Hoval BioLyt 50, BioLyt 70, BioLyt 110, BioLyt 130, BioLyt 150 Operating Instructions Manual

...
United Kingdom
Hoval Ltd. Northgate Newark Nottinghamshire NG24 1JN Phone +44 1636 67 27 11 Fax +44 1636 67 35 32
Hoval Aktiengesellschaft Austrasse 70 9490 Vaduz Principality of Liechtenstein Phone +423 399 24 00 Fax +423 399 24 11
Subject to modifi cations |
EN
Operating Instructions
BioLyt (50,70,75) BioLyt (100,110,130,150,160)
Wood pellet boiler
4 212 945 / 00 - 04/14
Figure: BioLyt (100-160)
Figure: BioLyt (50-75)
4 212 945 / 00
2
Table of contents
1. Information about your heating system ............................................................................. 4
1.1 Fuel quality / pellet delivery ................................................................................................................... 4
1.1.1 Fuel quality ................................................................................................................................................ 4
1.1.2 Pellet delivery ............................................................................................................................................ 4
1.2 Important addresses and telephone numbers ..................................................................................... 4
1.3 BioLyt (50-160) wood pellet boiler ......................................................................................................... 4
2. Important information .......................................................................................................... 5
2.1 Key to symbols used .............................................................................................................................. 5
2.2 Safety information ................................................................................................................................... 5
2.3 Entering the pellet storage room, storage tank ....................................................................................5
2.4 Cautionary notes ..................................................................................................................................... 6
3. Functional principle of the heating system ....................................................................... 7
3.1 What happens inside the BioLyt? ......................................................................................................... 9
3.2 How are the pellets extracted and conveyed from the storage room? ............................................ 10
4. Heating system control ..................................................................................................... 11
4.1 What is the function of the boiler controller TopTronic® T ................................................................. 11
4.2 How you can save energy ....................................................................................................................11
4.3 Basic display ......................................................................................................................................... 11
4.4 Operating and display elements .......................................................................................................... 12
4.4.1 Function of the operating elements ......................................................................................................... 12
4.4.2 Basic procedure for changing settings .................................................................................................... 12
4.4.3 What to do if ... ........................................................................................................................................13
4.4.4 Control elements on the boiler control panel ........................................................................................... 14
4.5 Main settings ......................................................................................................................................... 16
4.5.1 Changing the room temperature ............................................................................................................. 16
4.5.1.1 Setting the desired room temperature, day ................................................................................................................16
4.5.1.2 Setting the desired reduced (night-time) temperature ...............................................................................................17
4.6 Operating modes ................................................................................................................................... 18
4.6.1 Function of the operating modes ............................................................................................................. 18
4.6.2 Operating modes for holiday and absence? ............................................................................................ 19
4.6.3 Changing the operating mode - for "HOLIDAY TIL," "ABSENT TIL" and "PARTY TIL" ............................20
4.6.4 Changing the operating mode - for "AUTOMATIC," "SUMMER," "HEATING," "RED. HEATING" and
"STANDBY" ............................................................................................................................................. 21
4.7 Switching times (heating times) .......................................................................................................... 22
4.7.1 Standard heating times ........................................................................................................................... 22
4.7.2 Table for recording individual switching times .........................................................................................22
4.7.3 Changing the switching times (heating times) .........................................................................................23
4.7.4 Copying switching times .......................................................................................................................... 26
4.8 Heating curve ........................................................................................................................................ 28
4.8.1 Heating curve (heating characteristic curve) ........................................................................................... 28
4.8.2 Changing the heating curve (heating characteristic curve) ..................................................................... 29
4.9 Hot water ................................................................................................................................................ 30
4.9.1 Setting the domestic hot water temperature ...........................................................................................30
4.9.2 Manual DHW re-charging ........................................................................................................................ 31
4.9.3 Domestic hot water economy temperature (reduced temperature) ......................................................... 32
4.10 Further settings ..................................................................................................................................... 34
4.10.1 Setting the clock ...................................................................................................................................... 34
4.10.2 Setting the date ....................................................................................................................................... 35
4.10.3 Changing between summer and winter time ........................................................................................... 35
4.10.4 Setting the language ............................................................................................................................... 36
4.10.5 Reloading the standard switching times program - Deleting your own time program ............................. 37
4.10.6 Manual operation ................................................................................................................................... 39
4 212 945 / 00
3
Table of contents
4.11 System information ............................................................................................................................... 40
4.11.1 Information key for system temperatures and heating circuit information ............................................... 40
4.11.2 Information on the boiler status ............................................................................................................... 41
4.11.3 Displaying and resetting the consumption meters and cleaning messages ............................................ 43
4.11.4 Changing off-periods for the extraction system ....................................................................................... 46
4.11.5 Special symbols ...................................................................................................................................... 49
4.11.6 Maintenance message ............................................................................................................................ 49
4.11.7 Optional accessories ...............................................................................................................................50
5. Fault repair.......................................................................................................................... 51
5.1 Blocking switch and reset button ........................................................................................................ 51
5.2 Display of heating regulator alarms .................................................................................................... 51
5.3 Display of boiler controller alarms ...................................................................................................... 51
5.4 Overview of alarms, heating regulator TopTronic®T ........................................................................... 52
5.5 Overview of alarms, boiler controller .................................................................................................. 54
5.6 Checklist in case of faults .................................................................................................................... 55
6. Checking the water level ................................................................................................... 56
7. Maintenance BioLyt (50-75) ............................................................................................... 57
7.1 Commissioning ..................................................................................................................................... 57
7.2 Regular checks ...................................................................................................................................... 57
7.3 Cleaning the boiler ................................................................................................................................ 57
8. Maintenance BioLyt (100-160) ........................................................................................... 60
8.1 Commissioning ..................................................................................................................................... 60
8.2 Regular checks ...................................................................................................................................... 60
8.3 Cleaning the boiler ................................................................................................................................ 60
9. Emptying the ash box and resetting the counter ............................................................ 63
9.1 Resetting the message "empty ash box" (W:40)................................................................................63
10. How you can save energy ................................................................................................. 64
11. Instructions on proper disposal of individual system components ............................. 64
4 212 945 / 00
4
Information about your heating system
1. Information about your hea­ting system
Dear heating system owner, With the purchase of this Hoval BioLyt (50-160) wood pellet boiler, you have made an excellent cho­ice. It offers you all the advantages of a modern and efficient heating system.
Please read these instructions carefully. They de­scribe how the boiler works, how it is operated and serviced.
Further information can be obtained from our Sales and Service Centres. (See last page for contact de­tails).
1.1 Fuel quality / pellet delivery
1.1.1 Fuel quality
The BioLyt (50-160) wood pellet boiler has been de­signed for optimum combustion of wood pellets. The pellets must meet the requirements of at least one of the standards listed below
• ÖNORM M 7135
• DIN 51731 / HP5 (DINplus)
• SN 166000
• EN 14961-2 / A1 (ENplus/A1)
Hoval recommends ENplus (Class A1):
1.1.2 Pellet delivery
• Do not fill the storage room until after initial com-
missioning of the boiler.
• Switch off the heating system as instructed 15
min. before filling the storage room.
• To measure pellet consumption since the last deli-
very, reset the counter "USAGE 1." You can mea­sure consumption over a specific period of time (e.g. annual consumption) by always resetting the counter on a specific date (e.g. January 1). For further information, see Chapter 4.11.03.
1.2 Important addresses and telephone numbers
Heating engineer _________________________
________________________________________
________________________________________
Plumber__________________________
________________________________________
________________________________________
Electrician__________________________
________________________________________
________________________________________
Master chimney sweep_________________________
________________________________________
________________________________________
1.3 BioLyt (50-160) wood pellet boiler
To be completed by the heating engineer:
Order No. / Manufacturing No.:_ ________________
Boiler type: _________________________________
Boiler power rating: _______________________ kW
Hot water buffer storage tank size (if present): _____
Calorifier size: ______________________________
Heating pump type: __________________________
Heating regulator type: _______________________
Mixing valves type:___________________________
Calculation basis for heating system
Lowest outside temperature: _________________ °C
Energy demand: _________________________ kW
Max. flow temperature: _____________________ °C
4 212 945 / 00
5
Important information
• Parents must keep their children away from the boiler room; the heating system is not a toy!
• Do not burn unsuitable fuel (see Chapter 1.1); otherwise, any pos­sible warranty claims will become invalid.
• Do not carry out any modifications to the system (possible danger to persons; possible loss of warranty).
2.3 Entering the pellet storage room, storage tank
Under unfavourable circumstances, an increased concentration of harmful gases (such as carbon mo­noxide) may occur in pellet storage rooms, possib­ly posing a risk when accumulating over a longer period of time. Despite the fact that under normal circumstances, there is no risk at all, the possibility of such a scenario cannot be ruled out.
• If work is being carried out in filled storage rooms,
a second person must always be present outside the room for safety reasons.
• The pellet storage room must always be thorough-
ly aerated before anyone enters it. The storage room must be ventilated for at least 15 minutes. In the case of pellet storage rooms with a volume of more than 10 t, the duration of ventilation must be extended or mechanical venti­lation provided.
• No-one should enter the storage room in the four
weeks following filling. If it is necessary for persons to enter the storage room, the room must be venti­lated for at least 2 hours before entering.
• It must be ensured that the storage room door
remains open while there are persons inside the storage room.
• Entering fuel storage rooms that have not been
aerated (particularly underground tanks) must be avoided, and only trained personnel is permitted to do so. Before entering the room or tank, the con­centration of CO must be measured (the concen­tration must be less than 30 ppm). If necessary, thoroughly aerate the storage room or tank before entering it.
2. Important information
2.1 Key to symbols used
Please pay particular attention to the following sym­bols used in this operating manual.
Failure to observe instructions to this effect can lead to danger to persons.
Failure to observe instructions to this effect can lead to malfunctions or da­mage to the boiler or the heating sys­tem.
i
The marked sections of text contain
information and tips on operating and running the system.
2.2 Safety information
(Information for the protection of persons)
• Caution Switch off the heating system as
instructed 15 min. before filling the storage room.
Press the blocking switch.
• Keep the air supply to the boiler room open:
Air inlets and outlets must not be
closed. It is important to ensure that the combustion air required for correct operation of the boiler can flow unhindered in order to protect operating personnel from an oxygen-depleted atmosphere.
• Do not operate the boiler with the doors or pellet hopper open (dan­ger of burn-back). In addition, any sparks emitted from the boiler could cause a fire.
• The system must be cleaned regu­larly, otherwise any possible war­ranty claims will become invalid.
4 212 945 / 00
6
Important information
• It the storage area is difficult to access or if it is ac­cessible only from above (as in the case of under­ground tanks), the person entering the tank must be additionally secured.
• Keep children away from the pellet storage area!
• If there are moving parts (worm conveyors) in the storage room, turn off the mains switch of the he­ating system before entering the storage room, as otherwise there is a risk of injury.
• Smoking, naked flames and other possible sour­ces of ignition are prohibited inside the storage room.
2.4 Cautionary notes
(Information on the protection of the heating system)
Checking the water level
Check the water level in the system at regular inter­vals (see Chapter 6).
Filling the heating system
The heating system can normally be filled and top­ped up with mains water. No chemical additives should be added to the water. The water quality can vary greatly in different parts of the country (you can obtain information about the water quality from your local water company), and it might not always be suitable for filling the heating system (highly corrosi­ve or very hard water).
Please contact your heating engineer in such cases (see also Technical Information).
Circulation pumps
During the periods when no heating is required, the circulation pumps should be operated for approx. 2 minutes at least once every month. This will prevent the pumps from seizing up.
Tightness / Burn-back protection
The doors and pellet hopper must be checked for leaks on an annual basis. Smoke leaks should be avoided in order to prevent any toxic low-temperatu­re gases from escaping into the boiler room. Moreo­ver, leaky doors or a faulty pellet hopper seal could cause the embers to burn back into the pellet burner. .
Operation and cleaning
Periodic cleaning and inspection by the heating en­gineer or Hoval customer service will not only extend the service life of the pellet boiler, but also increase its operating safety and ensure that a high combus­tion efficiency is maintained.
• In winter mode, the boilers must be cleaned ap­prox. every 2 weeks by means of the special tool supplied and a vacuum cleaner with ash retainer.
• Pellet storage rooms must be cleaned regularly (approx. every 3-4 years), and the sawdust which has accumulated must be disposed of!
• Large-scale pellet-fired systems must be monito­red on a daily basis when operated in winter at full load. The pellet storage rooms and discharge systems must also be checked for fault-free ope­ration and to ensure that the supply of pellets is sufficient.
Protecting the boiler
Do not use sprays, solvents, chlorine based clea­ning products, paint, adhesives etc. in the proximity of the boiler. These substances can cause corrosion inside the boiler and the flue gas system.
Pressure relief valve, backfire protection and thermal discharge safety device
The correct functioning of the various safety devices (pressure relief valve on the heating installation, backfire protection valve on the burner, pellet hop­per seal, thermal discharge safety device) must be checked periodically by the heating engineer.
The heating installation must be inspected regularly according to local regulations.
For Austria only
In Austria, with industrial plants exceeding 50 kW, the FAV ordinance for combustion plants must also be observed.
4 212 945 / 00
7
Functional principle of the heating system
3. Functional principle of the heating system
It is important that the perfectly coordinated individual components function properly to ensure that your home stays warm in winter.
FUNCTION:
Burns the pellets safely and in an environmentally fri­endly manner.. Extracts the heat from the combustion gases and transfers it to the heating water.
The process of combustion within the boiler converts the natural energy contained in the pellets into heat.
It is used for intermediate storage of hot heating wa- ter (max. 90°C). It thus compensates for any differen­ces between heat generation and demand.
Holds a reserve of domestic hot water for household consumption (e.g. for showering).
Controls and monitors the operation of the boiler. Maintains the desired room temperature optimally and fuel-efficiently, independent of the outside tem­perature.
Releases the heat of the heating water into the room.
Transports the heating water from the boiler to the ra­diators and back into the boiler, where it is reheated.
Transports the heat which is generated from the boi­ler to the radiators.
COMPONENTS
Wood pellet boiler
Pellets
Optional heating water buffer storage tank
Storage calorifier
Boiler controller with heating regulator
Radiators underfloor heating, if fitted
Heating pump
Heating water and heating pipes
4 212 945 / 00
8
Functional principle of the heating system
Adjusts the heating flow temperature to the radiator to maintain the desired room temperature whatever the outside temperature. This is achieved by mixing in colder return heating water.
Displays the water pressure in the heating system.
Ensures that the heating pipes contain only heating water and no air.
Prevents overpressure in the system.
Maintains the pressure in the system at a constant level and absorbs the expansion water.
Mixing valve
Pressure gauge
Air vent
Safety valve
Membrane expansion tank
Depending on the type of heating system selected, some of the components might not be present or others added. The heating engineer will explain the system to you.
Calorifier
Mixing valve
Radiators underf­loor heating, if fitted
Heating pump
Wood pellet boiler
Hot water buffer storage tank (optional)
4 212 945 / 00
9
Functional principle of the heating system
3.1 What happens inside the BioLyt?
The Hoval BioLyt has been designed for the low­emission combustion of wood pellets in accordance with ÖNORM M 7135 and DIN 51731, HP5 (or DIN­plus), as well as EN 14961-2, A1 or ENplus. The metering screw conveys the wood pellets from the pellet hopper to the feeder screw via a down­pipe with rotary valve. The metering screw adjusts the amount of pellets conveyed as a function of the power demand, while the continuously opera­ting feeder screw feeds the pellets into the burner pipe. Degassing of the pellets takes place in the rear section of the burner pipe by means of primary air supplied by the pressure fan. The combustible gas thus generated is thoroughly mixed with secondary air (supplied by the induced draught fan) in the front section, where it burns cleanly and completely with low emission levels.
The horizontal combustion results in a flame simi­lar to that of an oil or gas burner. The combustion system achieves an excellent pellet burn-out rate. Thanks to the large, mostly refractory lined combus­tion chamber, it is possible to attain a long dwell time of the hot gases as well as sufficiently high com­bustion temperatures. These factors contribute to a further optimisation of the burn-out quality. The heat exchange between the hot gases and the heating water takes place by means of the proven thermo­lytic secondary heating surface. The secondary he­ating surface is cleaned fully automatically. The ashes arising as a result of the combustion pro­cess are collected in the combustion chamber and are periodically conveyed to the ash container by the ash discharge screw.
Fig. 01
Figure: BioLyt (100-160)
4 212 945 / 00
10
Functional principle of the heating system
3.2 How are the pellets extracted and conveyed from the storage room?
The pellets are extracted from the storage room by means of a worm conveyor and then transported to the pellet hopper on the boiler by means of a vacuum turbine.
The pellet hopper on the boiler includes two filling level indicators:
- for the signal “pellet hopper full” / top
- for the signal “pellet hopper empty” / bottom
The pellet hopper can only be filled during the preset enable time in order to minimise the noise in the building. The filling process is started every time the burner enters burn-out mode or, at the latest, when the bot­tom fill level indicator signals “empty”.
First, the suction turbine starts up. Then, the discharge screw starts operating after a delay of approx. 15 secs. As soon as the upper filling level indicator sends the signal for “pellet hopper full”, the discharge screw is stopped; the suction turbine then stops operating after a set time delay (for purging the hoses).
The extraction system can be disabled during two periods of time per day (e.g. to avoid unwelcome noise during the night). The factory settings are from
12.30 p.m. to 2.30 p.m. and from 9.30 p.m. to 8.00 a.m. To ensure that there is an adequate supply of pellets to span such off-periods, forced burn-out with filling of the pellet hopper is carried out 30 min. before the beginning of every off-period. Off-periods can be deactivated by setting the beginning and end of the respective period to 00.00 (see Chapter 4.11.4).
Fig. 02
Discharge screw
Suction turbine under
sound absorbing hood
Screw motor
4 212 945 / 00
11
Heating system control
4. Heating system control
4.1 What is the function of the boiler controller TopTronic
®
T
i
The boiler controller, together with the temperature sensor connected to it, is,
so to speak, the brain of the heating sys­tem. Its main functions are:
- maintaining the desired room tempera­ture independent of the outside tempe­rature
- heating the living space when required
- producing warm water (e.g. for show­ering) only when required
- displaying information
Further functions:
- input of desired temperatures and ope­rating modes
- turning the heat generator ON/OFF
- monitoring temperatures
The correct settings for the heating system have already been applied by Hoval, or the installer, du­ring commissioning. Any changes to those settings should only be carried out if you go away on a trip or if your home is too cold or too warm. You can find an overview of the most frequently asked questions and the answers to them in Chapter 4.4.3.
ENERGY
4.2 How you can save energy
i
For your benefit and for the environ­ment,
use energy efficiently and avoid
unneccessary losses:
With little effort, you can optimise the operation of your system and make it
worth while.
It is worth turning the heating off again during spells of warm weather
in autumn to prevent your heating sys-
tem generating unnecessary heat when
outside temperatures are low in the mor-
ning and thus overheating your home. Turning the heating on or off depending on the weather conditions is one of the most effective energy-saving measures. If you want to save yourself the effort of going down into the cellar, you may want to consider acquiring a “remote control”
from Hoval, which will allow you to ope-
rate and control the heating comfortably
from your living room.
4.3 Basic display
The basic display shows the day of the week, date and time as well as the current heat generator tempe­rature or another temperature (system dependent).
4 212 945 / 00
12
Heating system control
4.4 Operating and display elements
4.4.1 Function of the operating elements
The central PUSH & TURN button and the labelled keys are designed for easy
and straightforward operation.
PUSH & TURN button: Change and store values
4.4.2 Basic procedure for changing settings
An example
Select the desired function
Turn the PUSH & TURN button to select or change the desired pa­rameter (flashing word or number)
Press the Info key at any time to return to the basic display without storing the values set
Press the PUSH & TURN button to store the value set It is also possible to store the value using the selected function key.
Function keysFunction keys
4 212 945 / 00
13
Heating system control
4.4.3 What to do if ...
The following information can be used as a first level support in frequently occurring situations.
Observation Remedy
It is too cold
Set higher values for the room temperature with
and the rotary button
(Chapter 4.4.1).
It is too warm
Set lower values for the room temperature with
and the rotary button
(Chapter 4.4.1).
From now on, equal day and night temperatures should be maintained continuously
Use

to set the operating mode to "HEATING" (Chapter 4.6.1, 4.6.4).
This evening, I want the heating to remain on for longer
Use

to set the operating mode to "PARTY" and set the desired time
(Chapter 4.6.1, 4.6.3).
I require a larger amount of hot water at the mo­ment
Press
for 3 seconds and set the additional re-charging time (Chapter
4.9.2).
From now on, hot water but no heating is requi­red
Use

to set the operating mode to  "SUMMER" (heating off, hot water
only) (Chapter 4.6.1, 4.6.4).
Suddenly, there is no heating or hot water; it is cold.
Check the heating regulator and boiler controller for alarms (Chapter 5.2, 5.3) and consult a heating engineer if necessary
The room temperature setpoint requires fre­quent adjustments be­cause it is too cold or too hot
Change the set heating curve (Chapter 4.8.2). Changing the heating curve does not make sense if your system is fitted with a room air sensor (or room station) and an outside sensor. The correct settings for the heating curve are then provided automatically. Consult a specialist if necessary.
I will be absent for seve­ral hours during the day today
Use

to set the operating mode to "ABSENT TIL" and set the time of
your return (Chapter 4.6.1 - 4.6.3).
I am going away on a short trip (e.g. 3 days)
Use

to set the operating mode to "HOLIDAY TIL" and set the date
of your return (Chapter 4.6.1 - 4.6.3).
I am going away for an indefinite period of time
Use

to set the operating mode to  "RED. HEATING."
On your return, use

to set operating mode "AUTOMATIC"
(Chapter 4.6.1, 4.6.2, 4.6.4).
In summer, it is too cold or too warm.
Indicates that the summer disconnection is active. If it is too cold for you, use

to set operating mode "HEATING" (Chapter 4.6.1, 4.6.4).
4 212 945 / 00
14
Heating system control
4.4.4 Control elements on the boiler control panel
1
5
9
10
Key Designation Function
1
Blocking switch
Switch off and block the boiler (e.g for cleaning).
2
Daytime room temperature Set the daytime room temperature. Chap. 4.5.1.1
3
Reduced room temperature
Set the night-time room temperature (reduced hea­ting). Chap. 4.5.1.2
4
Domestic hot water tem­perature
Set the domestic hot water temperature. Manual DHW re-charging. Chap. 4.9.1, 4.9.2
5
Push & Turn button
Change the values by turning. Acknowledge the va­lues by pressing. Select functions by pressing and turning.
6
Information key
• Show operating data on the display
• Return to the basic display without saving the values. Ex. 4.11.1
7
Heating characteristics Set the heating curve Chap. 4.8.2
8 67
A 2nd electronic heating regulator can be installed here (for 2nd residential unit) if required.
2
3
4
12
11 13
14
4 212 945 / 00
15
Heating system control
Key Designation Function
8

Operating mode selection key
Select the operating modes
Holiday
Turn off the heating system while you are on holiday (frost protection) Chap. 4.6.1 - 4.6.3
Absence
Switch off the heating temporarily Chap. 4.6.1 - 4.6.3
Party
Extend heating operation Chap. 4.6.1 - 4.6.3
Automatic
Automatic heating according to the preset heating times = normal heating operation Chap. 4.6.1, 4.6.4
Summer
Hot water only, heating off Chap. 4.6.1, 4.6.4
Heating
Constant heating mode Chap. 4.6.1, 4.6.4
Reduced heating
Constant reduced heating operation Chap. 4.6.1, 4.6.2, 4.6.4
Standby
System off - frost protection active Chap. 4.6.1, 4.6.2, 4.6.4
9
Manual mode / emission measurement
For heating technician only or for preliminary ac­knowledgement of a maintenance prompt (see chap.
4.11.6).
10
Display
The basic display shows the day of the week, date and time, as well as the current heat generator tem­perature or another temperature (system-dependent).
2
1
3
4
6
7
5
Possible readouts: 1 Active heating time 24h 2 Day display 3 Display of the active operating state and the clock
programme 4 Time 5 Selected operating mode 6 Date / Day / Month / Year 7 Heat generator temperature or another temperature
(system-dependent)
11
Control panel fuse, under the hinged cover
Check the 6.3 A fuse if all displays remain dark. This may only be done by the heating technician!
12
Reset button, under the hinged cover
Press the Reset button under the hinged cover if the display shows “Error.” If this happens frequently, notify your Customer Service centre.
13
Brief operating instructions in the hinged cover
Special brief operating instructions are provided with the boiler controller.
14
Burner fault light Press the Reset button (see no. 12)
4 212 945 / 00
16
Heating system control
4.5 Main settings
4.5.1 Changing the room temperature
4.5.1.1 Setting the desired room temperature, day
Start - Basic display
Tap the “Daytime room temperatu­re” key.
The daytime room temperature set­point flashes.
Set the desired room temperature by turning the “PUSH & TURN but­ton.”
The new “Daytime room temperatu­re” setpoint appears on the display.
Tap the "Daytime room temperatu­re" key to acknowledge the tempe­rature setpoint.
Mo 16 AUG.'04
14 / 00 / 62.5
ROOM DAY
20.0
c
ROOM DAY
22.0
C
These adjustments can also be carried out on a room station.
If “MC1” is shown on the display, you need to select the heating cir­cuit. (Information on which heating cir­cuit to select for your home can be found on page 4 of these instruc­tions).
i
i
1
2
3
4
5
6
Setting range 5 - 30°C (Factory setting 20°C)
i
4 212 945 / 00
17
Heating system control
4.5.1.2 Setting the desired reduced (night-time) temperature
Mo 16 AUG.'04
14 / 00 / 62.5
ROOM NIGHT
20.0
C
ROOM NIGHT
18.0
C
1
2
3
4
5
6
Start - Basic display
Tap the “Reduced room temperatu­re” key.
The night-time room temperature setpoint flashes.
Set the desired room temperature by turning the “PUSH & TURN but­ton.”
The new “Reduced room tempera­ture” setpoint appears on the dis­play.
Tap the "Reduced room temperatu­re" key to acknowledge the tempe­rature setpoint.
If “MC1” is shown on the display, you need to select the heating cir­cuit.
i
Setting range 5 - 30°C (Factory setting 16°C)
i
4 212 945 / 00
18
Heating system control
Operating mode
HOLIDAY
ABSENT
PARTY
AUTOMATIC
SUMMER
HEATING
RED. HEATING
STANDBY
Function
- Heating system off while you are on holiday.
- Room temperature set to minimum (10°C).
- Calorifier frost protected (5 °C).
- Heating system OFF (heating temporarily switched off until set time).
- Room temperature set to minimum (10°C).
- Calorifier frost protected (5 °C).
- Extend heating operation (daytime room tempe­rature) up to set day/night time (you do not want to reduce the room temperature at the preset time).
- Automatic heating mode according to the heating times set in the 1st switching times program = normal heating mode.
- Heating system OFF
- DHW is produced at the times set in the switching times program (for showering, etc.)
- Frost protection active.
- The room temperature is not reduced during the night.
- The rooms are continuously heated at the set “daytime room temperature"
.
- DHW mode according to switching program.
- The rooms are continuously heated at the "Redu­ced room temperature."
- Continuous reduced heating mode.
- Heating system OFF.
- Frost protection active.
- No DHW mode.
4.6 Operating modes
4.6.1 Function of the operating modes
Application
You are going on holiday for e.g. 1 week and you know the date of your return.
Chap. 4.6.2, 4.6.3
You leave home in the morning and come back in the evening.
Chap. 4.6.2, 4.6.3
You have guests in the evening.
Chap. 4.6.3
You want to heat as cost effectively and efficient­ly as possible. Chap. 4.6.4
Heating the rooms is unnecessary due to the high outside temperatures. Chap. 4.6.4
You would like to heat the rooms during the night, too. Chap. 4.6.4
You are going away for an indefinite period of time.
Chap. 4.6.2, 4.6.4
You are travelling for an indefinite period of time in spring or in autumn. It does not matter if the rooms are cold on your return. You do not need
warm water on your return. Chap. 4.6.2, 4.6.4
i
End of holiday = Return date. Normal heating is resumed on the day of your return! Setting range: current date + 250 days. To switch back to automatic mode prematurely - press the "operating mode selection key"

for 3 seconds.
i
Setting range: 0.5 - 24 h. To switch back to automatic mode prematurely - press the "operating mode selection key"

for 3 se-
conds.
i
Setting range: 0.5 - 24 h.
To switch back to automatic mode prematurely - press the "operating mode selection key"

for 3 se-
conds.
i
Factory setting: Heating: 06.00 - 22.00 Reduced heating: 22.00 - 06.00 Domestic hot water: 05.00 - 22.00
i
Factory setting for domestic hot water: 05:00 - 22:00 Operating mode “Summer” cannot be selected if each heating circuit is adjusted separately.
4 212 945 / 00
19
Heating system control
4.6.2 Operating modes for holiday and absence?
Depending on how long you will be away and what your requirements are with re­gard to comfort, there are different operating modes available for interrupting or re­ducing the heating. In any case, you will save a lot of energy and money if the rooms are not heated or heated less during your absence. The following table is intended as a guide for finding the best operating mode for each particular case:
For a detailed description of how to set the operating modes, see Chap. 4.6.3, 4.6.4.
You can return to the “AUTOMATIC” function (normal heating mode) at any time by “pressing”

for 3 sec.
Application
You are going on holiday for e.g. 1 week and you know the date of your return.
You leave home in the mor­ning and come back in the evening.
You will be away for an inde­finite period of time and want the living area to be at the set reduced temperature on your return.
You will be away for an inde­finite period of time during spring or autumn and you don’t mind if your home is cool on your return.
Operating mode
"HOLIDAY TIL"
Heating system and DHW off while you are on holiday.
"ABSENT TIL"
Heating interrupted temporarily
"RED. HEATING"
Continuous reduced heating mode
"STANDBY"
System off - frost protection active
Function
- Heating system OFF / Calori­fier frost protected (5°C)
- Room temperature set to mini­mum (10°C)
Setting range: from current date
to 250 days in the future! End of holiday = Return date. Normal heating is resumed on the day of your return! Early return:
Press

for 3 sec. to return
to dann "AUTOMATIC" (Chap.
4.6.1, 4.6.3).
Heating temporarily interrupted until set time. Setting range: 0.5 - 24h
Continuous reduced heating and DHW mode (reduced, see Chap. 4.9.3) around the clock.
The entire heating system is switched off and frost-protected. Calorifier is frost-protected!
4 212 945 / 00
20
Heating system control
Tap the “Operating mode selection” key.
“OP. MODE” is displayed briefly.
The currently active operating mode is then shown flashing on the display.
Set the desired operating mode by turning the “PUSH & TURN button”:
The selected operating mode (e.g. "HOLIDAY TIL") is shown flashing on the display.
Tap the “PUSH & TURN button” to acknowledge the selected opera­ting mode.
Today’s date (“HOLIDAY TIL”) or the current time (“ABSENT TIL”, “PARTY TIL”) is shown flashing on the display.
Turn the “PUSH & TURN button” and select:
Tap the “PUSH & TURN button” to acknowledge the setting.
4.6.3 Changing the operating mode - for "HOLIDAY TIL," "ABSENT TIL" and "PARTY TIL"
Procedure for activating the operating modes “HOLIDAY TIL”, “ABSENT TIL” or “PARTY TIL”.
OP. MODE
AUTOMATIC
HOLIDAY TIL
HOLIDAY TIL
27.08

1
2
3
4
5
6
A black rectangle in the lower sec­tion of the display points to the cor­responding symbol!
i
7
8
9
- for “HOLIDAY TIL”, the date on which you return from your holi­day.
- for “ABSENT TIL”, the expected time of your return (within max. 24h).
- for “PARTY TIL”, the time the par­ty is expected to end.
i
"HOLIDAY TIL," "ABSENT TIL" or "PARTY TIL."
i
4 212 945 / 00
21
Heating system control
4.6.4 Changing the operating mode - for "AUTOMATIC," "SUMMER," "HEATING," "RED. HEA­TING" and "STANDBY"
Procedure for activating the operating modes “AUTOMATIC”, “SUMMER” , “HEATING”, “RED. HE­ATING” and “STANDBY”
Follow the steps 1 to 3 described in Chapter 4.6.3 “Changing the ope­rating mode”!
Set the desired operating mode by turning the “PUSH & TURN button”:
The selected operating mode (e.g. "RED. HEATING") is shown flas­hing on the display.
Tap the “PUSH & TURN button” to acknowledge the setting.
RED. HEATING
4
5
6
"AUTOMATIC," "SUMMER," "HEATING," "RED. HEATING" or "STANDBY."
i
4 212 945 / 00
22
Heating system control
4.7 Switching times (heating times)
In this menu, the switching times programs can be set individually for the heating and DHW modes.
The default heating times preset by the manufacturer are overwritten. However, you can restore the default times easily (see Chapter 4.10.5).
It is possible to program up to 3 heating times per day.
The switching times are only active when the “AUTOMATIC” mode is selec­ted.
4.7.1 Standard heating times
Circuit Day Heating from - to
All heating circuits (HC,MC-1,MC-2) Mo-Su 06.00 - 22.00
Hot water circuit (DHW) Mo-Su 05.00 - 22.00
Further standard programs can be - or may already have been - set-up or enabled for programming by the installer (P1-P3) see Page 23.
A maximum of 3 heating times per day are possible, e.g.:
4.7.2 Table for recording individual switching times
Switching times program for living area...............
(MC1)
Day
Cycle 1 Cycle 2 Cycle 3
from to from to from to Mo Tu We Th Fr Sa Su
Switching times program for living area..............
(MC2)
Day
Cycle 1 Cycle 2 Cycle 3
from to from to from to Mo Tu We Th Fr Sa Su
Switching times program for living area..............
(HC)
Day
Cycle 1 Cycle 2 Cycle 3
from to from to from to Mo Tu We Th Fr Sa Su
Switching time program for calorifier (DHW)
Day
Cycle 1 Cycle 2 Cycle 3
from to from to from to Mo Tu We Th Fr Sa Su
i
iii
... pro Tag
1 Heizzyklus!
... pro Tag
2 Heizzyklen!
... pro Tag
3 Heizzyklen!
... pro Tag
1 Heizzyklus!
... pro Tag
2 Heizzyklen!
... pro Tag
3 Heizzyklen!
4 212 945 / 00
23
Heating system control
Start - Basic display
Press the “PUSH & TURN button” for at least 3 sec.
“TIMEPROGRAMS” is shown flas­hing on the display.
Tap the “PUSH & TURN button” to acknowledge the selected operating mode.
“HC” is shown flashing on the dis­play
Select the desired heating circuit by turning the “PUSH & TURN button.”
Tap the “PUSH & TURN button” to acknowledge the selected heating circuit.
Mo 16 AUG.'04
14:00 62.5
C
TIMEPROGRAMS
TIMEPROGRAMS
HC
TIMEPROGRAMS
MC-1
e.g.
1
2
3
4
5
6
7
if necessary, select switching time program P1, P2 or P3.
i
4.7.3 Changing the switching times (heating times)
4 212 945 / 00
24
Heating system control
 0 2 4 6 8 10 12 14 16 18 20 22 24
06.00-22.00
MO-1-
 0 2 4 6 8 10 12 14 16 18 20 22 24
06.00-22.00
MO-1-
The first day of the week is shown flashing on the display.
Turn the “PUSH & TURN button” un­til the desired day is displayed.
The selected day of the week is shown flashing on the display.
Tap the “PUSH & TURN button” to acknowledge the day.
The heating start time is shown flashing on the display.
Set the desired heating start time by turning the “PUSH & TURN but­ton.”
Tap the “PUSH & TURN button” to acknowledge the set start time.
The heating end time is shown flas­hing on the display.
Set the desired heating end time by turning the “PUSH & TURN button.”

0 2 4 6 8 10 12 14 16 18 20 22 24
06.00-22.00
MO-1-
8
Change the flashing value by tur­ning the “PUSH & TURN button.” Acknowledge by tapping the “PUSH & TURN button.” Go back one step with . Return to the starting point with or, automatically, after approx. 60 sec.
i

9

0 2 4 6 8 10 12 14 16 18 20 22 24
06.00-22.00
MO-1-
10
11
12
13
14
15
16
4 212 945 / 00
25
Heating system control
If P1 is displayed, it means that further standard heating time programs are already enabled. If not, P2 and P3 can be enabled by the heating technician.
Circuit Day Heating from
All heating circuits (HC,MC-1,MC-2)
Mo-Th
Fr
Sa-Su
06.00-08.00 16.00-22.00
06.00-08.00 13.00-22.00
07.00-23.00
Hot water circuit (DHW)
Mo-Th
Fr
Sa-Su
05.00-08.00 15.30-22.00
05.00-08.00 12.30-22.00
06.00-23.00
Circuit Day Heating from
All heating circuits (HC,MC-1,MC-2)
Mo-Fr
Sa-Su
07.00-18.00
reduced
Hot water circuit (DHW)
Mo-Fr
Sa-Su
06.00-18.00
reduced
Factory setting: Switching times program P2
Factory setting: Switching times program P3

0 2 4 6 8 10 12 14 16 18 20 22 24
06.00-22.00
SU-1-

 0 2 4 6 8 10 12 14 16 18 20 22 24
-.---.--
MO-2-
Tap the “PUSH & TURN button” to acknowledge the set end time.
Turn the "Push & Turn" button to set a second heating time (Mo -2-).
Set the switching times as descri­bed for the previous heating circuits.
Set the switching times as descri­bed for the previous days.
Tap the “Operating mode selection” key to acknowledge the settings.

0 2 4 6 8 10 12 14 16 18 20 22 24
06.00-22.00
MO-1-
17
After confirmation of the end time, the day of the week flashes again.
i
18
19
Keep turning to reach the following day.
20
21
You can also copy the switching times from other days (see Chapter
4.7.4).
i
22
4 212 945 / 00
26
Heating system control
4.7.4 Copying switching times
COPY
DAY
Follow the steps 1 to 8 described in Chapter 4.7.3 “Changing the switching times”!
Select the “COPY”, “DAY” by turning the “PUSH & TURN button.”
The settings flash on the display.
Tap the “PUSH & TURN button” to acknowledge the settings.
The selected setting value is shown flashing on the display.
Select the day you want to copy by turning the “PUSH & TURN button”.
Tap the “PUSH & TURN button” to acknowledge the day.
The target day(s) is (are) shown flashing on the display.
Select the desired value by turning the “PUSH & TURN button.”
COPY
FROM MO
COPY MO
TO TU
10
11
12
13
14
15
16
Change the flashing value by tur­ning the “PUSH & TURN button.” Acknowledge by tapping the “PUSH & TURN button.” Go back one step with . Return to the starting point with

or, automatically, after approx.
60 sec.
i
Top line = value to copy Bottom line = target
i
Days of the week: MO, TU....
Whole week: 1 - 7 Workdays: 1 - 5 Weekend: 6 - 7.
i
17
4 212 945 / 00
27
Heating system control

Tap the “PUSH & TURN button” briefly to acknowledge the setting.
Confirmation for correct copying of day(s).
Target range for the next copy pro­cess is shown flashing on the dis­play.
Select the next copy range by tur­ning the “PUSH & TURN button.”
Target range for the copy process is shown again flashing on the dis­play.
Tap the “Operating mode selection” key to acknowledge the settings.
COPY
DAY OK
COPY MO
TO 6-7
COPY MO
TO 50
18
19
20
21
22
23
The same value as in the preceding action is copied to the target range!
i
Follow the same procedure to cre­ate any additional copies required.
i
The start display is shown (basic display).
i
4 212 945 / 00
28
Heating system control
4.8 Heating curve
4.8.1 Heating curve (heating characteristic curve)
The heating curve describes the flow temperature of a heating system as a function of the outside temperature.
The heating curve is preset by the installer *.
Carry out temporary changes to the room temperature settings via the “Dayti­me room temperature” or “Reduction temperature.”
The heating characteristic curve settings should only be changed if the room temperature is not reached over a longer period of time during the heating period.
Recommended settings: Underfloor heating: 0.3 to 0.8 Radiator heating: 1.0 to 2.0 Convector heating: 1.4 to 2.0
Heating flow temperature
Outside temperature
Heating curve slope
i
i
Example: You have set the system to radiator heating and a heating curve slope of 1.0. At an outside temperature of -10°C, this results in a flow temperature of approx. 52°C if a temperature of 20°C is required.
i
i
* Info : The heating curve for the direct circuit is set to OFF by default. The direct heating circuit is activated automatically by setting a value.
4 212 945 / 00
29
Heating system control
HEAT. CURVE
HC OFF
HEAT. CURVE
HC OFF
HEAT. CURVE
HC 1.5
Start - Basic display
Tap the "Heating characteristics“ key.
"Heating curve“ - display appears, "HC“ flashes
Select the desired heating circuit by turning the “PUSH & TURN button.”
Tap the “PUSH & TURN button” to acknowledge.
The slope of the heating charac­teristic curve is shown flashing on the display, or OFF if the selected heating circuit is not connected
Set the desired slope of the heating characteristic curve by turning the “PUSH & TURN button.”
Tap the “PUSH & TURN button” to acknowledge the selected value.
The selected slope of the heating characteristic curve is shown.
Mo 16 AUG.'04
14 / 00 / 62.5
C
4.8.2 Changing the heating curve (heating characteristic curve)
1
2
3
4
5
6
7
8
9
4 212 945 / 00
30
Heating system control

DHW
DAY 63.0
C
Start - Basic display
Tap the “Hot water temperature” key.
The currently set hot water tem­perature is shown flashing on the display.
Set the desired hot water tempera­ture by turning the “PUSH & TURN button.”
The selected hot water temperatu­re flashes.
Tap the “Domestic hot water tem­perature” key to acknowledge the temperature setpoint.
HEAT. CURVE
MC 1.00
Turn the PUSH & TURN button to set further heating circuits...
“Heating curves” appears again on the display.
Tap the “Operating mode selection” key to acknowledge the settings.
4.9 Hot water
4.9.1 Setting the domestic hot water temperature
Mo 16 AUG.'04
14 / 00 / 62.5
C
DHW
DAY 60.0
C
The start display is shown (basic display).
i
1
2
3
4
5
6
1
2
3
Setting range 10 - 65°C Factory setting 60°C
i
For example “MC” (flashing).
i
4 212 945 / 00
31
Heating system control
Start - Basic display
Press and hold the “Hot water tem­perature” key for 3 seconds.
The additional DHW charging time is displayed; the minutes display flashes.
Set the desired additional charging time by turning the “PUSH & TURN button.”
Tap the “PUSH & TURN button” to acknowledge the setting.
The selected additional charging time is shown.
DHW - RECHAR
0.0min
4.9.2 Manual DHW re-charging
In the case of increased hot water demand, it is possible to conduct a temporary additional heat-up of the calorifier. The calorifier is then re-charged once according to the set daytime hot water temperature.
DHW - RECHAR
14:16 63.0
C
Mo 16 AUG.'04
14 / 00 / 62.5
C
4
5
6
1
2
3
Setting range 0 - 240 min.
i
The information on the display dis­appears when re-charging is com­pleted.
i
4 212 945 / 00
32
Heating system control
Start - Basic display
Press the “PUSH & TURN button” for 3 seconds.
“Switching times” is shown flashing on the display.
Change the DHW setting by tur­ning the “PUSH & TURN button.”
"DHW" flashes on the display.
Tap the “PUSH & TURN button” to acknowledge the selected value.
“DHW” is shown flashing on the display again.
Tap the “PUSH & TURN button” to acknowledge the selected value.
4.9.3 Domestic hot water economy temperature (reduced temperature)
TIMEPROGRAMS
DOMESTIC HOT WATER
DHW
DHW
NIGHT 40.0
Mo 16 AUG.'04
14 / 00 / 62.5
C
Setting range 0 - 240 min.
i
4
5
6
1
2
3
The temperature shown corres­ponds to the set reduced DHW temperature.
i
7
8
4 212 945 / 00
33
Heating system control

DHW
NIGHT 40.0
The reduced night-time DHW tem­perature flashes.
Select the desired temperature va­lue by turning the “PUSH & TURN button.”
Tap the “PUSH & TURN button” to acknowledge the setting.
Tap the “Operating mode selection” key.
10
11
12
9
The start display is shown (basic display).
i
4 212 945 / 00
34
Heating system control
Follow the steps 1 to 3 described in Chapter 4.9.3 “Domestic hot water economy temperature”!
Select “Time-date” by turning the “PUSH & TURN button.”
“Time-date” is shown flashing on the display.
Tap the “PUSH & TURN button” to acknowledge the selected value.
“Time” is shown flashing on the dis­play.
Tap the “PUSH & TURN button” to acknowledge the selected value.
The “time” is shown flashing on the display.
Set the desired time by turning the “PUSH & TURN button.”
Tap the “PUSH & TURN button” to acknowledge the selected value.
4.10 Further settings
4.10.1 Setting the clock
TIME - DATE
TIME
14:00
TIME
14:00
4
5
6
7
8
9
10
11
Return to the starting page and save the set values with

.
Turn the "PUSH & TURN button“ to make further settings.
i
i
4 212 945 / 00
35
Heating system control

“Year” is shown flashing on the dis­play - acknowledge. Change the year setting by turning the “PUSH & TURN button” - ack­nowledge.
“Day...Month” is shown flashing on the display - acknowledge. Change the Day...Month setting by turning the “PUSH & TURN button”
- acknowledge.
“Change” is shown flashing on the display - acknowledge. Change SU-WI ON or OFF by tur­ning the “PUSH & TURN button” ­acknowledge.
Tap the “Operating mode selection” to acknowledge the selected sum­mer / winter time and to open the basic display.
4.10.2 Setting the date
YEAR
2004
DAY.. .......MONTH
Mo 27.09
CHANGE
SU-WI ON
4.10.3 Changing between summer and winter time
Return to the starting page and save the set values with

.
Turn the "PUSH & TURN button“ to make further settings.
i
i
12
13
14
15
Continuation of ”Setting the clock” (Chapter 4.10.1).
i
Continuation of ”Setting the date” (Chapter 4.10.2).
i
4 212 945 / 00
36
Heating system control

Follow the steps 1 to 3 described in Chapter 4.9.3 “Domestic hot water economy temperature”!
Select “System” on the display by turning the “PUSH & TURN button.”
“System” is shown flashing on the display.
Tap the “PUSH & TURN button” to acknowledge the selected value.
“Language” is shown flashing on the display
Tap the “PUSH & TURN button” to acknowledge the selected value.
Language is displayed - abbrevia­tions for the language are shown flashing.
Turn the “PUSH & TURN button” to select the desired language and tap to acknowledge.
Tap the “Operating mode selection” key to acknowledge the settings and to open the basic display.
SYSTEM
SY5T
LANGUAGE
SYST GB
4.10.4 Setting the language
4
5
6
You will be prompted for the desi­red language when switching on the control system for the first time. Changing the language is also pos­sible during normal operation.
i
DE = German GB = English FR = French IT = Italian etc.
i
LANGUAGE
SYST GB
7
8
10
11
12
4 212 945 / 00
37
Heating system control
4.10.5 Reloading the standard switching times program - Deleting your own time program
Follow the steps 1 to 3 described in Chapter 4.9.3 “Domestic hot water economy temperature”!
Tap the “PUSH & TURN button” to acknowledge the selected value.
The letters “HC” are shown flashing on the display.
Select "Default times" by turning the "PUSH & TURN" button.
“Default-time” is shown flashing on the display..
Tap the “PUSH & TURN button” to acknowledge the selected value.
The letters “HC” are shown flashing on the display.
Select the desired heating circuit by turning the “PUSH & TURN but­ton.”
DEFAULT-TIME
TIMEPROGRAMS
HC
DEFAULT-TIME
HC
This function allows you to reset all values preset at the factory!
i
4
5
6
7
8
9
10
4 212 945 / 00
38
Heating system control

RESET
HC
RESET
OK
Tap the “PUSH & TURN button” to acknowledge the selected value.
“Reset / HC” is displayed.
Press and hold the “PUSH & TURN button” for 3 sec.
"Reset / OK" is displayed to ack­nowledge.
Tap the “Operating mode selection” key to acknowledge the new set­tings and to open the basic display.
12
13
14
15
11
4 212 945 / 00
39
Heating system control
4.10.6 Manual operation
The following information is intended for the heating technician only
This function key is also used for emission measurement when it is only pressed briefly.
- See installation instructions; combustion control
All pumps are operating without restrictions. Available mixers are disconnec­ted and can be operated manually, if necessary, depending on the heat de­mand.
WARNING:
- The DHW temperature can reach the level of the boiler temperature set­point.
Danger of scalding if temperature setting is too high !
- To protect underfloor heating systems against impermissible overheating during manual operation, it is necessary to implement appropriate safety measures (e.g. safety temperature limiter with pump switch-off).
Note:
You can exit manual operating mode and emission measurement mode at any time by tapping the operating mode selection key

(Return to basic
display).
i
i
i
Manual operation
MANUAL MODE
35.0 60
Immediate end
PRESS > 5 seconds
REACTIONS for manual operation
- Set desired boiler temperature with button!
- All heating pumps ON
- Mixer without current - manual setting necessary!
- Note the maximum permissible temperature of the panel heating!
- The hot water temperature reaches the set DHW maximum temperature (service engineer level standard 65°C).
4 212 945 / 00
40
Heating system control
4.11 System information
4.11.1 Information key for system temperatures and heating circuit information
OPER. HOURS
0h
STARTS
0
DHW
55
C
OUTSIDE
7.5
C
Heat generator hours of operation
Heat generator Starts
Flow temperature
Domestic hot wa­ter temperature
Heat generator tempe­rature
Outside temperature
Actual values
All temperature values shown represent the current values. Press and hold the “PUSH & TURN button” to display the in­dividual set value.
only in conjunction with room sensor:
- Room temperature direct HC
- Room temperature MC 1
- Room temperature MC 2
turn to left turn to right
i
Exhaust
EXHAUST
50
c
HEAT GENER.
64.5
C
MODULATION
30
Modulation
Back to the start screen: Press briefly
FLOW
55
c
i
In certain cases, additi­onal information may be displayed.
4 212 945 / 00
41
Heating system control
4.11.2 Information on the boiler status
Viewing the current status of the heat generator.
Mo 16 AUG.'04
14 / 00 / 62.5
C
Start - Basic display
1
Press the “PUSH & TURN button” for 3 seconds.
TIMEPROGRAMS
2
“Switching times” is shown flashing on the display.
3
Select "FFA" by turning the "PUSH & TURN button."
FFA
4
“FFA” is shown flashing on the dis­play.
5
Tap the “PUSH & TURN button” to acknowledge the selected value.
INFORMATION
6
“INFORMATION” is shown flashing on the display.
4 212 945 / 00
42
Heating system control
7
Tap the “PUSH & TURN button” to acknowledge the selected value.
STATUS
3
8
“STATUS” is shown flashing on the display.
9
Turn the "PUSH & TURN button" to find the following values:
STATUS
Boiler status
0 Burner OFF,
Quiescent state
The burner is off and the boiler is in standby mode.
1 Ignition phase Burner is filled with pellets and ig-
nition takes place via hot air fan.
2 Fire-bed build-up A stable fire-bed is built up in the
burner and the output increased step by step
3 Normal operati-
on with modula­ting output
Modulating operation, adjustment of the burner output to the requi­red heat demand
5 BURN-OUT Burner is switched off and the fire-
bed burns out after the setpoint temperature is reached or in order to refill the pellet hopper.
6 Fault Burner fault is active (see Chap-
ter 5).
MODULATION
Modulation
BOILER
Boiler delivery flow temperature
BRU ACT
Return temperature
BUFFER
Buffer temperature
FLUE GAS
Flue gas temperature
COM.-CHAMBER
Combustion chamber temperature
INSERT-SCREW
Stoker/feeder screw temperature
CONSUMPTION 1
Consumption meter 1
CONSUMPTION 2
Consumption meter 2
10
Tap the "Information" key three times.
i
The start display is shown
(basic display).
4 212 945 / 00
43
Heating system control
4.11.3 Displaying and resetting the consumption meters and cleaning messages
MO. 16 AUG.'04
14 / 00 / 62.5
C
Start - Basic display
1
Press the “PUSH & TURN button” for 3 seconds.
TIMEPROGRAMS
2
“TIMEPROGRAMS” is shown flas­hing on the display.
3
Select "FFA" by turning the "PUSH & TURN button."
FFA
4
“FFA” is shown flashing on the dis­play.
5
Tap the “PUSH & TURN button” to acknowledge the selected value.
INFORMATION
6
“INFORMATION” is shown flashing on the display.
7
Select "COUNTER" by turning the "PUSH & TURN button."
4 212 945 / 00
44
Heating system control
COUNTER
8
“COUNTER” is shown flashing on the display.
9
Tap the “PUSH & TURN button” to acknowledge the selected value.
CONSUMPTION 1
0
10
"CONSUMPTION 1" is shown flas­hing on the display.
11
Turn the "PUSH & TURN button" to find the following values:
Viewing the consumption meters
CONSUMPTION 1
Pellet consumption for period: Pellet consumption since the last pellet delivery or over a specific period.
CONSUMPTION 2
Total pellet consumption: Pellet consumption since the last commissioning of the system.
ASHBOX
Pellet consumption since the last time the ash box was emptied.
Resetting consumption meters / cleaning message
RESET CONS.. 1
Resets consumption meter 1 or the pellet consumption within a specific period of time.
RESET CONS. 2
Resets consumption meter 2 or the pellet consumption since the last commissioning of the system.
RESET ASHBOX
Resets cleaning message W:40 or Empty ash box.
The cleaning message is issued after a pellet throughput of: 4 tons for type BioLyt (50-75) 9 tons for type BioLyt (110-160)
RESET CLEAN
Resets cleaning message W:41 or Clean boiler and bur­ner.
The cleaning message is issued after a pellet throughput of: 6 tons for BioLyt (50) 8 tons for BioLyt (70,75) 12 tons for BioLyt (100,110) 15 tons for BioLyt (130) 18 tons for BioLyt (150,160)
4 212 945 / 00
45
Heating system control
As an example, the procedure for resetting consumption meter 1 is described from step 12 onwards.
RESET CONS.. 1
OFF
12
"RESET CONS. 1" is shown flas­hing on the display.
13
Tap the “PUSH & TURN button” to acknowledge the selected value.
RESET CONS.. 1
OFF
14
“OFF” is shown flashing on the dis­play.
15
Select "SET" by turning the "PUSH & TURN button."
RESET CONS.. 1
SET
16
“SET” is shown flashing on the dis­play.
17
Tap the “PUSH & TURN button” to acknowledge the selected value.
18
Tap the "Information" key three times.
i
The start display is shown
(basic display).
4 212 945 / 00
46
Heating system control
4.11.4 Changing off-periods for the extraction system
MO. 16 AUG.'04
14 / 00 / 62.5
C
Start - Basic display
1
Press the “PUSH & TURN button” for 3 seconds.
TIMEPROGRAMS
2
“TIMEPROGRAMS” is shown flas­hing on the display.
3
Select "FFA" by turning the "PUSH & TURN button."
FFA
4
“FFA” is shown flashing on the dis­play.
5
Tap the “PUSH & TURN button” to acknowledge the selected value.
INFORMATION
6
“INFORMATION” is shown flashing on the display.
7
Select "FILLING" by turning the "PUSH & TURN button."
4 212 945 / 00
47
Heating system control
FILLING
8
“FILLING” is shown flashing on the display.
9
Tap the “PUSH & TURN button” to acknowledge the selected value.
PARAMETER 6
12:30
10
"PARAMETER 6" is shown flashing on the display.
11
Turn the "PUSH & TURN button" to find the following values:
Changing the off-periods Time
PARAMETER 6
Begin filling off-period 1 12:30
PARAMETER 7
End filling off-period 1 15:30
PARAMETER 8
Begin filling off-period 2 21:30
PARAMETER 9
End filling off-period 2 08:00
The extraction system can be disabled during two periods of time per day. You will find preset values in the table "Changing the off-periods" That is, the extraction system is disabled from 12.30 to 14.30 and from
21.30 to 8.00.
12
Tap the “PUSH & TURN button” to acknowledge the selected value.
PARAMETER 6
12:30
13
Time "12:30" is shown flashing on the display.
4 212 945 / 00
48
Heating system control
14
Set the desired time by turning the “PUSH & TURN button.”
i
Repeat steps 11-15 if you
wish to enter further off-pe­riods.
15
Tap the “PUSH & TURN button” to acknowledge the selected value.
16
Tap the "Information" key three times.
i
The start display is shown
(basic display).
4 212 945 / 00
49
Heating system control
4.11.5 Special symbols
MO. 16 AUG.'04
14 / 00 / 62.5
C
Ice crystal symbol: System frost protection activated
MO. 16 AUG.'04
14 / 00 / 62.5
C
Sunshade symbol: Summer disconnection active (heating switched off, DHW according to program).
HEAT GENER.
W:40
Cleaning the ash box: Empty the ash box and then reset counter "RESET ASHBOX"
BioLyt (50-75) Cleaning (Chapter 7.3) Reset counter (Chapter 4.11.3)
BioLyt (100-160) Cleaning (Chapter 8.3) Reset counter (Chapter 4.11.3)
HEAT GENER.
W:41
Cleaning the boiler: Clean boiler and burner and then reset counter "RESET CLEAN"
BioLyt (50-75) Cleaning (Chapter 7.3) Reset counter (Chapter 4.11.3)
BioLyt (100-160) Cleaning (Chapter 8.3) Reset counter (Chapter 4.11.3)
4.11.6 Maintenance message
-MAINTENANCE
Maintenance message (optional): If the display shows the basic display alternating with the maintenance prompt, call customer service. To temporarily suppress this message, press the Manu­al mode/Emission key
and acknowledge accor­ding to the display "RESET SET" by pressing the PUSH & TURN button for 3 seconds.
4 212 945 / 00
50
Heating system control
4.11.7 Optional accessories
Room station RS-T
The Room station RS-T offers additional operating convenience through decentralised monitoring and intervention options, since every heating circuit can be assigned with its own individual room station. Moreover, the central unit contains various control and regulating func­tions which can only be activated in conjunction with a room station. These include:
- Optimisation functions
- Automatic heating curve adaptation System-specific temperatures and switching times can be checked and modified via five control keys, also allowing the definition of individual system programs. The operation of the room station and the boiler control unit is identical.
Remote setting device with room sensor RFF-T
This auxiliary device monitors the current room temperature and allows the desired room temperature to be corrected. With the integrated operating mode key, you can select continuous hea­ting, reduced heating or automatic mode according to a preset automatic program stored in the central unit.
4 212 945 / 00
51
Fault repair
5. Fault repair
5.1 Blocking switch and reset button
The controller comprises a comprehensive alarm logic which displays the fault type by means of the corresponding error code, depending on the unit version.
i
Press the Reset button under the hinged cover if the display shows “Error.” If this hap­pens frequently, notify your Customer Ser­vice centre.
For further information, see the overview of alarms (Chapter 5.4/ 5.5).
Control panel fuse
Reset
Hinged cover with brief operating inst­ructions
Blocking switch and burner fault lamp
5.2 Display of heating regulator alarms
FLOW
ERROR 12-0
Example of sensor alarms (short-circuit or interruption) Error code 10-20 and index 0 or 1
see Chapter 5.4
5.3 Display of boiler controller alarms
If the display shows a fault message with "HEAT GENER", a boiler malfunction has occurred.
HEAT GENER.
ERROR E:02
Example of pellet boiler alarms (interruption/ short-circuit flue gas sensor)
see Chapter 5.5
4 212 945 / 00
52
Fault repair
FAULT REPORTING OVERVIEW TopTronic®T
Status
Designation
Fault type
Code
Remark
System External sensor Interruption 10-0
System External sensor Short-circuit 10-1
System Boiler sensor Interruption 11-0
System Boiler sensor Short-circuit 11-1
System Flow sensor 1 Interruption 12-0 MC1=off, YK1=no current
System Flow sensor 1 Short-circuit 12-1 MC1=off, YK1=no current
System Storage sensor Interruption 13-0
System Storage sensor Short-circuit 13-1
System VE 2 Interruption 14-0
System VE 2 Short-circuit 14-1
System VE 2 Alarm 14-7
System VE 3 Interruption 15-0
System VE 3 Short-circuit 15-1
System VE 3 Alarm 15-7
System VE 1 Interruption 16-0
System VE 1 Short-circuit 16-1
System VE 1 Alarm 16-7
System Solar tank sensor Interruption (KSPF) 17-0
System Solar tank sensor Short-circuit (KSPF) 17-1
System Flow sensor 2 Interruption 18-0 MC2=off, YK2=no current
System Flow sensor 2 Short-circuit 18-1 MC2=off, YK2=no current
System Collector sensor Interruption (KVLF) 19-0
System Collector sensor Short-circuit (KVLF) 19-1
System Room sensor (RS) Interruption 20-0
System Room sensor (RS) Short-circuit 20-1
System Burner 1 No switching off (1 min) 30-2 With par. log. alarm can be switched off
System Burner 1 No switching on (10 min) 30-3 With par. log. alarm can be switched off
System Burner 2 No switching off (1 min) 31-2 With par. log. alarm can be switched off
System Burner 2 No switching on (10 min) 31-3 With par. log. alarm can be switched off
System Exhaust gas temperature Exceeding 33-5
System Exhaust gas temperature SLT triggered 33-8
System Cleaning stage 1 Triggering by date 40-1
System Cleaning stage 1 Triggering by interval 40-2
System Cleaning stage 1 Triggering by counter 40-4
System Maintenance stage 1 Triggering by date 41-1
System Maintenance stage 1 Triggering by interval 41-2
System Maintenance stage 1 Triggering by counter 41-4
System Cleaning stage 2 Triggering by date 42-1
System Cleaning stage 2 Triggering by interval 42-2
System Cleaning stage 2 Triggering by counter 42-4
System Maintenance stage 2 Triggering by date 43-1
System Maintenance stage 2 Triggering by interval 43-2
System Maintenance stage 2 Triggering by counter 43-4
5.4 Overview of alarms, heating regulator TopTronic®T
4 212 945 / 00
53
Fault repair
FAULT REPORTING OVERVIEW TopTronic®T
Status
Designation
Fault type
Code
Remark
Logical Boiler temperature Not reached (90 min) 50-4
Logical Tank temperature Not reached (4 h) 51-4
Logical Flow temperature MC1 Not reached (1 h) 52-4
Logical Flow temperature MC2 Not reached (1 h) 53-4
Logical Room temperature HC Not reached (3 h) 54-4
Logical Room temperature MC1 Not reached (3 h) 55-4
Logical Room temperature MC2 Not reached (3 h) 56-4
System
Lock by energy supply company ST 2
Address collision 70-0
System Activity No T2B signal 70-1
System Activity No FA signal 70-6
System Activity
Regulator with address 10 is missing
70-8
System
Activity
Data bus error
70-9
No Hoval regulator
System HP return sensor Return min. temp. below setpoint 85-4
System HP return sensor Return max. temp. exceeded 85-5
System QF
Heat source min. temp. below setpoint
86-4
System QF
Heat source max. temp. exceeded
(cooling operation)
86-5
System
QF
Fault heat source sensor
--
Standard signal «VE-x»
System
WPS
Variable input HP fault
87-7
System
Pulse counter
No pulse (5 min)
90-0
System
Fault
Warning
W:XX
Warning in automatic fi ring device
System
Fault
Lock-out
E:XX
Fault in automatic fi ring device
System
Fault
Blocking
B:XX
Fault in automatic fi ring device
SENSOR ALLOC.
Par. Designation Factory 10 20 30 40 50 Lev.
1 Balancing external sensor 0 OEM
RS-T Balancing room sensor (only adjustable with RS-T) 0 HF
2 Balancing heat generator 0 OEM
3 Balancing tank sensor 0 OEM
4 Balancing ow sensor 1 0 OEM
5 Balancing ow sensor 2 0 OEM
6 Balancing solar collector sensor 0 OEM
7 Balancing solar buffer sensor 0 OEM
8 Balancing variable input 1 0 OEM
9 Balancing variable input 2 0 OEM
10 Balancing variable input 3 0 OEM
4 212 945 / 00
54
Fault repair
5.5 Overview of alarms, boiler controller
Error code Description What should be done?
E(01)
STL (safety temperature limiter) 1. Boiler STL has tripped:
To unlock, remove the cover on the controller box. Press in the button. Acknowledge the fault by pressing the reset button
2. Burn-back STL has tripped: To unlock, remove the cover of the STL on the down-pipe and press in the button. Acknowledge the fault by pressing the reset button
E:02/ E:03
Interruption/short-circuit, flue gas sensor Contact Hoval specialist
E:04/ E:05
Interruption/ short-circuit, combustion chamber sensor Contact Hoval specialist
E:06/ E:07
Interruption, boiler sensor Contact Hoval specialist
E:12
Feed signal, stoker/feeder screw: screw at a standstill
Contact Hoval specialist
E:13/ E:14
Interruption/ short-circuit, burn-back sensor Contact Hoval specialist
E:15
Burn-back Clean burner (see Chapter "Cleaning and maintenance“), if fault occurs
repeatedly, contact Hoval specialist
E:16
Number of start attempts exceeded (minimum combustion chamber temperature not re­ached after fire-bed build-up)
Contact Hoval specialist
E:29
Vacuum not OK Clean burner and boiler (see Chapter "Cleaning and maintenance“), if
fault occurs repeatedly at short intervals, contact Hoval specialist
E:31
Ball valve not closing/opening Contact Hoval specialist
E:33
Ignition not successful (no increase in combustion chamber temperature during the ignition process)
Clean burner (see Chapter "Cleaning and maintenance“), if fault occurs repeatedly, contact Hoval specialist
E:37
Filling time exceeded, but pellet hopper is empty
1. Check whether there are pellets left in the storage room
2. Check whether the suction hoses are clogged with pellets at some point Otherwise: contact Hoval specialist.
E:38
Filling process aborted due to:
1. Screw motor overheating or
2. Door contact switch (if fitted) opened or
3. Max. number of filling attempts exceeded (only possible if suction system is equipped with negati­ve pressure monitor)
1./ 3.: Check suction hoses and screw transfer station for blockages and remove if necessary.
2. Close the door to the storage room
E:50
Internal control error Contact Hoval specialist
B:20
Maximum boiler temperature exceeded
B:21
Blocking switch active Burner is switched off and blocked.
B:32
Filling level sensors, wrong signal order 1. Check pellet hopper for bridging (lower sensor is "in the open“ although
the upper sensor is still covered with material) as a result of too much dust in the fuel
2. Empty pellet hopper and clean it, remove dust from the sensors
3. Otherwise: contact Hoval specialist
B:34
Value measured by the lambda probe does not recover
W:08/ W:09
Interruption/ short-circuit, return sensor Contact Hoval specialist
W:10/ W:11
Interruption/short-circuit burner buffer sensor (if fitted)
Contact Hoval specialist
W:17
Filling time exceeded 1. Check whether pellets are available in the storage room
2. Check if pellets are blocking the suction hoses Otherwise: contact Hoval specialist.
W:18
Storage room empty (only if filling level sensor is fitted in the storage room)
Order pellets
E:19/ W:19
Lambda probe test failed
W:22
Filling blocked through off-period
W:23
Fire-bed extinguished during operation
E:24/ W:24
Lambda probe test aborted as a result of flue gas temperature
W:30
Low vacuum (10% increase active)
W:40
Empty ash box Empty ash box and reset counter; see Page 63
W:41
Boiler cleaning necessary Clean boiler and burner and reset counter
W:42
only with manual filling without automatic filling system: pellet hopper empty
Re-fill pellets
4 212 945 / 00
55
Fault repair
Fault Check/cause Remedy Chapter
Pellet boiler - Is power supply present - Check fuses. Turn on does not main switch start up
- Is the red fault indiactor lit - Press reset button (12) 4.4.4
- Contact customer service
Radiators - Are the slide valves in the heating - Open them do not flow and return open heat up
- Is the TopTronic
®
T timer - Check as described in operating 4.7
set correctly manual for the heating regulator
- Check water level and pressure - Top up and vent heating
- Are the radiator valves open - Open them
- The heating circulation pump - Open locking screw is not running Turn end of shaft vigorously with a screw- driver until there is no longer resistance
- Mixer does not open automatically - Open manually; call customer service
No - The charging pump is not running - Unscrew the locking screw hot Turn shaft end vigorously with a water screwdriver until there is no longer resistance
- Is there air in the charging line - If necessary, vent by hand
- Operate automatic air vent manually
5.6 Checklist in case of faults
Please note!
Please use the above checklist when carrying out the checks in the case of malfunctions.
If you are not able to resolve the fault, please contact the heating engineer or Hoval Customer Service.
i
4 212 945 / 00
56
Checking the water level
6. Checking the water level
i
If the system pressure is too low (check pressure gauge), inform your
installer or top it up with water.
Refilling the heating system
The heating system can normally be filled and top­ped up with mains water. In exceptional cases, the water quality may vary strongly and it might not al­ways be suitable for filling the heating system (highly corrosive or very hard water). Please contact a cer­tified specialist company in such cases.
Follow the procedure below
• Set main switch to "O."
• The shut-off valves in the flow and return lines must be open.
• The boiler filling and drain cock is accessible after removing the cover on the front of the boiler.
• Connect a hose between the filling cock and the water tap:
- Fill the hose with water before establishing the
connection to prevent any air from entering the heating system
- Unscrew the hose again after filling to break the
connection reliably.
• Slowly fill with water while checking the water level on the hydrometer or manometer.
• Open the bleed valves briefly after topping up until all the air has been vented from the radiator.
4 212 945 / 00
57
Maintenance BioLyt (50-75)
7. Maintenance BioLyt (50-75)
7.1 Commissioning
When commissioning the system, also observe the notes in the installation manual.
1. Checks:
• Are the slide valves in the heating flow and return lines open?
• Is the combustion air supply into the boiler room adequate?
• Is the main switch on the boiler control unit set to “ON”?
• Is the combustion chamber closed?
• Is the connection between burner and pellet hop­per OK (clamping ring)?
• Are all the burner connectors plugged in?
• Is the cleaning cover with the induced draught fan (top rear) closed?
• Is the pellet hopper full?
• Is the pellet hopper cover sealed tight?
2. Starting the burner:
• Takes place automatically via the heating regula­tor when there is a heat demand.
7.2 Regular checks
• Is the seal in the pellet hopper fitted cleanly and correctly?
• Is the combustion chamber door properly closed (palm grip closed tight)?
• Is the cleaning cover properly closed (all wing nuts tightened)?
7.3 Cleaning the boiler
Caution: NEVER use the main switch, but always the Stop button (or
TopTronic®T) to turn the burner off.
Checking / cleaning every 4-8 weeks or accor­ding to display or every 4 tonnes of pellets
1. Switch off the burner:
- Operate blocking switch
- Wait for burn-out to be completed
2. Allow boiler to cool down for 20 minutes
3. Remove the bottom front casing panel
(1, Fig. 03)
4. Unscrew and remove palm grip (2, Fig. 04), pull
out threaded rod and slide the ash box out from the front. Dispose of the ash.
1
Fig. 03
i
The threaded rod on the front can be screwed in for transporting the ash
box (3, Fig. 05).
2
Fig. 04
3
Fig. 05
5. Follow the steps above in reverse order to re­assemble; ensure that the ash box is fitted and sealed properly.
6. If necessary, reset display message "W:40", see chapter 9, page 63.
4 212 945 / 00
58
Maintenance BioLyt (50-75)
Cleaning every 2-6 months or every 6 tonnes of pellets (BioLyt 50) or every 8 tonnes of pellets (BioLyt 70,75)
Only by service engineers
1. Switch off the burner:
- Operate blocking switch
- Wait for burn-out to be completed
2. Allow boiler to cool down for 20 minutes.
3. Turn the boiler off with an omnipolar switch (must be de-energised)
4. Remove the bottom front casing panel.
5. Emptying the ash box: Unscrew palm grip, pull out the threaded rod and slide the ash box out from the front. Dispose of the ash.
6. Remove the pellet hopper cover.
7. Unscrew and remove the top front casing panel.
8. Remove both side plates: pull forward and then push down to remove them.
9. Open the clamping ring above the rotary valve (Fig. 06).
Remove the clamping ring before open ing the combustion chamber
door.
Fig. 06
10. Open the combustion chamber door (2 palm grips BioLyt (50), 4 palm grips BioLyt (70,75) Fig. 07). Check and ensure that all the parts have cooled down sufficiently! Wear safety gloves.
Fig. 07
11. Remove the ash from within the combustion cham­ber and from the baffle plate, ideally with a vacuum cleaner. Special attention must be paid to cleaning the flue gas outlet in the standing flue (arrows ­Fig. 08).
Fig. 08
i
Small tension cracks in the refracto­ries and slight deformation in the in­side of the burner and the combusti­on chamber will not affect the correct
functioning of the boiler. They are the
result of stresses caused by tempera­ture changes.
4 212 945 / 00
59
Maintenance BioLyt (50-75)
12. Remove the residues from the burner very care­fully, using a vacuum cleaner - especially in the rear area (directly beneath the feeder screw); the air holes must be free from any residues. Also vacuum the top of the burner. Wipe off any ash from the combustion chamber sensor (Fig. 09).
Fig. 09
Annual cleaning or every 18 tonnes of pellets (BioLyt 50) or every 24 tonnes of pellets (BioLyt 70,75)
In addition to the points described under “Cleaning every 2-6 months,” the flue gas collector must be cleaned once a year. To do this, dismantle the flue gas collector lid, including the fan (Fig. 10).
Procedure:
1. Remove casing panel
2. Disconnect plug (A)
3. Unscrew wing nuts (B)
4. Detach flue gas collector cover (C)
5. Vacuum out the ashes (D, Fig. 11)
The mechanism of the automatic heating surface cleaner should not be dismantled. The flue gas conduit between the boiler and the flue gas duct should also be checked for ash residues and cleaned if necessary.
Remove any dust adhering to the lambda probe (E), using a vacuum cleaner.
Also observe: Chapter "Maintenance" in the "Techn. Information / installation instructions"
It is essential to clean the entire boiler thoroughly at the end of the heating season. Insufficient cleaning leads to increased fuel consump­tion and also shortens the service life of the boiler.
i
Small tension cracks in the refrac-
tory lining will not affect the correct functioning of the boiler. They are the
result of stresses caused by tempera­ture changes.
The boiler should be serviced in accordance with the applicable country-specific regulations - but at least once per year - or thorough cleaning performed by a heating engineer (chimney sweep, installer or Hoval Customer Service).
E CA
B
B
B
B
Fig. 10
D
Fig. 11
4 212 945 / 00
60
Maintenance BioLyt (100-160)
1
2
Fig. 12
4. If the ash box is full: Unscrew palm grips (2, Fig.
12), pull out the threaded rods and slide the ash box out from the front (Fig. 13). Dispose of the ash.
Fig. 13
5. Follow the steps above in reverse order to re­assemble; ensure that the ash box is fitted and sealed properly, tighten the palm grips firmly and close the cover.
6. If necessary, reset display message "W:40", see chapter 9, page 63.
8. Maintenance BioLyt (100-160)
8.1 Commissioning
When commissioning the system, also observe the notes in the installation manual.
1. Checks:
• Are the slide valves in the heating flow and return lines open?
• Is the combustion air supply into the boiler room adequate?
• Is the main switch on the boiler control unit set to “ON”?
• Is the combustion chamber closed?
• Is the connection between burners and pellet box OK (clamping ring)?
• Are all the burner connectors plugged in?
• Is the cleaning cover with the induced draught fan (top rear) closed?
• Is the pellet hopper full?
• Is the pellet hopper cover sealed tight?
2. Starting the burner:
• Takes place automatically via the heating regula­tor when there is a heat demand.
8.2 Regular checks
• Is the seal in the pellet hopper fitted cleanly and correctly?
• Is the combustion chamber door properly closed (palm grip closed tight)?
• Is the cleaning cover properly closed (all wing nuts tightened)?
8.3 Cleaning the boiler
Caution: Always switch the burner off
via the blocking switch.
Checking / cleaning every 4-8 weeks or accor­ding to display or every 9 t of pellets
1. Switch off the burner:
- Operate blocking switch
- Wait for burn-out to be completed
2. Let the boiler cool down for 20 minutes
3. Remove the front cover (1, Fig. 12) to check the filling level of the ash box.
4 212 945 / 00
61
Maintenance BioLyt (100-160)
Cleaning every 2-6 months or according to display or every 12 t of pellets for the BioLyt (100,110), 15 t of pellets for the BioLyt (130) and 18 t of pellets for the BioLyt (150,160).
Only by service engineers
1. Switch off the burner:
- Operate blocking switch
- Wait for burn-out to be completed
2. Allow boiler to cool down for 20 minutes.
3. Turn the boiler off with an omnipolar switch (must be de-energised)
4. Emptying the ash box: Unscrew palm grip (2, Fig.
12), pull out the threaded rod and slide the ash box out from the front. Remove the cover of the ash box.Dispose of the ash.
5. Unscrew and remove the front casing panel.
6. Remove both side plates: pull forward and then push down to remove them.
7. Open the clamping ring above the rotary valve (Fig. 14).
Remove the clamping ring before opening the combustion chamber
door.
Fig. 14
8. Open the combustion chamber door (palm grips, Fig. 15). Check and ensure that all the parts have cooled down sufficiently! Wear safety gloves.
Fig. 15
9. Remove the ash from within the combustion chamber and from the baffle plate, ideally with a vacuum cleaner. Special attention must be paid to cleaning the flue gas outlet in the standing flue (arrows - Fig. 16).
Fig. 16
10. Remove the residues from the burner very ca­refully, using a vacuum cleaner - especially in
the rear area (directly beneath the feeder screw); the air holes must be free from any residues. Also vacuum the top of the burner. Wipe off any ash from the combustion chamber sensor (Fig. 17).
Fig. 17
i
Small tension cracks in the refracto­ries and slight deformation in the in­side of the burner and the combusti-
on chamber will not affect the correct functioning of the boiler. They are the
result of stresses caused by tempera­ture changes.
4 212 945 / 00
62
Maintenance BioLyt (100-160)
Clean annually or every 36 t of pellets for the BioLyt (100,110), 45 t of pellets for the BioLyt (130) and 54 t of pellets for the BioLyt (150,160).
In addition to the points described under “Cleaning every 2-6 months,” the flue gas collector must be cle­aned once a year. To do this, dismantle both covers of the flue gas collector lids in front of and behind the fan (Fig. 18).
Procedure:
1. Remove casing panel
2. Disconnect plug (A)
3. Unscrew wing nuts (B)
4. Remove insulation mats
5. Remove flue gas collector cover (C)
6. Vacuum out the ashes (D, Fig. 19)
The mechanism of the automatic heating surface cleaner should not be dismantled. The flue gas conduit between the boiler and the flue gas duct should also be checked for ash residues and cleaned if necessary.
Remove any dust adhering to the lambda probe (E), using a vacuum cleaner.
Also observe: Chapter "Maintenance" in the "Techn. Information / installation instructions"
It is essential to clean the entire boiler thoroughly at the end of the heating season. Insufficient cleaning leads to increased fuel consump­tion and also shortens the service life of the boiler.
i
Small tension cracks in the refrac-
tory lining will not affect the correct functioning of the boiler. They are the
result of stresses caused by tempera­ture changes.
The boiler should be serviced in accordance with the applicable country-specific regulations - but at least once per year - or thorough cleaning performed by a heating engineer (chimney sweep, installer or Hoval Customer Service).
A
B
B
B
B
B
B
B
B
CC
Fig. 18
D E
Fig. 19
4 212 945 / 00
63
Emptying ashbox / Resetting the counter
9. Emptying the ash box and resetting the counter
9.1 Resetting the message "empty ash box" (W:40)
WE. 27. OCT.'11
14:00 22.0
C
3 sec. press
TIMEPROGRAMS
turning until....
FFA
press shortly
INFORMATION
turning until....
COUNTER
press shortly
CONSUMPTION 1
turning until....
RESET ASHBOX
OFF
press shortly
RESET ASHBOX
OFF
turning until....
now the message "Emptying ashbox" is reset; the counter is now starting again at "0"
press 3 x
RESET ASHBOX
SET
press shortly!
RESET ASHBOX
SET
4 212 945 / 00
64
How you can save energy / Disposal instructions
10. How you can save energy
The room temperatures and the operating times of the heating system have a significant influence on fuel consumption.
Lowering room temperature by 1°C will result in a fuel saving of up to 6%. For this reason, bear in mind the following tips:
• It pays to turn off the radiators in unused rooms, as long as there is no risk of frost and no moisture damage to the building structure or furniture is to be expected.
• Set the switch on your heating regulator to “Sum­mer” as soon as the daily average outside tempe­rature exceeds 12°C.
• In the main living areas, additional heat is often generated by people, televisions, fire places, tiled stoves and also direct sunlight. These cannot be compensated for by a weather-dependent regula­tor. The installation of thermostatic radiator valves might be advisable in these rooms.
Draughts in the home are not only unpleasant, but also indicate that heating energy is being lost.
You can save fuel if you ...
• Keep the doors and windows closed in winter.
• Operate kitchen and bathroom ventilation fans only when vapours and smells need to be extracted.
• Only ventilate for short periods, but more often.
• Seal doors and windows to prevent constant lea­kage losses.
Insulation will help retain precious heat.
Take advantage of these possibilities and...
• Close the window and door shutters at night.
• Draw the curtains in the evening.
• Make sure that heating and hot water pipes are insulated in unheated rooms.
Maintaining the temperature of the radiators as low as possible will prevent unnecessary heat losses. For this reason, it is important to ensure that the ra­diator can release its heat into the room without any obstructions. You should therefore avoid:
• Covered radiators
• Floor-length curtains in front of radiators
• Windowsills covered with objects that prevent any air ingress.
Savings are also possible for water heating.
• Set the hot water temperature as low as possible. Find out at what temperature there is still sufficient hot water available.
• If you have installed a hot water circulation pump, it is worth switching it off during the night with a timer.
11. Instructions on proper dispo-
sal of individual system com­ponents
The individual components (particularly boiler body, refractory bricks, casing panels, insulation mats and electric control) must be disposed of separately.
4 212 945 / 00
65
United Kingdom
Hoval Ltd.
Northgate Newark Nottinghamshire NG24 1JN Phone +44 1636 67 27 11 Fax +44 1636 67 35 32 www.hoval.co.uk
Principality of Liechtenstein
Hoval Aktiengesellschaft
Austrasse 70 9490 Vaduz Phone +423 399 24 00 Fax +423 399 24 11 www.hoval.com
Switzerland
Hoval AG
General Wille-Strasse 201 CH-8706 Feldmeilen Phone +41 44 925 61 11 Fax +41 44 923 11 39 www.hoval.ch
Germany
Hoval GmbH
Humboldtstrasse 30 D-85609 Aschheim-Dornach Phone +49 89 92 20 97-0 Fax +49 89 92 20 97-77 www.hoval.de
Austria
Hoval Gesellschaft mbH
Hovalstrasse 11 A-4614 Marchtrenk Phone +43 50 365 - 0 Fax +43 50 365 - 5005 www.hoval.at
Italy
Hoval s.r.l.
Via per Azzano San Paolo, 26/28 I-24050 Grassobbio (BG) Phone +39 035 52 50 69 Fax +39 035 52 69.59 www.hoval.it
France
Hoval SAS
6, rue des Bouleaux F-67100 Strasbourg Phone +33 3 88 60 39 52 Fax +33 3 88 60 53 24 www.hoval.fr
Conservation of Energy - Protection of the Environment
Loading...