Howard Industries HI-105 Instructions Manual

Three-Phase Padmounted Distribution Transformers
Document 2.4.126, Revision 4
October 2017
Instructions (HI-105)
Installation, Operation, and Maintenance of Three-Phase Padmounted Distribution Transformers 45 kVA through 10,000 kVA
Howard Industries
Distribution Transformer Division
1
Document 2.4.126, Revision 4 October 2017
READ THIS IMPORTANT SAFETY INFORMATION
Read these instructions carefully and become familiar with the equipment before proceeding with installation, operation, or maintenance activities. This equipment contains extremely hazardous voltages. To prevent death, serious personal injury, or equipment damage, all information in these instructions should be read and observed. Safe use of this equipment is dependent on proper installation, operation, and maintenance procedures.
Certain information in this manual is marked with the words DANGER, WARNING, or CAUTION, which indicate hazards.
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious personal injury, and damage to the equipment.
WARNING indicates a potentially hazardous situation which, if not avoided, may result in death or serious personal injury, and/or damage to the equipment.
Three-Phase Padmounted Distribution Transformers
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate personal injury, and/or damage to the equipment.
No one should attempt to service or perform maintenance activities on the equipment until it has been effectively de-energized, and all high-voltage and low-
voltage bushing terminals have been properly grounded. Only qualied personnel should install, maintain, and operate this equipment. Qualied personnel are
those who are trained in the installation, maintenance, and operation of high­voltage equipment, trained in the proper use of personal protective equipment (such as rubber gloves, safety glasses, protective clothing, hard hats, etc.) and
trained in appropriate rst aid procedures.
The instructions contained herein are intended to be a general guide for the installation, operation and maintenance of this equipment, when operated in
“Usual Service Conditions” as dened in IEEE Standard C57.12.00. Features
presented herein may not be present in all equipment designs. Standard and optional features are subject to change without notice.
Although efforts have been made to ensure accuracy and completeness, these instructions do not address every conceivable application or circumstance that might be encountered. Howard Industries makes no representation or warranty with respect to, and assumes no responsibility for the completeness, accuracy,
sufciency, or usefulness of, these instructions.
Questions regarding installation, operation, and maintenance of the equipment, particularly when encountering unusual or special circumstances that may not
be sufciently covered by these instructions, should be directed to the Howard
Industries Transformer Division.
2
Three-Phase Padmounted Distribution Transformers
Document 2.4.126, Revision 4
October 2017
TABLE OF CONTENTS
Important Safety Information........................................................................................................................2
2
Section 1: Introduction.................................................................................................................................5
Section 2: Receiving, Handling and Storage...............................................................................................6
Drawings and Documents.........................................................................................................….....6
Lifting and Handling......................................................................................................................6
Initial Inspection............................................................................................................................6
Fluid Level.....................................................................................................................................7
Internal Inspection..........................................................................................................................7
Fluid Sampling..................................................................................................................................7
Transformer Storage......................................................................................................................8
Section 3: Installation..................................................................................................................................9
Lifting and Handling.........................................................................................................................9
Jacking, Skidding and Rolling............................................................................................................9
Location and Mounting..................................................................................................................9
Verifying Enclosure Integrity............................................................................................................10
Grounding.......................................................................................................................................10
High-Voltage and Low-Voltage Connections.......................................................................................10
High-Voltage Connections..............................................................................................................10
Low-Voltage Connections...............................................................................................................11
Section 4: Inspection and Testing Before and After Initial Energization.........................................................12
Pre-Energization Inspection and Tests..........................................................................................12
Ratio Test......................................................................................................................................12
Insulation Resistance Test.............................................................................................................12
Tap Changer Setting…………………………………………………………….........................................................12
Series/Multiple or Delta/Wye Switch Settings…………………………………................................................13
Grounding………………………………………………………………………............................................................….13
Bolted Connections……………………………………………………………...................................................….....13
Fluid Level………………………………………………………………………......................................................….....13
Fluid Temperature………………………………………………………………....................................................…...13
Internal Fault Detector...............................................................................................................…..13
Current Transformers…………………………………………………………....................................................…....13
Accessory Wiring……………………………………………………………….....................................................…....13
Tank Finish……………………………………………………………………...........................…............................….....13
Tools……………………………………………………………………………..........................................................…....13
Internal Inspection………………………………………………………………....................................................…..13
Post-Energization Inspection and Tests……………………………………...............................................….....14
Verifying Correct Voltage...........................................................................................................…...14
Checking for Leaks……………………………………………………………...................................................…......14
Observing Operation..............................................................................................................…......14
Checking Gauges………………………………………………………………..................................................…..14
Audible Sound…………………………………………………………………......................................................…....14
Locking the Terminal Compartment…………………………………………….........................................….......14
10 10 10 10 11
12 12 12 12 12 13 13 13 13 13 13 13 13 13 13 13 14 14 14 14 14 14 14
5
6 6 6 6
7 7 7
8
9 9 9 9
Section 5: Operation of Switching and Protective Devices………………................................................................15
Tap Changer……………………………………………………………………...................................................................15
Series/Multiple or Delta/Wye Switch………………………………………….........................................................16
Load-Break Switch…………………………………………………………..................................................................…16
Fuses………………………………………………………………………..................................................................…......16
15 15
16 16 16
3
Document 2.4.126, Revision 4 October 2017
Three-Phase Padmounted Distribution Transformers
Internal Weak-Link Cartridge Fuse……………………………………………..........................................................17
Bay-O-Net Fuse………………………………………………………………….................................................................17
Dead-Break Dry-Well Canister Fuse……………………………………………........................................................18
Internal Partial-Range Current-Limiting Fuse………………………………….....................................................19
S&C Arc-Strangler………………………………………………………………................................................................19
S&C Fused Switch………………………………………………………………...............................................................19
Vacuum Fault Interrupter……………………………………………………….............................................................19
Surge Arresters………………………………………………………………....................................................................20
Internal MOV Surge Arresters…………………………………………….........................................................…..….20
Molded-Case Circuit Breakers………………………………………………...........................................................…21
Hot-Stick Operable Devices……………………………………………………........................................................... 21
Other Switching and Fusing Devices…………………………………………..........................................................21
Section 6: Operation of Bushings, Gauges and Accessory Devices......................................................................22
Pressure-Vacuum Gauge……………………………………………………….............................................................22
Fluid Level Gauge and Sight Plug ……………………………….........................................................................22
Fluid Temperature Gauge………………………………………………………............................................................22
Drain Valve and Sampling Device……………………………………………...........................................................22
Automatic Pressure Relief Device………………………………………………........................................................23
Internal Fault Detector…………………………………………………………..............................................................23
High-Voltage Bushings…………………………………………………………..............................................................23
Low-Voltage Bushings……………………………………………………………............................................................24
Current Transformers…………………………………………………………….............................................................24
Accessor y Brackets…………………………………………………………….................................................................24
Flip-Top Terminal Compartment Cover…………………………………................................................................24
Door Handle, Padlock and Security Bolt……………………………………..........................................................24
Lift-Off Door Hinges……………………………………………………………................................................................24
Other Accessory Devices………………………………………………………..............................................................24
17 17
18 19 19 19 19 20 20 21 21 21
22 22 22 22 22 23 23 23 24 24 24 24 24 24 24
Section 7: Maintenance...........................................................................................................................................25
Periodic Inspection………………………………………………………………..............................................................25
Inspection Checklist………………………………………………………………............................................................26
Electrical Tests……………………………………………………………………...............................................................27
Exterior Paint Finish……………………………………………………………...............................................................28
Fluid Leaks………………………………………………………………………..................................................................28
Audible Sound Level……………………………………………………………...............................................................28
Molded-Case Circuit Breakers…………………………………………………...........................................................29
Other Accessory Devices………………………………………………………..............................................................29
Sampling and Testing the Fluid………………………………………………….........................................................29
Filtering the Fluid…………………………………………………………………..............................................................29
Removing or Lowering the Fluid………………………………………………...........................................................29
Filling with Fluid………………………………………………………………...................................................................29
Opening the Transformer Tank…………………………………………………..........................................................30
Torque Guidelines………………………………………………………………................................................................31
Table 1—Torque Guidelines for External Cabinet Fasteners………………...................................................31
Table 2—Torque Guidelines for External Bushing Mounting Hardware……..............................................31
Table 3—Torque Guidelines for External Bushing Terminal Connections….............................................32
Table 4—Torque Guidelines for Accessories………………………………..........................................................32
Additional Maintenance Instructions……………………………………...........................................................….33
Repair Parts………………………………………………………….....................................................................……….33
Warranty Claims……………………………………………………....................................................................……….
Transformer Disposal.……………………………………………....................................................................………
25 25 26
27
28 28 28 29 29 29 29 29 29 30
31 31
31 32 32 33 33 33
33
4
Three-Phase Padmounted Distribution Transformers
SECTION 1: INTRODUCTION
This document is intended as a general guide for the installation, operation and maintenance of Howard Industries three-phase compartmental padmounted distribution transformers. Although efforts have been made to ensure accuracy and completeness, these instructions do not address every conceivable application or circumstance that
might be encountered. Features presented herein
may not be present in all transformer designs. Standard and optional features are subject to change without notice.
The instructions contained herein are applicable to transformers operated in normal conditions
as specied in the “Usual Service Conditions” section of IEEE Standard C57.12.00. Questions
regarding installation, operation, and maintenance (particularly when encountering unusual or special
circumstances not sufciently covered by these
instructions) should be directed to the Howard Industries Transformer Division.
Document 2.4.126, Revision 4
October 2017
IT IS IMPORTANT TO READ AND COMPLY WITH ALL SAFETY INFORMATION, INSTRUCTIONS AND WARNINGS DISPLAYED THROUGHOUT THESE INSTRUCTIONS BEFORE ATTEMPTING ANY INSTALLATION, OPERATION, OR MAINTENANCE ACTIVITIES.
5
Document 2.4.126, Revision 4 October 2017
SECTION 2: RECEIVING, HANDLING AND STORAGE
Three-Phase Padmounted Distribution Transformers
Drawings and Documents
Locate all shipping papers, packing lists, outline drawings, and other pertinent information for use during inspection. The transformer outline drawing indicates the location of nameplates and warning labels, and provides physical dimensions and weights. The nameplate provides electrical characteristics, winding connections, and weights. The wiring diagram provides details of any control, fan and alarm wiring that may have been supplied.
Lifting and Handling
Lifting hooks are provided near the top of the transformer tank for lifting. All four lifting hooks must be used simultaneously. The transformer must not be lifted from any points other than the provided lifting hooks. Do not use holes in the lifting hooks for lifting. These holes are for tie-down purposes only and are not suitable for lifting.
WARNING
FAILURE TO FOLLOW THE INSTRUCTIONS BELOW MAY CAUSE DEATH OR SERIOUS PERSONAL INJURY AND/OR DAMAGE TO THE EQUIPMENT.
• Use a crane, suitable lifting cables or straps, and a spreader bar to unload the transformer.
• Do not unload using a forklift. Keep unnecessary personnel clear while
unloading and moving the transformer.
Transformers should be lifted in an upright position, allowing the transformer to tilt no more than 15° from vertical. Lifting cables should be no more than 20° from vertical. It is recommended that a spreader bar be used to keep the lifting cables nearly vertical to enable a safe lift and to reduce the likelihood of tank deformation or damage to painted surfaces.
Lifting the transformer with a forklift is not
recommended, since weight and balance can be problematic and radiator panels can be easily damaged. Refer to the transformer nameplate to determine the total weight of the assembled transformer. Special care must be taken when handling transformers when the ambient
temperature is below minus 20°C (minus 4°F);
otherwise, permanent damage to the transformer may result.
Initial Inspection Although all transformers, components, and accessories are carefully inspected and tested prior to shipment, a thorough receiving inspection should be conducted to detect any damage or loss that might have occurred during shipment. The receiving inspection should be completed upon receipt and
before unloading from the truck. Note any damage
or discrepancies on the bill of lading, le a claim
with the carrier, and notify the Howard Industries Transformer Division prior to unloading the
transformer and before attempting any repair. Before unloading the transformer, the following checks should be performed:
1. Read the serial number on the transformer nameplate and make sure it matches the serial number listed on the shipping documents. Also, check the nameplate for kVA rating, high-voltage rating, low-voltage rating, impedance and other design characteristics, and make sure they
comply with the specications.
2. Check shipping documents to make sure the shipment is complete, including all listed accessories and hardware. Be aware that additional items may arrive on separate pallets. Claims for shortages or errors must be noted on the shipping documents and reported immediately to the Howard Industries
Transformer Division. Failure to make a timely claim will constitute unqualied acceptance and
a waiver of all such claims by the purchaser.
3. The tank vacuum/pressure gauge may indicate a positive or negative reading when the transformer is received, depending on the
relative temperatures of the uid and ambient
6
Three-Phase Padmounted Distribution Transformers
Document 2.4.126, Revision 4
October 2017
air. A rising or falling reading that varies over time with ambient temperature indicates that the transformer tank is sealed effectively. If the vacuum/pressure gauge shows a constant zero reading, this indicates the possibility of a tank leak. If this occurs, the tank should be checked carefully for leaks as indicated in the following step.
4. Check the tank for indication of uid leaks,
looking carefully at weld seams, bushings,
gauges, valves and all other tank ttings. If
suspicious indications are found, investigate thoroughly to determine if a leak does exist on the transformer. Indications of a leak
can sometimes be residual uid that was not
cleaned during the manufacturing process and not an actual leak. In many cases a small pinhole tank leak or leak from a bushing, gauge,
valve or other tting can be easily repaired on
site. Refer to the “Maintenance” section for
information about the repair of uid leaks.
5. Check for external damage including dents or scratches on the tank walls, radiators and terminal compartment. Dents and scratches can often be repaired on site using simple touch-up procedures. If touch-up painting is performed, do not remove or obscure any warning labels, instructional labels or nameplates.
extremely hot. When checking the uid level, bear in mind that the level will vary as a function of uid
temperature.
A transformer found to have a low uid level should be checked for potential leaks and lled to the
proper level with the same type of liquid as that
specied on the transformer nameplate.
WARNING
FAILURE TO FOLLOW THE INSTRUCTIONS BELOW MAY CAUSE DEATH OR SERIOUS PERSONAL INJURY AND/OR DAMAGE TO THE EQUIPMENT.
• Do not energize the transformer if the
uid level is low.
• Maintain proper uid level at all times
while the transformer is energized.
• Exercise caution when checking the uid level with the uid level plug, as the uid
may spill and may be extremely hot.
6. Check for broken, cracked, or damaged
bushings, gauges, valves and other ttings and
accessories.
7. Check for missing or damaged component parts
and packages that shipped separately from the transformer.
Fluid Level
The transformer is shipped from the factory with
dielectric uid lled to the proper level. Before energizing the transformer, verify proper uid level by observing the uid level gauge. The uid level
gauge pointer should be between the “High” and
“Low” marks. For transformers supplied with a uid sight plug, the uid level can be directly observed
if it is within acceptable range. If the transformer
does not have a uid level gauge or sight plug, the uid level can be checked by removing the liquid
level plug located at the 25° C mark. Exercise
caution when checking the uid level using the uid level plug, as the uid may spill out and may be
Internal Inspection An internal inspection of the transformer tank is rarely necessary and is recommended only when there are obvious indications that the transformer has received severe impact damage during transit or when necessary to perform recommended pre­energization tests or inspections. Do not open the transformer tank without authorization from the Howard Industries Transformer Division. If the transformer tank must be opened, refer to “Opening the Transformer Tank” for instructions.
Fluid Sampling
Sampling and testing of the uid is not required
unless there is indication that moisture or other contaminants have accidently entered the tank during transit. If moisture or contaminates in the
uid is suspected, contact the Howard Industries
Transformer Division immediately for instructions.
If uid sampling is required, refer to “Sampling the Fluid” for instructions.
7
Document 2.4.126, Revision 4 October 2017
Transformer Storage Transformers may be temporarily stored if properly prepared. It is recommended that transformers be stored completely assembled. Prior to storage, transformers should be thoroughly inspected as described above in the “Initial Inspection” section. If the transformer is not completely assembled, separate components and accessories should be stored in a clean dry area in their original shipping containers. Do not store the transformer in a corrosive environment.
If the transformer is to be stored for an extended period of time before being placed into service,
it should be stored on a rm level surface. The gas space above the insulating uid should be
pressurized with dry nitrogen to a pressure of 2-3 PSIG. This will prevent a negative internal pressure that might draw moisture into the tank.
Three-Phase Padmounted Distribution Transformers
It is recommended that the transformer be inspected periodically while it is in extended storage. Ensure that an effective pressure seal is maintained, and check for leaks and corrosion. Any damage or defects should be repaired immediately.
8
Three-Phase Padmounted Distribution Transformers
SECTION 3: INSTALLATION
Document 2.4.126, Revision 4
October 2017
Lifting and Handling
Lifting hooks are provided near the top of the transformer tank for lifting. All four lifting hooks must be used simultaneously. The transformer must not be lifted from any points other than the provided lifting hooks. Do not use holes in the lifting hooks for lifting. These holes are for tie-down purposes only and are not suitable for lifting.
Transformers should be lifted in an upright position, allowing the transformer to tilt no more than 15 degrees from vertical. Lifting cables should be no more than 20° from vertical. It is recommended that a spreader bar be used to keep the lifting cables nearly vertical to enable a safe lift and to reduce the likelihood of tank deformation or damage to painted surfaces.
Lifting the transformer with a forklift is not recommended, since weight and balance can be problematic and radiator panels can be easily damaged. Refer to the transformer nameplate to determine the total weight of the assembled transformer. Special care must be taken when handling transformers when the ambient
temperature is below minus 20°C (minus 4°F);
otherwise, permanent damage to the transformer may result.
WARNING
FAILURE TO FOLLOW THE INSTRUCTIONS BELOW MAY CAUSE DEATH OR SERIOUS PERSONAL INJURY AND/OR DAMAGE TO THE EQUIPMENT.
• Use a crane, suitable lifting cables or straps, and a spreader bar to unload the transformer.
• Do not unload using a forklift. Keep unnecessary personnel clear while unloading and moving the transformer.
Jacking, Skidding, and Rolling
The transformer tank base is designed for jacking,
skidding and rolling. Do not use radiator ns, bushings, valves, pipe ttings, gauges or sheet
metal surfaces for jacking. Jacking must be done using the proper jacking provisions from two adjacent corners simultaneously to prevent warping of the tank bottom. When rolling, use an adequate number of rollers to distribute the transformer weight evenly. Refer to the transformer outline drawing for the total weight of the assembled transformer.
Location and Mounting
Consult local and national codes to ensure that the installation meets all applicable requirements. Location of the transformer must permit it to operate in conditions that meet the requirements
specied in the “Usual Service Conditions” section of IEEE Standard C57.12.00. Operation not
meeting these service condition requirements will compromise transformer capacity and reliability,
unless the transformer is designed specically
for operation in conditions other than usual service conditions. Contact the Howard Industries Transformer Division, if additional information is needed about location and mounting issues not covered by these instructions.
The transformer should be mounted on a level
concrete foundation of sufcient strength to
support the weight of the completely assembled
transformer. The transformer should sit ush with
the surface of the pad, so that there are no gaps that might compromise tamper resistance of the terminal compartment. The installed transformer should not tilt in any direction more than three degrees. Greater tilt may compromise insulation
uid coverage of live parts within the tank and may prevent insulating uid from circulating properly
through the cooling radiators. Improper circulation
of insulating uid may cause overheating and
reduced transformer life.
The transformer should be located at least 24
inches (710 mm) from any obstruction and
have adequate clearance to allow the terminal compartment doors to open fully. When installing transformers designed for indoor operation, adequate air inlets and outlets must be provided at the mounting location for proper cooling.
9
Document 2.4.126, Revision 4 October 2017
Avoid locating the transformer in corrosive areas. Remove any shipping braces and packing material that may have been installed at the factory.
Verifying Enclosure Integrity
Three-phase compartmental padmounted transformers are designed and constructed to be tamper resistant according to the requirements
of IEEE Standard C57.12.28 or C57.12.29, as
applicable, and therefore need not be located in a restricted area. Do not modify the tank or terminal compartment in such a way that it will compromise tamper resistance. If for any reason
modications must be made to the tank or terminal
compartment that compromise tamper resistance, the transformer must then be located in a restricted
area. Such modications of may void the warranty.
Consult with the Howard Industries Transformer
Division before making any modications to the
transformer.
Three-Phase Padmounted Distribution Transformers
DANGER
The transformer must be properly grounded at all times. FAILURE TO FOLLOW THIS INSTRUCTION WILL RESULT IN DEATH OR SERIOUS PERSONAL INJURY, AND DAMAGE TO THE EQUIPMENT.
High-Voltage and Low-Voltage Connections
Before making high-voltage and low-voltage line connections, check to make sure that all mating
connector surfaces are clean and smooth. Connections must be tightened appropriately to prevent overheating and possible failure of the connection. Refer to the nominal torque guidelines contained in Table 3. Connections should be made with care to avoid placing undue stress on the bushings.
DANGER
Do not make any modications to the
transformer that might compromise its tamper resistant construction. FAILURE TO FOLLOW THIS INSTRUCTION WILL RESULT IN DEATH OR SERIOUS PERSONAL INJURY, AND DAMAGE TO THE EQUIPMENT.
Grounding
The transformer must be permanently grounded according to applicable local and national codes. Ground the transformer by using ground pads or nuts located at the base of the front panel in the terminal compartment. Do not use hold-down
bolts, pipe connections or any other ttings for
ground connections. A proper low-resistance ground connection is necessary for safe operation.
Transformers with a grounded wye high-voltage winding and a wye low-voltage winding are designed for electric distribution systems that have a grounded neutral. All windings designed for grounded neutral operation must be permanently and solidly grounded to the system neutral.
High-Voltage Connections
Three-phase padmounted transformers with live-front construction are usually supplied with externally-clamped porcelain high-voltage bushings for connection to the high-voltage source. Bushings are supplied with tin-plated eye-bolt or spade terminals that are suitable for connection to both aluminum and copper conductors.
Three-phase padmounted transformers with dead­front construction are supplied with universal bushing wells, one-piece (integral) bushings or universal bushing wells with factory-installed inserts. One-piece (integral) bushings and bushing inserts are designed to interface with insulated elbow connectors, and can be supplied for either load-break or non load-break operation.
When transformers are supplied with bushing wells
only, inserts must be installed in the eld before
cable connections can be made. Bushing well inserts must compatible with the universal bushing well. Do not use incompatible or improperly rated inserts, or equipment damage might occur. When installing inserts, follow the manufacturer’s
instructions accompanying the insert.
On transformers with dead-front construction, grounding caps must be installed on all unused high-voltage bushings before energizing.
10
Three-Phase Padmounted Distribution Transformers
Low-Voltage Connections
Three-phase padmounted transformers are normally supplied with externally-clamped molded low-voltage bushings, with or without spade
terminals.
Document 2.4.126, Revision 4
October 2017
11
Loading...
+ 25 hidden pages