Hoyt Electrical Instrument Works, Inc. Alpha 41A Plus, Alpha 42A Plus, Alpha 40A Plus Operating Manual

Alpha 40A+/41A+/42A+
Operating Manual
Rev. 01_09/2015
2-60-006-00-00614
Section Contents
Installation & Operating Instructions
DIGITAL MULTIFUNCTION INSTRUMENT
1. Introduction
2. Measurement Reading Screens
3. Programming
3.1 Password Protection
3.2 Menu selection
3.2.1 System Parameter selection screen
3.2.1.1 System Type
3.2.1.2 Potential Transformer Primary value
3.2.1.3 Potential Transformer Secondary value
3.2.1.4 Current Transformer Primary value
3.2.1.5 Current Transformer Secondary value
3.2.1.6 Demand Integration Time
3.2.1.7 Auto Scrolling
3.2.1.8 Low Current Noise Cutoff
3.2.1.9 No. of Poles Selection
3.2.1.10 Energy Output
3.2.1.11 Energy Digit Reset count
3.2.1.12 Energy Rate
3.2.2 Communication Parameter selection screen
3.2.2.1 Address Setting
3.2.2.2 RS 485 Baud rate
3.2.2.3 RS 485 Parity selection
3.2.3 Reset Parameter selection screen
3.2.3.1 Resetting Parameter
3.2.4.1.1.1.1 Assignment of Energy to Pulse
3.2.4.1.1.1 Pulse Output
3.2.4.1.1 Relay Output Selection menu
3.2.4 Output Option selection screen (menu)
3.2.4.1.1.1.2 Pulse Duration Selection
3
3.2.6 Quit screen
7. Run - Hour
8. On - Hour
9. Number of Interruption Relay Output
10.
10.1 Pulse output
10.2 Limit Switch
Phasor Diagram
11.
12. Installation EMC Installation Requirements12.1
12.2 Case Dimensions and Panel Cut-out
12.3
Wiring
12.4 Auxiliary Supply
12.5 Fusing
12.6 Earth / Ground Connections
13.
Connection Diagrams
14.
Optional Pluggable Module
15.
16.
Connection for Optional Pulse output / RS 485
3.2.4.1.1.1.3 Pulse Rate
3.2.4.1.1.2 Limit output
3.2.4.1.1.2.1 Assignment of Limit Output to Parameter
3.2.4.1.1.2.3 Trip point selection
3.2.4.1.1.2.4 Hysteresis selection
3.2.4.1.1.2.5 Energizing delay time
3.2.4.1.1.2.6 De-energizing delay time
3.2.5 User Assignable Features
3.2.5.1 Feature Selection Menu
3.2.5.1.1 Backlit
3.2.5.1.2 User Assignable Screens
4. Current Reversal screen
5. Phase Rotation Error screen
6. Phase Absent screen
4
5
PT Primary, PT Secondary, CT Primary, CT Secondary 3 Phase 3W, 3 Phase 4W, 1 Phase 2W system.
The front panel has two push buttons using which the user can scroll
to measured power.
1. INTRODUCTION
The Multifunction Energy Meter is a panel mounted 114mm x 114mm ANSI round and 96 x 96mm
DIN Quadratic Digital Panel Meter, which measures important electrical parameters in 3 ph 4 wire
/ 3 wire / 1ph Network and replaces the multiple analog panel meters. It measures electrical
parameters like AC voltage, Current, Frequency, Power, Energy(Active / Reactive / Apparent), phase angle, power factor & many more. The instrument integrates accurate measurement technology (All Voltages & current measurements are True RMS upto 15th Harmonic) with LCD display with backlit.
UPDOWN
Impulse
Alpha 40A+
2. MEASUREMENT READING SCREENS
In normal operation, the user is presented with one of the measurement reading screens out of several screens. These screens may be scrolled through one at a time in incremental order by pressing the “UP key” and in decremental order by pressing “DOWN key”.
6
*Note: Units of these parameters will depend on “Energy Output”. (Refer section 3.2.1.10)
TABLE 1: Measured Parameters System Wise:
Voltage THD (System / Phase) Current THD (System / Phase)
% %
Measured Parameters
System Voltage System Current
Frequency
Voltage VL1-N / 2-N / 3-N Voltage VL1-L2 / L2-L3 / L3-L1
Current L1 / L2 / L3
Active Import Energy (9 Digit resolution)*
Units
Volts
Amps
Hz
Volts Volts Volts
Amps
kWh kWh
Active Export Energy (9 Digit resolution)*
Active Power (System / Phase) Reactive Power (System / Phase) Apparent Power (System / Phase) Power Factor (System / Phase) Phase Angle (System / Phase)
kW kVAr kVA
Degree
kVArh
Capacitive Reactive Energy (9 Digit resolution)*
kVArh
Inductive Reactive Energy (9 Digit resolution)*
kVAh
Apparent Energy (9 Digit resolution)*
Neutral Current
Current Demand kVA Demand kW Import Demand kW Export Demand Max Current Demand
Max kVA Demand
Max kW Import Demand Max kW Export Demand Run Hour On Hour Number of Interruptions Phase Rotation Error
kVA
kW
Amps
kVA
kW
kW kW Hours Hours
Counts
Amps
3P 4W 3P 3W 1P 2W
 
    
     
   
 
 
 
only system only system only system only system
only system only system only system only system only system only system
     
   
 
 
only system only system
Min / Max System Voltage Min / Max System Current
Volts
Amps
 
Phase Absent Indication Current Reversal Indication
 
 
7
TABLE 2 : Measurement Screens (Model wise)
Screen
No.
Parameters
Alpha 42A+
Alpha 41A+
Alpha 40A+
On
Display
On
Modbus
On
Display
On
Modbus
On
Display
On
Modbus
1 Sys Power / Voltage / Current ×
√ √
4 Current × 5 RPM / Frequency × 6 Sys W / VA / Phase Angle × × 7 Sys VAr / PF × only PF 8 Active Energy Import
9 Active Energy Export 10 Capacitive Reactive Energy × × 11 Inductive Reactive Energy × × 12 Apparent Energy × × 14 Min Sys Voltage & Current × × 15 Max Sys Voltage & Current × × 16 R Phase W/ VA / Phase Angle × only W 17 Y Phase W/ VA / Phase Angle × only W 18 B Phase W/ VA / Phase Angle × only W 19 R Phase VAr / PF × only PF 20 Y Phase VAr / PF × only PF 21 B Phase VAr / PF × only PF 22 W IMP / VA / Current Demand × × 23 Max W IMP / VA / Current Demand × × 24 W EXP / VA / Current Demand × × 25 Max W EXP / VA / Current Demand × × 26 Per Phase Voltage THD × × × × 27 Per Phase Current THD × × × × 28 Sys Voltage / Current THD × × × ×
L-N Voltage × L-L Voltage ×
2
3
8
TABLE 2 : Continued...
Available on Display × Not available on Display
Screen
No.
Alpha 42A+ Alpha 41A+ Alpha 40A+
On
Display
On
Modbus
On
Display
On
Modbus
On
Display
On
Modbus
29 Run Hour × 30 On Hour × 35 No of Interruptions × 37 I neutral × × 38 Old Active Import Energy × × 39 Old Active Export Energy × × 41 Old Reactive Capacitive Energy × × 42 Old Reactive Inductive Energy × × 43 Old Apparent Energy × × 45 Old Run Hour × × 46 Old On Hour × × 51 Old No of Interruptions × × 53 Current Reversal × × × 54 Phase Rotation Error × × × 55 Phase Absent × × ×
Parameters
SEL (Select)
B
: UP KEY
: DOWN KEY
Out PArA
(Output Parameter)
rELY out
(Relay Output)
quit
(Exit Menu)
quit
(Exit Menu)
Lt
(Limit Output)
Para. Selection
(Acc. To Table)
.
Selection
(Hi-E,Hi-d,
Lo-E,Lo-d)
trip (Trip Point)
10% to 100%
HYS
(Hysterisis)
0.5% to 50%
En-d
(Energizing Delay time)
1s to 10s
dE-d
(De-energizing Delay time)
1s to 10s
PUL
(Pulse Output)
dur
(Pulse Duration)
60,100,200
rAt
(Pulse Divisor Rate)
1, 10, 100, 1000
.
Para Selection
(i-E, E-E, C-rE, L-rE, A-E)
B
Exit
from setup Parameter to Main Display
rSEt
(Reset Parameter)
none (No Parameter), ALL (All Parameters), d (Demand), E (Energy), hi (Max values), Lo (Min values), Hr (Run Hour & On Hour), Intr (No. of Interrupts)
Select any one option using “Down” key.
Ser PArA
(Serial Comm.Parameter)
Addr
(Modbus Address)
br
(Baud Rate)
Pr
(Parity Bits)
codE (PassWord
)
SYS PArA
(System Parameter)
(Sec 3.2.1)
(Sec 3.2.2)
(Sec 3.2.3)
(Sec 3.2.4)
(Sec 3.2.4.1.1)
(Sec 3.2.4.1.1.1)
(Sec 3.2.4.1.1.1.1)
(Sec 3.2.4.1.1.1.2)
(Sec 3.2.4.1.1.1.3)
(Sec 3.2.4.1.1.2)
(Sec 3.2.4.1.1.2.1)
(Sec 3.2.4.1.1.2.2)
(Sec 3.2.4.1.1.2.3)
(Sec 3.2.4.1.1.2.4)
(Sec 3.2.4.1.1.2.5)
(Sec 3.2.4.1.1.2.6)
(Sec 3.2.2.1)
(Sec 3.2.2.2)
(Sec 3.2.2.3)
SYS
(System Type / Network)
UP
(PT Primary)
US
(PT Secondary)
AP
AS
dit
(Demand Integ. Time)
nC
(Noise Current Cut-off)
A
Auto
(Auto Scrolling)
(Sec 3.2.1.1)
(Sec 3.2.1.2)
(Sec 3.2.1.3)
(Sec 3.2.1.4)
(Sec 3.2.1.5)
(Sec 3.2.1.6)
(Sec 3.2.1.7)
(Sec 3.2.1.8)
Alpha 42A+/41A+/40A+ Setup Parameter Screen
(Sec 3.2.6)
(Sec 3.2.4)
Edrc
En.OP
(Energy Output)
(Sec 3.2.1.10)
(Sec 3.2.1.11)
(Energy digit reset count)
PoLE
(No. of poles selection)
(Sec 3.2.1.9)
A
Enrt
(Sec 3.2.1.12)
(Energy rate)
(CT Primary)
(CT Secondary)
USEr PArA
(User Assignable
bcLt
(Backlit On/Off)
(Sec 3.2.5)
(Sec 3.2.5.1.1)
Parameter)
(Sec 3.2.5.1.2)
Scrn
(User assignable
Screen feature)
quit
(Exit Menu)
(Sec 3.2.5)
A
B
9
3.1. Password Protection
Password protection can be enabled to
screens, by default password protection
Password protection is enabled by selecting
a password of 0000 disables the password
3. PROGRAMMING
The following sections comprise step by step procedures for configuring the Multifunction Meter according to individual user requirements.
To access the set-up screens press and hold “ UP” and “ DOWN” keys simultaneously for 5 seconds. This will take the User into the Password Protection Entry Stage (Section 3.1).
Enter Password, prompt for first digit. (*Denotes that decimal Point will be flashing).
prevent unauthorised access to set-up
is not enabled.
a four digit number other than 0000, setting
protection.
Enter Password, first digit entered, prompt for second digit.(*Denotes that decimal Point will be flashing).
Press the “ ” key to scroll the value of first digit from 0 through to 9, the value will wrap from 9 round to 0.
Press the “ ” key to advance to next digit.
Enter Password, second digit entered, prompt for third digit. (* Denotes that decimal point will be flashing).
Press the “ ” key to advance to next digit.
Enter Password, third digit entered, prompt for fourth digit. (*Denotes that decimal point will be flashing).
In special case where the Password is “0000” pressing the “ ” key when prompted for the first digit will advance to “Password confirmed” screen.
Press the “ ” key to advance to next digit.
Use the “ ” key to scroll the value of the third digit from 0 through to 9, the value will wrap from 9 round to 0.
Use the “ ” key to scroll the value of the fourth digit from 0 through to 9, the value will wrap from 9 round to 0.
Press the “ ” key to advance to verification of the password.
Enter Password, fourth digit entered, awaiting verification of the password.
Use the “ ” key to scroll the value of the second Digit from 0 through to 9, the value will wrap from 9 round to 0.
10
Pressing “ ” key will advance to the “New / change Password” entry stage.
Pressing the “ ” key to advance the operation
digit entered, prompting for second digit. (*Decimal point indicates that this will be
(* Decimal point indicates
New / Change Password
The unit has not accepted the Password entered.
Password Incorrect.
Pressing the “ ” key will scroll the value of the second digit from 0 through to 9, the value will wrap from 9 round to 0.
New / Change Password, second digit entered, prompting for third digit. (*decimal point indicates
Pressing the “ ” key will scroll the value of the third digit from 0 through to 9, the value will wrap from 9 round to 0.
New/ Change Password, third digit entered, prompting for fourth digit. (* denotes that
Pressing the “ ” key will return to the Enter Password stage.
Pressing the “ ” key exits the Password menu & returns operation to the measurement reading mode.
Pressing the “ ” key will scroll the value of the fourth digit from 0 through to 9, the value will wrap from 9 round to 0. Pressing the “ ” key to advance the operation to the
this case to “3”.
Pressing the “ ” key to advance the operation to the next digit and sets the third digit, in this case to “5”
Pressing the “ ” key to advance the operation to the next digit and sets the second digit, in this case to “1”
Pressing the “ ” key will advance to the Menu selection screen. (See section 3.2).
digit from 0 through to 9, the value will wrap from 9 round to 0.
Pressing the “ ” key will return to the “New/Change Password”.
3.2 Menu selection.
3.2.1 System Parameter selection screen
This screen is used to select the different system Parameter like “system type”,“CT
Pressing the “ ” key will advances to the Menu selection screen. (see section 3.2).
11
Pressing the “ ” key allows the user to select &
Ratio”,“PT Ratio”,Pressing the “ ” key allows the user to set Different system parameters. (see section 3.2.1.1 to 3.2.1.12)
3.2.2 Communication Parameter selection screen
This screen is used to select the different communication parameters like “Address selection”,“RS485 Parity selection”, “RS485 baud rate”.
This screen will allow the user to access different features like “Backlit”,“User assignable screens”.
Pressing the “ ” key will advance to Communication selection screen (see section 3.2.2)
Pressing the “ ” key allows the user to set different Communication parameters. (see section 3.2.2.1 to 3.2.2.3)
Pressing the “ ” key will advance to Reset parameter Screen.(see section 3.2.3)
3.2.3 Reset Parameter selection screen
This screen is used to Reset the different parameters.
Pressing the “ ” key allows the user to Reset different system parameters (see section 3.2.3.1)
Pressing the “ ” key will advance to Output Option selection screen (see section 3.2.4).
3.2.4 Output Option selection screen
This screen will allow the user to select Output option Like “Relay” Output.
Pressing the “ ” key will advance to User
Assignable Feature Selection screen. (see section 3.2.5)
Pressing the “ ” key will allow the user to select &
Pressing the “ ” key will advance to Quit screen. ( see section 3.2.6)
3.2.5 User Assignable Feature Selection screen
3.2.1.1 System Type
3.2.1 System parameters Selection
This screen is used to set the system type(only for 3 phase). System type “3” for 3 phase 3 wire, “4” for 3 phase 4 wire system & “1” for single phase system.
3.2.6 Quit screen
This screen will allow the user to Quit the Menu.
Pressing the “ ” key will allow the user to Quit from menu & return to measurement screen.
Pressing the “ ” key will advance to System Parameter Selection screen ( see section 3.2.1)
Pressing the “ ” key accepts the present value and advances to the “Potential transformer primary value Edit” menu. (see section 3.2.1.2)
12
This screen will only appear following the edit of system type.
3.2.1.2 Potential Transformer Primary Value
The nominal full scale voltage which will be displayed as the Line to Line voltages for all system types. The values displayed represent the voltage in kilovolts (note “K” symbol).
Pressing the “ ” key accepts the present value and advances to the “potential Transformer secondary Value Edit” menu. (See Section
3.2.1.3)
Initially the “multiplier must be selected, pressing the “ ” key will move the decimal point position to the
right until it reaches # # # #. after which it will return to #. # # #.
Pressing the “ ” key accepts the present multiplier (decimal point position) and advances to the “potential Transformer primary Digit Edit” mode.
Note :
1. PT Values must be set as Line to Line Voltage for Primary as Well as Secondary for all system types (3P3W/3P4W/1P2W).
2. Default value is set as System Input Voltage.
Pressing the “ ” key sets the displayed value and will advance to “Potential Transformer
Primary Value Edit” menu. (See section 3.2.1.2)
Pressing the “ ” key will return to the system type edit stage. NOTE: Default value is set to ‘4’ i.e. 3P 4W.
Pressing the “ ” key will enter the system type edit mode & scroll through the values available.
Pressing the “ ” key advances to the system
Pressing the “ ” key will enter the “Potential Transformer Primary Value Edit” mode.
The PT Primary value can be set from 100 VL- L to 1200 kVL-L. The value will be forced to 100 VL-L if set less than 100.
position, a steady decimal point will be present to identify the scaling of the number until the cursor position coincides with the steady decimal point
the “ ” key will advance to the “Potential Transformer
of 0.120 kV i.e. 120 Volts indicating steady decimal
position.
presently displayed Potential Transformer Primary Value together with the Current Transformer Primary Value, previously set, would result in a maximum system power of greater than 3000 MVA (1000 MVA per phase) in which case the digit range will be restricted.
Pressing the “ ” key accepts the present value at the cursor position and advances the cursor to the
Pressing the “ ” key will scroll the value of the
through to 9 unless the
Potential Transformer Primary Digit Edit
13
Loading...
+ 30 hidden pages