Installation, Operation, and Maintenance
of Three-Phase Padmounted Distribution Transformers
45 kVA through 10,000 kVA
Howard Industries
Distribution Transformer Division
1
Page 2
Document 2.4.126, Revision 4
October 2017
READ THIS IMPORTANT SAFETY INFORMATION
Read these instructions carefully and become familiar with the equipment before
proceeding with installation, operation, or maintenance activities. This equipment
contains extremely hazardous voltages. To prevent death, serious personal
injury, or equipment damage, all information in these instructions should be read
and observed. Safe use of this equipment is dependent on proper installation,
operation, and maintenance procedures.
Certain information in this manual is marked with the words DANGER, WARNING,
or CAUTION, which indicate hazards.
DANGER indicates an imminently hazardous situation which, if not avoided, will
result in death or serious personal injury, and damage to the equipment.
WARNING indicates a potentially hazardous situation which, if not avoided, may
result in death or serious personal injury, and/or damage to the equipment.
Three-Phase Padmounted Distribution Transformers
CAUTION indicates a potentially hazardous situation which, if not avoided, may
result in minor or moderate personal injury, and/or damage to the equipment.
No one should attempt to service or perform maintenance activities on the
equipment until it has been effectively de-energized, and all high-voltage and low-
voltage bushing terminals have been properly grounded. Only qualied personnel
should install, maintain, and operate this equipment. Qualied personnel are
those who are trained in the installation, maintenance, and operation of highvoltage equipment, trained in the proper use of personal protective equipment
(such as rubber gloves, safety glasses, protective clothing, hard hats, etc.) and
trained in appropriate rst aid procedures.
The instructions contained herein are intended to be a general guide for the
installation, operation and maintenance of this equipment, when operated in
“Usual Service Conditions” as dened in IEEE Standard C57.12.00. Features
presented herein may not be present in all equipment designs. Standard and
optional features are subject to change without notice.
Although efforts have been made to ensure accuracy and completeness, these
instructions do not address every conceivable application or circumstance that
might be encountered. Howard Industries makes no representation or warranty
with respect to, and assumes no responsibility for the completeness, accuracy,
sufciency, or usefulness of, these instructions.
Questions regarding installation, operation, and maintenance of the equipment,
particularly when encountering unusual or special circumstances that may not
be sufciently covered by these instructions, should be directed to the Howard
Industries Transformer Division.
2
Page 3
Three-Phase Padmounted Distribution Transformers
Document 2.4.126, Revision 4
October 2017
TABLE OF CONTENTS
Important Safety Information........................................................................................................................2
This document is intended as a general guide for
the installation, operation and maintenance of
Howard Industries three-phase compartmental
padmounted distribution transformers. Although
efforts have been made to ensure accuracy and
completeness, these instructions do not address
every conceivable application or circumstance that
might be encountered. Features presented herein
may not be present in all transformer designs.
Standard and optional features are subject to
change without notice.
The instructions contained herein are applicable
to transformers operated in normal conditions
as specied in the “Usual Service Conditions”
section of IEEE Standard C57.12.00. Questions
regarding installation, operation, and maintenance
(particularly when encountering unusual or special
circumstances not sufciently covered by these
instructions) should be directed to the Howard
Industries Transformer Division.
Document 2.4.126, Revision 4
October 2017
IT IS IMPORTANT TO READ AND COMPLY WITH
ALL SAFETY INFORMATION, INSTRUCTIONS
AND WARNINGS DISPLAYED THROUGHOUT
THESE INSTRUCTIONS BEFORE ATTEMPTING
ANY INSTALLATION, OPERATION, OR
MAINTENANCE ACTIVITIES.
5
Page 6
Document 2.4.126, Revision 4
October 2017
SECTION 2: RECEIVING, HANDLING AND STORAGE
Three-Phase Padmounted Distribution Transformers
Drawings and Documents
Locate all shipping papers, packing lists, outline
drawings, and other pertinent information for
use during inspection. The transformer outline
drawing indicates the location of nameplates and
warning labels, and provides physical dimensions
and weights. The nameplate provides electrical
characteristics, winding connections, and weights.
The wiring diagram provides details of any control,
fan and alarm wiring that may have been supplied.
Lifting and Handling
Lifting hooks are provided near the top of the
transformer tank for lifting. All four lifting hooks
must be used simultaneously. The transformer
must not be lifted from any points other than the
provided lifting hooks. Do not use holes in the
lifting hooks for lifting. These holes are for tie-down
purposes only and are not suitable for lifting.
WARNING
FAILURE TO FOLLOW THE INSTRUCTIONS
BELOW MAY CAUSE DEATH OR SERIOUS
PERSONAL INJURY AND/OR DAMAGE TO
THE EQUIPMENT.
• Use a crane, suitable lifting cables or
straps, and a spreader bar to unload the
transformer.
• Do not unload using a forklift. Keep
unnecessary personnel clear while
unloading and moving the transformer.
Transformers should be lifted in an upright position,
allowing the transformer to tilt no more than 15°
from vertical. Lifting cables should be no more
than 20° from vertical. It is recommended that
a spreader bar be used to keep the lifting cables
nearly vertical to enable a safe lift and to reduce
the likelihood of tank deformation or damage to
painted surfaces.
Lifting the transformer with a forklift is not
recommended, since weight and balance can be
problematic and radiator panels can be easily
damaged. Refer to the transformer nameplate
to determine the total weight of the assembled
transformer. Special care must be taken when
handling transformers when the ambient
temperature is below minus 20°C (minus 4°F);
otherwise, permanent damage to the transformer
may result.
Initial Inspection
Although all transformers, components, and
accessories are carefully inspected and tested prior
to shipment, a thorough receiving inspection should
be conducted to detect any damage or loss that
might have occurred during shipment. The receiving
inspection should be completed upon receipt and
before unloading from the truck. Note any damage
or discrepancies on the bill of lading, le a claim
with the carrier, and notify the Howard Industries
Transformer Division prior to unloading the
transformer and before attempting any repair.
Before unloading the transformer, the following
checks should be performed:
1. Read the serial number on the transformer
nameplate and make sure it matches the serial
number listed on the shipping documents. Also,
check the nameplate for kVA rating, high-voltage
rating, low-voltage rating, impedance and other
design characteristics, and make sure they
comply with the specications.
2. Check shipping documents to make sure
the shipment is complete, including all listed
accessories and hardware. Be aware that
additional items may arrive on separate
pallets. Claims for shortages or errors must
be noted on the shipping documents and
reported immediately to the Howard Industries
Transformer Division. Failure to make a timely
claim will constitute unqualied acceptance and
a waiver of all such claims by the purchaser.
3. The tank vacuum/pressure gauge may
indicate a positive or negative reading when
the transformer is received, depending on the
relative temperatures of the uid and ambient
6
Page 7
Three-Phase Padmounted Distribution Transformers
Document 2.4.126, Revision 4
October 2017
air. A rising or falling reading that varies over
time with ambient temperature indicates that
the transformer tank is sealed effectively. If the
vacuum/pressure gauge shows a constant zero
reading, this indicates the possibility of a tank leak.
If this occurs, the tank should be checked carefully
for leaks as indicated in the following step.
4. Check the tank for indication of uid leaks,
looking carefully at weld seams, bushings,
gauges, valves and all other tank ttings. If
suspicious indications are found, investigate
thoroughly to determine if a leak does exist
on the transformer. Indications of a leak
can sometimes be residual uid that was not
cleaned during the manufacturing process
and not an actual leak. In many cases a small
pinhole tank leak or leak from a bushing, gauge,
valve or other tting can be easily repaired on
site. Refer to the “Maintenance” section for
information about the repair of uid leaks.
5. Check for external damage including dents
or scratches on the tank walls, radiators and
terminal compartment. Dents and scratches
can often be repaired on site using simple
touch-up procedures. If touch-up painting
is performed, do not remove or obscure
any warning labels, instructional labels or
nameplates.
extremely hot. When checking the uid level, bear
in mind that the level will vary as a function of uid
temperature.
A transformer found to have a low uid level should
be checked for potential leaks and lled to the
proper level with the same type of liquid as that
specied on the transformer nameplate.
WARNING
FAILURE TO FOLLOW THE INSTRUCTIONS
BELOW MAY CAUSE DEATH OR SERIOUS
PERSONAL INJURY AND/OR DAMAGE TO
THE EQUIPMENT.
• Do not energize the transformer if the
uid level is low.
• Maintain proper uid level at all times
while the transformer is energized.
• Exercise caution when checking the uid
level with the uid level plug, as the uid
may spill and may be extremely hot.
6. Check for broken, cracked, or damaged
bushings, gauges, valves and other ttings and
accessories.
7. Check for missing or damaged component parts
and packages that shipped separately from the
transformer.
Fluid Level
The transformer is shipped from the factory with
dielectric uid lled to the proper level. Before
energizing the transformer, verify proper uid level
by observing the uid level gauge. The uid level
gauge pointer should be between the “High” and
“Low” marks. For transformers supplied with a uid
sight plug, the uid level can be directly observed
if it is within acceptable range. If the transformer
does not have a uid level gauge or sight plug, the
uid level can be checked by removing the liquid
level plug located at the 25° C mark. Exercise
caution when checking the uid level using the uid
level plug, as the uid may spill out and may be
Internal Inspection
An internal inspection of the transformer tank is
rarely necessary and is recommended only when
there are obvious indications that the transformer
has received severe impact damage during transit
or when necessary to perform recommended preenergization tests or inspections. Do not open the
transformer tank without authorization from the
Howard Industries Transformer Division.
If the transformer tank must be opened, refer to
“Opening the Transformer Tank” for instructions.
Fluid Sampling
Sampling and testing of the uid is not required
unless there is indication that moisture or other
contaminants have accidently entered the tank
during transit. If moisture or contaminates in the
uid is suspected, contact the Howard Industries
Transformer Division immediately for instructions.
If uid sampling is required, refer to “Sampling the
Fluid” for instructions.
7
Page 8
Document 2.4.126, Revision 4
October 2017
Transformer Storage
Transformers may be temporarily stored if properly
prepared. It is recommended that transformers
be stored completely assembled. Prior to storage,
transformers should be thoroughly inspected as
described above in the “Initial Inspection” section.
If the transformer is not completely assembled,
separate components and accessories should be
stored in a clean dry area in their original shipping
containers. Do not store the transformer in a
corrosive environment.
If the transformer is to be stored for an extended
period of time before being placed into service,
it should be stored on a rm level surface. The
gas space above the insulating uid should be
pressurized with dry nitrogen to a pressure of 2-3
PSIG. This will prevent a negative internal pressure
that might draw moisture into the tank.
Three-Phase Padmounted Distribution Transformers
It is recommended that the transformer be
inspected periodically while it is in extended
storage. Ensure that an effective pressure seal
is maintained, and check for leaks and corrosion.
Any damage or defects should be repaired
immediately.
8
Page 9
Three-Phase Padmounted Distribution Transformers
SECTION 3: INSTALLATION
Document 2.4.126, Revision 4
October 2017
Lifting and Handling
Lifting hooks are provided near the top of the
transformer tank for lifting. All four lifting hooks
must be used simultaneously. The transformer
must not be lifted from any points other than the
provided lifting hooks. Do not use holes in the
lifting hooks for lifting. These holes are for tie-down
purposes only and are not suitable for lifting.
Transformers should be lifted in an upright position,
allowing the transformer to tilt no more than 15
degrees from vertical. Lifting cables should be no
more than 20° from vertical. It is recommended
that a spreader bar be used to keep the lifting
cables nearly vertical to enable a safe lift and
to reduce the likelihood of tank deformation or
damage to painted surfaces.
Lifting the transformer with a forklift is not
recommended, since weight and balance can be
problematic and radiator panels can be easily
damaged. Refer to the transformer nameplate
to determine the total weight of the assembled
transformer. Special care must be taken when
handling transformers when the ambient
temperature is below minus 20°C (minus 4°F);
otherwise, permanent damage to the transformer
may result.
WARNING
FAILURE TO FOLLOW THE INSTRUCTIONS
BELOW MAY CAUSE DEATH OR SERIOUS
PERSONAL INJURY AND/OR DAMAGE TO THE
EQUIPMENT.
• Use a crane, suitable lifting cables or
straps, and a spreader bar to unload the
transformer.
• Do not unload using a forklift. Keep
unnecessary personnel clear while
unloading and moving the transformer.
Jacking, Skidding, and Rolling
The transformer tank base is designed for jacking,
skidding and rolling. Do not use radiator ns,
bushings, valves, pipe ttings, gauges or sheet
metal surfaces for jacking. Jacking must be done
using the proper jacking provisions from two
adjacent corners simultaneously to prevent warping
of the tank bottom. When rolling, use an adequate
number of rollers to distribute the transformer
weight evenly. Refer to the transformer outline
drawing for the total weight of the assembled
transformer.
Location and Mounting
Consult local and national codes to ensure that
the installation meets all applicable requirements.
Location of the transformer must permit it to
operate in conditions that meet the requirements
specied in the “Usual Service Conditions” section
of IEEE Standard C57.12.00. Operation not
meeting these service condition requirements will
compromise transformer capacity and reliability,
unless the transformer is designed specically
for operation in conditions other than usual
service conditions. Contact the Howard Industries
Transformer Division, if additional information is
needed about location and mounting issues not
covered by these instructions.
The transformer should be mounted on a level
concrete foundation of sufcient strength to
support the weight of the completely assembled
transformer. The transformer should sit ush with
the surface of the pad, so that there are no gaps
that might compromise tamper resistance of the
terminal compartment. The installed transformer
should not tilt in any direction more than three
degrees. Greater tilt may compromise insulation
uid coverage of live parts within the tank and may
prevent insulating uid from circulating properly
through the cooling radiators. Improper circulation
of insulating uid may cause overheating and
reduced transformer life.
The transformer should be located at least 24
inches (710 mm) from any obstruction and
have adequate clearance to allow the terminal
compartment doors to open fully. When installing
transformers designed for indoor operation,
adequate air inlets and outlets must be provided at
the mounting location for proper cooling.
9
Page 10
Document 2.4.126, Revision 4
October 2017
Avoid locating the transformer in corrosive areas.
Remove any shipping braces and packing material
that may have been installed at the factory.
Verifying Enclosure Integrity
Three-phase compartmental padmounted
transformers are designed and constructed to be
tamper resistant according to the requirements
of IEEE Standard C57.12.28 or C57.12.29, as
applicable, and therefore need not be located
in a restricted area. Do not modify the tank or
terminal compartment in such a way that it will
compromise tamper resistance. If for any reason
modications must be made to the tank or terminal
compartment that compromise tamper resistance,
the transformer must then be located in a restricted
area. Such modications of may void the warranty.
Consult with the Howard Industries Transformer
Division before making any modications to the
transformer.
Three-Phase Padmounted Distribution Transformers
DANGER
The transformer must be properly grounded
at all times. FAILURE TO FOLLOW THIS
INSTRUCTION WILL RESULT IN DEATH OR
SERIOUS PERSONAL INJURY, AND DAMAGE
TO THE EQUIPMENT.
High-Voltage and Low-Voltage Connections
Before making high-voltage and low-voltage line
connections, check to make sure that all mating
connector surfaces are clean and smooth.
Connections must be tightened appropriately to
prevent overheating and possible failure of the
connection. Refer to the nominal torque guidelines
contained in Table 3. Connections should be made
with care to avoid placing undue stress on the
bushings.
DANGER
Do not make any modications to the
transformer that might compromise its
tamper resistant construction. FAILURE TO
FOLLOW THIS INSTRUCTION WILL RESULT IN
DEATH OR SERIOUS PERSONAL INJURY, AND
DAMAGE TO THE EQUIPMENT.
Grounding
The transformer must be permanently grounded
according to applicable local and national codes.
Ground the transformer by using ground pads or
nuts located at the base of the front panel in the
terminal compartment. Do not use hold-down
bolts, pipe connections or any other ttings for
ground connections. A proper low-resistance ground
connection is necessary for safe operation.
Transformers with a grounded wye high-voltage
winding and a wye low-voltage winding are
designed for electric distribution systems that
have a grounded neutral. All windings designed for
grounded neutral operation must be permanently
and solidly grounded to the system neutral.
High-Voltage Connections
Three-phase padmounted transformers with
live-front construction are usually supplied with
externally-clamped porcelain high-voltage bushings
for connection to the high-voltage source. Bushings
are supplied with tin-plated eye-bolt or spade
terminals that are suitable for connection to both
aluminum and copper conductors.
Three-phase padmounted transformers with deadfront construction are supplied with universal
bushing wells, one-piece (integral) bushings or
universal bushing wells with factory-installed
inserts. One-piece (integral) bushings and bushing
inserts are designed to interface with insulated
elbow connectors, and can be supplied for either
load-break or non load-break operation.
When transformers are supplied with bushing wells
only, inserts must be installed in the eld before
cable connections can be made. Bushing well
inserts must compatible with the universal bushing
well. Do not use incompatible or improperly
rated inserts, or equipment damage might occur.
When installing inserts, follow the manufacturer’s
instructions accompanying the insert.
On transformers with dead-front construction,
grounding caps must be installed on all unused
high-voltage bushings before energizing.
10
Page 11
Three-Phase Padmounted Distribution Transformers
Low-Voltage Connections
Three-phase padmounted transformers are
normally supplied with externally-clamped molded
low-voltage bushings, with or without spade
terminals.
Document 2.4.126, Revision 4
October 2017
11
Page 12
Document 2.4.126, Revision 4
October 2017
SECTION 4: INSPECTION AND TESTING BEFORE AND
AFTER INITIAL ENERGIZATION
DANGER
FAILURE TO FOLLOW THE INSTRUCTIONS
BELOW WILL RESULT IN DEATH OR SERIOUS
PERSONAL INJURY, AND DAMAGE TO THE
EQUIPMENT.
• Energize the transformer from a remote
location.
• Do not energize the transformer using
single-phase switches or fuses. Use only
gang-operated three-phase switches to
energize a three-phase transformer.
• Do not operate the transformer with any
of the primary phases open.
• Only qualied personnel with appropriate
equipment should measure transformer
voltages.
• Be aware of dangerous voltages within
the terminal compartment and avoid
personal contact with live terminals.
• Wear personal protective equipment to
prevent injury from potential arc-ash or
contact with dangerous voltages.
• Make sure the transformer is properly
grounded at all times.
• Insulated dead-end caps or plugs must
be installed on all unused dead-front
high-voltage bushings. Dust caps must
not be used in place of insulated deadend caps or plugs.
• Current transformer (CT) leads must
be connected to the metering load
or shorted together and grounded to
prevent dangerous voltages at the CT
terminals.
Three-Phase Padmounted Distribution Transformers
Pre-Energization Inspection and Tests
After the transformer has been installed, but before
it is energized, the following tests and checks
should be performed at a minimum to ensure that
the transformer is ready to be energized. Do not
energize the transformer without performing these
tests and checks.
1. Ratio Test—Using a transformer turns ratio
tester (TTR), perform a ratio test to verify
the primary-to-secondary winding ratio.
The measured value should be within
0.5% of the voltage ratio indicated on the
transformer nameplate. If the transformer
is supplied with high-voltage taps, measure
the ratio at each tap position to ensure
that each of the ratios is correct. Follow the
instructions and safety precautions provided
by the TTR equipment manufacturer. For
additional information about ratio testing,
refer to IEEE Standard C57.12.90.
2. Insulation Resistance Test— Perform a
1,000-Volt insulation test (Megger test) to
measure the resistance of the insulation
between windings and from each winding
to ground. Follow the instructions and
safety precautions provided by the test
equipment manufacturer. Prior to the test,
bushings must be thoroughly cleaned with
denatured alcohol to remove any moisture
or contaminates that could inuence the
test results. Measured resistance should be
at least 1.0 GΩ.
An insulation resistance test must not
be performed on a wye-wye connected
transformer with an Ho-Xo bushing without
rst disconnecting the internal connection
between the primary and secondary
neutrals. This connection can be found on a
terminal board located below the uid level
in the transformer tank. Refer to “Opening
the Transformer Tank” for instructions.
3. Tap Changer Setting—Check the tap
changer setting to ensure it is set to the
proper position for the required voltage.
12
Page 13
Three-Phase Padmounted Distribution Transformers
Document 2.4.126, Revision 4
October 2017
4. Series/Multiple or Delta/Wye Switch
Settings—Check series/multiple and delta/
wye switch settings to make sure they are
set to the correct position. If delta/wye
or series/multiple connections are made
using an internal terminal board instead
of a switch, check to ensure that these
connections are made properly according
to the chart on the transformer nameplate.
Refer to “Opening the Transformer Tank” for
instructions.
5. Grounding—Check to ensure that the
transformer tank is permanently and
effectively grounded. The transformer tank
ground pad is located inside the terminal
compartment near the bottom of the tank.
6. Bolted Connections—Check all bolted
connections for tightness, referring to
nominal torque guidelines contained in
Tables 1 through 4.
11. Accessory Wiring—Check wiring of control
and alarm circuits (if supplied) to make
sure there are no loose connections and no
damage to wire insulation.
12. Tank Finish—Check all painted surfaces
to make sure that there is no damage or
corrosion.
13. Tools—Check to make sure that all tools and
equipment are accounted for.
14. Internal Inspection—The transformer tank
is sealed and should not be opened unless
necessary. If the transformer tank must be
opened, refer to “Opening the Transformer
Tank” for instructions.
7. Fluid Level—Check to make sure the uid
level is correct as indicated by the uid level
gauge or sight plug. If the transformer does
not have a uid level gauge or sight plug,
the uid level can be checked by temporarily
removing the liquid-level plug located at the
25° C mark.
8. Fluid Temperature—Observe the uid
temperature gauge and make sure the
temperature is no lower than indicated
below before the unit is energized.
-20°C (-4°F) for conventional
transformer oil
-0°C (32°F) for R-Temp uid
-10°C (14°F) for FR3 uid
9. Internal Fault Detector—If the transformer
is supplied with an Internal Fault Detector
(IFD), remove the red shipping lock
after installation and before placing the
transformer into service.
10. Current Transformers—If current
transformers (CTs) are present, connect CT
leads to the metering load. If CT leads are
not connected to a metering load, they must
be shorted together and grounded before
the transformer is energized.
13
Page 14
Document 2.4.126, Revision 4
October 2017
Three-Phase Padmounted Distribution Transformers
Post-Energization Inspection and Tests
After the transformer is energized, the following
tests and inspections should be performed.
DANGER
FAILURE TO FOLLOW THE INSTRUCTIONS
BELOW WILL RESULT IN DEATH OR SERIOUS
PERSONAL INJURY, AND DAMAGE TO THE
EQUIPMENT.
• Energize the transformer from a remote
location.
• Do not energize the transformer using
single-phase switches or fuses. Use only
gang-operated three-phase switches to
energize a three-phase transformer.
• Do not operate the transformer with any
of the primary phases open.
• Only qualied personnel with appropriate
equipment should measure transformer
voltages.
• Be aware of dangerous voltages within
the terminal compartment and avoid
personal contact with live terminals.
• Wear personal protective equipment to
prevent injury from potential arc-ash or
contact with dangerous voltages.
• Make sure the transformer is properly
grounded at all times.
• Insulated dead-end caps or plugs must
be installed on all unused dead-front
high-voltage bushings. Dust caps must
not be used in place of insulated deadend caps or plugs.
• Current transformer (CT) leads must
be connected to the metering load or
shorted together and grounded to prevent
dangerous voltages at the CT terminals.
1. Verifying Correct Voltage—Before supplying
voltage from the transformer to the load,
verify that the secondary voltage is correct.
Using a suitable AC voltmeter, measure the
voltage of the secondary windings and make
sure they agree with the secondary voltages
listed on the transformer nameplate.
2. Checking for Leaks—Check the tank to make
sure there are no uid leaks.
3. Observing Operation—After the transformer
is initially energized, visually inspect it
occasionally for a few hours, to make sure
that no abnormal conditions are observed.
4. Checking Gauges—Observe the uid level
and uid temperature gauges to conrm the
proper uid level and temperature.
5. Audible Sound— It is normal for transformers
to emit an audible humming sound, which
is primarily caused by alternating magnetic
ux in the transformer core. Amplitude and
harmonic content of the sound is inuenced
by transformer size, the energizing voltage
level and sinusoidal purity, load conditions
and acoustic conditions at the installation
site. Refer to NEMA Standards Publication
TR-1, Transformers, Regulators and
Reactors, and IEEE Standard C57.12.90,
IEEE Standard Test Code for Liquid-
Immersed Distribution, Power, and
Regulating Transformers, for more
information about design sound levels and
factory sound testing. Unusual sounds
should be investigated, as this might
indicate a potential problem.
6. Locking the Terminal Compartment—Before
leaving the installation site, make sure the
terminal compartment is secure using the
following procedure.
− Lower the ip-top cover (if supplied)
and engage the center-mounted cover
security bolt
− Close the primary compartment door
and engage each security bolt.
− Close the secondary compartment
door and turn the handle to the closed
position. Engage the secondary
compartment door security bolt.
− Install a suitable heavy-duty padlock.
14
Page 15
Three-Phase Padmounted Distribution Transformers
SECTION 5: OPERATION OF SWITCHING AND PROTECTIVE DEVICES
The following operating instructions and
descriptions of switching and fusing devices are
intended to be a general guide for operation of
Howard three-phase padmounted transformers in
normal environments. Although efforts have been
made to ensure accuracy and completeness, these
instructions and descriptions do not address every
conceivable application or circumstance that might
be encountered. Personnel should read and comply
with any safety and instructional labels that might
accompany an accessory device.
DANGER
Document 2.4.126, Revision 4
October 2017
DANGER
FAILURE TO FOLLOW THE INSTRUCTIONS BELOW
WILL RESULT IN DEATH OR SERIOUS INJURY,
AND DAMAGE TO THE EQUIPMENT.
• Do not operate uid-immersed load-break
fusing and switching devices when the
insulating uid temperature is below the
following limits:
- 20°C (-4°F) for conventional
transformer oil
-0°C (32°F) for R-Temp uid
-10°C (14°F) for FR3 uid
FAILURE TO FOLLOW THE INSTRUCTIONS
BELOW WILL RESULT IN DEATH OR SERIOUS
INJURY, AND DAMAGE TO THE EQUIPMENT.
• Do not operate load-break equipment if a
fault condition is suspected.
• Use a live-line tool (hot stick or shotgun
stick) to operate transformer load-break
equipment.
• After operating transformer loadbreak
equipment, check that voltages at
transformer terminals are the expected
values. Checking voltages veries that
loadbreak equipment operated properly
and that electrical circuit conditions are
as expected.
• Before servicing the transformer,
ALWAYS de-energize the transformer
from a remote upstream source and
then proceed to ground all primary
and secondary transformer terminals
following industry-accepted safe
grounding practices. Grounding secondary
terminals protects against situations
such as a standby generator energizing
transformer from the secondary circuit.
• Follow industry-accepted safety practices.
Utilize personal protective equipment
when working with this equipment.
Many of the accessory devices described below are
optional and may not be present in any particular
transformer design. The inclusion of particular
accessory devices in any transformer design is
governed by industry standards and by individual
customer specications.
Tap Changer
The de-energized (no-load) tap changer may be used
to adjust the voltage ratio of a transformer while it
is de-energized. It is intended to allow adjustment of
the output (secondary) voltage to the rated value. Do
not use the tap changer to raise or lower the output
voltage to any voltage other than that indicated
on the transformer nameplate. If the tap changer
is set to provide an output voltage different from
rated secondary voltage, core saturation may occur,
resulting in a high noise level and high core loss.
DANGER
FAILURE TO FOLLOW THE INSTRUCTIONS
BELOW WILL RESULT IN DEATH OR SERIOUS
PERSONAL INJURY, AND DAMAGE TO THE
EQUIPMENT.
• Do not operate a de-energized (no-load)
tap changer unless the transformer is
totally de-energized.
• Do not re-energize the transformer unless
the tap changer handle is locked into
position.
15
Page 16
Document 2.4.126, Revision 4
October 2017
Three-Phase Padmounted Distribution Transformers
The tap changer is operated by use of a rotating
handle located inside the terminal compartment.
Never operate a de-energized tap changer while the
transformer is energized. Tap changers normally
have ve or seven tap positions as indicated on
the tap changer dial plate and the transformer
nameplate. A locking mechanism is normally
provided to lock the tap changer into position and
prevent accidental operation. Do not re-energize the
transformer until the tap changer is rmly locked
into a tap position. The transformer is shipped
from the factory with the tap changer in the rated
voltage position, unless otherwise specied by the
customer.
Series/Multiple or Delta/Wye Switch
Transformers designed with series/multiple
windings (dual-voltage or triple-voltage
transformers) are supplied with a de-energized
series/multiple switch. Transformers with reconnectable delta/wye windings are supplied with
a delta/wye switch. The presence of either of
these switches will be indicated on the transformer
nameplate.
the high-voltage compartment. These switches can
be either two-position (ON-OFF) switches or three-
or four-position sectionalizing switches. Switch
positions are marked on the transformer front panel
and shown on the nameplate diagram. Rotary loadbreak switches are designed to be operated with a
live-line tool (hot stick or shotgun stick) and should
not be operated by hand.
The two-position switch is operated by inserting
the live-line tool into the operating handle and
rotating the switch to either the ON or OFF position.
The three- or four-position switch is operated by
inserting the live-line tool in the index plate and
moving the plate over the peg between its present
setting and the next setting. The index plate
prevents the switch from switching more than one
position at a time. The live-line tool is then inserted
into the switch operating handle and turned until
the switch snaps into the next position. Repeat this
procedure until the switch is in the desired position.
Do not stop and reverse direction of the switch
before it has changed position, as this will damage
the switch mechanism.
The transformer must be completely de-energized
before operating either of these switches. If the
transformer is not de-energized before operating
the switch, personal injury and permanent
equipment damage will result. Unless otherwise
specied, series/multiple transformers are shipped
from the factory with the series/multiple switch in
the highest voltage position.
DANGER
FAILURE TO FOLLOW THE INSTRUCTIONS
BELOW WILL RESULT IN DEATH OR SERIOUS
PERSONAL INJURY, AND DAMAGE TO THE
EQUIPMENT.
• Do not operate a de-energized series/
multiple or delta/wye switch unless the
transformer is totally de-energized.
• Do not re-energize the transformer
unless the series/multiple or delta/wye
switch handle is locked into position.
Load-Break Switch
One or more rotary under-oil load-break switches
may be supplied on the transformer and located in
CAUTION
FAILURE TO FOLLOW THE INSTRUCTIONS
BELOW MAY RESULT IN MINOR OR
MODERATE PERSONAL INJURY, AND /OR
DAMAGE TO THE EQUIPMENT.
• Do not operate a load-break switch by
hand. Operate only using a live-line tool
(hot stick or shotgun stick).
• Do not stop and reverse direction of the
load-break switch before it has changed
position.
Fuses
A blown fuse may indicate a faulted transformer.
Do not replace a blown fuse unless the cause of the
fuse operation has been identied and corrected.
Fuses should be applied according to the fuse
rating. Replacement fuses should have the proper
rating and operating characteristics. Refer to the
circuit diagram on the transformer nameplate for
the location of fuses.
16
Page 17
Three-Phase Padmounted Distribution Transformers
DANGER
FAILURE TO FOLLOW THE INSTRUCTIONS
BELOW WILL RESULT IN DEATH OR SERIOUS
PERSONAL INJURY, AND DAMAGE TO THE
EQUIPMENT.
• De-energize the transformer before
replacing fuses.
• Do not energize or de-energize a
three-phase transformer using singlephase switches or fuses. Use only
gang-operated three-phase switches to
energize or de-energize a three-phase
transformer.
• Do not operate the transformer with any
phases open.
• Only qualied personnel with appropriate
measurement devices should measure
the voltages on the transformer.
Document 2.4.126, Revision 4
October 2017
Bay-O-Net Fuse
A Bay-O-Net is a uid-immersed, draw-out, dead-
front, single-pole fused disconnect device that is
rated for load-break operation. It is designed to be
operated with a live-line tool (hot stick or shotgun
stick) and should not be operated by hand. Bay-ONet devices (one device per phase) are normally
located in the high-voltage compartment near the
high-voltage bushings. The Bay-O-Net is available as
an expulsion fuse device or as a full-range currentlimiting fuse device.
A Bay-O-Net expulsion fuse device is equipped with
a series-connected uid-immersed isolation link,
or if specied by the customer, a series-connected
partial-range current-limiting fuse. Isolation
links and partial-range current-limiting fuses
are designed to blow in the event of an internal
transformer fault. A transformer with a blown
isolation link or partial-range current-limiting fuse
cannot be re-energized and must be removed from
service.
DANGER
Internal Weak-Link Cartridge Fuse
A weak-link cartridge fuse is an internal, uid-
immersed expulsion fuse. These fuses are installed
under uid inside the transformer tank on mounting
blocks located above the core and coil assembly.
These fuses can be replaced in a de-energized
transformer by removing the tank hand-hole cover.
1. Make sure the transformer tank is properly
grounded.
2. Remove the tank hand-hole cover. Refer
to “Opening the Transformer Tank” for
instructions.
3. Identify the fuse block assembly.
4. Remove leads attached to each end of the
cartridge fuse, being careful not to drop any
nuts or washers into the tank.
5. Replace the fuse and reconnect leads to
their original positions using the washers
and nuts removed in step 4.
6. Re-install the tank hand-hole cover. Refer
to “Opening the Transformer Tank” for
instructions.
FAILURE TO FOLLOW THE INSTRUCTIONS
BELOW WILL RESULT IN DEATH OR SERIOUS
PERSONAL INJURY, AND DAMAGE TO THE
EQUIPMENT.
• Bay-O-Net fuse devices are not
recommended for fault closing.
The Bay-O-Net device should not be
used to re-energize a transformer that is
suspected to be faulted.
• Operate the Bay-O-Net device with a
live-line tool (hot stick or shotgun stick).
Never operate the Bay-O-Net device by
hand.
• After replacing a blown fuse, the
transformer should be re-energized from
a remote location.
• Operate the pressure relief device to vent
pressure in the transformer tank before
unlatching a Bay-O-Net device to prevent
hot oil from being expelled during fuse
removal.
17
Page 18
Document 2.4.126, Revision 4
October 2017
Three-Phase Padmounted Distribution Transformers
The following procedure should be used to operate
a Bay-O-Net fuse device. Open both compartment
doors and engage the prop rods on each door to
latch them in the open position. On transformers
supplied with a hinged terminal compartment cover,
disengage the center security bolt and raise the
cover until the support arm latches in place.
Remove Fuse Holder—The following procedure
should be used to draw the fuse holder out of the
Bay-O-Net housing.
1. Vent the transformer by operating the
pressure relief valve. Keep the valve open
until the sound of air venting can no longer
be heard.
2. Stand to one side of the Bay-O-Net device
being operated.
3. Attach a live-line tool to the holder eye.
4. Twist the live-line tool to unlock the fuse
holder.
5. Rotate the holder 90° clockwise in the
housing to break the seal between the
gasket and the housing.
6. Firmly and quickly pull the fuse holder out
about 8 to 10 inches to open the circuit.
Wait a few seconds while the uid drains
back into the tank, and then completely
withdraw the fuse holder. Wipe the fuse
holder and cartridge to remove excess uid.
Dead-Break Dry-Well Canister Fuse
The dead-break dry-well canister is a uid-tight,
single-pole, current-limiting fuse holder. It is
designed to be operated with a live-line tool (hot
stick or shotgun stick) and should not be operated
by hand. Dry-well canisters (one per phase) are
mounted on the transformer front panel in the highvoltage section of the terminal compartment.
Dead-break dry-well canisters are not designed to
break load and must only be operated when the
transformer is de-energized. When specied, dry-
well canisters are mechanically interlocked with a
load-break switch to prevent removal of the fuses
while the transformer is energized.
DANGER
FAILURE TO FOLLOW THE INSTRUCTIONS
BELOW WILL RESULT IN DEATH OR SERIOUS
INJURY, AND DAMAGE TO THE EQUIPMENT.
• Do not operate a dead-break canister
fuse device while the transformer is
energized.
• When replacing a blown current-limiting
fuse, the transformer should be re-
energized from a remote location.
7. If uid continues to ow from the Bay-O-Net
device, operate the pressure relief device
again to vent pressure from the tank.
Replace Fuse Link—Replace the fuse according to
the manufacturer’s instructions included with the
replacement fuse.
Re-Insert Fuse Holder—Re-insert the fuse holder
using the following procedure.
1. Using a live-line tool attached to the eye of
the fuse holder, re-insert the holder rmly
into the Bay-O-Net housing.
2. Twist the locking handle, latching it to the
shoulder of the Bay-O-Net housing. Make
sure that the metal washer is positioned
tightly on the end of the Bay-O-Net housing.
3. Inspect the fuse holder carefully to make
sure it is fully seated and latched properly.
18
The following describes proper operation of the
dead-break canister device.
Remove Fuse Holder—The following procedures
should be used to remove the fuse holder.
1. Make sure the transformer is de-energized.
2. Attach a live-line tool to the hook eye.
3. Quickly pull the fuse holder assembly
completely from the housing.
Replace Fuse—The fuse should be replaced using
the following procedure.
1. Unscrew the fuse from the fuse holder.
2. Replace with new fuse of equivalent rating
and characteristics.
3. Tightly screw the new fuse onto the fuse
holder.
Page 19
Three-Phase Padmounted Distribution Transformers
Re-Insert Fuse Holder—Re-insert the fuse holder
using the following procedure.
1. Attach a live-line tool to the hook eye.
Document 2.4.126, Revision 4
October 2017
DANGER
2. Insert the fuse holder into the housing.
3. Push the fuse holder in rmly until the
dust cap seats against the housing and
grounding clip.
Internal Partial-Range Current Limiting Fuse
Internal partial-range (backup) current-limiting
fuses (one fuse per phase or two parallel fuses per
phase) are connected in series with low current
interrupting devices, such as weak-link cartridge
fuses or Bay-O-Net expulsion fuses. Partial-range
current-limiting fuses are designed to clear low
impedance (high current) faults, while expulsion
fuses are designed to clear a high impedance fault
or overload. When properly applied, partial-range
current-limiting fuses will operate only for internal
transformer faults. When a partial-range currentlimiting fuse has blown, the transformer should be
considered faulted and removed from service.
S&C Arc-Strangler
The S&C Arc-Strangler (one per phase) is a 200
Ampere, air-insulated, load-break, single-pole device
that is designed to be operated with a live-line tool
(hot stick or shotgun stick). The Arc-Strangler device
may include a full-range current-limiting fuse on the
switch blade or a clip-style current-limiting fuse.
To operate the switch, insert the live-line tool in the
operating hook and pull forward, swinging the ArcStrangler open. To remove the Arc-Strangler, insert
the live-line tool in the hinge opening and lift up.
FAILURE TO FOLLOW THE INSTRUCTIONS
BELOW WILL RESULT IN DEATH OR SERIOUS
INJURY, AND DAMAGE TO THE EQUIPMENT.
• Arc-Strangler devices are not
recommended for fault closing. ArcStrangler devices should not be used
to re-energize a transformer that is
suspected to be faulted.
• Operate Arc-Strangler devices with a
live-line tool (hot stick or shotgun stick).
Never operate by hand.
• After replacing a blown fuse, the
transformer should be re-energized from
a remote location.
S&C Fused Switch
S&C fused switches should be operated according
to instruction provided by S&C. S&C tools should be
used to operate an S&C fused switch.
Vacuum Fault Interrupter
The vacuum fault interrupter (VFI) transformer
is equipped with a three-phase molded vacuum
interrupter mounted in the high-voltage section of
the terminal compartment. This device is capable
of making, carrying and automatically interrupting
currents through 12,500 Amperes (symmetrical) at
distribution system voltages of 5 kV to 38 kV.
The device combines vacuum interrupters,
programmable electronic control, trip-free
mechanism and universal molded elbow connection
interfaces. The control is eld programmable
with a wide range of time-current characteristic
curves and trip settings and is SCADA capable. The
molded vacuum interrupter should be operated and
maintained according to the VFI manufacturer’s
instructions provided with the device.
19
Page 20
Document 2.4.126, Revision 4
October 2017
Three-Phase Padmounted Distribution Transformers
Surge Arresters
Surge arresters can be used in three-phase
padmounted transformer installations to protect the
transformer and underground cable from damage
due to voltage surges.
DANGER
FAILURE TO FOLLOW THE INSTRUCTIONS
BELOW WILL RESULT IN DEATH OR SERIOUS
PERSONAL INJURY, AND DAMAGE TO THE
EQUIPMENT.
• De-energize the transformer from a
remote location and make sure all
transformer terminals and bushings
have zero voltage before connecting or
servicing surge arresters.
• Disconnect all surge arresters before
performing impulse, induced potential or
applied potential tests.
Surge arresters should be installed only on
systems where the power frequency voltage at the
arrester does not exceed the published maximum
continuous operating voltage (MCOV) values.
Disconnect surge arresters before performing
impulse, induced-potential or applied-potential
tests; otherwise, the arresters may be damaged.
Reconnect surge arresters after testing and before
placing the transformer into service.
inside the transformer tank. It is recommended that
uid-immersed MOV arresters not be exposed to an
average oil temperature exceeding 90°C (194°F)
and a maximum oil temperature exceeding 125°C
(257°F).
Disconnect uid-immersed MOV surge arresters
before performing impulse, induced-potential or
applied-potential tests; otherwise, the arresters
may be damaged. Reconnect surge arresters after
testing and before placing the transformer into
service.
Optional arrester disconnectors provide a means
to disconnect the uid-immersed MOV arrester
grounds for transformer testing without entering
the transformer tank. Individual disconnectors are
provided for each MOV arrester. Two different styles
of disconnectors are available, one manufactured
by ERMCO Components Inc. (ECI) and one
manufactured by Cooper Power Systems (CPS).
These two styles operate differently as indicated
below.
Before testing the transformer, disconnect the
arresters using the following procedure for the
disconnector on each phase.
1. Make sure the transformer tank is properly
grounded.
2. De-energize the transformer from a remote
location.
3. Ground all bushings and terminals.
4. Disconnect the MOV arresters by operating
the disconnectors as described below.
For the CPS disconnector (identied by a
black plastic external cap):
a. Unscrew the black disconnector cap
from the shaft.
b. Re-attach the small diameter end of
the disconnector cap to the shaft.
c. Push the handle and shaft toward
transformer until the shaft ange is
ush to the sealing gland.
For the ECI disconnector (identied by a
7/16” square brass metal head):
a. Unscrew the 7/16” square metal head
until the thread disengages.
b. Pull the shaft out to its full extent
(approximately 2”).
5. It is now safe to perform impulse, inducedpotential or applied-potential tests.
After testing the transformer, reconnect the MOV
arresters using the following procedure.
1. Make sure the tank is properly grounded.
2. De-energize the transformer from a remote
location.
3. Ground all bushings and terminals.
4. Reconnect the MOV arresters by operating
the disconnectors as described below.
For the CPS disconnector:
a. Pull the disconnector handle and shaft
fully away from transformer.
20
Page 21
Three-Phase Padmounted Distribution Transformers
Document 2.4.126, Revision 4
October 2017
b. Unscrew the disconnector cap and re-
attach it with the large diameter end
toward the transformer. Rotate the
handle clockwise to tighten.
For the ECI disconnector:
a. Push the shaft inward until the threads
engage.
b. Tighten the 7/16” square head
according to the torque guidelines listed
in Table 4.
If arrester disconnectors are not provided, the
uid-immersed MOV arresters must be manually
disconnected before testing by opening the
transformer tank.
MOV arresters can be manually disconnected using
the following procedure.
1. Make sure that tank is properly grounded.
2. De-energize the transformer from a remote
location.
3. Ground all bushings and terminals.
Hot-Stick Operable Devices
Some devices such as draw-out expulsion fuses,
dry-well canister fuses, dead-front high-voltage
elbow terminations, rotary load-break switches and
automatic pressure relief devices are designed
to be operated with a live-line tool (hot stick or
shotgun stick). Do not attempt to operate by
hand any device that is designed to be operated
with a live-line tool. Use the live-line tool properly
according to the instructions provided by the liveline tool manufacturer.
Other Switching and Fusing Devices
Transformers may be supplied with switching and
fusing devices not discussed in these instructions.
In such cases, contact the Howard Industries
Transformer Division or the device manufacturer for
instructions.
4. Remove the tank cover. Refer to “Opening
the Transformer Tank” for instructions.
5. Locate the disconnect points to which the
arrester line leads are attached.
6. Disconnect the three arrester leads from
their junction points and isolate the lead
ends at least six inches from each other and
from any other part of the transformer.
7. It is now safe to perform impulse, induced-
potential or applied-potential tests.
The following procedure should be followed to
manually reconnect the arrester leads.
1. Reconnect each of the three arrester leads to
their junction points.
2. Re-install the tank cover. Refer to “Opening
the Transformer Tank” for instructions.
Molded-Case Circuit Breakers
Molded-case circuit breakers use an automatic
trip system to help protect the transformer and
connected equipment from damage caused by
overloads and short circuits. Molded-case circuit
breakers should be operated and maintained
according to instructions provided by the breaker
manufacturer.
21
Page 22
Document 2.4.126, Revision 4
October 2017
Three-Phase Padmounted Distribution Transformers
SECTION 6: OPERATION OF BUSHINGS, GAUGES
AND OTHER ACCESSORY DEVICES
Many of the accessory devices described below are
optional and may not be present in any particular
transformer design. The inclusion of particular
accessory devices in any transformer design is
governed by industry standards and by individual
customer specications.
The transformer nameplate, supplied on each
transformer according to IEEE Standard C57.12.00,
provides a circuit diagram and certain physical and
electrical information.
Pressure-Vacuum Gauge
The pressure-vacuum gauge is a dial-type
instrument that indicates the pressure in the tank
gas space relative to atmospheric pressure. The
gauge is mounted on the front panel in the terminal
compartment above the uid level. Pressure in the
tank will normally vary as a function of transformer
and ambient temperatures. If the transformer is
lightly loaded or de-energized during times of low
ambient temperature, the gauge may indicate a
negative pressure.
Pressure-vacuum gauges can be supplied with
optional switch contacts, which can be used
to provide remote alarm of positive or negative
pressure.
WARNING
If the pressure-vacuum gauge constantly
reads zero under varying load and ambient
conditions, the transformer should be
checked for a possible tank leak. A leak
will allow moisture and air to enter the
transformer tank, which could degrade the
paper insulation and insulating uid. Left
unrepaired, a leak could limit transformer
life or cause a violent failure. FAILURE
TO FOLLOW THESE INSTRUCTIONS MAY
RESULT IN DEATH, SEVERE PERSONAL
INJURY AND/OR DAMAGE TO THE
EQUIPMENT.
Fluid Level Gauge and Sight Plug
The uid level gauge is a dial-type device that
indicates the uid level inside the transformer tank.
The gauge is mounted on the front panel in the
terminal compartment at the normal 25°C uid
level.
If the gauge reads “LOW,” the cause of the low
reading should be investigated and corrected. A low
uid level can cause overheating of the transformer
and can compromise the insulation system.
Fluid level gauges can be supplied with optional
switch contacts, which can be used to provide a
remote alarm of low uid level.
Transformers may also be supplied with a sight
plug, which provides direct observation of the uid
level.
Fluid Temperature Gauge
The uid temperature gauge is a dial-type bi-metal
instrument that indicates the uid temperature at
the top of the uid column in degrees centigrade.
The temperature gauge is mounted on the front
panel in a dry leak-proof well, permitting removal of
the gauge without exposure to the tank uid.
The gauge may be furnished with a red drag-hand
pointer that indicates the maximum temperature
reached since it was last reset. The drag-hand can
be reset by rotating the magnet at the center of the
dial or, on some types, by pressing a reset button.
Fluid level gauges may also be supplied with switch
contacts, which can be used to provide a remote
alarm indication of low or high temperature, or to
energize a fan control circuit.
During normal operation the uid temperature
gauge should read less than the sum of the
ambient temperature and the rated temperature
rise (normally 85°C). Refer to IEEE Standard C57.91
for loading recommendations.
Drain Valve and Sampling Device
The drain valve and sampling device permits
draining the transformer uid and sampling the uid
for testing purposes. The valve is located in the
22
Page 23
Three-Phase Padmounted Distribution Transformers
terminal compartment at the bottom of the front
panel. Refer to “Sampling and Testing the Fluid”
and “Draining and Filling the Tank” for the uid
sampling and draining procedures.
Automatic Pressure Relief Device
The automatic pressure relief device (PRD) is
designed to relieve excessive tank pressure that
might occur during operation of the transformer.
The device consists of a self-resealing, springloaded diaphragm. Some PRD types also include a
re-settable visual ag to indicate that the valve has
operated. PRD’s are usually mounted on the front
panel inside the terminal compartment; however
some high ow-rate PRD’s are designed to be
mounted externally on the tank cover and enclosed
in a tamper-resistant housing.
When gas pressure in the tank exceeds the PRD’s
specied limit, the gas pressure will cause the valve
to open, venting the excess pressure. After the
internal pressure decreases below the PRD reseal
rating, the valve will automatically close and reseal
the transformer. For PRDs’ equipped with a visual
indicating ag, the ag must be manually reset.
Some PRD’s can be supplied with optional switch
contacts, which can be used to provide a remote
alarm of valve activation.
WARNING
The cause of PRD activation should always
be investigated, since pressure venting
may indicate a potential problem inside
the transformer. FAILURE TO FOLLOW THIS
INSTRUCTION MAY RESULT IN DEATH,
SEVERE PERSONAL INJURY AND/OR
DAMAGE TO THE EQUIPMENT.
Document 2.4.126, Revision 4
October 2017
WARNING
FAILURE TO FOLLOW THE INSTRUCTIONS
BELOW MAY RESULT IN DEATH OR SERIOUS
PERSONAL INJURY, AND/OR DAMAGE TO
THE EQUIPMENT.
• Do not re-energize a transformer if the
IFD has operated.
• Always assume that a transformer
might be faulted, even if the IFD has not
operated.
• Never rely solely on the IFD as an
indicator of transformer condition.
• Transformers should always be reenergized according to the user’s
standard safety procedures.
The IFD also includes a standard pressure relief
device that is integrated into the sensor to relieve
excessive tank pressures that might occur during
normal operation of the transformer.
The IFD incorporates a removable shipping lock
for transportation and storage. The shipping lock
must be removed after transformer installation.
Always transport IFD-equipped transformers with
the shipping lock installed to prevent accidental
operation.
High-Voltage Bushings
Three-phase padmounted transformers with livefront construction are normally supplied with
externally-clamped porcelain high-voltage bushings
for connection to the high-voltage source. Bushings
are usually supplied with tin-plated eye-bolt
terminals that are suitable for connection to both
aluminum and copper conductors.
Internal Fault Detector
The Internal Fault Detector (IFD) is a mechanical
sensor that activates when sudden pressure
from an internal arcing fault occurs inside the
transformer. If an internal fault occurs, the IFD
releases a visible, non-resettable orange signal ag.
This signal ag alerts crews that the transformer is
faulted and should not be re-energized.
Three-phase padmounted transformers with deadfront construction are supplied with universal
bushing wells, one-piece (integral) bushings or
universal bushing wells with factory-installed
inserts. One-piece bushings and bushing inserts
are designed to interface with insulated elbow
connectors, and can be supplied as either loadbreak or non load-break devices.
23
Page 24
Document 2.4.126, Revision 4
October 2017
Three-Phase Padmounted Distribution Transformers
When transformers are supplied with bushing wells
only, inserts must be installed in the eld before
cable connections can be made. High-voltage
terminations may be congured for radial (three
terminations) or loop feed (six terminations).
WARNING
Do not exceed the cantilever load rating of a
low-voltage or high-voltage bushing. FAILURE
TO FOLLOW THIS INSTRUCTION MAY RESULT
IN DEATH OR SEVERE PERSONAL INJURY,
AND/OR DAMAGE TO THE EQUIPMENT.
Low-Voltage Bushings
Three-phase padmounted transformers are
normally supplied with externally-clamped molded
low-voltage bushings, with or without spade
terminals.
Current Transformers
Molded current transformers (CTs) are designed to
be mounted around each low-voltage line terminal
for metering applications. Transformers are shipped
from the factory with CT leads shorted together
and grounded. If the CTs are not connected to
a metering load, they must remain shorted and
grounded to avoid hazardous voltage at the CT
secondary terminations.
bushings. These brackets are used as mounting
locations for portable feed-throughs, insulated
standoff bushings and other similar devices.
Flip-Top Terminal Compartment Cover
The transformer may be equipped with a ip-
top terminal compartment cover, which can be
raised to facilitate operation of Bay-O-Net fuses
and to provide clearance for pulling cables into
the terminal compartment. To open the cover,
disengage the center security bolt and rotate the
cover upward. A latch is provided to secure the
cover in the open position.
Door Handle, Security Bolt and Padlock
Three-phase compartmental padmounted
transformers are designed and constructed to be
tamper resistant according to the requirements
of IEEE Standards C57.12.28 or C57.12.29, as
applicable, and as such are provided with a door
handle with interlocking penta-head security bolt
and padlock provisions. To ensure enclosure
integrity and prevent unauthorized entry, the handle
should be latched, the security bolt should be fully
engaged and a suitable heavy-duty padlock should
be installed.
Lift-Off Door Hinges
Lift-off door hinges are provided, so that the
primary and secondary compartment doors can be
removed. The door design prevents their removal
while in the closed position.
WARNING
CT leads must be connected to a load or
short-circuited and grounded before the
transformer is energized to avoid hazardous
voltage at the CT terminals. FAILURE TO
FOLLOW THIS INSTRUCTION MAY RESULT
IN DEATH OR SERIOUS PERSONAL INJURY,
AND/OR DAMAGE TO THE EQUIPMENT.
Accessory Brackets
Accessory brackets (parking stands) are provided
on dead-front transformers and are located inside
the terminal compartment near the high-voltage
24
Other Accessory Devices
Transformers may be supplied with accessory
devices not discussed in these instructions. In such
cases, contact the Howard Industries Transformer
Division for information.
Page 25
Three-Phase Padmounted Distribution Transformers
SECTION 7: MAINTENANCE
Document 2.4.126, Revision 4
October 2017
WARNING
The transformer must be de-energized
before performing any maintenance
work. FAILURE TO FOLLOW THIS
INSTRUCTION MAY RESULT IN SEVERE
PERSONAL INJURY OR DEATH, AND/OR
DAMAGE TO THE EQUIPMENT.
These instructions are intended as a general
guide for the maintenance of Howard threephase compartmental padmounted distribution
transformers, when used in typical applications
and operated in normal environments. Although
efforts have been made to ensure accuracy and
completeness, these instructions do not address
every conceivable application or circumstance that
might be encountered.
Transformers should be inspected periodically while
in service, with the frequency determined by service
conditions. Transformers operating in unusual
service conditions should be inspected more
frequently. Refer to IEEE Standard C57.12.00 for a
discussion of usual and unusual service conditions.
WARNING
FAILURE TO FOLLOW THE INSTRUCTIONS
BELOW MAY RESULT IN DEATH OR SEVERE
PERSONAL INJURY, AND /OR DAMAGE TO
THE EQUIPMENT.
• De-energize transformer from a remote
location before opening cabinet to
perform inspection or maintenance.
• Make sure all transformer terminals and
bushings have zero voltage.
• Make sure that the transformer is
properly grounded.
• Fluid leaks should be repaired as soon as
they are discovered.
Accessories such as a pressure relief device,
temperature gauge, uid level gauge, pressure-
vacuum gauge and drain valve typically require no
maintenance, except replacement in the event of
damage. Gauges should be checked periodically to
make sure they are operating properly.
Periodic Inspection
The transformer’s terminal compartment interior,
all exterior surfaces and the transformer’s
surroundings should be inspected. Inspection
frequency should be governed by operating
conditions at the installation site. More severe
conditions indicate the need for more frequent
inspection.
25
Page 26
Document 2.4.126, Revision 4
October 2017
WARNING
FAILURE TO FOLLOW THE INSTRUCTIONS
BELOW MAY RESULT IN DEATH OR SEVERE
PERSONAL INJURY, AND /OR DAMAGE TO
THE EQUIPMENT.
• De-energize transformer from a remote
location before opening cabinet to
perform inspection or maintenance.
• Make sure all transformer terminals and
bushings have zero voltage.
• Make sure that the transformer is
properly grounded.
• Fluid leaks should be repaired as soon as
they are discovered.
Inspection Checklist
Observing the safety instructions above, open the
compartment doors and perform the following
checks.
1. Inspect for dents or other damage to metal
surfaces and make the necessary repairs
2. Inspect the cabinet for evidence of
tampering and immediately repair any
damage to ensure cabinet integrity and
prevent unauthorized entry.
3. Inspect the paint nish for damage,
corrosion or weathering that exposes the
primer coat or bare metal. Repair any paint
damage that might be found. Refer to
“Exterior Paint Finish” for instructions.
4. Inspect thoroughly for evidence of uid
leaks, including tank, radiators, bushings,
gauges, switches, valves, fuse holders
and all other accessories. Check the uid
level gauge or sight glass to determine the
uid level. Check the pressure-vacuum
gauge (if present) for a zero reading, which
indicates the possibility of a tank leak (The
pressure-vacuum gauge can indicate zero
occasionally, but normally indicates a slight
positive or negative pressure, dependent on
uid and ambient temperatures). Perform a
Three-Phase Padmounted Distribution Transformers
pressure test according to the instructions
in “Pre-energization Inspection and Tests.”
Add uid as necessary to ensure that the
proper uid level is maintained. Repair as
necessary. Fluid leaks must be repaired
immediately to prevent serious damage to
the transformer and danger to life. Refer to
“Fluid Leaks” for instructions.
5. Visually check all gaskets for cracking
or other signs of deterioration. Replace
as necessary. When replacing a gasket
carefully clean mating surfaces to remove
any rust, dirt, transformer uid, old gasket
material, or other contamination that might
prevent a good seal. Use appropriate
gasket cement when installing new gaskets.
Do not reuse old gaskets. Six months after
replacing a gasket, check and re-tighten, if
necessary.
6. Maintain a clean and unobstructed area
around the transformer, including sufcient
clearance around radiator panels, to ensure
adequate cooling of the transformer.
7. Inspect the base of the transformer tank
and terminal compartment and make sure
that there is no accumulated dirt or other
debris that might promote corrosion.
8. Inspect the base of the terminal
compartment and make sure that it is
sitting level and at on the surface of the
pad with no gaps that might compromise
tamper-resistance.
9. Check bushings, gauges, switches, fuse
holders and all other accessories for
proper operation and repair or replace any
defective devices.
10. Check all fasteners for signs of corrosion
and replace as necessary.
11. Check the uid temperature gauge,
including the maximum temperature drag
hand (if supplied) to determine whether
the uid temperature has exceeded the
design limit. Any such indication should be
investigated to determine and correct the
cause.
12. Check the torque values on all electrical
connections, including the ground
26
Page 27
Three-Phase Padmounted Distribution Transformers
Document 2.4.126, Revision 4
October 2017
Inspection Checklist (cont.)
connections and tighten as necessary
(Refer to torque guidelines contained in
Tables 1 through 4).
13. Replace any damaged or unreadable
nameplates, instructional labels, and safety
labels.
14. If it is suspected that water or other
contaminates may have entered the tank,
the uid should be tested to determine
its condition. For transformers lled with
conventional transformer oil, Refer to IEEE
Standard C57.106, Guide for Acceptance
and Maintenance of Insulating Oil in
Equipment. For transformer lled with
less-ammable high molecular weight
hydrocarbon insulating uid (such as
R-Temp), refer to IEEE Standard C57.212,
Guide for Acceptance and Maintenance
of Less Flammable Hydrocarbon Fluids in
Transformers. For transformers lled with
silicone uid or seed-based uid (such
as Envirotemp FR3), contact the Howard
Industries Transformer Division for testing
recommendations.
Electrical Tests
The following tests can be used to determine
the condition of the transformer. Comply with
instructions and precautions provided by the test
equipment manufacturer. Contact the Howard
Industries Transformer Division to discuss any of
these tests.
DANGER
FAILURE TO FOLLOW THE INSTRUCTIONS
BELOW WILL RESULT IN DEATH OR SERIOUS
PERSONAL INJURY, AND EQUIPMENT DAMAGE.
• Energize the transformer from a remote
location.
• Do not energize the transformer using
single-phase switches or fuses. Use only
gang-operated three-phase switches to
energize a three-phase transformer.
• Do not operate the transformer with any of
the primary phases open.
• Only qualied personnel with appropriate
equipment should measure transformer
voltages.
• Be aware of dangerous voltages within the
terminal compartment and avoid personal
contact with live terminals.
• Wear personal protective equipment to
prevent injury from potential arc ash or
contact with dangerous voltages.
• Make sure the transformer is properly
grounded at all times.
• Insulated dead-end caps or plugs must be
installed on all unused dead-front highvoltage bushings. Dust caps must not be
used in place of insulated dead-end caps or
plugs.
• CT leads must be connected to the
metering load or shorted together and
grounded to prevent dangerous voltages at
the CT terminals.
27
Page 28
Document 2.4.126, Revision 4
October 2017
Three-Phase Padmounted Distribution Transformers
Electrical Tests (cont.)
1. Insulation Resistance Test. Refer to
“Insulation Resistance Test” for instructions.
2. Turns Ratio Test. Refer to “Ratio Test” for
instructions
3. Insulation Power Factor Test
4. Fluid quality tests, such as moisture
content, power factor, dielectric strength
and dissolved gas analysis.
Exterior Paint Finish
Any damage to the exterior paint nish that exposes
the primer coat or bare metal should be repaired
immediately in order to prevent corrosion. Areas
to be repaired should be thoroughly clean and dry.
The surface should be sanded to remove rust, loose
paint akes and other debris. The surface should
then be cleaned with a suitable solvent to remove
any oil, grease or other contaminates. At lease two
coats of a high-quality touchup paint should be
applied to the damaged area. Bare metal should
receive a primer coat before applying the nal
nish. Touch-up paint is available in aerosol cans
from the Howard Industries Transformer Division.
Fluid Leaks
Check the tank for indication of uid leaks, looking
carefully at weld seams and at tank ttings, such
as bushings, gauges, plugs and valves. Fluid leaks
should be repaired as soon as possible to prevent
moisture contamination of the insulating uid and
to prevent internal ashover due to low uid level.
WARNING
FAILURE TO FOLLOW THE INSTRUCTIONS BELOW
MAY RESULT IN DEATH OR SEVERE PERSONAL
INJURY, AND /OR DAMAGE TO THE EQUIPMENT.
• De-energize transformer from a remote
location before opening cabinet to perform
inspection or maintenance.
• Make sure all transformer terminals and
bushings have zero voltage.
• Make sure that the transformer is properly
grounded.
• Fluid leaks should be repaired as soon as
they are discovered.
If a uid leak is suspected, investigate thoroughly
to determine if an actual leak does exist on the
transformer. False indications of a leak can occur
as a result of residual uid that was not sufciently
cleaned after the transformer was lled with uid.
In some cases silicone lubricant used to install
high-voltage bushing inserts can ow onto the front
panel, giving a false indication of a uid leak.
In addition to the presence of uid residue, a low
reading on the uid level gauge and a constant
zero reading on the pressure/vacuum gauge (which
does not vary over time as a function of transformer
loading and ambient temperature) are also
indications of a possible uid leak.
To verify that a uid leak exists, clean the
suspected leak area with an appropriate solvent
to completely remove the uid and observe the
area for reappearance of uid. Pressurize the tank
with dry air or dry nitrogen through the pressure
test tting to a pressure of 3-4 PSIG. Let the tank
stand under pressure for one to two hours, then
examine the tank and ttings for leaks. Leaks above
the uid level can be detected by applying soap
solution to all welds, joints, pipe ttings, and cable
connections.
In many cases a small pin-hole tank leak or leak
from a bushing, gauge, valve or other tting can be
repaired on site. Pin-hole and weld seam leaks can
usually be repaired by welding on a de-energized
transformer. Welding on radiator panels is not
recommended due to the thinner gauge material.
Very small pin-hole leaks can sometimes be
repaired using an epoxy patch kit designed to repair
oil leaks.
Bushing leaks can sometimes be corrected by
tightening the bushing clamp bolts. Do not exceed
the recommended torque values listed in Table
2 to prevent the possibility of bushing or gasket
damage.
Audible Sound Level
It is normal for transformers to emit an audible
humming sound, which is primarily caused by
alternating magnetic ux in the transformer core.
Amplitude and harmonic content of the sound is
inuenced by transformer size, the energizing
28
Page 29
Three-Phase Padmounted Distribution Transformers
Document 2.4.126, Revision 4
October 2017
voltage level and sinusoidal purity, load conditions
and acoustic conditions at the installation site.
Unusual sounds should be investigated, as this
might indicate a potential problem.
Refer to NEMA Standards Publication TR-1,
Transformers, Regulators and Reactors, and IEEE
Standard C57.12.90, IEEE Standard Test Code
for Liquid-Immersed Distribution, Power, and
Regulating Transformers, for more information
about design sound levels and factory sound
testing.
Molded-Case Circuit Breakers
Molded-case circuit breakers are sealed devices
requiring minimal maintenance. Refer to inspection
and maintenance instructions provided by the
breaker manufacturer. Test sets are available from
breaker manufacturers that can be used to test and
calibrate breakers.
Other Accessory Devices
Other accessory devices, such as a gauges and
valves typically require no maintenance except for
replacement in the event of malfunction or damage.
Sampling and Testing the Fluid
Before sampling the insulating uid, de-energize
the transformer from a remote location and make
sure all bushings and terminals are effectively
grounded. Samples should be drawn from the
bottom of the tank. Refer to ASTM D923 Standard
Practices for Sampling Electrical Insulating Liquids
for recommended sampling procedures. Also, refer
to any sampling recommendations supplied by the
uid test equipment manufacturer.
It is recommended that a uid sample be drawn
annually and tested for dielectric strength.
Dielectric strength should measure at least 26 kV.
Filtering the Fluid
Insulating uids such as mineral oil, R-Temp or
seed-based uids can be ltered using a lter
press system. A lter press can remove particle
contaminates as well as small amounts of moisture.
Follow the operating instructions provided by the
lter press system manufacturer.
Continue to lter the uid until the dielectric test
result is 26kV or greater.
When ltering any particular type of insulating
uid, make sure the lter press system is not
contaminated with any other type of uid.
Contamination of the uid may alter its chemical
or physical characteristics and could reduce its re
point.
Removing or Lowering the Fluid
Should it be necessary to remove or lower the
insulating uid, the following procedure should be
used.
1. De-energize the transformer and make
sure the tank, bushings, and terminals are
effectively grounded.
2. If cover removal is required, remove the
cover as outlined in the “Opening the
Transformer Tank” section.
3. Use a clean, dry temporary storage
container to contain the uid.
4. Use clean pumps and hoses that have not
been contaminated by different types of
uids. Hoses must be designed for handling
the particular uid in the transformer (As an
example, rubber hoses should not be used
with mineral oil.).
5. Connect the pump intake line to the drain
valve at the bottom of the transformer tank.
6. Place the pump discharge line nozzle at the
bottom of storage container.
7. Pump slowly, and do not allow the uid
to splash into the container, as this will
introduce air and moisture into the uid.
8. Do not lower the insulating uid below the
top of the core/coil clamp pan. Exposing
coils may allow moisture to contaminate coil
insulation.
Filling with Fluid
When relling the transformer with insulating
uid, ll with the same type of uid. Do not mix
different types of uids. Care should be taken to
avoid introduction of air bubbles during the lling
process. After relling is complete, allow 24 hours
for dissipation of air bubbles before energizing the
transformer. Trapped air bubbles can reduce the
insulation value of the uid and cause a ash-over.
29
Page 30
Document 2.4.126, Revision 4
October 2017
Three-Phase Padmounted Distribution Transformers
1. Pump from the bottom of temporary storage
container. To prevent bubbles in the uid,
do not allow air to enter the pump intake.
2. Place the discharge hose at the bottom of
the transformer tank below the uid surface
to prevent aeration and the introduction of
bubbles.
3. Pump and ll the transformer tank slowly.
Fill with uid to ll line marked inside the
transformer tank on the interior surface
of the front panel. If the ll line cannot be
viewed, use the indication on the uid level
gauge or sight plug (if supplied) or ll to the
bottom of the ll plug.
Opening the Transformer Tank
Transformer tanks are shipped sealed and should
not be opened unless necessary. If it is necessary
to open the tank, follow the instructions below and
observe all safety warnings.
WARNING
FAILURE TO FOLLOW THE INSTRUCTIONS BELOW
MAY RESULT IN DEATH OR SEVERE PERSONAL
INJURY, AND/OR DAMAGE TO THE EQUIPMENT.
• Before servicing the transformer, ALWAYS
de-energize the transformer from a
remote upstream source and then proceed
to ground all primary and secondary
transformer terminals following industryaccepted safe grounding practices.
Grounding secondary terminals protects
against situations such as a standby
generator energizing transformer from the
secondary circuit.
• Release internal pressure before opening
the tank.
• Never allow anyone to enter the
transformer tank until an analysis of the
air inside the tank indicates at least 19.5%
oxygen.
Transformer tanks should not remain open for more
than two hours. If work is interrupted, the tank
should be resealed, evacuated, and lled with dry
air or nitrogen.
To prevent contamination of the transformer, do
not open the transformer tank in an unprotected
area during inclement weather or where the air
may contain dirt or other particles. Any of these
situations could contaminate the insulating uid
and cause a transformer failure. The tank opening
should be protected against entry of foreign matter.
If it is necessary to remove some uid from the
tank to allow for inspection or other work, the
transformer must be re-lled with uid after work is
completed.
Personnel should not be permitted on top of or
inside the transformer while it is open unless they
have emptied all pockets and checked for loose
objects that might fall into the tank. All tools should
be accounted for after work is completed. It is
recommended that any tools used on top of the
transformer or inside the tank be attached with
safety cords to prevent them from being lost inside
the transformer.
Personnel must not stand directly on any electrical
insulation. Clean drop cloths should be used under
working areas in the transformer to prevent objects
from dropping into the core/coil assembly.
The following procedure should be used to remove
the hand-hole cover.
1. Thoroughly clean the hand-hole cover.
Remove all moisture, dirt, and grease to avoid
contaminating the transformer tank.
2. Relieve internal tank pressure by manually
operating the pressure relief valve.
3. Remove cover fasteners.
4. Gently pry the cover upward, making sure that
the cover gasket does not fall into the tank. Lift
the cover vertically to prevent damage to cover,
bolts, and gasket.
5. Remove the gasket from the hand-hole ange.
• Whenever someone is inside the tank, a
person should be stationed near the handhole to ensure the safety of the person
inside the tank.
30
The following procedure should be used to re-install
the hand-hole cover.
1. Place the gasket in its original position. If the
gasket is damaged, it should be replaced.
Page 31
Three-Phase Padmounted Distribution Transformers
Document 2.4.126, Revision 4
October 2017
2. Re-install the hand-hole cover. Reinstall fasteners according to the torque
recommendations in Table 1. After tightening
all fasteners, re-torque each one to ensure
proper torque.
3. Pressurize the headspace to 3-4 PSIG and
check for uid leaks. This pressure should be
maintained for at least four hours.
Torque Guidelines
Tables 1 through 4 below contain recommended torque values for tightening various connections on the
transformer. Connections with gaskets and those involving rubber components (such as high-voltage busing
inserts) will normally relax after initial tightening. Nominal torque values listed below include an allowance
for normal relaxation.
Do not over-tighten any connection; otherwise, gaskets may split due to over-compression, and components
may break. Fluid leaks may result if tank-mounted components are over tightened. Check with the Howard
Industries Transformer Division for recommended torque values for any devices or connections not listed
below. Use the manufacturer’s recommended torque values for any customer-supplied devices.
Table 1: Torque Guidelines for External Cabinet Fasteners
Fastener TypeNominal Torque (in-lbs)Torque Range (in-lbs)
When checking tightness of gasketed components, the measured torque will normally be less than the nominal torque listed in the
table above due to relaxation of the gasket material. Additional tightening of bushing mounting hardware may cause the component
to crack or the gasket to become over-compressed.
31
Page 32
Document 2.4.126, Revision 4
October 2017
Three-Phase Padmounted Distribution Transformers
Table 3: Torque Guidelines for External Bushing Terminal Connections
Terminal TypeNominal Torque (in-lbs)Torque Range (in-lbs)
High-voltage molded bushing insert
180170-190
High-voltage porcelain bushing eye-bolt210180-240
High-voltage porcelain bushing end cap168156-180
Low-voltage bushing, 5/8” jam nut600480-720
Low-voltage bushing, 1” jam nut600480-720
Low-voltage bushing, 1-1/4” jam nut720600-840
Apply silicone grease before installation according to the insert manufacturer’s instructions.
When checking tightness of gasketed components, the measured torque will normally be less than the
nominal torque listed in the table above due to relaxation of the gasket material. Additional tightening
of bushing mounting hardware may cause the component to crack or the gasket to become overcompressed.
When checking tightness of gasketed components, the measured torque will normally be less than the
nominal torque listed in the table above due to relaxation of the gasket material. Additional tightening of
bushing mounting hardware may cause the component to crack or the gasket to become over-compressed.
32
Page 33
Three-Phase Padmounted Distribution Transformers
Document 2.4.126, Revision 4
October 2017
Additional Maintenance Instructions
Features and accessory devices discussed herein
may not be present in all transformers. Some
features or accessory devices may be present
on a transformer, but not discussed in these
instructions. Howard Industries does not represent
that these instructions are complete, sufcient,
accurate or useful for all circumstances.
Questions regarding installation, operation, and
maintenance (particularly when encountering
unusual or special circumstances not sufciently
covered by these instructions) should be directed
to the Howard Industries Transformer Division.
Repair Parts
Repair parts can be ordered from the Howard
Industries Transformer Division. A description of
the part and the transformer serial number will be
required to ensure that the correct part has been
ordered.
the transformer cover or hand-hole cover, and then
completely purging the interior with pure air or an inert
gas such as nitrogen.
Warranty Claims
The Howard Industries Transformer Division
should be notied immediately when problems are
discovered during the warranty period. All warranty
repairs must be made or approved by the Howard
Industries Transformer Division.
Transformer Disposal
Comply with all local, state and federal regulations when
disposing of any insulating uid. Fluid type and volume
can be determined by referring to the transformer
nameplate. Contact Howard Industries to obtain the
appropriate uid Safety Data Sheet (SDS). The SDS
identies uid composition and properties, and describes
important safety, handling and storage, ecological,
regulatory, disposal and other pertinent information.
WARNING
Improper disposal of a transformer could result in
personal injury or death and could be hazardous to
the environment.
Before the transformer tank can be safely cut with a
grinder or torch, any potentially explosive gasses must
be removed from the tank interior. This can be done by
rst operating the pressure relief device to slowly bring
the tank interior to atmospheric pressure, removing
33
Page 34
Document 2.4.126, Revision 4October 2017
NOTES
Three-Phase Padmounted Distribution Transformers
34
Page 35
Three-Phase Padmounted Distribution Transformers
NOTES
Document 2.4.126, Revision 4
October 2017
35
Page 36
Document 2.4.126, Revision 4October 2017
Three-Phase Padmounted Distribution Transformers
36
HI-105
Instructions for Installation, Operation and Maintenance
of Three-Phase Padmounted Distribution Transformers,