Hoval RoofVent RH, RoofVent RC, RoofVent RHC, RoofVent R Original Operating Manual

RoofVent® RH | RC | RHC | R
Original operating manual
RoofVent® RH
®
RoofVent
RoofVent
RoofVent
RC
®
RHC
®
R
RoofVent® RH | RC | RHC | R
1 Use 3
1.1 Intended use 3
1.2 User group 3
2 Safety 4
2.1 Symbols 4
2.2 Operational safety 4
3 Construction and operation 5
3.1 Construction 5
3.2 Air distribution with the Air-Injector 5
3.3 Function diagram 7
3.4 Operating modes 8
4 Unit type reference 10
5 Technical data 12
5.1 Application limits 12
5.2 Heat recovery system (HRS) 12
5.3 Air ltration 12
5.4 Flow rate, product parameters 13
5.5 Heat output 14
5.6 Cooling capacities 15
5.7 Dimensions and weights of the RoofVent
5.8 Dimensions and weights of the RoofVent
5.9 Dimensions and weights of the RoofVent
5.10 Dimensions and weights of the RoofVent
®
RH 16
®
RC 18
®
RHC 20
®
R 22
7 Transport and installation 29
7.1 Delivery 29
7.2 Requirements for the installation site 31
7.3 Installation 32
7.4 Connecting air ducts and Air-Injectors 38
7.5 Hydraulic installation 39
7.6 Condensate connection 40
7.7 Electrical installation 42
8 Operation 43
8.1 Initial commissioning 43
8.2 Operation 43
9 Maintenance and repair 44
9.1 Safety 44
9.2 Maintenance 45
9.3 Repair 47
10 Dismantling 47
11 Disposal 47
6 Options 24
6.1 Oil-proof design 24
6.2 Design for high extract air humidity 24
6.3 Corrosion-protected design 24
6.4  Corrosion-protected design for high extract air humidity 24
6.5 Connection module 25
6.6 Design with 2 Air-Injectors 25
6.7 Design without Air-Injector 25
6.8 Paint nish of below-roof unit 25
6.9 Fresh air silencer 26
6.10 Exhaust air silencer 26
6.11 Supply air and extract air silencers 27
6.12 Hydraulic assembly diverting system 27
6.13 Mixing valve 27
6.14 Condensate pump 27
6.15 Socket 28
6.16 Energy monitoring 28
6.17 Return temperature sensor 28
6.18  Pump control for mixing or injection system 28
RoofVent® RH | RC | RHC | R
Use

1 Use

1.1 Intended use

RoofVent® units are supply and extract air handling units for use in tall, single-oor halls. They have the following functions:
Fresh air supply
Extract air removal
Energy recovery with highly efcient plate heat exchanger
Filtering of the fresh air and the extract air
Air distribution with adjustable Air-Injector
Additional functions depending on unit type:
Heating (with connection to a hot water supply)
Cooling (with connection to a water chiller)
®
A system usually consists of several RoofVent uted throughout the hall roof. The individual units are regulated individually and controlled based on zones. The system exibly adjusts to local requirements.
®
RoofVent relating to environmentally friendly design of ventilation systems. They are systems of the 'non-residential ventilation unit' (NRVU) and 'bidirectional ventila­tion unit' (BVU) type.
Intended use also includes compliance with the operating instructions. Any usage over and above this use is considered to be not as intended. The manufacturer can accept no liability for damage resulting from improper use.
units comply with all the requirements of the Ecodesign Directive
units. These are installed distrib-

1.2 User group

The units are only allowed to be installed, operated and maintained by authorised and instructed personnel who are well acquainted with the units and are informed about possible dangers. The operating instructions are for operating engineers and technicians as well as specialists in building, heating and ventilation technology.
RoofVent® RH | RC | RHC | R
Safety

2 Safety

2.1 Symbols

Caution
This symbol warns against risk of injury. Please heed all instructions desig­nated by this symbol to prevent injuries and/or death.
Attention
This symbol warns against property damage. Please heed the respective instructions to prevent risk of damage to the unit and its functions.
Notice
This symbol denotes information about the economic use of the equipment or special tips.

2.2 Operational safety

The unit is built to conform to the state-of-the-art and is operationally safe. Despite every precaution being taken, potential and not immediately obvious risks always remain, for example:
Dangers when working with the electrical system
Parts (e.g. tools) can fall down below when working on the ventilation unit.
Dangers from working on the roof
Damage to devices or components due to lightning
Malfunctions as a result of defective parts
Hazards from hot water when working on the hot water supply
Water penetration through the roof unit if the access panels are not closed
correctly
Therefore:
Please read the operating instructions before unpacking, installing, commis-
sioning and before maintaining the equipment.
Store the operating instructions so that they are easily accessible.
Observe any attached information and warning signs.
Immediately replace damaged or removed informational and warning signs.
Follow the local safety and accident prevention regulations at all times.
When working in the unit, take precautions against unprotected, sharp metal
edges.
The unit may only be installed, operated and serviced by authorised, trained
and instructed skilled personnel:
Specialists as dened by these operating instructions are those persons
who, based on their training, knowledge and experience as well as their knowledge of the relevant regulations and guidelines, can carry out the work assigned to them and recognise potential hazards.
Unauthorised reconguration or modication of the unit is not permitted.
a
b
d
c
RoofVent® RH | RC | RHC | R
Construction and operation

3 Construction and operation

3.1 Construction

RoofVent® units consist of the following components:
Roof unit with energy recovery
Below-roof unit
The components are bolted together and can be dismantled. The connections of the coil are located under the extract air grille as standard. The heating/cooling section can also be mounted on the connection module turned round.

3.2 Air distribution with the Air-Injector

The patented air distributor – called the Air-Injector – is the core element. The air discharge angle is set by means of the innitely variable guide vanes. It depends on the air ow rate, the mounting height and the temperature difference between the supply air and room air. The air is therefore blown into the room vertically downward, conically or horizontally. This ensures that:
®
with each RoofVent
unit a large area of the hall can be reached,
the occupied area is draught-free,
the temperature stratication in the room is reduced, thus saving energy.
Roof unit with energy recovery
Below-roof unit
a Connection module b Heating section (RoofVent c Cooling section (RoofVent d Air-Injector
Fig. 1: Components of RoofVent® units
®
RH, RHC only)
®
RC, RHC only)
RoofVent® RH | RC | RHC | R
Construction and operation
Condensate separator
®
(RoofVent
RC, RHC only)
Cooling coil
®
(RoofVent
RC, RHC only)
Heating coil
®
(RoofVent
RH, RHC only)
Access panel, coil
Access panel, connection box
Supply air fans
Supply air access door
Control block
Exhaust air access door
Exhaust air fans
Plate heat exchanger with bypass (for performance control and as recirculation bypass)
Fresh air damper with actuator
Bypass damper with actuator
Fresh air lter
Fresh air access door
Extract air and recirculation dampers with actuator
Extract air access door
Extract air lter
Extract air grille
Frost controller
®
(RoofVent
RH, RC, RHC only)
Condensate connection
®
(RoofVent
RC, RHC only)
Actuator of the Air-Injector
Fig. 2: Structure of the RoofVent® units
RoofVent® RH | RC | RHC | R
Construction and operation

3.3 Function diagram

Fresh air
Fresh air lter with differential pressure switch
Temperature sensor air inlet ER (optional)
Bypass damper with actuator
Exhaust air temperature sensor
Exhaust air fans with ow rate monitoring
Exhaust air
Fresh air damper with actuator
Plate heat exchanger
Extract air temperature sensor
Extract air damper with actuator
Recirculation damper (opposed to the extract air damper)
Fig. 3: Function diagram
Temperature sensor air outlet ER (optional)
Extract air lter with differential pressure switch
Supply air fans with ow rate monitoring
Extract air
Heating coil (RoofVent® RH, RHC only)
Frost controller (RoofVent® RH, RC, RHC only)
Cooling coil (RoofVent® RC, RHC only)
Condensate separator (RoofVent® RC, RHC only)
Air-Injector with actuator
Supply air sensor
Supply air
RoofVent® RH | RC | RHC | R
Construction and operation

3.4 Operating modes

The units have the following operating modes:
Ventilation
Ventilation (reduced)
Air quality
Recirculation (
The TopTronic
depending on unit type
®
C control system regulates these operating modes automatically for each control zone in accordance with the specications in the calendar. The following points also apply:
The operating mode of a control zone can be switched over manually.
®
Each RoofVent
unit can operate individually in a local operating mode: Off,
Recirculation, Supply air, Exhaust air, Ventilation.
Code Operating mode Description
VE Ventilation
The unit blows fresh air into the room and exhausts polluted room air. The room temperature set value day is active. Depending on the temperature conditions, the system continuously controls:
the energy recovery
the heating/cooling
VEL Ventilation (reduced)
As VE, but the unit only operates with the set minimum values for the supply and exhaust air volumes
Exhaust air
Supply air
Standby
)
Forced heating
Supply air fan ................... on
Exhaust air fan ................. on
Energy recovery ............... 0-100 %
Extract air damper ............ open
Recirculation damper ....... closed
Heating/cooling ................ 0-100 %
*) Adjustable ow rate
Supply air fan ................... MIN
Exhaust air fan ................. MIN
Energy recovery ............... 0-100 %
Extract air damper ............ open
Recirculation damper ....... closed
Heating/cooling ................ 0-100 %
*)
*)
AQ Air quality
This is the operating mode for demand-controlled ventilation of the room. The room temperature set value day is active. Depending on the tempera­ture conditions, the system continuously controls:
the energy recovery
the heating/cooling
Depending on the room air quality, the system operates in one of the following operating states:
AQ_REC
Air quality Recirculation:
When air quality is good, the unit heats or cools in recirculation operation.
AQ_ECO
Air quality Mixed air:
When ventilation requirements are medium, the unit heats or cools in mixed air operation. The supply/exhaust air volume is based on the air quality.
AQ_VE
Air quality Ventilation:
When ventilation requirements are high, the unit heats or cools in pure ventilation operation. The supply/exhaust air volume is based on the air quality.
Like REC
Supply air fan ................... MIN-MAX
Exhaust air fan ................. MIN-MAX
Energy recovery ............... 0-100 %
Extract air damper ............ 50 %
Recirculation damper ....... 50 %
Heating/cooling ................ 0-100 %
Supply air fan ................... MIN-MAX
Exhaust air fan ................. MIN-MAX
Energy recovery ............... 0-100 %
Extract air damper ............ open
Recirculation damper ....... closed
Heating/cooling ................ 0-100 %
RoofVent® RH | RC | RHC | R
Construction and operation
Code Operating mode Description
REC Recirculation
On/Off recirculation operation with TempTronic algorithm: During heat or cool demand, the unit draws in room air, heats or cools it and blows it back into the room. The room temperature set value day is active. The
ow rate is controlled in 2 stages.
EA Exhaust air
The unit extracts spent room air. There is no room temperature control.
Unltered fresh air enters the room through open windows and doors or
another system provides air supply.
SA Supply air
The unit blows fresh air into the room. The room temperature set value day is active. Depending on the temperature conditions, the system controls the heating/cooling. Spent room air passes through open windows and doors or another system provides extraction.
Supply air fan ................... 0 / Speed 1 / Speed 2
Exhaust air fan ................. off
Energy recovery ............... 0 %
Extract air damper ............ closed
Recirculation damper ....... open
Heating/cooling ................ on
*) Depending on heat or cool demand
Supply air fan ................... Off
Exhaust air fan ................. on
Energy recovery ............... 0 %
Extract air damper ............ open
Recirculation damper ....... closed
Heating/cooling ................ off
*) Adjustable ow rate
Supply air fan ................... on
Exhaust air fan ................. off
Energy recovery ............... 0 %
Extract air damper ............ open
Recirculation damper ....... closed
Heating/cooling ................ 0-100 %
*) Adjustable ow rate **) Fresh air and bypass dampers are open
*)
*)
*)
*)
**)
ST Standby
The unit is normally switched off. The following functions remain active:
CPR
Cooling protection:
If the room temperature drops below the set value for cooling protec­tion, the unit heats up the room in recirculation operation.
OPR
Overheating protection:
If the room temperature rises above the set value for overheating protection, the unit cools down the room in recirculation operation. If the temperatures also permit fresh air cooling, the units automatically switches to night cooling (NCS) to save energy.
NCS
Night cooling:
If the room temperature exceeds the set value for night cooling and the current fresh air temperature permits it, the unit blows cool fresh air into the room and extracts warmer room air.
L_OFF Off (local operating mode)
The unit is switched off. Frost protection remains active.
Forced heating
The unit draws in room air, warms it and blows it back into the room. Forced heating is activated by inserting a wire jumper in the control block. For example, it is suitable for heating the hall before taking the control system into operation or if the controller fails during the heating period. Connecting a room thermostat makes it possible to specify a room temperature set value.
Supply air fan ................... MAX
Exhaust air fan ................. off
Energy recovery ............... 0 %
Extract air damper ............ closed
Recirculation damper ....... open
Heating/cooling ................ on
Supply air fan ................... on
Exhaust air fan ................. on
Energy recovery ............... 0 %
Extract air damper ............ open
Recirculation damper ....... closed
Heating/cooling ................ off
*) Adjustable ow rate
Supply air fan ................... Off
Exhaust air fan ................. off
Energy recovery ............... 0 %
Extract air damper ............ closed
Recirculation damper ....... open
Heating/cooling ................ off
Supply air fan ................... MAX
Exhaust air fan ................. off
Energy recovery ............... 0 %
Extract air damper ............ closed
Recirculation damper ....... open
Heating ............................ on
*)
*)
Table 1: Operating modes of the RoofVent® units
RoofVent® RH | RC | RHC | R
Unit type reference

4 Unit type reference

RHC - 9 B C - RX / ST . -- / V0 . D1 . LU / AF . SI / Y . KP . -- . SD / TC . EM . PH . RF / S---
Unit type
RoofVent
Unit size
6 or 9
Heating section
- without heating section B with coil type B C with coil type C D with coil type D
Heating/cooling section
- without heating/cooling section C with coil type C D with coil type D
Heat recovery
RX Temperature efciency ErP 2018
Design
ST Standard OE Oil-proof design HA Design for high extract air humidity KG Corrosion-protected design KA Corrosion-protected design for high extract air humidity
®
RH | RC | RHC | R
Reserve
Connection module
V0 Standard V1 Length + 250 mm V2 Length + 500 mm V3 Length + 1000 mm
Air outlet
D1 Design with 1 Air-Injector D2 Design with 2 Air-Injectors D0 Design without Air-Injector
Paint nish
- without LU Paint nish of below-roof unit
Art.No. 4 214 745-en-04 / Page 10
RoofVent® RH | RC | RHC | R
Unit type reference
RHC - 9 B C - RX / ST . -- / V0 . D1 . LU / AF . SI / Y . KP . -- . SD / TC . EM . PH . RF / S---
Silencers outside
- without A- Fresh air silencer
-F Exhaust air silencer AF Fresh air and exhaust air silencer
Silencers inside
- without SI Supply air and extract air silencer
Hydraulics
- without Y Hydraulic assembly diverting system M Mixing valve
Condensate pump
- without KP Condensate pump
Socket
- without SD Socket in the unit CH Socket in the unit Switzerland
Control system
TC TopTronic
Energy monitoring
- without EM Energy monitoring
Pump control
- without PH Heating pump PK Heating or cooling pump PP Heating pump and cooling pump
Return temperature sensor
- without RF Return temperature sensor
®
C
Special project
Marking for customer-specic adaptations
Table 2: Unit type reference
Art.No. 4 214 745-en-04 / Page 11
RoofVent® RH | RC | RHC | R
Technical data

5 Technical data

5.1 Application limits

Extract air temperature max. 50 °C
Extract air relative humidity max. 60 %
Moisture content of extract air max. 12.5 g/kg
Fresh air temperature min. -30 °C
Temperature of the heating medium max. 90 °C
Pressure of the heating/cooling medium max. 800 kPa
Supply air temperature max. 60 °C
Air ow rate Size 6:
Size 9:
Condensate quantity Size 6:
Size 9:
Table 3: Application limits
min. min.
max. max.
3100 5000
90
150
m³/h m³/h
kg/h kg/h

5.2 Heat recovery system (HRS)

Unit size 6 9
Temperature efciency, dry % 77 78
Temperature efciency, wet % 89 90
Table 4: Thermal transfer level of the plate heat exchanger

5.3 Air filtration

Filter Fresh air Extract air
Class acc. to ISO 16890 ePM
Class acc. to EN 779 F7 M5
Factory setting of differential pressure switches 250 Pa 250 Pa
Table 5: Air ltration
55 % ePM10 65 %
1
Art.No. 4 214 745-en-04 / Page 12
RoofVent® RH | RC | RHC | R
Technical data

5.4 Flow rate, product parameters

Unit size 6 9
Nominal air ow rate m³/h 5500 8000
m³/s 1.53 2.22
Floor area reached 480 797
Specic fan power SFP
Face velocity m/s 2.69 2.98
Static efciency of the fans % 62 63
Internal pressure drop of ventilation components
Maximum leakage rate
int
Fresh air/supply air Pa 270 268
Extract air/exhaust air Pa 300 316
External % 0.45 0.25
Internal % 1.50 1.20
W/(m³/s)
920 940
Unit type RH-6 RH-9
Coil type B C B C D
Nominal external pressure
Effective electric power input kW 2.01 2.09 3.10 3.24 3.34
Unit type RC-6 RC-9
Coil type C C D
Nominal external pressure
Effective electric power input kW 2.18 3.38 3.49
Unit type RHC-6 RHC-9
Coil type BC CC BC BD CC CD DC DD
Nominal external pressure
Effective electric power input kW 2.27 2.33 2.90 3.60 3.63 3.74 3.74 3.98
Unit type R-6 R-9
Nominal external pressure
Effective electric power input kW 1.93 2.99
Supply air Pa 220 180 300 260 230
Extract air Pa 190 190 300 300 300
Supply air Pa 110 220 190
Extract air Pa 190 300 300
Supply air Pa 80 50 170 140 130 100 100 40
Extract air Pa 190 190 300 300 300 300 300 300
Supply air Pa 260 330
Extract air Pa 190 300
Table 6: Technical data of the RoofVent® units
Art.No. 4 214 745-en-04 / Page 13
RoofVent® RH | RC | RHC | R
Technical data

5.5 Heat output

Unit Q Q
TG
H
max
t
∆p
S
Size Type kW kW m °C kPa l/h
6
B 30.3 19.7 16.0 28.7 5 1300
C 50.0 39.5 11.6 39.3 6 2150
B 43.2 28.8 16.4 28.7 4 1856
9
C 73.8 59.5 11.7 40.1 6 3172
D 91.0 76.6 10.5 46.4 6 3908
Legend: Type = Type of coil
Q = Coil heat output
= Output to cover fabric heat losses
Q
TG
= Maximum mounting height
H
max
= Supply air temperature
t
S
= Water pressure drop
∆p
W
= Water quantity
m
W
Reference: Fresh air: -15 °C
Room air: 18 °C Extract air: 20 °C / 20 % rel. humidity Heating medium: 60/40 °C
®
Fig. 4: Heat output of the RoofVent
RH / RC / RHC
W
m
W
Art.No. 4 214 745-en-04 / Page 14
RoofVent® RH | RC | RHC | R
Technical data

5.6 Cooling capacities

Unit Q
sen
Q
Q
tot
TG
t
∆p
S
W
Size Type kW kW kW °C kPa l/h kg/h
6 C 24.5 34.5 19.1 15.7 39 4943 14.7
9
Legend: Type = Type of coil
Reference: Fresh air: 32 °C / 40 % rel. humidity
Fig. 5: Cooling capacity of RoofVent
C 36.0 49.6 28.2 15.5 36 7105 20.0
D 44.2 66.6 36.4 12.5 40 9542 33.0
= Sensible cooling capacity
Q
sen
= Total cooling capacity
Q
tot
= Output for coverage of transmission sensible gains (→ sensible cooling load)
Q
TG
= Supply air temperature
t
S
= Water pressure drop
∆p
W
= Water quantity
m
W
= Condensate quantity
m
C
Room air: 26 °C Extract air: 28 °C / 50 % rel. humidity Cooling medium: 6/12 °C
®
RC / RHC
m
m
W
C
Art.No. 4 214 745-en-04 / Page 15
Loading...
+ 33 hidden pages