6.4 Corrosion-protected design
for high extract air humidity 24
6.5 Connection module 25
6.6 Design with 2 Air-Injectors 25
6.7 Design without Air-Injector 25
6.8 Paint nish of below-roof unit 25
6.9 Fresh air silencer 26
6.10 Exhaust air silencer 26
6.11 Supply air and extract air silencers 27
6.12 Hydraulic assembly diverting system 27
6.13 Mixing valve 27
6.14 Condensate pump 27
6.15 Socket 28
6.16 Energy monitoring 28
6.17 Return temperature sensor 28
6.18 Pump control for mixing or injection system 28
Art.No. 4 214 745-en-04 / Page 2
RoofVent® RH | RC | RHC | R
Use
1 Use
1.1 Intended use
RoofVent® units are supply and extract air handling units for use in tall, single-oor
halls. They have the following functions:
■ Fresh air supply
■ Extract air removal
■ Energy recovery with highly efcient plate heat exchanger
■ Filtering of the fresh air and the extract air
■ Air distribution with adjustable Air-Injector
Additional functions depending on unit type:
■ Heating (with connection to a hot water supply)
■ Cooling (with connection to a water chiller)
®
A system usually consists of several RoofVent
uted throughout the hall roof. The individual units are regulated individually and
controlled based on zones. The system exibly adjusts to local requirements.
®
RoofVent
relating to environmentally friendly design of ventilation systems. They are
systems of the 'non-residential ventilation unit' (NRVU) and 'bidirectional ventilation unit' (BVU) type.
Intended use also includes compliance with the operating instructions. Any usage
over and above this use is considered to be not as intended. The manufacturer
can accept no liability for damage resulting from improper use.
units comply with all the requirements of the Ecodesign Directive
units. These are installed distrib-
1.2 User group
The units are only allowed to be installed, operated and maintained by authorised
and instructed personnel who are well acquainted with the units and are informed
about possible dangers.
The operating instructions are for operating engineers and technicians as well as
specialists in building, heating and ventilation technology.
Art.No. 4 214 745-en-04 / Page 3
RoofVent® RH | RC | RHC | R
Safety
2 Safety
2.1 Symbols
Caution
This symbol warns against risk of injury. Please heed all instructions designated by this symbol to prevent injuries and/or death.
Attention
This symbol warns against property damage. Please heed the respective
instructions to prevent risk of damage to the unit and its functions.
Notice
This symbol denotes information about the economic use of the equipment
or special tips.
2.2 Operational safety
The unit is built to conform to the state-of-the-art and is operationally safe. Despite
every precaution being taken, potential and not immediately obvious risks always
remain, for example:
■ Dangers when working with the electrical system
■ Parts (e.g. tools) can fall down below when working on the ventilation unit.
■ Dangers from working on the roof
■ Damage to devices or components due to lightning
■ Malfunctions as a result of defective parts
■ Hazards from hot water when working on the hot water supply
■ Water penetration through the roof unit if the access panels are not closed
correctly
Therefore:
■ Please read the operating instructions before unpacking, installing, commis-
sioning and before maintaining the equipment.
■ Store the operating instructions so that they are easily accessible.
■ Observe any attached information and warning signs.
■ Immediately replace damaged or removed informational and warning signs.
■ Follow the local safety and accident prevention regulations at all times.
■ When working in the unit, take precautions against unprotected, sharp metal
edges.
■ The unit may only be installed, operated and serviced by authorised, trained
and instructed skilled personnel:
– Specialists as dened by these operating instructions are those persons
who, based on their training, knowledge and experience as well as their
knowledge of the relevant regulations and guidelines, can carry out the work
assigned to them and recognise potential hazards.
■ Unauthorised reconguration or modication of the unit is not permitted.
Art.No. 4 214 745-en-04 / Page 4
a
b
d
c
RoofVent® RH | RC | RHC | R
Construction and operation
3 Construction and operation
3.1 Construction
RoofVent® units consist of the following components:
■ Roof unit with energy recovery
■ Below-roof unit
The components are bolted together and can be dismantled. The connections of
the coil are located under the extract air grille as standard. The heating/cooling
section can also be mounted on the connection module turned round.
3.2 Air distribution with the Air-Injector
The patented air distributor – called the Air-Injector – is the core element. The air
discharge angle is set by means of the innitely variable guide vanes. It depends
on the air ow rate, the mounting height and the temperature difference between
the supply air and room air. The air is therefore blown into the room vertically
downward, conically or horizontally. This ensures that:
®
■ with each RoofVent
unit a large area of the hall can be reached,
■ the occupied area is draught-free,
■ the temperature stratication in the room is reduced, thus saving energy.
Roof unit with energy recovery
Below-roof unit
a Connection module
b Heating section (RoofVent
c Cooling section (RoofVent
d Air-Injector
Fig. 1: Components of RoofVent® units
®
RH, RHC only)
®
RC, RHC only)
Art.No. 4 214 745-en-04 / Page 5
RoofVent® RH | RC | RHC | R
Construction and operation
Condensate separator
®
(RoofVent
RC, RHC only)
Cooling coil
®
(RoofVent
RC, RHC only)
Heating coil
®
(RoofVent
RH, RHC only)
Access panel, coil
Access panel, connection box
Supply air fans
Supply air access door
Control block
Exhaust air access door
Exhaust air fans
Plate heat exchanger with bypass
(for performance control and as
recirculation bypass)
Fresh air damper with actuator
Bypass damper with actuator
Fresh air lter
Fresh air access door
Extract air and recirculation
dampers with actuator
Extract air access door
Extract air lter
Extract air grille
Frost controller
®
(RoofVent
RH, RC, RHC only)
Condensate connection
®
(RoofVent
RC, RHC only)
Actuator of the Air-Injector
Fig. 2: Structure of the RoofVent® units
Art.No. 4 214 745-en-04 / Page 6
RoofVent® RH | RC | RHC | R
Construction and operation
3.3 Function diagram
Fresh air
Fresh air lter with differential pressure switch
Temperature sensor air inlet ER (optional)
Bypass damper with actuator
Exhaust air temperature sensor
Exhaust air fans with ow rate monitoring
Exhaust air
Fresh air damper with actuator
Plate heat exchanger
Extract air temperature sensor
Extract air damper with actuator
Recirculation damper (opposed to the extract air
damper)
Fig. 3: Function diagram
Temperature sensor air outlet ER (optional)
Extract air lter with differential pressure switch
Supply air fans with ow rate monitoring
Extract air
Heating coil (RoofVent® RH, RHC only)
Frost controller (RoofVent® RH, RC, RHC only)
Cooling coil (RoofVent® RC, RHC only)
Condensate separator (RoofVent® RC, RHC only)
Air-Injector with actuator
Supply air sensor
Supply air
Art.No. 4 214 745-en-04 / Page 7
RoofVent® RH | RC | RHC | R
Construction and operation
3.4 Operating modes
The units have the following operating modes:
■ Ventilation
■ Ventilation (reduced)
■ Air quality
■ Recirculation (
The TopTronic
depending on unit type
®
C control system regulates these operating modes automatically
for each control zone in accordance with the specications in the calendar. The
following points also apply:
■ The operating mode of a control zone can be switched over manually.
®
■ Each RoofVent
unit can operate individually in a local operating mode: Off,
The unit blows fresh air into the room and exhausts polluted room air. The
room temperature set value day is active. Depending on the temperature
conditions, the system continuously controls:
■ the energy recovery
■ the heating/cooling
VELVentilation (reduced)
As VE, but the unit only operates with the set minimum values for the
supply and exhaust air volumes
■ Exhaust air
■ Supply air
■ Standby
)
■ Forced heating
Supply air fan ................... on
Exhaust air fan ................. on
Energy recovery ............... 0-100 %
Extract air damper ............ open
Recirculation damper ....... closed
Heating/cooling ................ 0-100 %
*) Adjustable ow rate
Supply air fan ................... MIN
Exhaust air fan ................. MIN
Energy recovery ............... 0-100 %
Extract air damper ............ open
Recirculation damper ....... closed
Heating/cooling ................ 0-100 %
*)
*)
AQAir quality
This is the operating mode for demand-controlled ventilation of the room.
The room temperature set value day is active. Depending on the temperature conditions, the system continuously controls:
■ the energy recovery
■ the heating/cooling
Depending on the room air quality, the system operates in one of the
following operating states:
AQ_REC
■ Air quality Recirculation:
When air quality is good, the unit heats or cools in recirculation
operation.
AQ_ECO
■ Air quality Mixed air:
When ventilation requirements are medium, the unit heats or cools in
mixed air operation. The supply/exhaust air volume is based on the air
quality.
AQ_VE
■ Air quality Ventilation:
When ventilation requirements are high, the unit heats or cools in pure
ventilation operation. The supply/exhaust air volume is based on the air
quality.
Like REC
Supply air fan ................... MIN-MAX
Exhaust air fan ................. MIN-MAX
Energy recovery ............... 0-100 %
Extract air damper ............ 50 %
Recirculation damper ....... 50 %
Heating/cooling ................ 0-100 %
Supply air fan ................... MIN-MAX
Exhaust air fan ................. MIN-MAX
Energy recovery ............... 0-100 %
Extract air damper ............ open
Recirculation damper ....... closed
Heating/cooling ................ 0-100 %
Art.No. 4 214 745-en-04 / Page 8
RoofVent® RH | RC | RHC | R
Construction and operation
CodeOperating modeDescription
RECRecirculation
On/Off recirculation operation with TempTronic algorithm: During heat
or cool demand, the unit draws in room air, heats or cools it and blows it
back into the room. The room temperature set value day is active. The
ow rate is controlled in 2 stages.
EAExhaust air
The unit extracts spent room air. There is no room temperature control.
Unltered fresh air enters the room through open windows and doors or
another system provides air supply.
SASupply air
The unit blows fresh air into the room. The room temperature set value
day is active. Depending on the temperature conditions, the system
controls the heating/cooling.
Spent room air passes through open windows and doors or another
system provides extraction.
Supply air fan ................... 0 / Speed 1 / Speed 2
Exhaust air fan ................. off
Energy recovery ............... 0 %
Extract air damper ............ closed
Recirculation damper ....... open
Heating/cooling ................ on
*) Depending on heat or cool demand
Supply air fan ................... Off
Exhaust air fan ................. on
Energy recovery ............... 0 %
Extract air damper ............ open
Recirculation damper ....... closed
Heating/cooling ................ off
*) Adjustable ow rate
Supply air fan ................... on
Exhaust air fan ................. off
Energy recovery ............... 0 %
Extract air damper ............ open
Recirculation damper ....... closed
Heating/cooling ................ 0-100 %
*) Adjustable ow rate
**) Fresh air and bypass dampers are open
*)
*)
*)
*)
**)
STStandby
The unit is normally switched off.
The following functions remain active:
CPR
■ Cooling protection:
If the room temperature drops below the set value for cooling protection, the unit heats up the room in recirculation operation.
OPR
■ Overheating protection:
If the room temperature rises above the set value for overheating
protection, the unit cools down the room in recirculation operation. If
the temperatures also permit fresh air cooling, the units automatically
switches to night cooling (NCS) to save energy.
NCS
■ Night cooling:
If the room temperature exceeds the set value for night cooling and
the current fresh air temperature permits it, the unit blows cool fresh air
into the room and extracts warmer room air.
L_OFFOff (local operating mode)
The unit is switched off. Frost protection remains active.
–Forced heating
The unit draws in room air, warms it and blows it back into the room.
Forced heating is activated by inserting a wire jumper in the control
block. For example, it is suitable for heating the hall before taking the
control system into operation or if the controller fails during the heating
period. Connecting a room thermostat makes it possible to specify a room
temperature set value.
Supply air fan ................... MAX
Exhaust air fan ................. off
Energy recovery ............... 0 %
Extract air damper ............ closed
Recirculation damper ....... open
Heating/cooling ................ on
Supply air fan ................... on
Exhaust air fan ................. on
Energy recovery ............... 0 %
Extract air damper ............ open
Recirculation damper ....... closed
Heating/cooling ................ off
*) Adjustable ow rate
Supply air fan ................... Off
Exhaust air fan ................. off
Energy recovery ............... 0 %
Extract air damper ............ closed
Recirculation damper ....... open
Heating/cooling ................ off
Supply air fan ................... MAX
Exhaust air fan ................. off
Energy recovery ............... 0 %
Extract air damper ............ closed
Recirculation damper ....... open
Heating ............................ on
*)
*)
Table 1: Operating modes of the RoofVent® units
Art.No. 4 214 745-en-04 / Page 9
RoofVent® RH | RC | RHC | R
Unit type reference
4 Unit type reference
RHC - 9 B C - RX / ST . -- / V0 . D1 . LU / AF . SI / Y . KP . -- . SD / TC . EM . PH . RF / S---
Unit type
RoofVent
Unit size
6 or 9
Heating section
- without heating section
B with coil type B
C with coil type C
D with coil type D
Heating/cooling section
- without heating/cooling section
C with coil type C
D with coil type D
Heat recovery
RX Temperature efciency ErP 2018
Design
ST Standard
OE Oil-proof design
HA Design for high extract air humidity
KG Corrosion-protected design
KA Corrosion-protected design for high extract air humidity
®
RH | RC | RHC | R
Reserve
Connection module
V0 Standard
V1 Length + 250 mm
V2 Length + 500 mm
V3 Length + 1000 mm
Air outlet
D1 Design with 1 Air-Injector
D2 Design with 2 Air-Injectors
D0 Design without Air-Injector
Paint nish
- without
LU Paint nish of below-roof unit
Art.No. 4 214 745-en-04 / Page 10
RoofVent® RH | RC | RHC | R
Unit type reference
RHC - 9 B C - RX / ST . -- / V0 . D1 . LU / AF . SI / Y . KP . -- . SD / TC . EM . PH . RF / S---
Silencers outside
- without
A- Fresh air silencer
-F Exhaust air silencer
AF Fresh air and exhaust air silencer
Silencers inside
- without
SI Supply air and extract air silencer
Hydraulics
- without
Y Hydraulic assembly diverting system
M Mixing valve
Condensate pump
- without
KP Condensate pump
Socket
- without
SD Socket in the unit
CH Socket in the unit Switzerland
Control system
TC TopTronic
Energy monitoring
- without
EM Energy monitoring
Pump control
- without
PH Heating pump
PK Heating or cooling pump
PP Heating pump and cooling pump
Return temperature sensor
- without
RF Return temperature sensor
®
C
Special project
Marking for customer-specic adaptations
Table 2: Unit type reference
Art.No. 4 214 745-en-04 / Page 11
RoofVent® RH | RC | RHC | R
Technical data
5 Technical data
5.1 Application limits
Extract air temperaturemax.50 °C
Extract air relative humiditymax.60 %
Moisture content of extract airmax.12.5 g/kg
Fresh air temperaturemin.-30 °C
Temperature of the heating mediummax.90 °C
Pressure of the heating/cooling mediummax.800 kPa
Supply air temperaturemax.60 °C
Air ow rate Size 6:
Size 9:
Condensate quantity Size 6:
Size 9:
Table 3: Application limits
min.
min.
max.
max.
3100
5000
90
150
m³/h
m³/h
kg/h
kg/h
5.2 Heat recovery system (HRS)
Unit size69
Temperature efciency, dry%7778
Temperature efciency, wet%8990
Table 4: Thermal transfer level of the plate heat exchanger
5.3 Air filtration
FilterFresh airExtract air
Class acc. to ISO 16890ePM
Class acc. to EN 779F7M5
Factory setting of differential pressure switches250 Pa250 Pa
Table 5: Air ltration
55 % ePM10 65 %
1
Art.No. 4 214 745-en-04 / Page 12
RoofVent® RH | RC | RHC | R
Technical data
5.4 Flow rate, product parameters
Unit size69
Nominal air ow ratem³/h55008000
m³/s1.532.22
Floor area reachedm²480797
Specic fan power SFP
Face velocitym/s2.692.98
Static efciency of the fans%6263
Internal pressure drop of ventilation
components
Maximum leakage rate
int
Fresh air/supply airPa270268
Extract air/exhaust air Pa300316
External%0.450.25
Internal%1.501.20
W/(m³/s)
920940
Unit typeRH-6RH-9
Coil typeBCBCD
Nominal external
pressure
Effective electric power inputkW2.01 2.09 3.10 3.24 3.34
Unit typeRC-6RC-9
Coil typeCCD
Nominal external
pressure
Effective electric power inputkW2.183.383.49
Unit typeRHC-6RHC-9
Coil typeBCCCBCBDCCCDDCDD
Nominal external
pressure
Effective electric power inputkW2.27 2.33 2.90 3.60 3.63 3.74 3.74 3.98
Unit typeR-6R-9
Nominal external
pressure
Effective electric power inputkW1.932.99
Supply airPa220 180 300 260 230
Extract airPa190 190 300 300 300
Supply airPa110220190
Extract airPa190300300
Supply airPa8050 170 140 130 100 10040
Extract airPa190 190 300 300 300 300 300 300
Supply airPa260330
Extract airPa190300
Table 6: Technical data of the RoofVent® units
Art.No. 4 214 745-en-04 / Page 13
RoofVent® RH | RC | RHC | R
Technical data
5.5 Heat output
UnitQQ
TG
H
max
t
∆p
S
SizeTypekWkWm°CkPal/h
6
B30.319.716.028.751300
C50.039.511.639.362150
B43.228.816.428.741856
9
C73.859.511.740.163172
D91.076.610.546.463908
Legend:Type = Type of coil
Q = Coil heat output
= Output to cover fabric heat losses
Q
TG
= Maximum mounting height
H
max
= Supply air temperature
t
S
= Water pressure drop
∆p
W
= Water quantity
m
W
Reference:Fresh air: -15 °C
Room air: 18 °C
Extract air: 20 °C / 20 % rel. humidity
Heating medium: 60/40 °C
®
Fig. 4: Heat output of the RoofVent
RH / RC / RHC
W
m
W
Art.No. 4 214 745-en-04 / Page 14
RoofVent® RH | RC | RHC | R
Technical data
5.6 Cooling capacities
UnitQ
sen
Q
Q
tot
TG
t
∆p
S
W
SizeTypekWkWkW°CkPal/hkg/h
6C24.534.519.115.739494314.7
9
Legend:Type = Type of coil
Reference:Fresh air: 32 °C / 40 % rel. humidity
Fig. 5: Cooling capacity of RoofVent
C36.049.628.215.536710520.0
D44.266.636.412.540954233.0
= Sensible cooling capacity
Q
sen
= Total cooling capacity
Q
tot
= Output for coverage of transmission sensible gains (→ sensible cooling load)
Q
TG
= Supply air temperature
t
S
= Water pressure drop
∆p
W
= Water quantity
m
W
= Condensate quantity
m
C
Room air: 26 °C
Extract air: 28 °C / 50 % rel. humidity
Cooling medium: 6/12 °C
®
RC / RHC
m
m
W
C
Art.No. 4 214 745-en-04 / Page 15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.