Only qualified service technicians should attempt to install, service, or maintain
this icemaker. No service or maintenance should be undertaken until the
technician has thoroughly read this Service Manual. Failure to service and
maintain the equipment in accordance with this manual may adversely affect
safety, performance, and warranty coverage.
HOSHIZAKI provides this manual primarily to assist qualified service technicians in the
service and maintenance of the icemaker.
Should the reader have any questions or concerns which have not been satisfactorily
addressed, please call, write, or send an e-mail message to the HOSHIZAKI Technical
Support Department for assistance.
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem
IMPORTANT
This manual should be read carefully before the icemaker is serviced or
maintenance operations are performed. Only qualified service technicians
should install, service, and maintain the icemaker. Read the warnings
contained in this booklet carefully as they give important information regarding
safety. Please retain this booklet for any further reference that may be
necessary.
CONTENTS
I. Specifications ...................................................................................................................... 5
A. Icemaker ....................................................................................................................... 5
2. Sanitizing Procedure - Following Cleaning Procedure .......................................... 56
B. Maintenance ................................................................................................................ 57
C. Preparing the Icemaker for Long Storage ................................................................... 57
I. Specifications
AC SUPPLY VOLTAGE208-230/60/1 (3 wire with neutral for 115V)
AMPERAGE13.4 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
APPROXIMATE ICE PRODUCTIONAmbientWATER TEMP. (°F)
PER 24 HR.Temp.(°F)507090
lbs./day ( kg/day )70*1492 (677)1501 (681)1419 (643)
Reference without *marks801499 (680)1513 (686)1378 (625)
901501 (681)*1523 (691)1408 (639)
1001453 (659)1496 (679)1303 (591)
SHAPE OF ICECrescent Cube
ICE PRODUCTION PER CYCLE30.2 lbs. (13.7 kg) 1440 pcs.
APPROXIMATE STORAGE CAPACITYN/A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2410(3.8)2300(3.7)
WATER gal./24HR (gal./100 lbs.)373(24.5)698(46.8)
WATER COOLED CONDENSER1493(98)930(62)
gal./24HR (gal./100 lbs.)
EXTERIOR DIMENSIONS (WxDxH)48" x 27-3/8" x 27-3/8" (1219 x 695 x 695 mm)
EXTERIOR FINISHStainless Steel, Galvanized Steel (Rear)
WEIGHTNet 310 lbs. ( 141 kg ), Shipping 360 lbs. ( 163 kg )
CONNECTIONS - ELECTRICPermanent - Connection
- WATER SUPPLYInlet 1/2" FPTCondenser Inlet 1/2" FPT
- DRAINOutlet 3/4" FPTCondenser Outlet 3/8" FPT
3/8" OD Tube
CUBE CONTROL SYSTEMFloat Switch
HARVESTING CONTROL SYSTEMHot Gas and Water, Thermistor and Timer
ICE MAKING WATER CONTROLTimer Controlled. Overflow Pipe
COOLING WATER CONTROLPressure Regulator
BIN CONTROL SYSTEMThermostat
COMPRESSORHermetic, Model CS18K6E-PFV-237
CONDENSERWater-cooled, Tube in tube type
EVAPORATORVertical type, Stainless Steel and Copper
REFRIGERANT CONTROLThermostatic Expansion Valve
REFRIGERANT CHARGER-404A, 3 lbs. 1 oz. ( 1400g )
DESIGN PRESSUREHigh 427PSIG, Low 230PSIG
P.C. BOARD CIRCUIT PROTECTIONHigh Voltage Cut-out ( Internal )
COMPRESSOR PROTECTIONAuto-reset Overload Protector ( Internal )
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pressure Control Switch
LOW WATER PROTECTIONFloat Switch
ACCESSORIES -SUPPLIEDN/A
-REQUIREDIce Storage Bin
OPERATING CONDITIONSVOLTAGE RANGE187 - 253 V
AMBIENT TEMP.45 -100° F
WATER SUPPLY TEMP.45 - 90° F
WATER SUPPLY PRESSURE10 - 113 PSIG
A. Icemaker
1. KM-1601SWH (water-cooled)
Note: We reserve the right to make changes in specifications and design without prior
notice.
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE9.0 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
APPROXIMATE ICE PRODUCTIONAmbientWATER TEMP. (°F)
PER 24 HR.Temp.(°F)507090
lbs./day ( kg/day )70*1555 (705)1558 (707)1466 (665)
Reference without *marks801557 (706)1562 (708)1417 (643)
901558 (707)*1565 (710)1440 (653)
1001507 (684)1536 (697)1326 (601)
SHAPE OF ICECrescent Cube
ICE PRODUCTION PER CYCLE30.2 lbs. (13.7 kg) 1440 pcs.
APPROXIMATE STORAGE CAPACITYN/A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2410(3.7)2270(3.5)
WATER gal./24HR (gal./100 lbs.)372(23.8)804(51.7)
WATER COOLED CONDENSER1565(100)910(59)
gal./24HR (gal./100 lbs.)
EXTERIOR DIMENSIONS (WxDxH)48" x 27-3/8" x 27-3/8" (1219 x 695 x 695 mm)
EXTERIOR FINISHStainless Steel, Galvanized Steel (Rear)
WEIGHTNet 310 lbs. ( 141 kg ), Shipping 360 lbs. ( 163 kg )
CONNECTIONS - ELECTRICPermanent - Connection
- WATER SUPPLYInlet 1/2" FPTCondenser Inlet 1/2" FPT
- DRAINOutlet 3/4" FPTCondenser Outlet 3/8" FPT
3/8" OD Tube
CUBE CONTROL SYSTEMFloat Switch
HARVESTING CONTROL SYSTEMHot Gas and Water, Thermistor and Timer
ICE MAKING WATER CONTROLTimer Controlled. Overflow Pipe
COOLING WATER CONTROLPressure Regulator
BIN CONTROL SYSTEMThermostat
COMPRESSORHermetic, Model CS18K6E-TF5-237
CONDENSERWater-cooled, Tube in tube type
EVAPORATORVertical type, Stainless Steel and Copper
REFRIGERANT CONTROLThermostatic Expansion Valve
REFRIGERANT CHARGER-404A, 3 lbs. 1 oz. ( 1400g )
DESIGN PRESSUREHigh 427PSIG, Low 230PSIG
P.C. BOARD CIRCUIT PROTECTIONHigh Voltage Cut-out ( Internal )
COMPRESSOR PROTECTIONAuto-reset Overload Protector ( Internal )
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pressure Control Switch
LOW WATER PROTECTIONFloat Switch
ACCESSORIES -SUPPLIEDN/A
-REQUIREDIce Storage Bin
OPERATING CONDITIONSVOLTAGE RANGE187 - 253 V
AMBIENT TEMP.45 -100° F
WATER SUPPLY TEMP.45 - 90° F
WATER SUPPLY PRESSURE10 - 113 PSIG
2. KM-1601SWH3 (water-cooled)
Note: We reserve the right to make changes in specifications and design without prior
notice.
3a. KM-1601SRH (remote air-cooled) (auxiliary codes: R-0; R-1; some S-1)
AC SUPPLY VOLTAGE208-230/60/1 (3 wire with neutral for 115V)
AMPERAGE12.8 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
APPROXIMATE ICE PRODUCTIONAmbientWATER TEMP. (°F)
PER 24 HR.Temp.(°F)507090
lbs./day ( kg/day )70*1583 (718)1550 (703)1435 (651)
Reference without *marks801558 (707)1507 (684)1353 (614)
901550 (703)*1472 (668)1332 (604)
1001503 (682)1439 (653)1203 (546)
SHAPE OF ICECrescent Cube
ICE PRODUCTION PER CYCLE29.4 lbs. (13.3 kg) 1440 pcs.
APPROXIMATE STORAGE CAPACITYN/A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2640(4.3)2440(3.7)
WATER gal./24HR (gal./100 lbs.)255(17.3)503(31.8)
EXTERIOR DIMENSIONS (WxDxH)48" x 27 3/8" x 27 3/8" (1219 x 695 x 695 mm)
EXTERIOR FINISHStainless Steel, Galvanized Steel (Rear)
WEIGHTNet 275 lbs. (125 kg), Shipping 350 lbs. (159 kg)
CONNECTIONS - ELECTRICPermanent - Connection
- WATER SUPPLYInlet 1/2" FPT
- DRAINOutlet 3/4" FPT
- CONDENSATE DRAIN3/8" OD Tube
CUBE CONTROL SYSTEMFloat Switch
HARVESTING CONTROL SYSTEMHot Gas and Water, Thermistor and Timer
ICE MAKING WATER CONTROLTimer Controlled. Overflow Pipe
COOLING WATER CONTROLN/A
BIN CONTROL SYSTEMThermostat
COMPRESSORHermetic, Model CS18K6E-PFV
CONDENSERAir-Cooled Remote, Condenser Unit URC-21F
EVAPORATORVertical type, Stainless Steel and Copper
REFRIGERANT CONTROLThermostatic Expansion Valve
Condensing Pressure Regulator on URC-21F
REFRIGERANT CHARGER404A, 24 lb. 14.6 oz. (11300g)
(Icemaker 15 lb. 3.4 oz. Cond. Unit 9 lb. 11.2 oz.)
DESIGN PRESSUREHigh 467PSIG, Low 230PSIG
P.C. BOARD CIRCUIT PROTECTIONHigh Voltage Cut-out ( Internal )
COMPRESSOR PROTECTIONAuto-reset Overload Protector ( Internal )
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pressure Control Switch
LOW WATER PROTECTIONFloat Switch
ACCESSORIES -SUPPLIEDN/A
-REQUIREDIce Dispenser or Ice Storage Bin, Remote Condenser Unit
OPERATING CONDITIONSVOLTAGE RANGE187 - 253 V
AMBIENT TEMP.45 -100° F
WATER SUPPLY TEMP.45 - 90° F
WATER SUPPLY PRESSURE10 - 113 PSIG
This data applies to units with an 8 l/min water valve. The 8 l/min water valve is part
number 3U0111-02 and has J248-032 stamped on the side of the valve facing the
rear of the unit.
Note: We reserve the right to make changes in specifications and design without prior
notice.
3b. KM-1601SRH (remote air-cooled) (auxiliary codes: some S-1; S-2 and later)
AC SUPPLY VOLTAGE208-230/60/1 (3 wire with neutral for 115V)
AMPERAGE12.8 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
APPROXIMATE ICE PRODUCTIONAmbientWATER TEMP. (°F)
PER 24 HR.Temp.(°F)507090
lbs./day ( kg/day )70*1564 (709)1547 (702)1468 (666)
Reference without *marks801551 (703)1524 (691)1415 (642)
901547 (702)*1505 (683)1407 (638)
1001512 (686)1482 (672)1317 (597)
SHAPE OF ICECrescent Cube
ICE PRODUCTION PER CYCLE31.2 lbs. (14.2 kg) 1440 pcs.
APPROXIMATE STORAGE CAPACITYN/A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2700(4.3)2610(4.0)
WATER gal./24HR (gal./100 lbs.)375(24.9)785(50.2)
EXTERIOR DIMENSIONS (WxDxH)48" x 27 3/8" x 27 3/8" (1219 x 695 x 695 mm)
EXTERIOR FINISHStainless Steel, Galvanized Steel (Rear)
WEIGHTNet 275 lbs. (125 kg), Shipping 350 lbs. (159 kg)
CONNECTIONS - ELECTRICPermanent - Connection
- WATER SUPPLYInlet 1/2" FPT
- DRAINOutlet 3/4" FPT
- CONDENSATE DRAIN3/8" OD Tube
CUBE CONTROL SYSTEMFloat Switch
HARVESTING CONTROL SYSTEMHot Gas and Water, Thermistor and Timer
ICE MAKING WATER CONTROLTimer Controlled. Overflow Pipe
COOLING WATER CONTROLN/A
BIN CONTROL SYSTEMThermostat
COMPRESSORHermetic, Model CS18K6E-PFV
CONDENSERAir-Cooled Remote, Condenser Unit URC-21F
EVAPORATORVertical type, Stainless Steel and Copper
REFRIGERANT CONTROLThermostatic Expansion Valve
Condensing Pressure Regulator on URC-21F
REFRIGERANT CHARGER404A, 24 lb. 14.6 oz. (11300g)
(Icemaker 15 lb. 3.4 oz. Cond. Unit 9 lb. 11.2 oz.)
DESIGN PRESSUREHigh 467PSIG, Low 230PSIG
P.C. BOARD CIRCUIT PROTECTIONHigh Voltage Cut-out ( Internal )
COMPRESSOR PROTECTIONAuto-reset Overload Protector ( Internal )
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pressure Control Switch
LOW WATER PROTECTIONFloat Switch
ACCESSORIES -SUPPLIEDN/A
-REQUIREDIce Dispenser or Ice Storage Bin, Remote Condenser Unit
OPERATING CONDITIONSVOLTAGE RANGE187 - 253 V
AMBIENT TEMP.45 -100° F
WATER SUPPLY TEMP.45 - 90° F
WATER SUPPLY PRESSURE10 - 113 PSIG
This data applies to units with a 15 l/min or 11 l/min water valve. The 15 l/min water
valve is part number 3U0111-01 and has J248-030 stamped on the side of the valve
facing the rear of the unit. The 11 l/min water valve is part number 4A1176-04 and
has the part number stamped on the side of the valve facing the front of the unit.
Note: We reserve the right to make changes in specifications and design without prior
notice.
4a. KM-1601SRH3 (remote air-cooled) (auxiliary codes: R-0; R-1; some S-1)
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE7.9 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
APPROXIMATE ICE PRODUCTIONAmbientWATER TEMP. (°F)
PER 24 HR.Temp.(°F)507090
lbs./day ( kg/day )70*1596 (724)1556 (706)1436 (651)
Reference without *marks801565 (710)1503 (682)1347 (611)
901556 (706)*1459 (662)1316 (597)
1001510 (685)1426 (647)1184 (537)
SHAPE OF ICECrescent Cube
ICE PRODUCTION PER CYCLE29.4 lbs. (13.3 kg) 1440 pcs.
APPROXIMATE STORAGE CAPACITYN/A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2580(4.3)2450(3.7)
WATER gal./24HR (gal./100 lbs.)261(17.9)504(31.6)
EXTERIOR DIMENSIONS (WxDxH)48" x 27 3/8" x 27 3/8" (1219 x 695 x 695 mm)
EXTERIOR FINISHStainless Steel, Galvanized Steel (Rear)
WEIGHTNet 275 lbs. (125 kg), Shipping 350 lbs. (159 kg)
CONNECTIONS - ELECTRICPermanent - Connection
- WATER SUPPLYInlet 1/2" FPT
- DRAINOutlet 3/4" FPT
- CONDENSATE DRAIN3/8" OD Tube
CUBE CONTROL SYSTEMFloat Switch
HARVESTING CONTROL SYSTEMHot Gas and Water, Thermistor and Timer
ICE MAKING WATER CONTROLTimer Controlled. Overflow Pipe
COOLING WATER CONTROLN/A
BIN CONTROL SYSTEMThermostat
COMPRESSORHermetic, Model CS18K6E-TF5
CONDENSERAir-Cooled Remote, Condenser Unit URC-21F
EVAPORATORVertical type, Stainless Steel and Copper
REFRIGERANT CONTROLThermostatic Expansion Valve
Condensing Pressure Regulator on URC-21F
REFRIGERANT CHARGER404A, 24 lb. 14.6 oz. (11300g)
(Icemaker 15 lb. 3.4 oz. Cond. Unit 9 lb. 11.2 oz.)
DESIGN PRESSUREHigh 467PSIG, Low 230PSIG
P.C. BOARD CIRCUIT PROTECTIONHigh Voltage Cut-out ( Internal )
COMPRESSOR PROTECTIONAuto-reset Overload Protector ( Internal )
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pressure Control Switch
LOW WATER PROTECTIONFloat Switch
ACCESSORIES -SUPPLIEDN/A
-REQUIREDIce Dispenser or Ice Storage Bin, Remote Condenser Unit
OPERATING CONDITIONSVOLTAGE RANGE187 - 253 V
AMBIENT TEMP.45 -100° F
WATER SUPPLY TEMP.45 - 90° F
WATER SUPPLY PRESSURE10 - 113 PSIG
This data applies to units with an 8 l/min water valve. The 8 l/min water valve is part
number 3U0111-02 and has J248-032 stamped on the side of the valve facing the
rear of the unit.
Note: We reserve the right to make changes in specifications and design without prior
notice.
4b. KM-1601SRH3 (remote air-cooled) (auxiliary codes: some S-1; S-2 and later)
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE7.9 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
APPROXIMATE ICE PRODUCTIONAmbientWATER TEMP. (°F)
PER 24 HR.Temp.(°F)507090
lbs./day ( kg/day )70*1585 (719)1563 (709)1464 (664)
Reference without *marks801568 (711)1535 (696)1396 (633)
901563 (709)*1511 (685)1387 (629)
1001520 (689)1482 (672)1273 (577)
SHAPE OF ICECrescent Cube
ICE PRODUCTION PER CYCLE31.2 lbs. (14.2 kg) 1440 pcs.
APPROXIMATE STORAGE CAPACITYN/A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2960(4.7)2580(3.9)
WATER gal./24HR (gal./100 lbs.)363(24.0)781(49.3)
EXTERIOR DIMENSIONS (WxDxH)48" x 27 3/8" x 27 3/8" (1219 x 695 x 695 mm)
EXTERIOR FINISHStainless Steel, Galvanized Steel (Rear)
WEIGHTNet 275 lbs. (125 kg), Shipping 350 lbs. (159 kg)
CONNECTIONS - ELECTRICPermanent - Connection
- WATER SUPPLYInlet 1/2" FPT
- DRAINOutlet 3/4" FPT
- CONDENSATE DRAIN3/8" OD Tube
CUBE CONTROL SYSTEMFloat Switch
HARVESTING CONTROL SYSTEMHot Gas and Water, Thermistor and Timer
ICE MAKING WATER CONTROLTimer Controlled. Overflow Pipe
COOLING WATER CONTROLN/A
BIN CONTROL SYSTEMThermostat
COMPRESSORHermetic, Model CS18K6E-TF5
CONDENSERAir-Cooled Remote, Condenser Unit URC-21F
EVAPORATORVertical type, Stainless Steel and Copper
REFRIGERANT CONTROLThermostatic Expansion Valve
Condensing Pressure Regulator on URC-21F
REFRIGERANT CHARGER404A, 24 lb. 14.6 oz. (11300g)
(Icemaker 15 lb. 3.4 oz. Cond. Unit 9 lb. 11.2 oz.)
DESIGN PRESSUREHigh 467PSIG, Low 230PSIG
P.C. BOARD CIRCUIT PROTECTIONHigh Voltage Cut-out ( Internal )
COMPRESSOR PROTECTIONAuto-reset Overload Protector ( Internal )
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pressure Control Switch
LOW WATER PROTECTIONFloat Switch
ACCESSORIES -SUPPLIEDN/A
-REQUIREDIce Dispenser or Ice Storage Bin, Remote Condenser Unit
OPERATING CONDITIONSVOLTAGE RANGE187 - 253 V
AMBIENT TEMP.45 -100° F
WATER SUPPLY TEMP.45 - 90° F
WATER SUPPLY PRESSURE10 - 113 PSIG
This data applies to units with a 15 l/min or 11 l/min water valve. The 15 l/min water
valve is part number 3U0111-01 and has J248-030 stamped on the side of the valve
facing the rear of the unit. The 11 l/min water valve is part number 4A1176-04 and
has the part number stamped on the side of the valve facing the front of the unit.
Note: We reserve the right to make changes in specifications and design without prior
notice.
10
B. Condensing Unit
1. URC-21F
Unit: mm (inches)
11
MODEL: URC-21F
AC SUPPLY VOLTAGE115/60/1 (Connection to Icemaker)
FAN MOTOR 115 VTotal 2.6FLA130W
EXTERIOR DIMENSIONS (WxDxH)46-3/8" x 15-11/16" x 25-15/16" (1178 x 398 x 659 mm)
DIMENSIONS INCLUDING LEGS (WxDxH)48-7/16" x 18-1/8" x 40-7/8" (1230 x 460 x 1039 mm)
EXTERIOR FINISHGalvanized Steel
WEIGHTNet 158 lbs. ( 72 kg ) Shipping 169 lbs. ( 77 kg )
CONNECTIONS - ELECTRICPermanent - Connection
- REFRIGERANTDischarge Line 1-1/16"-12 UNF Fitting (#10 AEROQUIP)
Liquid Line 5/8"-18 UNF Fitting (#6 AEROQUIP)
CONDENSERAir-cooled, Fin and tube type
FAN MOTOR PROTECTIONThermal Protection
REFRIGERANT CONTROLCondensing Pressure Regulator
REFRIGERANT CHARGER-404A9 lb. 11oz.(4400g)
DESIGN PRESSUREHigh 467 PSIG32.2 Bar
OPERATING CONDITIONSVOLTAGE RANGE104 ~ 127 V
AMBIENT TEMP.-20 ~ 122 °F
ACCESSORIES -SUPPLIEDLeg2 pcs
Hex. Head Bolt w/Washer 8 x 168 pcs
Hex. Nut88 pcs
SPECIFICATIONS
1
II. General Information
A. Construction
1. KM-1601SWH, KM-1601SWH3 (water-cooled)
Spray Tubes
Inlet Water
Valve
Expansion Valves
Evaporator Assembly
Cleaning Valve
Check Valve
(water)
Water Pump
Float Switch
Compressor
Water Supply Inlet
Junction Box
Hot Gas Valve
Check Valves
Water Regulator
Water-cooled
Condenser
Control Box
Bin Control Thermostat
Control Switch
Transformer Box
(KM-1601SWH3)
Capacitor Box
(KM-1601SWH)
1
Drier
Liquid Line Valve
2. KM-1601SRH, KM-1601SRH3 (remote air-cooled)
Spray Tubes
Evaporator Assembly
Cleaning Valve
Check Valve
(water)
Water Pump
Float Switch
Compressor
Inlet Water
Valve
Expansion Valves
Water Supply Inlet
Hot Gas Valve
Junction Boxes
Check Valves
Receiver Tank
Bin Control Thermostat
Control Switch
Transformer Box
(KM-1601SRH3)
Capacitor Box
(KM-1601SRH)
1
Control Box
Drier
Liquid Line Valve
B. Sequence of Operation
The steps in the sequence are as outlined below. When power is supplied, a 5 second
delay occurs at startup. Note that the order of the LEDs from the outer edge of the board is
1, 4, 3, 2.
1. One Minute Fill Cycle
LED 4 is on. WV opens and the fill period begins. After 1 minute, the board checks for
a closed F/S. If F/S is closed, the harvest cycle begins. If not, WV will remain energized
through additional 1 minute cycles until water enters the sump and F/S closes. This serves
as a low water safety to protect the water pump.
2. Initial Harvest Cycle
LEDs 1, 4, and 2 are on. WV remains open, Comp and FMR energize, HGV opens,
and harvest begins. As the evaporator warms, the thermistor located on the suction line
checks for a 48°F (9°C) temperature. When 48°F (9°C) is reached, a 3.9 kΩ signal turns
the harvest over to the adjustable harvest timer which is factory set for normal conditions.
The timer has settings of 60, 90, 120, and 180 seconds (dip switch 1 & 2). The water valve
is open during harvest for a maximum of 6 minutes or the length of harvest, whichever is
shorter. When the harvest timer completes its count down, the harvest cycle is complete
and the freeze cycle starts. The minimum total time allowed by the board for a complete
harvest cycle is 2 minutes.
3. Freeze Cycle
LED 1 is on. Comp and FMR continue to run, PM and FMS energize, LLV opens, HGV
and WV close, and the freeze cycle starts. For the first 5 minutes the control board will not
accept a signal from F/S. This 5 minute minimum freeze acts as a short cycle protection. At
the end of 5 minutes, F/S assumes control. As ice builds on the evaporator the water level
in the sump lowers. The freeze continues until F/S opens and terminates ice production.
4. Pump-Out Cycle
LEDs 1, 3, and 2 are on. Comp and FMR continue to run, HGV opens, LLV closes, and
FMS deenergizes. PM stops for 2 seconds and reverses, taking water from the bottom of
the sump and forcing pressure against the check valve seat allowing water to go through
the check valve and down the drain. At the same time water flows through the small tube
to power flush the F/S. When the pump-out timer stops counting, the pump out is complete.
Pump out always occurs on the 2nd harvest after startup. Then, depending on the control
board setting, pump out occurs every cycle, or every 2nd, 5th, or 10th cycle (dip switch 5 &
6).
5. Normal Harvest Cycle
LEDs 1, 4, and 2 are on. Comp and FMR continue to run, HGV remains open, and WV
opens. As the evaporator warms, the thermistor reaches 48°F (9°C). The control board
then receives the thermistor's 3.9 kΩ signal and starts the harvest timer. The water valve
is open during harvest for a maximum of 6 minutes or the length of harvest, whichever is
shorter. When the harvest timer completes its count down, the harvest cycle is complete
and the next freeze cycle starts. The unit continues to cycle through 3, 4, and 5 sequence
until the bin control senses ice and shuts the unit down.
Legend: Comp–compressor; FMR–remote fan motor; FMS–self-contained fan motor;
F/S–float switch; HGV–hot gas valve; LLV–Liquid Line Valve; PM–pump motor;
WV–inlet water valve
1
Cycle
4. Pump-Out
F/S in
control
5 minute timer
in control
• Minimum freeze time: 5 minutes
• Maximum freeze time: freeze timer setting
Pump motor stops
for 2 sec. and then
reverses for 10/20 sec.
Freeze cycle
operation turned
over to F/S
F/S closed
FMR continues
HGV de-energized
Comp continues
F/S Check
each 1, 2, 5, or 10 cycles.
WV de-energized
Comp continues
PM energized
FMR continues
HGV energized
FMS energized
F/S open
FMS de-energized
1 to 3 minute timer
in control
Thermistor temp
reaches 48°F (9°C)
2. Harvest Cycle3. Freeze Cycle
Thermistor in
• Maximum harvest time: 20 minutes
Fill Cycle
control
F/S closed
F/S Check
Comp energized
WV Energized
HGV energized
• Maximum inlet water valve time: 6 minutes
1. One Minute
KM-1601SWH/3, KM-1601SRH/3 Sequence Flow Chart and Component Operation
Cycle Steps
"E" board will have
Initial startup always
5 second delay
begins here
Harvest timer starts
(3.9 kΩ or less)
FMR energized
WV continues
F/S open
If F/S is open, compressor stops and cycle returns to 1 minute fill
Components Energized when the Control Switch is in the "WASH" Position
The "WASH" position on the control switch is used when cleaning and sanitizing the unit. When in the
"WASH" position, power is supplied to the pump motor. With the cleaning valve closed, the cleaner and
sanitizer flow over the outside of the evaporator plate assembly. With the cleaning valve open, the cleaner
and sanitizer flow over both the outside and the inside of the evaporator plate assembly.
Note: Close the cleaning valve after cleaning and sanitizing are complete, otherwise the unit will not re-start
Legend:
Comp - compressor
FMR - remote fan motor
FMS - self-contained fan motor
F/S - float switch
HGV - hot gas valve
PM - pump motor
when the control switch is placed in the "ICE" position.
WV - inlet water valve
1
C. Control Board
• A HOSHIZAKI exclusive solid-state control is employed in KM-1601SWH,
KM-1601SWH3, KM-1601SRH, and KM-1601SRH3 Stackable Crescent Cubers.
• All models are pretested and factory-adjusted.
CAUTION
1. Fragile, handle very carefully.
2. A control board contains integrated circuits, which are susceptible to failure
due to static discharge. It is especially important to touch the metal part of
the unit before handling or replacing the board.
3. Do not touch the electronic devices on the board or the back of the board to
prevent damage to the board.
4. Do not change wiring and connections. Do not misconnect K3, K4, and K5,
because the same connector is used for the thermistor and float switch. K4 is
not connected.
5. Always replace the whole board assembly if it goes bad.
6. Do not short out power supply to test for voltage.
1
1. Control Board Layout
Control Products "E" Control Board
Alarm Reset Switch
Backup Freeze
Timer LED
Backup Harvest
Timer LED
Alarm Buzzer
Dip Switch
Output Test Switch
(used to test relays on board)
Connector K3
Harvest Control
(thermistor)
Connector K4
Open
(not connected)
Power LED
(lights when
power is supplied
to the board)
Relay LEDs (4)
(indicate which
relays are energized
as listed below)
LED 2
Hot Gas Valve (HGV)
Self-Contained Fan
Motor (FMS) (FMS
off when LED on)
LED 3
Pump Motor (PM)
(on at pump out only)
LED 4
Water Valve (WV)
LED 1
Compressor (Comp)
Remote Fan Motor
(FMR)
Transformer
Connector
Microprocessor
(board revision level
indicated by last 2
digits on label)
Connector K5
Float Switch
Part Number
Connector K1
Pins #1 through #10
#1, 9 Magnetic Contactor
#2 Hot Gas Valve
#3 Line Valve
Self-Contained Fan Motor (FMS)
#4 Pump Motor (icemaking)
#5 Pump Motor (drain)
#6 Water Valve
#7, 10 Power (line, bin control)
#8 Open
Switch for "C" board
and "ALPINE" board
(service boards only)
Control Board
Part Number2A1410-01 (factory); 2A1410-02 (service)
TypeHOS-001A (Control Products - 10 Pin)
1