSTRUCTIONS ENGLISH 71576286 - 07/06
Page 29 of 35
Page 30
8.1.4 50 FP Pumps
FP USER INSTRUCTIONS ENGLISH 71576286 - 07/06
Page 30 of 35
Page 31
8.1.565 FP, 80 FP, 100 FP, 125 FP Pumps
FP USER INSTRUCTIONS ENGLISH 71576286 - 07/06
Page 31 of 35
Page 32
FP USER INSTRUCTIONS ENGLISH 71576286 - 07/06
8.2 Sectional drawings part list
8.2.1 Parts list pumps 122 FP
NDESIGNATIONNDESIGNATION
1130Suction casing4120Stuffing box gland
1140Discharge casing4130Gland packing
1160Stage casing4131Follower
1410-01 Diffuser4590Gasket
1410-02 Diffuser4610-01
1500-01 Casing wear ring4610-02
1500-02 Casing wear ring4610-03
1500-03 Casing wear ring6515Drain plug
1500-04 Casing wear ring6544Circlip
Round section joint
ring
Round section joint
ring
Round section joint
ring
8.2.2 Parts list pumps 152 FP
NDESIGNATIONNDESIGNATION
1130Suction casing4134Lantern ring
1140Discharge casing4590-01 Gasket
1160Stage casing4590-02 Gasket
1410-01 Diffuser4610-01
1410-02 Diffuser4610-02
1500-01 Casing wear ring4610-03
1500-02 Casing wear ring4610-04
2110Pump shaft6515Drain plug
2250Impeller6569Plug
2410Interstage sleeve6571Tie bolt
Round section joint
ring
Round section joint
ring
Round section joint
ring
Round section joint
ring
2110Pump shaft6571Tie bolt
2250Impeller6572Stud
2410Interstage sleeve6577Hexagon head bolt
2450Shaft sleeve6578Threaded plug
2540Thrower6581-01 Hexagon nut
2905Washer6581-02 Hexagon nut
2910Shaft nut6700-01 Key
3011-01 Radial ball bearing6700-02 Key
3011-02 Radial ball bearing6700-03 Key
3200Bearing housing6700-04 Key
3260Bearing cover6814Grub screw
3853Grease nipple9331Cover plate
2450Shaft sleeve6572Stud
2540Thrower6577-01 Hexagon head bolt
2905Washer6577-02 Hexagon head bolt
2910Shaft nut6577-03 Hexagon head bolt
3011-01 Radial ball bearing 6578-01 Threaded plug
3011-02 Radial ball bearing 6578-02 Threaded plug
3200Bearing housing6581-01 Hexagon nut
3260Bearing cover6581-02 Hexagon nut
3853Grease nipple6700-01 Key
4110
4120Stuffing box gland6700-03 Key
4130Gland packing6700-04 Key
Stuffing box
housing
6700-02 Key
4131Follower9331Cover plate
Page 32 of 35
Page 33
FP USER INSTRUCTIONS ENGLISH 71576286 - 07/06
8.2.3Parts list pumps 202 FP
NDESIGNATIONNDESIGNATION
1130Suction casing4590-01 Gasket
1140Discharge casing4590-02 Gasket
1160Stage casing4610-01
1410-01 Diffuser4610-02
1410-02 Diffuser4610-03
1500Casing wear ring4610-04
2110Pump shaft6515Drain plug
2250Impeller6569Plug
2410Interstage sleeve6571Tie bolt
2450Shaft sleeve6572Stud
Round section joint
ring
Round section joint
ring
Round section joint
ring
Round section joint
ring
8.2.4 Parts list pumps 50 FP
NDESIGNATIONNDESIGNATION
1130Suction casing3853Grease nipple
1140Discharge casing4120Gland
1150Stage casing4130Gland packing
1410Diffuser4132
1470Diffuser plate4590Gasket
1500Casing wear ring4610
2110Pump shaft6515Drain plug
2250Impeller6544Circlip
2410Interstage sleeve6571Tie bolt
2450Shaft sleeve6572Stud
Stuffing box neck
bush
Round section joint
ring
2540Thrower6577-01 Hexagon head bolt
2905Washer6577-02 Hexagon head bolt
2910Shaft nut6577-03 Hexagon headbolt
3011-01 Radial ball bearing6578-01 Threaded plug
3011-02 Radial ball bearing6578-02 Threaded plug
3200Bearing housing6581-01 Hexagon nut
3260Bearing cover6581-02 Hexagon nut
3853Grease nipple6700-01 Key
4110
4120Stuffing box gland6700-03 Key
4130Gland packing6700-04 Key
4131Follower9331Cover plate
Stuffing box
housing
6700-02 Key
2520Loose collar6577Hexagon head bolt
2540Thrower6578Threaded plug
2905Washer6581-01 Hexagon nut
2910Shaft nut6581-02 Hexagon nut
3011-01 Radial ball bearing 6581-03 Hexagon nut
3011-02 Radial ball bearing 6700-01 Key
3200Bearing housing6700-02 Key
3260Bearing cover9331Cover plate
Page 33 of 35
Page 34
FP USER INSTRUCTIONS ENGLISH 71576286 - 07/06
8.2.5 Parts list pumps 65 FP, 80 FP, 100 FP, 125
FP
NDESIGNATIONNDESIGNATION
1130Suction casing4120Gland
1140Discharge casing4130Gland packing
1150Stage casing4132
1410Diffuser4590Gasket
1470Diffuser plate4610
1500Casing wear ring6515Drain plug
2110Pump shaft6544Circlip
2250Impeller6571Tie bolt
2410Interstage sleeve6572Stud
2450Shaft sleeve6577-01 Hexagon head bolt
2520Loose collar6577-02 Hexagon head bolt
Stuffing box neck
bush
Round section joint
ring
9 CERTIFICATION
Certificates determined from the Contract
requirements are provided with these instructions
where applicable. Examples are certificates for CE
marking, ATEX marking etc. If required, copies of
other certificates sent separately to the Purchaser
should be obtained from the Purchaser for retention
with these User Instructions.
10 OTHER RELEVANT
DOCUMENTATION AND MANUALS
10.1 Supplementary User Instructions
Supplementary instructions such as for a driver,
instrumentation, controller, seals, sealant system etc
are provided as separate documents in their original
format. If further copies of these are required they
should be obtained from the supplier for retention
with these User Instructions.
10.2 Change notes
Ifanychanges, agreedwith Flowserve Pump Division,
aremadetotheproductafterits supply, a recordofthe
details should be maintained with these User
Instructions.