Howden Roots Tri-RAM 416, Roots Tri-RAM 413, Roots Tri-RAM 722, Roots Tri-RAM 728, Roots Tri-RAM832 Installation, Operation & Maintenance Manual

...
www.howden.com
Roots
TM
Tri-RAM
TM
Tri-lobe
Blowers
Installation Operation & Maintenance Manual
Contents
Information Summary ...............................................................2
Safety Precautions
Operating Limitations
Installation
........................................................................... 4 - 6
Lubrication
Operation
..................................................................................8
....................................................................3
................................................................3
................................................................................7
Troubleshooting
Inspection & Maintenance
Figures
............................................................................ 11 - 12
Tables
.....................................................................................13
Parts List
.................................................................... 14, 17, 19
Assembly Drawings
Do these things to get the most from your Roots Blower
........................................................................9
......................................................10
...........................................15 - 16, 18, 20
Check shipment for damage. If found, file claim with carrier and notify Howden.
Unpack shipment carefully, and check contents against Packing List. Notify Howden if a shortage appears.
Store in a clean, dry location until ready for installation. Lift by methods discussed under INSTALLATION to avoid straining or distorting the equipment. Keep covers on all openings. Protect against weather and corrosion if outdoor storage is necessary.
Read OPERATING LIMITATIONS and INSTALLATION sections in this manual and plan the complete installation.
Provide for adequate safeguards against accidents to persons working on or near the equipment during both installation and operation. See SAFETY PRECAUTIONS.
Install all equipment correctly. Foundation design must be adequate and piping carefully done. Use
recommended accessories for operating protection.
Make sure both driving and driven equipment is correctly lubricated before start-up. See LUBRICATION.
In event of trouble during installation or operation, do not attempt repairs of Roots furnished equipment. Notify Roots, giving all nameplate information plus an outline of operating conditions and a description of the trouble. Unauthorized attempts at equipment repair may void Roots warranty.
Units out of warranty may be repaired or adjusted by the owner. Good inspection and maintenance practices should reduce the need for repairs.
NOTE: Information in this manual is correct as of the date of publication. Howden reserves the right to make design or material changes without notice, and without obligation to make similar changes on equipment of prior manufacture.
For your nearest Howden Office, dial our Customer Service Hot Line toll free in the U.S.; 1 877 363 7668 or direct +1
Roots products are sold subject to the current General Terms of Sale, ES104 and Warranty Policy WP-5020. Copies are available upon request.
2
GEA19684 ISRB_2008 rev._11.15
Safety Precautions
It is important that all personnel observe safety precautions to minimize the chances of injury. Among many consider­ations, the following should be particularly noted:
Blower casing and associated piping or accessories may become hot enough to cause major skin burns on contact.
Internal and external rotating parts of the blower and driving equipment can produce serious physical injuries. Do not reach into any opening in the blower while it is operating, or while subject to accidental starting. Pro­tect external moving parts with adequate guards.
Disconnect power before doing any work, and avoid bypassing or rendering inoperative any safety or protec­tive devices.
If blower is operated with piping disconnected, place a strong coarse screen over the inlet and avoid standing
in the discharge air stream.
Operating Limitations
A Roots blower or exhauster must be operated within certain approved limiting conditions to enable continued satisfactory performance. Warranty is contingent on such operation.
Maximum limits for pressure, temperature and speed are specified in TABLE 1, page 13 for various models & sizes of blowers & exhausters. These limits apply to all units of normal construction, when operated under standard atmospheric conditions. Be sure to arrange connections or taps for instruments such as thermometers and pressure or vacuum gauges at or near the inlet and discharge connec­tions of the unit. These, along with a tachometer, will enable periodic checks of operating conditions.
PRESSURE – The pressure rise, between inlet and dis­charge, must not exceed the figure listed for the specific unit frame size concerned. Also, in any system where the unit inlet is at a positive pressure above atmosphere a maximum case rating of 25 PSI gauge (1725 mbar) should not be exceeded without first consulting Roots. Never should the maximum allowable differential pressure be exceeded.
On vacuum service, with the discharge to atmospheric pres­sure, the inlet suction or vacuum must not be greater than values listed for the specific frame size.
TEMPERATURE – Blower & exhauster frame sizes are ap­proved only for installations where the following temperature limitations can be maintained in service:
CAUTION: Never cover the blower inlet with your hand or other part of body.
Stay clear of inlet and discharge openings.
Stay clear of the blast from pressure relief valves and the suction area of vacuum relief valves.
Use proper care and good procedures in handling, lift­ing, installing, operating and maintaining the equipment.
Casing pressure must not exceed 25 PSI (1725 mbar) gauge. Do not pressurize vented cavities from an exter­nal source, nor restrict the vents without first consulting Roots.
Do not use air blowers on explosive or hazardous gases.
Other potential hazards to safety may also be associat­ed with operation of this equipment. All personnel work­ing in or passing through the area should be trained to exercise adequate general safety precautions.
Measured temperature rise must not exceed listed val­ues when the inlet is at ambient temperature. Ambient is considered as the general temperature of the space around the unit. This is not outdoor temperature unless the unit is installed outdoors.
If inlet temperature is higher than ambient, the listed allowable temperature rise values must be reduced by 2/3 of the difference between the actual measured inlet temperature and the ambient temperature.
The average of the inlet and discharge temperature must not exceed 250°F. (121°C).
The ambient temperature of the space the blower/ motor is installed in should not be higher than 120°F
(48.8°C).
SPEED – These blowers & exhausters may be operated at speeds up to the maximum listed for the various frame sizes. They may be direct coupled to suitable constant speed drivers if pressure/temperature conditions are also within limits. At low speeds, excessive temperature rise may be a limiting factor.
Special Note: The listed maximum allowable temperature rise for any particular blower & exhauster may occur well before its maximum pressure or vacuum rating is reached. This may occur at high altitude, low vacuum or at very low speed. The units’ operating limit is always determined by the maximum rating reached first. It can be any one of the three: Pressure, Temperature or Speed.
GEA19684 ISRB_2008 rev._11.15
3
Installation
Roots blowers & exhausters are treated after factory assembly to protect against normal atmospheric corrosion. The maxi­mum period of internal protection is considered to be one year under average conditions, if shipping plugs & seals are not removed. Protection against chemical or salt water atmosphere is not provided. Avoid opening the unit until ready to start installation, as corrosion protection will be quickly lost due to evaporation.
If there is to be an extended period between installation and start up, the following steps should be taken to ensure corro­sion protection.
Coat internals of cylinder, gearbox and drive end bearing reservoir with Nox-Rust VCI-10 or equivalent. Repeat once a year or as conditions may require. Nox­Rust VCI-10 is petroleum soluble and does not have to be removed before lubricating. It may be obtained from Daubert Chemical Co., 2000 Spring Rd., Oak Brook, Ill.
60521.
Paint shaft extension, inlet and discharge flanges, and all other exposed surfaces with Nox-Rust X-110 or equivalent.
Seal inlet, discharge, and vent openings. It is not recommended that the unit be set in place, piped to the system, and allowed to remain idle for extended periods. If any part is left open to the atmosphere, the Nox-Rust VCI-10 vapor will escape and lose its effec­tiveness.
Protect units from excessive vibration during storage.
Rotate shaft three or four revolutions every two weeks.
Prior to start up, remove flange covers on both inlet and discharge and inspect internals to insure absence of rust. Check all internal clearances. Also, at this time, re­move gearbox and drive end bearing cover and inspect gear teeth and bearings for rust.
Because of the completely enclosed unit design, location of the installation is generally not a critical matter. A clean, dry and protected indoor location is preferred. However, an out­door location will normally give satisfactory service. Important requirements are that the correct grade of lubricating oil be provided for expected operating temperatures, and that the unit be located so that routine checking and servicing can be performed conveniently. Proper care in locating driver and accessory equipment must also be considered.
Supervision of the installation by a Roots Service Engineer is not usually required for these units. Workmen with experience in installing light to medium weight machinery should be able to produce satisfactory results. Handling of the equipment needs to be accomplished with care, and in compliance with safe practices. Unit mounting must be solid, without strain or twist, and air piping must be clean, accurately aligned and properly connected.
Bare-shaft Units: Two methods are used to handle a unit without base. One is to use lifting lugs bolted into the top of the unit headplates. Test them first for tightness and fractures by tapping with a hammer. In lifting, keep the direction of cable pull on these bolts as nearly vertical as possible. If lifting lugs are not available, lifting slings may be passed under the
cylinder adjacent to the headplates. Either method prevents strain on the extended drive shaft.
Packaged Units: When the unit is furnished mounted on a baseplate, with or without a driver, use of lifting slings passing under the base flanges is required. Arrange these slings so that no strains are placed on the unit casing or mounting feet, or on any mounted accessory equipment. DO NOT use the lifting lugs in the top of the unit headplates.
Before starting the installation, remove plugs, covers or seals from unit inlet and discharge connections and inspect the inte­rior completely for foreign material. If cleaning is required, finish by washing the cylinder, headplates and impeller thoroughly with a petroleum solvent. Turn the drive shaft by hand to make sure that the impellers turn freely at all points. Anti-rust compound on the connection flanges and drive shaft exten­sion may also be removed at this time with the same solvent. Cover the flanges until ready to connect piping.
Mounting
Care will pay dividends when arranging the unit mounting. This is especially true when the unit is a “bare-shaft” unit furnished without a baseplate. The convenient procedure may be to mount such a unit directly on a floor or small concrete pad, but this gen­erally produces the least satisfactory results. It definitely causes the most problems in leveling and alignment and may result in a “Soft Foot” condition. Correct soft foot before operation to avoid unnecessary loading on the casing and bearings. Direct use of building structural framing members is not recommended.
For blowers without a base, it is recommended that a well anchored and carefully leveled steel or cast iron mounting plate be provided. The plate should be at least 1 inch (25 mm) thick, with its top surface machined flat, and large enough to provide leveling areas at one side and one end after the unit is mounted. It should have properly sized studs or tapped holes located to match the unit foot drilling. Proper use of a high quality machinist’s level is necessary for adequate installation.
With the mounting plate in place and leveled, set the unit on it without bolting and check for rocking. If it is not solid, determine the total thickness of shims required under one foot to stop rocking. Place half of this under each of the diagonally­opposite short feet, and tighten the mounting studs or screws. Rotate the drive shaft to make sure the impellers turn freely. If the unit is to be direct coupled to a driving motor, consider the height of the motor shaft and the necessity for it to be aligned very accurately with the unit shaft. Best unit arrange­ment is directly bolted to the mounting plate while the driver is on shims of at least 1/8 inch (3mm) thickness. This allows adjustment of motor position in final shaft alignment by varying the shim thickness.
Aligning
When unit and driver are factory mounted on a common baseplate, the assembly will have been properly aligned and is to be treated as a unit for leveling purposes. Satisfactory instal­lation can be obtained by setting the baseplate on a concrete slab that is rigid and free of vibration, and leveling the top of the base carefully in two directions so that it is free of twist. The slab must be provided with suitable anchor bolts. The use of grouting under and partly inside the leveled and shimmed base is recom­mended.
4
GEA19684 ISRB_2008 rev._11.15
It is possible for a base-mounted assembly to become twisted during shipment, thus disturbing the original align­ment. For this reason, make the following checks after the base has been leveled and bolted down. Disconnect the drive and rotate the unit shaft by hand. It should turn freely at all points. Loosen the unit foot hold-down screws and determine whether all feet are evenly in contact with the base. If not, insert shims as required and again check for free impeller rota­tion. Finally, if unit is direct coupled to the driver, check shaft and coupling alignment carefully and make any necessary corrections.
In planning the installation, and before setting the unit, consider how piping arrangements are dictated by the unit design and assembly. Drive shaft rotation must be established accordingly and is indicated by an arrow near the shaft.
Typical arrangement on vertical units has the drive shaft at the top with counterclockwise rotation and discharge to the left. Horizontal units are typically arranged with the drive shaft at the left with counterclockwise rotation and discharge down. See Figure 4 for other various unit arrangements and possible conversions.
When a unit is DIRECT COUPLED to its driver, the driver RPM must be selected or governed so as not to exceed the maximum speed rating of the unit. Refer to Table 1, page 13 for allowable speeds of various unit sizes.
A flexible type coupling should always be used to connect the driver and unit shafts.
When direct coupling a motor or engine to a blower you must ensure there is sufficient gap between the coupling halves and the element to prevent thrust loading the blower bearings. When a motor, engine or blower is operated the shafts may expand axially. If the coupling is installed in such a manner that there is not enough room for expansion the blower shaft can be forced back into the blower and cause the impeller to contact the gear end headplate resulting in damage to the blower. The two shafts must be in as near perfect alignment in all directions as possible, and the gap must be established with the motor armature on its electrical center if end-play ex­ists. Coupling manufacturer’s recommendations for maximum misalignment, although acceptable for the coupling, are normally too large to achieve smooth operation and maximum life of the blower.
The following requirements of a good installation are recommended. When selecting a coupling to be fitted to the blower shaft Roots recommends a taper lock style coupling to ensure proper contact with the blower shaft. Coupling halves must be fitted to the two shafts with a line to line thru .001” interference fit. Coupling halves must be warmed up per coupling manufacturer’s recommendations. Maximum deviation in offset alignment of the shafts should not exceed .005” (.13 mm) total indicator reading, taken on the two coupling hubs. Maximum deviation from parallel of the inside coupling faces should not exceed .001” (.03 mm) when checked at six points around the coupling.
When a unit is BELT DRIVEN, the proper selection of sheave diameters will result in the required unit speed. When selecting a sheave to be fitted to the blower shaft Roots recommends a taper lock style sheave to insure proper contact with the blower shaft. This flexibility can lead to operating temperature
problems caused by unit speed being too low. Make sure the drive speed selected is within the allowable range for the specific unit size, as specified under Table 1, page 13.
Belt drive arrangements should employ two or more V-belts running in grooved sheaves. Installation of the driver is less critical than for direct coupling, but its shaft must be level and parallel with the unit shaft. The driver should be mounted
on the inlet side of a vertical unit (horizontal piping) and on the side nearest to the shaft on a horizontal unit. The
driver must also be mounted on an adjustable base to permit installing, adjusting and removing the V-belts. To position the driver correctly, both sheaves need to be mounted on their shafts and the nominal shaft center distance known for the belt lengths to be used.
CAUTION: Drive couplings and sheaves (pulleys) should have an interference fit to the shaft of the blower (set screw types of attachment generally do not provide reliable service.) It is recommended that the drive coupling or sheave used have a taper lock style bushing which is properly sized to provide the correct interference fit required. Drive couplings, that require heating to fit on the blower shaft, should be installed per coupling manufacturer recommendations. A drive coupling or sheave should not be forced on to the shaft of the blower as this could affect internal clearances resulting in damage to the blower.
Engine drive applications often require special con­sideration to drive coupling selection to avoid harm­ful torsional vibrations. These vibrations may lead to blower damage if not dampened adequately. It is often necessary to install a fly-wheel and/or a torsionally soft elastic element coupling based on the Engine manufac­turer recommendations.
The driver sheave should also be mounted as close to its bearing as possible, and again should fit the shaft correctly. Position the driver on its adjustable base so that 2/3 of the total movement is available in the direction away from the unit, and mount the assembly so that the face of the sheave is accurately in line with the unit sheave. This position minimizes belt wear, and allows sufficient adjustment for both installing and tightening the belts. After belts are installed, adjust their tension in accordance with the manufacturer’s instructions. However, only enough tension should be applied to prevent slippage when the unit is operating under load. Excessive tightening can lead to early bearing concerns or shaft break­age.
Before operating the drive under power to check initial belt tension, first remove covers from the unit connections. Make sure the interior is still clean, then rotate the shaft by hand. Place a coarse screen over the inlet connection to prevent anything being drawn into the unit while it is operating, and avoid standing in line with the discharge opening. Put oil in the sumps per instructions under LUBRICATION.
Piping
Before connecting piping, remove any remaining anti-rust compound from Unit connections. Clean pipe should be no smaller than unit connections. In addition, make sure it is free of scale, cuttings, weld beads, or foreign material of any kind. To further guard against damage to the unit, especially when an inlet filter is not used, install a substantial screen
GEA19684 ISRB_2008 rev._11.15
5
Fig. 1 - Acceptable Blower Drive Arrangement Options
Acceptable Unacceptable
Top Shaft
INLETDISCHARGE
Motor on Inlet Side of Blower (Top Shaft)
DISCHARGE
Bottom Shaft
INLET
Motor on Inlet Side of Blower (Bottom Shaft)
Above are suggested locations for available accessories.
of 16 mesh backed with hardware cloth at or near the inlet connections. Make provisions to clean this screen of collected debris after a few hours of operation. It should be removed when its usefulness has ended, as the wire will eventually deteriorate and small pieces going into the unit may cause serious damage.
Pipe flanges or male threads must meet the unit connections accurately and squarely. DO NOT attempt to correct misalign­ment by springing or cramping the pipe. In most cases this will distort the unit casing and cause impeller rubbing. In se­vere cases it can prevent operation or result in a broken drive shaft. For similar reasons, piping should be supported near the unit to eliminate dead weight strains. Also, if pipe expan­sion is likely to occur from temperature change, installation of flexible connectors or expansion joints is advisable.
Figure 3, page 11 represents an installation with all accessory items that might be required under various operating condi­tions. Inlet piping should be completely free of valves or other restrictions. When a shut-off valve can not be avoided, make sure a full size vacuum relief is installed nearest the unit inlet. This will protect against unit overload caused by accidental closing of the shut-off valve.
Need for an inlet silencer will depend on unit speed and pres­sure, as well as sound-level requirements in the general
surroundings. An inlet filter is recommended, especially in dusty or sandy locations. A discharge silencer is also normally suggested, even though Whispair units operate at generally
Top Shaft
DISCHARGE
INLET
Motor on Discharge Side of Blower (Top Shaft)
INLETDISCHARGE
Bottom Shaft
Motor on Discharge Side of Blower (Bottom Shaft)
lower noise levels than conventional rotary blowers. Specific recommendations on silencing can be obtained from your local Roots distributor.
Discharge piping requires a pressure relief valve, and should include a manual unloading valve to permit starting the unit under no-load conditions. Reliable pressure/vacuum gauges and good thermometers at both inlet and discharge are recommended to allow making the important checks on unit operating conditions. The back-pressure regulator shown in Figure 3, page 11 is useful mainly when volume demands vary while the unit operates at constant output. If demand is constant, but somewhat lower than the unit output, excess may be blown off through the manual unloading valve.
In multiple unit installations where two or more units operate with a common header, use of check valves is mandatory. These should be of a direct acting or free swing-
ing type, with one valve located in each line between the unit and header. Properly installed, they will protect against damage from reverse rotation caused by air and material back-flow through an idle unit.
After piping is completed, and before applying power, rotate the drive shaft by hand again. If it does not move with uniform freedom, look for uneven mounting, piping strain, excessive belt tension or coupling misalignment.
DO NOT operate the unit at this time unless it has been lubricated per instructions.
6
GEA19684 ISRB_2008 rev._11.15
Lubrication
Due to sludge build-up and seal leakage problems, Roots recommendation is DO NOT USE Mobil SHC synthetic oils in Roots blowers.
LUBRICATION: For Units with Splash Lubrication on Both Ends.
The specified and recommended oil is Roots Synthetic oil of correct viscosity per Table 2, page 13.
The proper oil level should be half way or middle of the sight gauge when the blower is not operating. DO NOT OVERFILL OIL SUMP/S as damage to the blower may occur.
Oil level may rise or fall in the gauge during operation to an extent depending somewhat on oil temperature and blower speed.
It is recommended that the oil be changed after initial 100 hours of operation.
Proper service intervals of the oil thereafter are based on the discharge air temperature of the blower. Please refer to the information below to properly determine the oil service intervals.
If you choose to use another oil other than the specified and recommended Roots Synthetic, use a good grade of industrial type non-detergent, rust inhibiting, anti­foaming oil and of correct viscosity per Table 2, page
13.
Roots does NOT recommend the use of automotive type lubricants, as they are not formulated with the
properties mentioned above.
Normal life expectancy of the specified and recommended Roots Synthetic oil is approximately 6000 hours with an oil temperature of 180°F (82°C) or less. As the oil temperature increases by increments of 15°F (8°C), the oil life is reduced by half for each 15°F (8°C) increase. Example: Oil tem­peratures of 195°F (90.5°C) will produce a life expectancy reduced by half or 3000 hours oil service life.
Normal life expectancy of petroleum based oils is about 2000 hours with an oil temperature of about 180°F (82°C). As the oil temperature increases by increments of 15°F (8°C), the life is reduced by half for each 15°F (8°C) increase. Example: Oil temperatures of 195°F (90.5°C) will produce life expectancy reduced by half or 1000 hours oil service life.
NOTE: To estimate oil temperature, multiply the discharge temperature of the blower by 0.88. Example: if the discharge air temperature of the blower is 200° F, it is estimated that the oil temperature is 176° F.
High ambient temperatures contribute to increased lubrication sump temperatures. In situations such as blowers in a enclo­sure, blowers exposed to radiant heat from other sources, blowers installed in areas with poor air circulation or ambient temperatures above 80°F the lubrication sump temperature should be measured rather than fully rely on the calculation.
Bearings and oil seals are lubricated by the action of the timing gears or oil slingers which dip into the main oil sumps causing oil to splash directly on gears and into bearings and seals. A drain port is provided below each bearing to prevent an excessive amount of oil in the bearings. Seals located inboard of the bearings in each headplate effectively retain oilwithin the sumps. Any small leakage that may occur should the seals wear passes into a cavity in each vented headplate and is drained downward. Oil sumps on each end of the blower are filled by removing top vent plugs, Item (21), and filling until oil reaches the middle of the oil level sight gauge, Item (37).
Initial filling of the sumps should be accomplished with the blower not operating, in order to obtain the correct oil level. Approximate oil quantities required for blowers of the various models and configurations are listed in Table 3, page 13.
The oil level should not fall below the middle of the site gauge when the blower is idle.
Proper lubrication is usually the most important single consideration in obtaining maximum service life and satisfac­tory operation from the unit. Unless operating conditions are severe, a weekly check of oil level and necessary addition of lubricant should be sufficient. During the first week of opera­tion, check the oil levels in the oil sumps about once a day, and watch for leaks. Replenish as necessary. Thereafter, an occasional check should be sufficient.
More frequent oil service may be necessary if the blower is operated in a very dusty location.
*Roots Synthetic oil is superior in performance to petroleum based products. It has high oxidation stability, excellent cor­rosion protection, extremely high film strength and low coef­ficient of friction. Typical oil change intervals are increased 2-3 times over petroleum based lubricants. Also, Roots Synthetic oil is 100% compatible with petroleum based oils. Simply drain the oil in the blower and refill the reservoirs with Roots Synthetic oil to maintain optimum performance of your Roots blower.
GEA19684 ISRB_2008 rev._11.15
7
Loading...
+ 15 hidden pages