Hoyles Stainless Steel EXITGUARD Flush mount User Manual

Page 1
EXITGUARD EX104, EX105 & EX106 24 hour Door Alarm
The EX100 series EXITGUARD provides a simple to operate solution for the 24 hour protection of fire exit and other doors. A number of options are available that can be set up at the installation stage. The following features are standard to all EX100 series EXITGUARDs:
Magnetic Door Contact. Fit to door frame and protect from moisture
8mm (max gap).
Magnet. Fit to door & align with contact
6 x AA batteries (Ex104 versions) Do NOT power from 12vdc. This will result
Bk Rd Yl Bl
Tamper
Volt free auxiliary relay contacts. Change on alarm condition EX105 & Ex106 versions
Tamper
12 vdc Power In Ex105 or 12 vdc Power Out 150ma EX106
F U S E
in damage.
N E L
220/240vac EX106 only
Move jumper to select
Lo
Hi
TONE
Jumper links shown in factory default positions
4Basic Chime repeating at 15 sec intervals [1] 4Auto Reset adjustable 1 sec to 90 secs [2] 4Keyswitch Reset [3] 4Instant Alarm [4] 4Reduced alarm after 2 minutes if not reset 4Delay before alarm without pre-warn [5] 4Delay before alarm with pre-warn [6] 4Low level tamper for 2 mins then every 5 mins 4Tamper omit. 4Low battery warning on set & at 5 min intervals 4Hi & Lo level alarm tones 4LED status indicator 4Double bleep for set, single bleep for un-set. 4Pass through/ safe set facility.
Powered from 6 x AA batteries (supplied) EX104 or from a 12vdc intruder alarm supply Ex105
EX105KM is fitted with auxiliary volt free terminals for remote signalling of Set/Unset
16vac
from
transformer
COM
NO
NC
COM
NO
K1 K2 To1To2
Yellow
White
Blue
Keyswitch
NC
A1
A2
T1
T2
Alarm Input
Tamper Input
10s
RESET
1s
CONTROL
90s
Key Reset ie 2mins +
-ve
+ve
low pitch tone
On
Off
DELAY
Move jumper to select 15s
alarm delay (DOTL)
Move jumper to select
On
door chime facility
Off
CHIME
Factory
Options
www.hoyles.com
Default
Start
Chime
or
Alarm
Alarm
Auto
or Key
Reset
[3]
Key
Delayed
or Instant
Alarm
Instant [4]
On On On On
Off Off Off Off
DELAY DELAY DELAY DELAY
On On On On
Off Off Off Off
CHIME CHIME CHIME CHIME
Auto reset
Turn pot fully clockwise to invoke Key Reset ie Factory default
Delayed
Chime [1]
Basic CHIME facilty repeats at 15second intervals
Auto Reset time can be adjusted between 1 sec and 90 secs. Beyond 90 secs it becomes Key Reset
10s
1s
The exact position for maximum reset time (90 secs) is approx. 2 o'clock. To determine this position exactly ensure that the door contact and the tamper loop are both open. The keyswitch should be in the O (Off) position. Apply power and switch to the I (On) position within 3 seconds. The sounder will give a bleep followed by four rapid bleeps Turn the potentiometer slowly and observe the following: At Key Reset a Chime & no LED At Max Reset a Barp & no Led Below Max Reset Silence and steady LED
Warning
at start of
delay
Yes
Tone Select does not affect any other programming
90s
[2]
No
Lo
Hi
TONE
Set jumpers for desired operation
Control with
Keyswitch
Note: There are no programming options for tamper facilities.
Dwg 60095 Iss 3 Oct 13
[1][5][6]
Page 2
EXITGUARD EX104, EX105 & EX106 24 hour Door Alarm
The EX100 series EXITGUARD provides a simple to operate solution for the 24 hour protection of fire exit and other doors. A number of options are available that can be set up at the installation stage. The following features are standard to all EX100 series EXITGUARDs:
Magnetic Door Contact. Fit to door frame and protect from moisture
8mm (max gap).
Magnet. Fit to door & align with contact
6 x AA batteries (Ex104 versions) Do NOT power from 12vdc. This will result
Bk Rd Yl Bl
Tamper
Volt free auxiliary relay contacts. Change on alarm condition EX105 & Ex106 versions
Tamper
12 vdc Power In Ex105 or 12 vdc Power Out 150ma EX106
F U S E
in damage.
N E L
220/240vac EX106 only
Move jumper to select
Lo
Hi
TONE
Jumper links shown in factory default positions
4Basic Chime repeating at 15 sec intervals [1] 4Auto Reset adjustable 1 sec to 90 secs [2] 4Keyswitch Reset [3] 4Instant Alarm [4] 4Reduced alarm after 2 minutes if not reset 4Delay before alarm without pre-warn [5] 4Delay before alarm with pre-warn [6] 4Low level tamper for 2 mins then every 5 mins 4Tamper omit. 4Low battery warning on set & at 5 min intervals 4Hi & Lo level alarm tones 4LED status indicator 4Double bleep for set, single bleep for un-set. 4Pass through/ safe set facility.
Powered from 6 x AA batteries (supplied) EX104 or from a 12vdc intruder alarm supply Ex105
EX105KM is fitted with auxiliary volt free terminals for remote signalling of Set/Unset
16vac
from
transformer
COM
NO
NC
COM
NO
K1 K2 To1To2
Yellow
White
Blue
Keyswitch
NC
A1
A2
T1
T2
Alarm Input
Tamper Input
10s
RESET
1s
CONTROL
90s
Key Reset ie 2mins +
-ve
+ve
low pitch tone
On
Off
DELAY
Move jumper to select 15s
alarm delay (DOTL)
Move jumper to select
On
door chime facility
Off
CHIME
Factory
Options
www.hoyles.com
Default
Start
Chime
or
Alarm
Alarm
Auto
or Key
Reset
[3]
Key
Delayed
or Instant
Alarm
Instant [4]
On On On On
Off Off Off Off
DELAY DELAY DELAY DELAY
On On On On
Off Off Off Off
CHIME CHIME CHIME CHIME
Auto reset
Turn pot fully clockwise to invoke Key Reset ie Factory default
Delayed
Chime [1]
Basic CHIME facilty repeats at 15second intervals
Auto Reset time can be adjusted between 1 sec and 90 secs. Beyond 90 secs it becomes Key Reset
10s
1s
The exact position for maximum reset time (90 secs) is approx. 2 o'clock. To determine this position exactly ensure that the door contact and the tamper loop are both open. The keyswitch should be in the O (Off) position. Apply power and switch to the I (On) position within 3 seconds. The sounder will give a bleep followed by four rapid bleeps Turn the potentiometer slowly and observe the following: At Key Reset a Chime & no LED At Max Reset a Barp & no Led Below Max Reset Silence and steady LED
Warning
at start of
delay
Yes
Tone Select does not affect any other programming
90s
[2]
No
Lo
Hi
TONE
Set jumpers for desired operation
Control with
Keyswitch
Note: There are no programming options for tamper facilities.