8 9
INSTALLATION INSTRUCTIONS
Your Hotpod should only be installed by competent personnel in the strict application
of normal practices and all safety precautions. All local regulations, including those
referring to national and European standards need to be complied with when installing
the appliance.
An incorrectly installed stove can cause serious accidents.
The manufacturer’s responsibility shall be limited to the supply of the equipment only.
THE ROOM
VENTILATION: For satisfactory operation with a natural draught, check that sufcient
air for combustion is available in the room. The Hotpod should be installed in a room
with a permanently open air vent (e.g. air brick) with an opening of at least 1100mm²
(or 2350mm² if a draught stabiliser is tted). The vent should be installed in such a
way that it is not liable to blockage. It is a good idea where possible to position the air
vent close to the Hotpod to prevent cold drafts travelling across the room.
Extractor fans must not be placed in the same room as the Hotpod.
FLOORS: Before installing the Hotpod, you must ensure that the load-bearing capacity
of the oor can withstand the weight of the Hotpod plus the ue pipe and connections.
If an existing construction doesn’t meet this prerequisite, suitable measures (e.g. load
distributing plate ) should be taken to achieve it.
HEARTH: The hearth must be suitable for use with solid fuel burning appliances and
must comply with Current Building Regulations. If in doubt, consult your local buildings
inspector.
The Hotpod hearth temperature does not exceed 100 degrees Celsius and therefore
may be placed on a 12mm non-constructional hearth directly onto the oor.
CLEARANCES: The Hotpod should not be positioned close to combustible materials.
The minimum distance to combustible materials is 500mm. This includes above the
hotplate e.g. to a wooden mantelpiece or lintel.
The recommended minimum clearance to non-combustibles (e.g. the walls of the
replace) is 100mm. This allows for free air movement around the Hotpod improving
convection and therefore efciency.
THE FLUE
The Hotpod has an outlet designed for 125mm (5”) ue pipe (or connecting pipe
into an existing masonry chimney). It can be used with either a top or rear ue by
swapping the ue spigot and the blanking plate. They should both be sealed to the
Hotpod body with a suitable proprietary sealant such as re cement.
THE FLUE MUST NOT BE SHARED WITH OTHER APPLIANCES.
The ue must not be supported by the stove.
The ue must be in good condition and must provide sufcient draught.
THE FLUE DRAUGHT SHOULD BE 12PA. A FLUE WITH A DRAUGHT MUCH
ABOVE OR BELOW 12 PA CAN BE DANGEROUS THROUGH EITHER INEFFICIENT
OR OVER BURNING.
The ue must be suitable for the installation of solid fuel burning appliances and
comply with Current Building Regulations.
The ue must be clean. It should be swept to remove soot and dislodge tar deposits.
If the chimney has any down draught tendency, due to its position in relation to nearby
obstacles, then an anti-down draught cowl must be installed or the chimney height
increased.
If the decompression in the chimney is excessive, a draught stabiliser should be
installed.