Only qualified service technicians should attempt to service or maintain this
unit. No such service or maintenance should be undertaken until the technician
has thoroughly read this Service Manual.
HOSHIZAKI provides this manual primarily to assist qualified service technicians in the
service and maintenance of the unit.
Should the reader have any questions or concerns which have not been satisfactorily
addressed, please call, write or send an e-mail message to the HOSHIZAKI Technical
Support Department for assistance.
HOSHIZAKI AMERICA, INC.
618 Highway 74 South
Peachtree City, GA 30269
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem
2
Please review this manual. It should be read carefully before the unit is serviced or
maintenance operations are performed. Only qualified service technicians should service
and maintain the unit. This manual should be made available to the technician prior to
service or maintenance.
CONTENTS
I. Specifications ...................................................................................................................... 5
A. Nameplate Ratings........................................................................................................ 5
B. Dimensions ................................................................................................................... 6
1. Notes for All Units .................................................................................................... 6
1. Refrigerator and Refrigerator Side of Dual Temp Models
a) Sequence of Operation
POWER ON
Board Self Check
Display reads "r_##"
(## is board revision)
1. Frame heaters on
2. Evaporator fan on
Cycle On (Cut-on
temperature reached)
[Minimum 2.5 minutes]
1. Compressor on
2. Condenser fan on
2.5 minute delay
1. Compressor start-up
2. Condenser fan start-up
If evaporator temperature
reaches 13°F (8°F for Pass Thru),
unit initiates defrost.
1. Compressor off
(Note: Condenser fan and
evaporator fan are on.)
Cycle Off (Cut-out
temperature reached)
[Minimum 2.5 minutes]
1. Compressor off
2. Condenser fan off
Evaporator temperature
reaches 40°F, defrost
terminated
1. Compressor on
2. Condenser fan on
Normal cycling continues
Note: The start circuit of the compressor is timed such that at power-up and during
any compressor off time, there will be at least a 2 1/2 minute delay before the
compressor will start. The only exception is when the overload activates and
deactivates. The compressor has a 2 1/2 minute minimum run time during every
run cycle.
11
b) Timing Chart
For refrigerator, and refrigerator side of Dual Temp models.
12
2. Freezer (except freezer side of RFH1-SSB-HD) auxiliary code P5 and earlier
a) Sequence of Operation
POWER ON
Board Self Check
Display reads "r_##"
(## is board revision)
Frame heaters on
Cycle On (Cut-on
temperature reached)
[Minimum 2.5 minutes]
1. Compressor on
2. Condenser on
3. Evaporator on
2.5 minute delay
1. Compressor start-up
2. Condenser fan start-up
3. Evaporator fan start-up
Defrost Start
Preprogrammed time interval
1. Compressor off
2. Evaporator fan off
3. Condenser fan off
4. Defrost heater on
5. "dEF" displayed
Cycle Off (Cut-out
temperature reached)
[Minimum 2.5 minutes]
1. Compressor off
2. Condenser fan off
3. Evaporator fan off
Defrost End
Defrost thermistor
reaches 100°F;
Defrost heater off
Five minutes after
defrost heater off
1. Compressor on
2. Condenser fan on
Note: The start circuit of the compressor is timed such that at power-up and during
any compressor off time, there will be at least a 2 1/2 minute delay before the
compressor will start. The only exception is when the overload activates and
deactivates. The compressor has a 2 1/2 minute minimum run time during every
run cycle.
Evaporator temperature
reaches below 70°F
1. Evaporator fan on
13
Cabinet temperature reads
a value below 15°F above
the setpoint.
"dEF" no longer displayed,
cabinet temp. displayed.
Normal cycling continues
b) Timing Chart
For freezer (except freezer side of RFH1-SSB-HD) auxiliary code P5 and earlier.
14
3. Freezer (except freezer side of RFH1-SSB-HD) auxiliary code P6 and later
a) Sequence of Operation
POWER ON
Board Self Check
Display reads "r_##"
(## is board revision)
1. Frame heaters on
2. Evaporator fan on
Cycle On (Cut-on
temperature reached)
[Minimum 2.5 minutes]
1. Compressor on
2. Condenser fan on
2.5 minute delay
1. Compressor start-up
2. Condenser fan start-up
Defrost Start
Preprogrammed time interval
1. Compressor off
2. Evaporator fan off
3. Condenser fan off
4. Defrost heater on
5. "dEF" displayed
Cycle Off (Cut-out
temperature reached)
[Minimum 2.5 minutes]
1. Compressor off
2. Condenser fan off
Defrost End
Defrost thermistor
reaches 100°F;
Defrost heater off
Five minutes after
defrost heater off
1. Compressor on
2. Condenser fan on
Evaporator temperature
reaches below 70°F
1. Evaporator fan on
Normal cycling continues
Cabinet temperature reads
a value below 15°F above
the setpoint.
"dEF" no longer displayed,
cabinet temp. displayed.
Note: The start circuit of the compressor is timed such that at power-up and during
any compressor off time, there will be at least a 2 1/2 minute delay before the
compressor will start. The only exception is when the overload activates and
deactivates. The compressor has a 2 1/2 minute minimum run time during every
run cycle.
15
b) Timing Chart
For freezer (except freezer side of RFH1-SSB-HD) auxiliary code P6 and later.
16
4. Freezer Side of RFH1-SSB-HD
a) Sequence of Operation
POWER ON
Board Self Check
Display reads "r_##"
(## is board revision);
Frame heaters on
Cycle On (Cut-on
temperature reached)
[Minimum 2.5 minutes]
1. Compressor on
2. Condenser fan on
2.5 minute delay
1. Compressor start-up
2. Condenser fan start-up
3. Evaporator fan start-up
Defrost Start
Preprogrammed time interval
1. Compressor off
2. Evaporator fan off
3. Condenser fan off
4. Defrost heater on
5. "dEF" displayed
Cycle Off (Cut-out
temperature reached)
[Minimum 2.5 minutes]
1. Compressor off
2. Condenser fan off
Defrost End
Defrost thermistor
reaches 100°F;
Defrost heater off
Five minutes after
defrost heater off
1. Compressor on
2. Condenser fan on
Evaporator temperature
reaches below 70°F
1. Evaporator fan on
Cabinet temperature reads
a value below 15°F above
the setpoint.
"dEF" no longer displayed,
cabinet temp. displayed.
Normal cycling continues
Note: The start circuit of the compressor is timed such that at power-up and during
any compressor off time, there will be at least a 2 1/2 minute delay before the
compressor will start. The only exception is when the overload activates and
deactivates. The compressor has a 2 1/2 minute minimum run time during every
run cycle.
17
b) Timing Chart
For freezer side of RFH1-SSB-HD.
18
B. Display Board
The display board is located on the right hand side of the control panel between the top
of the door and the front panel. From this area, information regarding the functioning
of the unit can be obtained. When the unit is turned on, the first display reads "r_##",
where "##" indicates the board revision level. From the display board, various electronic
controls and functions can also be adjusted. See "D. Settings and Diagnostics."
Evercheck Display Board
19
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.