Only qualied service technicians should attempt to install, service, or maintain
this icemaker. No service or maintenance should be undertaken until the
technician has thoroughly read this Service Manual. Failure to service and
maintain the equipment in accordance with this manual may adversely affect
safety, performance, and warranty coverage.
Hoshizaki provides this manual primarily to assist qualied service technicians in the
service and maintenance of the icemaker.
Should the reader have any questions or concerns which have not been satisfactorily
addressed, please call, write, or send an e-mail message to the Hoshizaki Technical
Support Department for assistance.
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number ________________________
• Serial Number ________________________
• Complete and detailed explanation of the problem.
2
IMPORTANT
This manual should be read carefully before the icemaker is serviced or
maintenance operations are performed. Only qualied service technicians
should install, service, and maintain the icemaker. Read the warnings
contained in this booklet carefully as they give important information regarding
safety. Please retain this booklet for any further reference that may be
necessary.
CONTENTS
I. Specications ..................................................................................................................... 5
II. General Information ........................................................................................................... 6
A. Construction .................................................................................................................. 6
B. Sequence of Operation ................................................................................................. 7
1. One Minute Fill Cycle .............................................................................................. 7
2. Sanitizing Procedure - Following Cleaning Procedure .......................................... 43
B. Maintenance ............................................................................................................... 44
C. Preparing the Icemaker for Long Storage .................................................................. 44
4
I. Specications
AC SUPPLY VOLTAGE115-120/60/1
AMPERAGE12.0 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY15 A
MAXIMUM FUSE SIZE15 A
APPROXIMATE ICE PRODUCTIONAmbientWATER TEMP. (°F)
PER 24 HR.Temp.(°F)507090
lbs./day ( kg/day )70*592 (269)566 (257)516 (234)
Reference without *marks80572 (260)532 (241)474 (215)
90566 (257)*503 (228)447 (203)
100551 (250)490 (222)396 (180)
SHAPE OF ICECrescent Cube
ICE PRODUCTION PER CYCLE14.3 lbs. (6.5 kg) 720 pcs.
APPROXIMATE STORAGE CAPACITYN/A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)1190(5.7)1040(4.2)
WATER gal./24HR (gal./100 lbs.)99(19.7)259(43.7)
CEC/CEE TIER LEVEL2
ENERGY STARYES
EXTERIOR DIMENSIONS (WxDxH)22" x 27-3/8" x 37-7/16" (560 x 695 x 950 mm)
EXTERIOR FINISHStainless Steel, Galvanized Steel (Rear)
WEIGHTNet 169 lbs. (77 kg), Shipping 200 lbs. (91 kg)
CONNECTIONS - ELECTRICPermanent - Connection
- WATER SUPPLYInlet 1/2" FPT
- DRAINOutlet 3/4" FPT
3/8" OD Tube
CUBE CONTROL SYSTEMFloat Switch
HARVESTING CONTROL SYSTEMHot Gas and Water, Thermistor and Timer
ICE MAKING WATER CONTROLTimer Controlled. Overflow Pipe
COOLING WATER CONTROLN/A
BIN CONTROL SYSTEMThermostat
COMPRESSORHermetic, Model RST55C1E-CAA
CONDENSERAir-Cooled , Fin and tube type
EVAPORATORVertical type, Stainless Steel and Copper
REFRIGERANT CONTROLThermostatic Expansion Valve
REFRIGERANT CHARGER-404A, 1 lb. 11 oz. (765g)
DESIGN PRESSUREHigh 467PSIG, Low 230PSIG
P.C. BOARD CIRCUIT PROTECTIONHigh Voltage Cut-out ( Internal )
COMPRESSOR PROTECTIONAuto-reset Overload Protector ( Internal )
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pressure Control Switch
LOW WATER PROTECTIONFloat Switch
ACCESSORIES -SUPPLIEDN/A
-REQUIREDIce Storage Bin
OPERATING CONDITIONSVOLTAGE RANGE104 - 127 V
AMBIENT TEMP.45 -100° F
WATER SUPPLY TEMP.45 - 90° F
WATER SUPPLY PRESSURE10 - 113 PSIG
A. Icemaker
KM-600MAH (air-cooled)
Note: We reserve the right to make changes in specications and design without prior
notice.
5
II. General Information
A. Construction
1. KM-600MAH (air-cooled)
Bin Control Thermostat
Control Switch
Expansion Valve
Spray Tubes
Water Supply Pipe
Condenser
Control Box
Fan Motor
Float Switch
Hot Gas Valve
Drier
Compressor
Water Pump
6
B. Sequence of Operation
The steps in the sequence are as outlined below. When power is supplied, the red
"POWER OK" LED on the control board comes on. A 5-second delay occurs at startup.
Note that the order of the LEDs from the outer edge of the board is 1, 4, 3, 2.
1. One Minute Fill Cycle
LED 4 is on. WV opens and the ll period begins. After 1 minute, the board checks for
a closed F/S. If F/S is closed, the harvest cycle begins. If not, WV will remain energized
through additional 1 minute cycles until water enters the sump and F/S closes. This
serves as a low water safety to protect the PM.
2. Initial Harvest Cycle
LEDs 1, 4, and 2 are on. WV remains open, Comp and HGV energize. The control board
monitors the warming of the evaporator via the thermistor located on the suction line.
When the thermistor reaches 48°F (9°C), the control board reads a 3.9 kΩ signal from
the thermistor and turns harvest termination over to the adjustable harvest timer (S4 dip
switch 1 & 2) which is factory set for normal conditions. The harvest timer has settings
of 60, 90, 120, and 180 seconds. For details, see "II.C.3.b) Harvest Timer (S4 dip switch
1 & 2)." When the harvest timer completes its countdown, the harvest cycle is complete
and the freeze cycle starts. The minimum total time allowed by the control board for a
complete harvest cycle is 2 minutes. WV is energized during harvest for a maximum of
6 minutes or the length of harvest, whichever is shorter. At the end of harvest, the control
board checks the position of F/S and proceeds to the freeze cycle if it is closed or calls
for a 1-minute ll if it is open.
3. Freeze Cycle
LED 1 is on. Comp continues to run, PM and FMS energize, HGV and WV close, and
the freeze cycle starts. For the rst 5 minutes the control board will not accept a signal
from F/S. This 5 minute minimum freeze acts as a short cycle protection. At the end of
5 minutes, F/S assumes control. As ice builds on the evaporator the water level in the
sump lowers. The freeze continues until F/S opens and terminates ice production.
4. Pump-Out Cycle
LEDs 1, 3, and 2 are on. Comp continues to run, HGV opens, and FMS de-energizes.
PM stops for 2 seconds and reverses, taking water from the bottom of the sump and
forcing pressure against the check valve seat allowing water to go through the check
valve and down the drain. At the same time, water ows through the small tube to power
ush the F/S. When the pump-out timer (S4 dip switch 3 & 4) stops counting, the pump
out is complete. The 1st pump out occurs after the 1st freeze cycle. The pump-out
frequency control (S4 dip switch 5 & 6) is factory-adjusted to drain the water tank every
10th cycle thereafter, and no adjustment is required. However, where water quality is
bad and the icemaker needs a pump out more often, the pump-out frequency control
(S4 dip switch 5 & 6) can be set to have a pump out occur every cycle, or every 2, 5, or
10 cycles. For details, see "II.C.3.d) Pump-Out Frequency Control (S4 dip switch 5 & 6)."
7
5. Normal Harvest Cycle
LEDs 1, 4, and 2 are on. Comp and HGV remain energized. PM stops and WV
energizes. The control board monitors the warming of the evaporator via the thermistor
located on the suction line. When the thermistor reaches 48°F (9°C), the control board
reads a 3.9 kΩ signal from the thermistor and turns harvest termination over to the
adjustable harvest timer (S4 dip switch 1 & 2) which is factory set for normal conditions.
The harvest timer has settings of 60, 90, 120, and 180 seconds. For details, see "II.
C.3.b) Harvest Timer (S4 Dip Switch 1 & 2)." When the harvest timer completes its
countdown, the harvest cycle is complete and the freeze cycle starts. The minimum
total time allowed by the control board for a complete harvest cycle is 2 minutes. WV is
energized during harvest for a maximum of 6 minutes or the length of harvest, whichever
is shorter. At the end of harvest, the control board checks the position of F/S and
proceeds to the freeze cycle if it is closed or calls for a 1-minute ll if it is open.
Legend: Comp–compressor; FMS–self-contained fan motor; F/S–float switch;
HGV–hot gas valve; PM–pump motor; WV–inlet water valve
8
Cycle
Pump motor stops
for 2 sec. and then
reverses for 10/20 sec.
each 1, 2, 5, or 10 cycles.
Comp continues
HGV energized
4. Pump-Out
F/S in
control
Freeze cycle
operation turned
over to F/S
5 minute timer
in control
F/S closed
Comp continues
HGV de-energized
WV de-energized
• Minimum freeze time: 5 minutes
• Maximum freeze time: freeze timer setting
F/S Check
PM energized
FMS de-energized
FMS energized
F/S open
1 to 3 minute timer
in control
2. Harvest Cycle3. Freeze Cycle
Thermistor in
• Maximum inlet water valve time: 6 minutes
control
• Maximum harvest time: 20 minutes
Thermistor temp
reaches 48°F (9°C)
F/S closed
Comp energized
HGV energized
(3.9 kΩ or less)
Harvest timer starts
WV continues
Components Energized when the Control Switch is in the "WASH" Position
The "WASH" position on the control switch is used when cleaning and sanitizing the unit. When in the
"WASH" position, power is supplied to the pump motor. With the cleaning valve closed, the cleaner and
sanitizer ow over the outside of the evaporator plate assembly. With the cleaning valve open, the cleaner
and sanitizer ow over both the outside and the inside of the evaporator plate assembly.
Note: Close the cleaning valve after cleaning and sanitizing are complete, otherwise the unit will not re-start
when the control switch is placed in the "ICE" position.
KM-600MAH Sequence Flow Chart and Component Operation
F/S open
Fill Cycle
1. One Minute
Cycle Steps
F/S Check
WV Energized
"E" board will have
Initial startup always
5 second delay
begins here
If F/S is open, compressor stops and cycle returns to 1 minute ll
Legend:
Comp-compressor
FMS-self-contained fan motor
F/S-oat switch
HGV-hot gas valve
PM-pump motor
WV-inlet water valve
9
C. Control Board
• A Hoshizaki exclusive solid-state control is employed in the KM-600MAH Modular
Crescent Cuber.
• All models are pretested and factory-adjusted.
CAUTION
1. Fragile, handle very carefully.
2. The control board contains integrated circuits, which are susceptible to
failure due to static discharge. It is especially important to touch the metal
part of the unit before handling or replacing the board.
3. Do not touch the electronic devices on the board or the back of the board to
prevent damage to the board.
4. Do not change wiring and connections. Do not misconnect K3, K4, and K5,
because the same connector is used for the thermistor and oat switch. K4
is not connected.
5. Always replace the whole board assembly if it goes bad.
6. Do not short out power supply to test for voltage.
10
1. Control Board Layout
Control Products "E" Control Board
"ALARM RESET" Switch
Backup Freeze
Timer LED
Backup Harvest
Timer LED
Alarm Buzzer
S4 Dip Switch
"OUTPUT TEST" Switch
(used to test relays on board)
Connector K3
Harvest Control
(thermistor)
Connector K4
Open
(not connected)
Power LED
(lights when
power is supplied
to the board)
Relay LEDs (4)
(indicate which
relays are energized
as listed below)
LED 2
Hot Gas Valve
(HGV)
Self-Contained Fan
Motor (FMS) (FMS
off when LED on)
LED 3
Pump Motor (PM)
(on at pump out only)
LED 4
Inlet Water Valve (WV)
LED 1
Compressor (Comp)
Transformer
Connector
Microprocessor
(board revision level
indicated by last 2
digits on label)
Connector K5
Float Switch
Part Number
Connector K1
Pins #1 through #10
#1, 9 Magnetic Contactor
#2 Hot Gas Valve
#3 Self-Contained Fan Motor (FMS)
#4 Pump Motor (icemaking)
#5 Pump Motor (pump out)
#6 Inlet Water Valve
#7, 10 Power Supply
#8 Open
Switch for "C" board
and "ALPINE" board
(service boards only)
Control Board
Part Number2A1410-01 (factory); 2A1410-02 (service)
TypeHOS-001A (Control Products - 10 Pin)
11
2. Features
a) Maximum Water Supply Period – 6 minutes
The inlet water valve will be open during harvest for 6 minutes or the length of harvest
whichever is shorter.
b) Harvest Backup Timer and Freeze Timer
The harvest backup timer shuts down the icemaker if, for two cycles in a row, the harvest
cycle takes more than 20 minutes to complete. The control board will signal this problem
using 2 beeps every 3 seconds.
The freeze timer shuts down the icemaker if, for two cycles in a row, the freeze
cycle takes longer than the time specied to complete. The control board will signal
this problem using 3 beeps every 3 seconds. The time is factory set using S4 dip
switch 9 & 10.
The "ALARM RESET" button on the control board must be pressed with power on to
reset either of these safeties.
c) High Temperature Safety
The temperature of the suction line in the refrigeration circuit is limited by the high
temperature safety. This protects the unit from excessively high temperatures. If the
evaporator temperature rises above 127 ± 7°F (53 ± 4°C), the control board reads a
.804 kΩ signal from the thermistor and operates the safety. This shuts down the circuit
and the icemaker automatically stops.
The control board will signal this problem using 1 beep every 3 seconds. The "ALARM
RESET" button on the control board must be pressed with power on to reset the safety.
d) Low Water Safety
The control board checks the position of the oat switch at the end of the initial 1 minute
water ll cycle and at the end of each harvest cycle.
If the oat switch is in the up position (electrical circuit closed), the control board
changes to the ice making cycle. If the oat switch is in the down position (electrical
circuit open), the control board changes to additional 1 minute water ll cycles until water
enters the sump and the oat switch closes. When the oat switch closes, the control
board changes to the ice making cycle. The unit will not start without adequate water in
the sump. This serves as a low water safety to protect the pump motor from mechanical
seal failure.
e) High Voltage and Low Voltage Cut-outs
The maximum and minimum allowable supply voltages of this icemaker are limited by
the high voltage and low voltage cut-outs.
If miswiring (especially on single phase 3 wire models) causes excessive voltage
(147Vac ±5% or more) on the control board, the high voltage cut-out shuts down the
circuit in 3 seconds and the icemaker automatically stops. The control board will signal
this problem using 7 beeps every 3 seconds.
The icemaker also automatically stops in cases of insufcient voltage (92Vac ±5% or
less). The control board will signal this problem using 6 beeps every 3 seconds.
When the proper supply voltage is resumed, the icemaker automatically starts running
again.
12
f) LED Lights and Audible Alarm Safeties
The red LED indicates proper control voltage and will remain on unless a control voltage
problem occurs. At startup, a 5 second delay occurs while the board conducts an
internal timer check. A beep occurs when the power is turned off.
The green LEDs 1 through 4 energize and sequence from initial startup as listed in the
table below. Note that the order of the LEDs from the outer edge of the board is 1, 4, 3,
2. For more information, see "II.B. Sequence of Operation."
Sequence StepLED
1 Minute Fill Cycle
Harvest Cycle1, 4, and 2WV, HGV,
Freeze Cycle1Comp, PM,
Pump-Out Cycle1, 4*, 3, and 2Comp, HGV,
The built in safeties shut down the unit and have alarms as listed below.
No. of Beeps
(every 3 sec.)
1High Evaporator Temp.
2Harvest Backup Timer
4WV60 seconds
Type of AlarmNotes
(temperature > 127°F)
(53°C)
(harvest > 20 min. for two
cycles in a row)
Energized
Components
Comp
FMS
PM, WV*
Check for harvest problem (stuck HGV or
relay), hot water entering unit, or shorted
thermistor.
Orange LED marked H TIMER lights up.
Check for open thermistor, HGV not opening,
TXV leaking by, low charge, or inefficient
Comp.
Min.Max.Avg.
2 minutes20 minutes3 to 5 minutes
5 minutesfreeze timer
10 seconds 20 seconds *pump-out timer
Time LEDs are On
setting
30 to 35 minutes
setting
3Freeze Timer
(freeze > specified setting
for two cycles in a row)
Timer is factory set using
S4 dip switch 9 & 10
To reset the above safeties, press the "ALARM RESET" button with the power supply on.
6Low Voltage
(92Vac ±5% or less)
7High Voltage
(147Vac ±5% or more)
Legend: Comp–compressor; FMS–self-contained fan motor; F/S–float switch;
HGV
–hot gas valve; PM–pump motor; TXV–thermostatic expansion valve;
WV–inlet water valve
Yellow LED marked F TIMER lights up. Check
for F/S stuck closed (up), WV leaking by, HGV
leaking by, PM not pumping, TXV not feeding
properly, low charge, or inefficient Comp.
Red LED will turn off if voltage protection
operates.
The control voltage safeties automatically
reset when voltage is corrected.
13
3. Controls and Adjustments
CAUTION
Dip switches are factory set. Failure to maintain factory settings may adversely
affect performance and warranty coverage. For more information, contact
Hoshizaki Technical Support at 1-800-233-1940.
a) Default S4 Dip Switch Settings
The dip switches are factory-adjusted to the following positions:
S4 Dip Switch No.12345678910
KM-600MAH
OFF OFF OFF OFF ON ON OFF OFF OFF OFF
Freeze Timer (9 & 10)
Normally off (7 & 8)
Pump-Out Frequency Control (5 & 6)
Do Not Adjust
Pump-Out Timer (3 & 4)
Harvest Timer (1 & 2)
b) Harvest Timer (S4 dip switch 1 & 2)
The harvest timer starts counting when the thermistor reaches 48°F (9°C) at the
evaporator outlet and the control board reads the thermistor's 3.9 kΩ signal. The harvest
timer is factory-adjusted, and no adjustment is required. However, a setting longer than
the factory setting may be advised in cases where the ush provided at harvest needs
to be prolonged for extra cleaning. Before changing this setting, contact Hoshizaki
Technical Support at 1-800-233-1940 for recommendations. Keep in mind that setting
the harvest timer to a longer setting will decrease 24 hour production.
Note that the pump-out timer (S4 dip switch 3 & 4) acts in place of the harvest timer
during cycles with a pump out
S4 Dip Switch SettingTime
No. 1No. 2
OFFOFF60
ONOFF90
OFFON120
ONON180
(seconds)
14
Loading...
+ 31 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.