
EX205 & EX206
generated.
alarm condition is
change state when an
These relay contacts
EX205 only.
EXITGUARDis armed.
change state when the
These relay contacts
Door Switch Contact Rd/Yl
loop Bl/Bk
8mm (max gap)
Door Switch tamper
EX204 Battery powered for use where a 4. OUT OF THE BOX factory default settings
separate supply of power is not available and are suitable for most applications. On first use
EXITGUARD EX200 series Installation Instructions
the protected door is opened infrequently or we recommend that you use these settings to
there is no requirement to sound the sounder test the EXITGUARD. They can be changed
O/P to optional MULTIGUARD
12vdc
RELAY 1 RELAY 2
COM
protect from moisture
Fit to door frame and
& align with contact
Magnet. Fit to door
Magnetic Door Contact.
Apply momentary 12vdc +ve for return pass through.
derived from an intruder, time clock or keyswitch etc..
Apply 12vdc +ve to invoke Fire Door Checker. This can be
+ve-
R
ve
Input for Fire Door Checker (see scenario 4) Or Temporary Pass through (see scenario 7)
To
M
T
d. ignored and not connected at all.
NC
A
remote location.
c. wired to a remote device to give a warning at a
when the Exitguard is armed.
switch contact pair to give an alarm condition only
b. wired in series with the Blue or Yellow of the door
tamper loop to give an audible alarm at any time.
COM
HED
NO
a. wired in series with the Red or Black door switch
If required the tamper switch To can be:
NO
NC
{
EX206 12vdc available here @ 100ma max when mains power is available.
EX205 Apply 12vdc (165ma max) here.
EX204 Apply 12vdc (140ma max) here if required.
and operates when the lid is removed.
ensuring contact with the wall when the lid is fitted,
If the tamper switch is required fit the spring
connected to these two terminals, To
The on board tamper switch is
are only used on
EX204 & EX206
These terminals
MULTIGUARD 2000 - 6
Z2
Z3Z4Z5
Z6
DWG No: 60112 Issue 2, Nov 2013
Z1
F3
Sounder Tone 1
DOTL2 delay 00 Seconds
DOTL1 delay 00 seconds
Auto re-arm period 30 seconds
User Code None
The Factory default settings are as follows:
code. Re-close the tamper & door contact..
illuminated inviting you to enter a new user
and the four mode LEDs should be
normal position. Two beeps will be heard
will be heard. Replace the jumper to the
reset position. Re-apply power four bleeps
jumper J1 from its normal position to the
are open. Move the SYSTEM RESET
EX206 Mains Powered Version Only
box and is pre-wired to the circuit board.
Transformer is fitted in the enclosure back
230vac
Neutral
Earth
1 AM
P
SYSTEM J1
RESET
RESET
NORM
16vac
Hoyles Electronic Developments Ltd
T. 01744 886600 F. 01744 886607 E. sales@hoyles.com W. www.hoyles.com
BK RD PP
secs. Ensure the door contact & tamper loop
disconnect power completely for about 10
To restore the factory default settings
Factory Default.
for long periods. Can be powered from 12vdc if later to suit local requirements. Test by entering
necessary. (Discard batteries)
EX205 12vdc powered for use where the
protected door may be opened frequently or
the integral sounder needs to sound for
protracted periods. This version can also be
interfaced with other equipment. There are volt
free relay contacts to separately signal
ON/OFF status and alarm conditions at remote
points. Cannot be powered from batteries.
EX206 230vac powered version where the
protected door may be opened frequently or
the sounder needs to sound for protracted
periods. There is a volt free alarm relay contact.
This version is supplied with 6 x AA alkaline
batteries for standby - Note: the batteries will
not power the alarm relay.
All versions have key pad control, integral
sounder with programmable tones, 5 mode
LEDs, a front/back acting tamper switch and a
logic output to signal to a MULTIGUARD
indicator from HED. All are supplied with a door
contact, fixing screws and door warning label.
Quick Install
EXITGUARDS are NOT intended for external
use and to avoid damage should not be fixed to
the protected door itself.
1.The door contact is in two parts; the magnet
should be fixed to the door and the contact with
its cable fitted to the frame. The cable should
be taken to the EXITGUARD and connected as
shown. A is the alarm input for the switch
element (BL/YL) of the contact and T is from
the tamper loop (RD/BK) of the contact.
2. Make all connections, apply power, a double
bleep will be heard and the four mode LEDs will
illuminate.
3. When the EXITGUARD leaves the factory
there are no codes in memory. The four
illuminated red LEDs are inviting you to
enter a User Code. This must be a four digit
memorable code. As the code is entered
acknowledge bleeps are heard and each of
the mode LEDs will extinguish. The code is
now stored in memory and the EXITGUARD
will emit a double bleep and should be in the
OFF mode.
the user code and pressing I for Chime Mode.
A chime will be heard each time the door is
opened.
Advanced Installation
The following parameters can be changed
through the keypad:
1. User Code
2. Select one of six different alarm tones
3. Change auto re-arm delay 0 - 88 secs
4. Change Door Open Too Long (DOTL1)
delay for keypad reset mode 0 secs - 88 mins.
5. Change DOTL2 delay for auto reset mode
0secs - 88mins.
6. Switch Bleep In Off (BIO) on or off.
7.Add or change a Reset/Pass Code
8. Add or change a Manager Code.
OUT OF THE BOX User Operation.
There are four possible modes:
Off Mode
Chime Mode I
Keypad Reset Mode II
Auto re-arm Mode III
When the User Code is entered the
EXITGUARD is interrogated and one of the
mode LEDs illuminates to indicate the current
status.
After the User Code is entered there is a 5sec
window to change the mode, eg. If the current
mode is OFF and it is desired to switch to the
Keypad Reset mode just enter II ie 2 on the
keypad. Within 5secs the LED will extinguish. If
a mistake has been made this can be rectified
before the LED extinguishes by simply
selecting the desired mode, the LED indication
will change to the new mode.
If the Auto re-arm mode is selected then the
factory default period of 30secs will be used
unless set up differently. (see programming
instructions to change the Auto re-arm period
and other functions)
Power LED
Setup LED
Mode
LEDs
exitguard
Chime mode
Keypad reset mode
Auto re-arm mode
Off
I
II
III
II IIII IIIIII
2
1
4 5 6
7 8 0
3
Keypad

EXITGUARD Set-up
The EXITGUARD contains a non volatile memory
(NVM). The User Code and any programmed
functions are stored in this NVM even if power is
lost for long periods. If you have forgotten the
User Code (or manager code if used) it will be
necessary to reset to the factory default settings.
Any functions that you have programmed will be
lost.
Before altering any functions such as the re-arm
period or door open too long delays (DOTL) etc..
consider if the factory defaults will meet your
requirements. The following scenarios are quite
typical. The first four involve no programming
other than setting the User Code. The remaining
scenarios require a little programming.
Scenario 1. Typical Fire Exit Door.
An audible alarm is required when the door is
opened. Use the factory default settings and arm
the EXITGUARD for either Keypad reset II or
Auto re-arm III mode. ie. the EXITGUARD
silences and re-arms after a 30 second delay if the
door has been closed.
Scenario 2. Shop or Reception Door.
A chime is required each time the door is opened.
Use the factory default settings and arm the
EXITGUARD for Chime I mode.
Scenario 3. Fire Door Checker.
The EXITGUARD can be used to verify that all
Fire Exit Doors are available for use when a
building is occupied. The R terminal of each
EXITGUARD is connected to a switched +ve
12vdc of the building’s intruder alarm. When the
alarm is set this signal is applied to the
EXITGUARDs. When the intruder alarm is un-set
the signal is removed and the EXITGUARDs will
strobe and double bleep every 30 secs. Opening
and re-closing the door causes the strobing and
the periodic bleeps to cease. The EXITGUARD
then automatically reverts to the mode it was set to
during the previous period of occupancy; O, I, II
or III. If the intruder alarm has been set in error it
can be un-set and re-set without the necessity to
open and re-close all doors for checking.
Scenario 4. Loading Bay Door.
Invoke the Bleep In Off facility (see programming
below). Arm the EXITGUARD in Keypad reset II
mode. Switch Off with keypad for deliveries. The
Bleep In Off will remind staff to re-arm the
EXITGUARD after each delivery.
Scenario 5. Fire Stop Corridor Door.
Staff are able to pass through the door without
generating an alarm but if left open then an alarm
will be generated. Set the Auto re-arm period at 00
and DOTL2 delay at 10. Door must be closed
within 10 seconds. It is recommended that a door
closer spring is fitted. Arm the EXITGUARD in III code is pressed an LED will extinguish. When the to the procedure for DOTL1 above
mode. code is complete a double bleep is heard. The unit
Scenario 6. Temporary Pass Through
In this scenario a Pass Code is used to allow passage
through to say a storeroom without the necessity to
switch the EXITGUARD Off. When using a pass code
there is a 10 sec window to open the door and a further
time period to pass through and close the door. This
time is specified by either DOTL1 or DOTL2,
depending on which mode the EXITGUARD is armed
in. To use a pass code DOTL1, DOTL2 or both must be
set depending on whether you wish to use mode II or
III. See later instructions for setting DOTL1 and
DOTL2. To return through the door a momentary +ve
must be applied to the R terminal, this will bleep the
unit and strobe the LEDs to warn that the door is about
to open. Arm the EXITGUARD in mode II or III.
High Level Security.
In some applications it may be necessary to allow only
selected persons to change the various parameters. A
Manager Code gives an extra level of security by only
allowing a manager to change:
A. User and Pass & Manager Codes
B. Bleep In Off (BIO)
C. Auto re-arm delays
D. Door Open Too Long delays (DOTL)
Programming.
Before the EXITGUARD can be programmed a User
Code must have been set up as detailed overleaf. The
following functions can be programmed into the NVM:
1. Four digit User Code.
2. Select one of six different alarm tones
3. Change auto re-arm time 0 - 88 seconds
remains in the SET-UP mode and further
programming can be carried out following the
instructions below.
Tone Select.
?
2
In Set-up mode enter 2. A bleep is heard and a
single mode LED illuminates to indicate that a one
digit number in the range 1 - 6 is needed.
The tones are:
1 & 2. High (Factory default setting is 1)
Ear defenders are recommended!!!!!
3 & 4. Normal
5 & 6. Low entered an LED will extinguish. When the code is
If an incorrect digit is entered a ‘Barp’ will be heard
and the LED continues to indicate that a single digit
is still required. When a correct digit is entered the a
short sample of the tone is played with the strobing
LEDs to indicate the selected tone. The Set-up LED
flashes to indicate that you are still in Set-up mode.
Enter 0 to leave if set-up is complete.
Auto re-arm period.
3
?
?
In Set-up mode enter 3. A bleep is heard and two
mode LEDs will illuminate to indicate that a two digit
number corresponding to the required period eg. 00
for instant re-arm, 05 for 5secs, 88 for 88secs etc..
As the digits are entered the LEDs extinguish and a Note: If the EXITGUARD has been set up with a
double bleep is heard when both digits have been Manager Code then both the User Code and
entered. The Set-up LED continues to flash to Manager Code must be used to enter the set-up
Bleep In Off (BIO).
BIO BIO
6 6
PP
O
In Set-up mode BIO can be toggled On and Off .
The default factory setting is Off,
In Set-up mode enter 6. If one bleep is heard then
BIO is off, if two bleeps are heard then BIO is on.
Successively pressing 6 will toggle BIO on and off.
Add or change a Reset/Pass Code.
7
PUPUP
In set-up mode enter 7. A single bleep is heard and
four mode LEDs illuminate inviting you to enter a
four digit Reset/Pass Code PPPP. As each digit is
complete a double bleep is heard. The Set-up LED
continues to flash to indicate that you are still in the
Set-up mode. Ensure DOTL1 and DOTL2 are set.
Add or Change a Manager Code.
8
M M M M
In set-up mode enter 8. a triple bleep is heard and
four mode LEDs illuminate inviting you to enter a
four digit Manager Code MMMM. As each digit is
entered an LED will extinguish. When the code is
complete a double bleep is heard. To change any
further settings in future you will need to use the
Manager Code in order to enter the set-up mode
rather than the User Code.
4. Change DOTL1 delay for keypad reset mode 0 indicate that you are still in the Set-up mode. mode and change any settings. Proceed as
seconds - 88 minutes. follows:
5. Change DOTL2 delay for auto reset mode 0 Enter the User Code UUUU, Press and hold 7.
seconds - 88 minutes. The LED illuminates steady. Enter the
6. Switch Bleep In Off (BIO) on or off.
7.Add or change a four digit Reset/ Pass Code.
8. Add or change a four digit Manager Code.
Programming is carried out in Set-up mode digit number for minutes eg. 00 for zero mins 05 for
To Enter Set-up Mode.
?
?
? ?
7
To enter the this mode type the User Code UUUU and
hold down the 7 key until two beeps are heard. The
Set-up LED flashes. To leave this mode type 0. The
system always reverts to the OFF when leaving Setup. See also Manager Code later.
Changer User Code.
1
UPU
In Set-up mode enter 1, a double bleep is heard and
the four mode LEDs will illuminate inviting you to enter
a new four digit User Code UUUU. As each digit of the
Door Open Too Long Delay for Keypad
reset mode (DOTL1.)
?
4
?
?
?
In Set-up mode enter 4. A bleep is heard and the
bottom two mode LEDs illuminate to request a two
5mins, 88 for 88 mins etc.. As the digits are entered
the LEDs extinguish and a single bleep is heard
when both digits have been entered. The top two
mode LEDs now illuminate requesting a two digit
number for seconds eg. 00 for zero secs, 15 for
15secs up to a maximum of 58secs. The maximum
is therefore 88m58s. A double bleep is heard when
all digits have been entered correctly. The Set-up
LED continues to flash to indicate that you are still in
the Set-up mode.
Door Open Too Long Delay for Auto re-arm
Mode (DOTL2.)
5
?
?
?
?
In Set-up mode enter 5. The procedure is identical
Manager Code M M M M, the LED flashes.
To delete a Pass or Manager Code use the User
Code for either or both..
Leave Set-up Mode.
0
In Set-up mode enter 0, a double bleep is heard as the
EXITGUARD leaves set-up mode. The EXITGUARD
will now be in the OFF mode as indicated by the OFF
LED. Whilst this LED is illuminated the EXITGUARD
can be switched
to any other mode
I, II or III or
even back to Setup mode by
pressing and
holding 7.
Dimensions mm
exitguard
Off
125
Chime mode
Keypad reset mode
Auto re-arm mode
DWG No: 60112 Iss 2 Nov 2013
2
1
3
4 5 6
7 8 0
175
60
50