Hoval TopGas 80 Installation Instructions Manual

Technical Information Installation Instructions
EN
4 207 803 / 01 - 11/09 Subject to modifications
Gas condensing boiler TopGas® (80) for natural and liquid gas
Wall-mounted gas boilers TopGas® (80) accord­ing to DIN 4702, DIN EN 483 and DIN EN 677 are suitable and approved as heat producers for hot water heating systems with a permissible flow temperature of up to 85°C). They are de­signed for a flexibly reduced operation in heating systems according.
Hoval gas boilers are only to be installed and placed in operation by technicians; these instruc­tions are therefore intended for the specialist. Electrical installation work is only to be carried out by an electrician.
Rated output levels at 40/30°C and natural gas
2-TopGas
®
(80) 17,3 - 80,0 kW
4 207 803 / 01
2
Contents
1. General Information ........................................................................................4
1.1 Symbols ........................................................................................................................ 4
1.2 Guarantee ..................................................................................................................... 4
1.3 Other instructions .......................................................................................................4
1.4 Safety instructions ...................................................................................................... 4
1.5 Regulations, official approvals ................................................................................... 5
1.6 Transport and storage ................................................................................................. 5
2. Technical Information .....................................................................................6
2.1 Technical Data ............................................................................................................. 6
2.2 Dimensions .................................................................................................................. 7
2.3 Boiler flow resistance .................................................................................................8
2.4 Short description of the automatic firing unit BIC 335 ............................................ 8
2.5 Control of the boiler .................................................................................................... 9
2.6 Adjustable parameters .............................................................................................. 11
3. Installation ..................................................................................................... 13
3.1 Description of the Hoval TopGas® ...........................................................................13
3.1.1 Diaphragm expansion tank .......................................................................................... 13
3.1.2 Boiler casing ................................................................................................................ 13
3.1.3 Gas fittings ................................................................................................................... 13
3.1.4 Automatic gas firing unit and heating controller ........................................................... 13
3.1.5 Heating circulation pump ............................................................................................. 13
3.1.6 Hot water supply .......................................................................................................... 13
3.1.7 Scope of supply ........................................................................................................... 13
3.1.8 TopGas
®
component designation ................................................................................ 14
3.2 Boiler installation room ............................................................................................15
3.3 Installing the boiler .................................................................................................... 15
3.4 Hydraulic connection ................................................................................................ 15
3.4.1 Protection planning guidelines for the hy drau-lic connection ....................................... 15
3.4.2 Boil-dry safeguard .......................................................................................................15
3.4.3 Gravity brake ............................................................................................................... 15
3.4.4 Minimum flow rate .......................................................................................................15
3.4.5 To be provided by customer......................................................................................... 16
3.4.6 Examples of hydraulic interconnection ........................................................................ 16
3.5 Flue gas connection, chimney and condensate pipeline ...................................... 17
3.5.1 Waste gas pipelines in compliance with building construction law .............................. 17
3.5.2 Project planning information for the TopGas
®
............................................................. 17
3.5.3 Natural ventilation flue example ................................................................................... 18
3.5.4 Flue gas system for room sealed operation.................................................................19
3.5.5 Roof heating centre concentric flue (room sealed) ......................................................19
3.5.6 Wall outlet .................................................................................................................... 20
3.5.7 Connection of pipelines ............................................................................................... 21
3.5.8 Condensate draining and neutralisation ...................................................................... 21
3.5.9 Gas connection ............................................................................................................ 21
3.6 Electrical connection ................................................................................................21
3.6.1 Electrical connection regulations ................................................................................. 21
3.6.2 Electrical connection (mains) 230 V, 50 Hz .................................................................22
3.6.3 Boiler control / electrical connection diagram .............................................................. 22
3.6.4 Connection of the heating controller ............................................................................ 22
3.6.4.1 TopTronic
®
RS-OT ........................................................................................................ 22
3.6.4.2 TopTronic
®
T/N ............................................................................................................. 22
4 207 803 / 01
3
Contents
4. Commissioning ............................................................................................. 22
4.1 Setting the control .....................................................................................................22
4.2 Water quality .............................................................................................................. 22
4.2.1 Heating water ..............................................................................................................23
4.2.2 Filling and replacement water ...................................................................................... 23
4.2.3 Filling up the system .................................................................................................... 24
4.3 Gas adjustment .......................................................................................................... 24
4.3.1 Bleeding the gas pipeline ............................................................................................24
4.3.2 Commissioning ............................................................................................................ 24
4.3.3 Gas inlet pressure .......................................................................................................24
4.3.4 Gas fitting ....................................................................................................................24
4.3.5 Setting the gas flow rate .............................................................................................. 25
4.3.6 Changing to a different kind of gas .............................................................................. 25
4.4 Handing over to the user .......................................................................................... 26
4.4.1 Instruction the user ...................................................................................................... 26
4.4.2 Checking the water level .............................................................................................. 26
4.4.3 Maintenance ................................................................................................................ 26
5. Decommissioning ......................................................................................... 27
6. System maintenance and cleaning .............................................................. 27
6.1 Water-side leak check ............................................................................................... 27
6.2 Refilling ......................................................................................................................27
6.3 Maintenance includes: ..............................................................................................27
6.4 Cleaning the heat exchanger .................................................................................... 27
6.5 Function check .......................................................................................................... 27
7. Faults .............................................................................................................. 29
8. Automatic firing unit BIC 335-Parameter list .............................................. 32
4 207 803 / 01
4
1. General Information
1.1 Symbols
Safety information (Instructions for the safety and protec-
tion of persons)
Warning information (Instructions for the protection of the
heating system)
Bold type = Important information
1.2 Guarantee
Important Note Proper functioning is only guaranteed if the operating instructions are observed and the boiler is regularly maintained according to the DVGW (German association of gas and water management / ÖVGW (Austrian association of gas and water management), respectively SVGW (Switzerland association of gas and water management) directives by an approved specialist. Troubleshooting and damage repair caused by contaminated operating media (gas, water, combustion air), unsuitable chemical ad­ditives to the heating water, incorrect handling, faulty installation, inadmissible modifications and damage due to the exercising of force are not covered by our warranty; the same applies to corrosion through halogen compounds, e.g. from spray cans, paints, adhesives, solvents and cleaning agents. Hoval gas boilers are only to be installed by approved specialists. No modifications are to be made to the boilers.
1.3 Other instructions
Depending on the model, any further instructions are enclosed with the individually packed components.
- Adjustment
- Accessories
Further information sources
- Hoval catalogue
- Standards, regulations
1.4 Safety instructions
When working on the TopGas
®
the following points
need to be noted:
If you smell flue gas or gas:
- no open fire or sparks,
- do not smoke,
- deflector off the heating system,
- close the gas cock,
- open doors and windows
The system may only be placed in operation when all relevant standards and safety regulations have been complied with. However, for a trial operation, at least the following conditions must be satisfied:
- Safety valve installed (closed system)
- Control operative (connected to power supply)
- System filled with water
- Expansion tank connected
- Boiler is connected to the regulation type flue
gas pipeline
- Burner is preset.
• Withmaintenanceandrepair
- Allow the gas boiler to cool.
- Deflector off the gas boiler and disconnect from
the electrical supply.
- Shut off the gas cock.
- Close the shut-off cocks of the appliance (cold
water, heating flow and return).
- Inappropriate actions on water-carrying parts
of the gas boiler can result in an outflow of hot water and cause severe burns.
- Replace all removed covers and cladding on
completion of the repair / maintenance work.
- Do not exceed the maximum operating pressure
and temperature of the gas boiler (see identifica­tion plate).
- Open the appliance cocks (cold water, heating
flow and return).
- Open the gas cock.
1. General Information
4 207 803 / 01
5
and further standards and regulations issued by CEN, CEN ELEC, DIN, VDE, DVGW, TRD and by the legislator.
Also to be complied with are the regulations of the local building authorities, insurance companies and chimney sweeping operations. When using gas as a fuel, the regulations of the responsible gas supply company are also to be complied with and any neces­sary official approval obtained.
The regulations concerning condensate pipe­lines and treatment are subject to the regu­lations of the local water authorities and can differ from the provisions of the technical drain­age directive ATVM251. Please obtain informa­tion on the relevant local regulations.
1.6 Transport and storage
Please remove the packing materials and examine the consignment for correctness, completeness and possible transport damage. The appliance is only to be transported and stored only in its original packing. Interim storage of Hoval gas boilers is only to take place in weather protected rooms and only in the original packing. The ambient conditions for storage must be within the following limits:
- Air temperature: -10°C - +50°C
- Air humidity: 50 - 85% relative humidity
- no condensation
1.5 Regulations, official approvals
The following regulations are to be complied with for installation and operation, in addition to the recognised rules of the art:
Germany
• DIN EN 12831 Heating systems in buildings ­Methods for calculating the design heat load
• DIN EN 13384 Flue gas systems - Heat and flow calculation methods
• DIN EN 12828 Heating systems in buildings - Plan­ning of hot water heating systems.
• VDI 2035 Prevention of damage through cor­rosion and scale formation in hot water heating systems.
• Firing regulation for the Federal regions
• DVGW-TRGI 86-96
• Technical regulations of gas supply enterprises
• VDE 0100 for electrical installations and the TAB
(technical connection conditions of the responsible energy supplier)
• ATV data sheet M251
• Accident prevention regulations
- VBG 1 General regulations
- VBG 4 Electric systems and equipment
Austria
OENORM 12831 Heating systems in buildings
- Methods for calculating the design heat load
OENORM 13384 Flue gas systems - Heat and flow calculation methods
OENORM 12828 Heating systems in buildings
- Planning of hot water heating systems.
OENORM H5152 Brennwert
- Feuerungsanlagen
OENORM H5195-1 Prevention of damage through corrosion
M 7443, (Part 2,3,7) Gas appliances with atmo­spheric burners
M 7446, Heat output appliances for gaseous fu­els
M 7457, Heat output appliances with mechanically supported premix bat-wing burners
M 7444, Special gas boilers with burners without fan
M 7459, Gas appliances with gas-air compound controller
ÖVGW TR- Gas
Technical provisions of the gas suppliers
1. General Information
Switzerland
SN EN 12831 Heating systems in buildings - Meth­ods for calculating the design heat load
SN EN 13384 Flue gas systems - Heat and flow calculation methods
SN EN 12828 Heating systems in buildings - Plan­ning of hot water heating systems.
Requirements of the VKF Cantonal Fire Insurance Association
Fire service regulations
SVGW directives, gas guiding standard G1
SNV271020 Aeration and ventilation of the boiler
installation room
SWKI 88-4 Water treatment for heating, steam and air conditioning systems
SWKI 80-2 Technical safety regulations for heating systems
KRW Corrosion through halogen compounds
Procal/FKR Plug-in electrical connections on heat-
ing boiler and burner
Technical tank regulations TTV 1990
EKAS - Guideline for liquid gas part 2
4 207 803 / 01
6
2. Technical Information
2.1 Technical Data
2. Technical Information
Type (80)
• Nominaloutput80/60°Cwithnaturalgas1 kW 15,8 - 72,4
• Nominaloutput40/30°Cwithnaturalgas1 kW 17,3 - 80,0
• Nominaloutput80/60°Cwithpropanegas3 kW 19,5 - 72,4
• Nominaloutput40/30°Cwithpropanegas3 kW 21,6 - 80,0
• Nominalloadwithnaturalgas1 kW 16,5 - 75,0
• Nominalloadwithpropanegas3 kW 20,0 - 75,0
• Workingpressureheatingmaximum/minimum bar 4,0/1,5
• Workingtemperaturemaximum °C 85
• Boilerwatercontent  l 10
• Minimumwaterow  l/h 800
• Boilerweight(withoutwatercontent) kg 107
• Standardefciency(DIN4702,part8) 40/30°C % 109,4
• (relatedtonet/grosscaloricvalue) 75/60 °C % 106,1
• Stand-bylossat70°C  Watt 95
• Standardemissionrate
Nitrogen oxides mg/kWh 18 Carbon monoxide mg/kWh 27
• ContentofCO2 in the exhaust gas maximum/minimum output % 9,0 / 8,8
• Dimensions: seetableofdimensions
• Connections
Flow/Return Inches Rp 1¼" Gas Inches R ¾" Flue gas/combustion air (concentrically) mm C100 / 150
• Gasowpressureminimum/maximum
Natural gas E/LL mbar 18 - 50 Propane gas mbar 37 - 50
• Gasconnectionvalueat0°C/1013mbar::
Natural gas E - (Wo = 15,0 kWh/m
3
) Hu = 9,97 kWh/m
3
m3/h 1,65 - 7,5
Propane gas 3 (Hu = 25,9 kWh/m3) m3/h 0,77 - 2,90
• Operationvoltage V/Hz 230/50
• Controlvoltage V/Hz 24/50
• Minimum/maximumelectricalpowerconsumption Watt 23/130
• Stand-by Watt 7
• IPrating(integralprotection) IP 20
• Soundpowerlevel  dB(A) 63
• Soundpressurelevel(dependingoninstallationconditions)2 dB(A) 53
• Condensatequantity(naturalgas)at40/30°C l/h 7,1
• pHvalueofthecondensate ca.4,2
• Valueforchimneycalculation
Requirement flue gas system, temperature class T 120 Flue gas mass flow kg/h 124,5 Flue gas temperature at operation 80/60 °C °C 79 Flue gas temperature at operation 40/30 °C °C 49 Feed pressure total at the combustion air/flue gas pipe Pa 140 Maximum draught / depression at flue gas outlet Pa -50
1
Data related to Hu. The boiler series is tested for EE/H-settings. With a factory setting of the Wobbe coefficient of 15.0 kWH/m3 operation at a
Wobbe coefficient of 12.0 up to 15.7 kWh/m3 is possible without new settings.
2
See also notes at „Engineering“.
3
Data related to Hu.
4 207 803 / 01
7
2. Technical Information
2.2 Dimensions Measurements (mm)
• Distancefromtheside50mm
• Distancefromtheceilingdependenton
the utilised flue gas pipeline system
• Inthefront500mm
1 Gas connection Rp ¾" 2 Heating flow Rp 1¼" 3 Heating return Rp 1¼" 4 Condensate drain DN 40 5 LAS Flue gas-/combustion
air connection C 100/150 6 Cover control panel 7 Safety valve 8 Ball valve
View from bottom
View from top
4 207 803 / 01
8
0
50
100
150
200
250
300
0.0 1.0 2.0 3.0 4.0 5.0 6.0
2.3 Boiler flow resistance
2. Technical Information
Water-side resistance [mbar]
Flow rate [m3/h]
2.4 Short description of the automatic firing unit BIC 335
The automatic firing unit operates both without con­troller (TTT/N) and also without room station (RS­OT). The automatic firing unit comprises the follow­ing functions
- PWM- fan (230V~)
- Modulating operation
- Inputs for Flow sensor
Return sensor Flue gas sensor Gas pressure deflector Air pressure deflector: (not used) Water pressure deflector Safety temperature limiter: (external flue gas thermo­ stat) HW-buffer sensor Outdoor sensor Locking entry: (Burner blocking)
- Status exit „Failure“ (invertible by parameter set-
ting)
- Three-way-valve control for heating/hot water
or loading pump control (230V~exits); Exit for a three-way-valve / HW loading pump is invertible by a parameter.
- Collective electrode for ignition and flame guide
(Ionisation)
- Main gas valve (ev. LPG- valve) / heating room
ventilation accessable
Boiler incl. con­nection kit
Boiler only
Fuses
On the automatic firing unit theres is a mains fuse. The breakdown of this fuse (2AT) is noticeable by an empty display even the main deflector is on.
Ionisation flow
The value of the ionisation flow is noted on the infor­mation level and appears as step 8. The access to the information level is explained in 2.5.
- Interface to display
- OpenTherm- interface (RS-OT, TTT/N)
- RS 232- interface to PC
- Start attempts: 4
- Safety period: 5 sek
- Ignition period: 5 sek
- Pre-ventilation period: 20 sek
- After-run time main pump / heating pump (230V ~): 10 min
- After-run time three-way valve / HW-loading pump: 2 min
- Restart locking after a heat demand: 2 min
- Restart locking after a temperature blocking: 2 min
4 207 803 / 01
9
2. Technical Information
2.5 Control of the boiler Control elements on the boiler control panel / Basic control N4.1
Usually, no settings of the basic control have to be made by the user. All settings have been made by the installer or by the manufacturer.
Display: temperature
Changing of the values
Display: Mode
RESET
Fault-clearance (display is blin­king, if there is a failure)
Saving of the settings
Options, to change settings (Parmeter) (p.ex. Calorifier temperature)
ON/OFF Manometer
Function
Standby-Mode
Normal position, Start position
no indication
Value indication
current flow temperature
Mode indication
Function options (stepwise display option)
Parameter
Indication
Meaning, Description
0 = Standby, no heat demand, Waiting time main gasvalve 1 = Rinsing 2 = Ignition 3 = Burner „on“ in heating operation 4 = Burner „on“ in hot water operation 5 = Air pressure deflector defectiv (no air pressure deflector in use) 6 = Burner „off“ in heating operation (flow-Temp > flow-temp set point + blockage Offset ZH) 7 = Pump after-run time in heating operation 8 = Pump after-run time in hot water operation 9 = Burner „off“ on hot water operation (flow-Temp > flow­ temp. set point + Par.1 (2AB)) Fr = Frost protection is activated Su = Summer short operation is activated
4 207 803 / 01
10
2. Technical Information
Meaning, DescriptionFunction
Value indica-
tion
Mode indication
Parameter
Indication
0 z.B. 45° Current flow temperature (Heating water temperature) 1 z.B. 40° Current return temperature 2 z.B. 60° Current temperature in water heater 3 z.B. 3° Current outdoor temerature 4 z.B. 55° Current flue gas temperature 5 z.B. 50° Flow set value in the heating system 6 z.B. 70° Flow set value in hot water operation 7 z.B.23 RPM Fan speed in hundreds 8 z.B. 4 µ A Ionisation flow
It is possible to read monetary values from here
Informations-Mode
Point is blinking
Point appears
Settings can be changed in this mode. Procedure:
1. Select parameter Mode (press Mode key 2 x) Parameter (P.7) and setting appear
alternate
2. Select parameter to be changed (Step key)
3. Change setting using + - keys
4. Save
(press Store key 1 x) Automatic return to standby mode in 20 minutes or with Mode key.
Parameter-Mode
P.7 60 = Hot water set value if threre is no TopTronic® attached.
P.18 80 = Max. Flow temperature during heating ope ration
Par. 18
Setting of the service codes
For entering the code, press the keys „Mode“ und „Step“ simultaneously. The blinking numeral can be chan­ged with the „+“ and „-“ –keys. To deflector between the numerals press the „Step“- key. To confirm and safe the total code press the „Store“- key. After 20 minutes it will be changed into the indication level.
Parameter level (constant point)
The parameter level will be signalised by a constant point behind the second sign. If none of both keys „+“/“-„ are pressed, “P“ + the parameter number will be shown alternating and then also the coresponding parameter value. By pressing „+“ or „-“ the parameter value can be changed. To save the changing press the „Store“- key, which will be confirmed by blinking twice (Wait for blinking before pessing any further keys!). If the „Store“- key won‘t be pressed, the settings are not saved.
4 207 803 / 01
11
2. Technical Information
2.6 Adjustable parameters
Parameter 7 (2AH) – Set point DHW charging temperature – Using this parameter the reference value for the DHW temperature can be set where there is no room con­trol unit or other regulatory device installed. If a reference value is transmitted via an OT bus, the latter (value via OT) will always override this parameter.
Parameter 8 (2AI) – Pump after-run time (DHW) – During the time which can be set using this parameter the pump continues to run after a phase of hot water demand. The after-run time occurs before a switchover to heating operation as well as before a switchover to to stand-by mode (to be set at the RS-OT or control unit) or when the firing device is switched OFF. It also occurs of course when the desired DHW value has been reached and further heating operation is not required.
Parameter 9 (2AJ) – Legionella protection time – The boiler is periodically heated to the temperature defined using parameter 2AF for the time period which can be set using this parameter for protection against legionella infestation. If the parameter value is set to 0 the legionella protection function is deactivated.
Parameter 10 (2AK) – Maximum fan speed in DHW mode – The parameter defines the maximum rpm value for the fan during DHW operation.
Parameter 18 (2BH) – Maximum heating temperature (when minimum outside temperature has been reached) – The value which can be set here determines the flow temperature which is to be achieved when the out­side temperature falls below the value set using parameter 19 (2BI) (minimum outside temperature). (see diagram 2). If the OT bus sends a reference value to the firing device, this value is limited by the value set using parameter 18.
Parameter 19 (2BI) - Minimum outside temperature - 19 (2BI) – Minimum outside temperature – This parameter defines the minimum outside temperature which marks the limit where the flow temperature target is to be set at the temperature given by parameter 18 (2BH).
Parameter 20 (2BJ) – Minimum heating temperature (when maximum outside temperature has been
reached) – If the outside temperature sensor registers the value set using parameter 21 (2BK), then the system targets the minimum heating temperature set using this parameter. If the outside temperature exceeds the param­eter value, the heating demand is cancelled.
Parameter 21 (2BK) – Maximum outside temperature – If the outside temperature exceeds the values set using this parameter, the heating demand is cancelled. At the point where the parameter value is reached the system targets the minimum heating temperature which has been set using parameter 20 (2BJ).
Parameter 22 (2BL) –Restart delay following temperature blocking in heating operation mode – When the boiler is shut down on account of a temperature limit being exceeded, i.e. a set point plus offset, the boiler restart is delayed for the period which can be set using this parameter – irrespective of whether the hysteresis set for the next heating demand has expired or not.
Parameter 23 (2BM) – Restart delay following heating demand during heating operation – Immediately following the end of a heating demand phase boiler restarts are delayed. That is to say, if the boiler is shut down on account of a reference value trigger being sent from the OT bus to the firing device, a restart (triggered by another reference value being reached) is delayed for at least the period of time which can be set using this parameter.
Loading...
+ 23 hidden pages