36
42
54-1/2
Side View
27
Rear View
36
42
27
2
3-1/2
2-1/2
25-1/2*
Side View
Rear View
5-1/4
25-3/4
23-1/2
11-1/2
NWXR483EG – Hotpoint 6.0 Cu. Ft. Extra-Large Capacity Electric Dryer
Dryer Dimensions (in inches)
* 24-1/2” from the edge of the side panel to the front.
Specification Revised 5/09
470146
25-1/2” from front to edge of end caps.
Listed by
Underwriters
Laboratories
Exhaust Options:
4-way via rear, right, left and bottom.
Circuit Requirements:
An individual, properly-grounded branch circuit, protected by a
30-amp circuit breaker or a time-delay fuse, is required.
Electric Dryer Rating:
240V, 5600W, 60Hz, 24 Amp
208V, 4400W, 60Hz, 22 Amp
Installation Information: For complete information, see installation
instructions packed with product for current dimensional data.
Special Installation Requirements
Alcove or Closet Installation:
• If your dryer is approved for installation in an alcove or closet, it will be stated on a
label on the dryer back.
• The dryer MUST be exhausted to the outside.
• Minimum clearances between dryer cabinet and adjacent walls or other surfaces are:
0" either side
3" front and rear
• Minimum vertical space from floor to overhead cabinets, ceilings, etc. is 52”.
• Closet doors must be louvered or otherwise ventilated and must contain a minimum of
60 sq. in. of open area equally distributed. If this closet contains both a washer and a
dryer, doors must contain a minimum of 120 sq. in. of open area equally distributed.
• No other fuel-burning appliance shall be installed in the same closet with a gas dryer.
Bathroom or Bedroom Installation:
• The dryer MUST be exhausted to the outdoors.
• The installation must conform with the local codes, or in the absence of local codes,
with the National Electric Code and National Fuel Gas Code, ANSI Z223 for gas dryers.
Minimum Clearances other than Alcove or Closet Installation:
• Minimum clearances to combustible surfaces
0" both sides
3" rear
NWXR483EG – Hotpoint 6.0 Cu. Ft. Extra-Large Capacity Electric Dryer
0 90 ft. 60 ft.
1 60 ft. 45 ft.
6.0 and 5.8 cu. ft. 2 45 ft. 35 ft.
Capacity Models 3 35 ft. 25 ft.
all Electric Dryers 4 25 ft. 15 ft.
0 90 ft. 60 ft.
6.0 and 5.8 cu. ft. 1 60 ft. 45 ft.
Capacity Models 2 45 ft. 35 ft.
all Gas Dryers 3 30 ft. 25 ft.
Portable/Stationary Models
DSKS433EB 0 46 ft. 37 ft.
DSKS333EC 1 38 ft. 30 ft.
DSKP333EC 2 31 ft. 22 ft.
WSM2780H 3 24 ft. 15 ft.
0 56 ft. 42 ft.
1 46 ft. 36 ft.
Unitized Model 2 34 ft. 28 ft.
WSM2700H 3 32 ft. 18 ft.
Unitized Models 0 43 ft. 36 ft.
WSM2420D 1 33 ft. 26 ft.
WSM2480D 2 23 ft. 16 ft.
Number
of
90°
Turns
Maximum Length of
4"-Dia. Rigid Metal Duct
Exhaust Hood Type
Domestic
Dryer Models
A
4" OpeningB2-1/2"
Opening
Best Performance
B
2-1/2
4
A
A
Dryer Exhausting Information – Use Metal Duct Only
Vertical and Horizontal Ducting
Specification Revised 5/09
470146
For complete information, see installation instructions packed with your dryer.
Ducting Materials:
For best performance, this dryer should be vented with 4" diameter all rigid metal exhaust duct.
If rigid metal duct cannot be used, then UL-listed flexible metal (semi-rigid) ducting can be used
(Kit WX08X10077). In special installations, it may be necessary to connect the dryer to the
house vent using a flexible metal (foil-type) duct. A UL-listed flexible metal (foil-type) duct may
be used ONLY in installations where rigid metal or flexible metal (semi-rigid) ducting cannot be
used AND where a 4” diameter can be maintained throughout the entire length of the transition
duct. Please see installation instruction packed with your dryer for complete instructions when
using flexible metal (foil type) ducting.
Exhaust Length Calculation:
1. Determine the number of 90° turns needed for your installation. If you exhaust to the side or
bottom of dryer, add one turn.
2. The maximum length of 4' rigid (aluminum or galvanized) duct which can be tolerated is
shown in the table.
A turn of 45° or less may be ignored. Two 45° turns within the duct length should be treated
as a 90° elbow. A turn over 45° should be treated as a 90° elbow.
Dryers must be exhausted to the outside.
Caution: For personal safety do not terminate exhaust into a chimney, under any enclosed
house floor (crawl space), or into an attic, since the accumulated lint could create a fire hazard or
moisture could cause damage. Never terminate the exhaust into a common duct or plenum with
a kitchen exhaust, since the combination of lint and grease could create a fire hazard.
Exhaust ducts should be terminated in a dampered wall cap to prevent back drafts, bird nesting,
etc. The wall cap must also be located at least 12" above the ground or any other obstruction
with the opening pointed down.
Listed by
Underwriters
Laboratories